Spec No. 1745 [REV. 06.22.17] Page 1/2
Model No’s. ACSPR-2009, ACSPR-2009-VTE
Rackmount Panels
20A power panels with surge protection
Features
• 20A system circuit breaker and a receptacle (always on) that is
independently protected by a 5A circuit breaker
• Line-to-neutral power protection compliant with UL1449 4th edition
and ANSI C62.41 to defeat surges up to 72,000A
ACSPR-2009-VTE
• LED status indicators
• 19”W x 9”D x 1.75”H (1U) chassis
• Lighted on/off actuation switch on front panel
• Rear panel layout has one unswitched duplex outlet, one unswitched
single outlet, one switched duplex, three switched single outlets
• 9-ft. attached cord with NEMA 5-20P plug
• ETL Listed in the US and Canada.
• Made in the U.S.A.
Model Specific Features (ACSPR-2009-VTE)
• Over/Under protection (VTE) automatically turns receptacles off when
line voltage drops below 100V or rises above 140V
• Following a voltage tolerance shutdown, the unit will automatcially
restore power to the receptacles when the unit detects acceptable
line voltage
A & E Specifications
The AC power panel shall be Lowell Model ____________ (ACSPR-2009,
ACSPR-2009-VTE). It shall be ETL Listed and have a power rating of 120VAC,
60Hz/20A with EMI/RFI ltering and nine outlets (4 unswitched, 5 switched). It
shall be housed in a 1U rackmount steel chassis nished in black epoxy paint.
Front activation shall be via a lighted rocker switch. It shall include advanced
surge protection that is UL1449 fourth edition and ANSI C62.41 compliant to
defeat surges up to 72,000A. Termination shall be 9-ft attached cord with NEMA
5-20P plug.
Model with over/under voltage protection (ACSPR-2009-VTE) shall include auto
reset circuitry to turn all receptacles off when line voltage exceeds 140V or
drops below 100V.
Specifications
Power Rating: 120VAC, 60Hz, 20A 2400W
Actuation Switch: Front panel lighted on/off rocker switch
Termination: 9-ft. attached cord with NEMA 5-20P plug
Circuit Breaker: 20A
Receptacles (9): Front: One single unswitched - always on
(independently protected by 5A circuit breaker)
Rear: One duplex unswitched - always on
One single unswitched - always on
One duplex switched
Three single switched
Chassis: Steel with black powder epoxy paint nish.
Dimensions: 19”W x 1.75”H (1U) x 9”D
Weight: 12 lbs.
Safety Agency Approvals: ETL Listed in US and Canada to UL Standard 60065
Three-Stage Surge Suppressor
Maximum Surge Current 72,000A (exceeds UL1449-4 6000V, 3000A).
Initial Clamping Voltage 205V, UL rating 400V
Endurance IEEE C62.41-1991, B3 (C1), Pulses (lifetime):
1kv≥1,000,000; 3kv≥100,000; 6kv≥5000
Transient Noise Reduction 25dB@100kHz, 50dB@1MHz
Response Time Less than 5 nanoseconds
Protection Mode Line to neutral, zero ground leakage
UL1449-2 Adjunct Results 1000 surges, 6000 volts, 3000A, C1 and B3 waveforms
(IEEE C62.41), No failures
Diagnostic LED’s* One green LED for each stage
All stages active when lit
Applicable Standards: IEEE standard 587-80 A & B, IEEE standard C62.41-
1991, IEC 1000-4-5-1995 (IEC 801-5).
EMI/RFI Filter: 19dB@500kHz, 42dB@30MHz
Additional for Model with Voltage Tolerance Envelope (ACSPR-2009-VTE)
Over/Under Voltage Protection All receptacles turn off when power in exceeds 140V or
drops below 100V. Receptacles turn back on when power
returns to acceptable range.
* Lowell’s Triple Clamping Redundancy is exactly that - triple clamping for triple protection. This
means that if one section of the suppressor has gone off-line, there are two additional sections
available to safeguard equipment. Device is endurance tested.
Lowell makes every effort to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without notication.
©2016 Lowell Manufacturing Company, 100 Integram Dr., Pacic MO 63069 | 800.325.9660 | www.lowellmfg.com
Spec No. 1745 [REV. 06.22.17] Page 2/2
Rocker Switch
Activation
Rocker Switch
Activation
Green LEDs - three
stage surge protection,
active when lit
Over/Under Voltage Protection
Green LED - Voltage Normal (110-130)
Yello LEDs - Voltage (100, 135)
Red LED - Voltage (under 100, over 140) Shutdown Activated
Circuit Breaker
Circuit Breaker
Green LEDs - three
stage surge protection,
active when lit
ACSPR-2009
FRONT VIEW
ACSPR-2009-VTE
FRONT VIEW
REAR VIEW (BOTH)
Includes 9-ft. attached cord
with NEMA 5-20P plug
Model No. Summary
Model No. Description Outlets Amperage Surge Protection Over/Under Voltage Protection Chassis
ACSPR-2009 AC Rackmount Panel (1U) 9 20A Yes No 19” x 9” x 1.75”
ACSPR-2009-VTE AC Rackmount Panel (1U) 9 20A Yes Yes 19” x 9” x 1.75”
Lowell makes every effort to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without notication.
©2016 Lowell Manufacturing Company, 100 Integram Dr., Pacic MO 63069 | 800.325.9660 | www.lowellmfg.com