Lowell RPC-15-S, RPC-15 Specifications

Spec No. 1220 [REV. 06.24.19] Page 1/2
Model No’s.
RPC-15, RPC-15S
Stand-alone units with cord
Lowell Remote Power Controls can be combined with a variety of switches or sequential control devices that provide a dry contact closure for an intrinsically safe low voltage method of controlling AC power to equipment at a remote loca­tion. The ability to safely control AC power distribution without directly accessing equipment minimizes the potential for accidental or unauthorized activation. Typ­ical applications include commercial, entertainment, government, education and house-of-worship venues where remote power control is often required.
RPCs are typically installed in close proximity of equipment to be controlled. Low-voltage cable is run from the RPC terminal strip to a control switch (such as a switch from Lowell’s RPS Series) or other control method. Systems can be congured with multiple RPCs activated by a single switch. Systems can also be congured with multiple switches or trigger voltage sources controlling a single RPC. (See connection diagrams on next page.) RPCs also serve as a key compo­nent in Lowell’s low voltage sequential control systems (SEQ Series).
Construction & Features
Compact steel chassis with black powder epoxy nish
Power Rating: 15A 125VAC
One duplex outlet
Terminates with 6-ft. cord and NEMA 5-15P plug
ETL Listed (UL 60065) in U.S.A. and Canada
Made in the U.S.A.
Model No. RPC-15S also includes surge protection:
Maximum Surge Current: .................................................... 20,000A
VPR: ....................................................................................... 400V
Response Time: ..........................................................1 nanosecond
EMI/RFI Noise Reduction: ..........................................20dB@100kHz
Protection Mode: .......................................................Line to Neutral
Ground Contamination: ............................................................None
Model No. RPC-15
Model No. RPC-15S includes surge protection
A&E Specifications
The device for remotely controlling AC power shall be Lowell Remote Power Control Model No. ___________, which shall include a power supply and relay housed in a 7.5”L x 3.25”W x 1.75” steel chassis with a black powder epoxy nish. The unit shall include one duplex outlet with 15A power rating and six-ft. cord with NEMA plug. [ Model No. RPC-15S shall also include surge protection up to 20,000A. ]
Related Accessories (order separately)
RPS Series Switch. Selection of rackmount and wall-mount SPST
maintained and momentary switches with rocker or key activation.
SEQ Series Sequencers. Selection of modular low voltage sequenc-
ers.
MSM2. Momentary Switch Module used with momentary contact
switches.
Model Numbers Summary
Model No. Description Chassis Length Chassis Width Chassis Height Total Outlets Surge Protection Switch Type
RPC-15 Low voltage remote power control 7.5 in. 3.25 in. 1.75 in. 2 ---- dry contact
RPC-15S Low voltage remote power control 7.5 in. 3.25 in. 1.75 in. 2 Yes dry contact
*Minimum rating 30 vdc, 40 mA.
Lowell makes every effort to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without notication. ©2016 Lowell Manufacturing Company, 100 Integram Dr., Pacic MO 63069 | 800.325.9660 | www.lowellmfg.com
Spec No. 1220 [REV. 06.24.19] Page 2/2
Green LED (surge protection – Model No. RPC-15S ONLY)
ON = protection active OFF = protection compromised
Red LED (AC power indicator)
ON = power applied to unit OFF = no power to unit
Test Switch
TEST = AC power applied to receptacles (bypassing external controls) NORM = external control connections enabled
Green LED (receptacle power indicator)
ON = power applied to receptacles (i.e. receptacles active) OFF = no power to receptacles
Equipment
to be
controlled
(6-ft. long cord)
Typical RPC Control Methods: low voltage, limited current Class 2 wiring
Connect to appropriate 125VAC power source.
EXAMPLE 1 EXAMPLE 2
Switch
Common
Lowell RPS Series
MAINTAINED SWITCH
(Not momentary switch)
SWITCH SCHEMATIC
Switch
Common
+24V Out
+24VDC Output
250mA Max.
Switch SPST
2.2K 1/2W Resistor
LED
Switch
Common
+24VDC Output
250mA Max.
No Conn.
( + ) Com
( – )
Dry Contact Closure or open-collector transistor switch provided by external sequencer (Lowell SEQ Series) or control system (by others). Follow polarity indicators, if any, on sequencer/ controller. (min. rating: 24V, 40mA)
ON = connection applied (closed) OFF = connection removed (open)
FIRE ALARM PANEL INTERFACE
APPLICATION EXAMPLE: RPC provides power for retail store music/paging system. Fire Alarm Panel forces music/paging system OFF so alarm can be heard.
NOTE: Use normally closed (NC) contact from Fire Alarm Panel.
Switch
Common
+24VDC Output
250mA Max.
To re alarm panel
Lowell makes every effort to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without notication. ©2016 Lowell Manufacturing Company, 100 Integram Dr., Pacic MO 63069 | 800.325.9660 | www.lowellmfg.com