Lowell ACS1524-2C Series, ACS2024-2C Series Installation Instructions Manual

Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A.
Ca ll 800.325.9 660 , 636 .25 7.3 400 • Fa x 636 .257. 660 6 • Cl ic k www. low ell mfg.c om
P/N 16099
pg 1 of 2
Printed in U.S.A. © 10-09-08
ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
Installation Instructions
Model Specifications
ACS-1524-2C ACS-2024-2C
15 Amp 20 Amp
24 outlets 24 outlets
125 VAC 125 VAC
70"L 70"L
1.5"W 1.5"W
1.625"D 1.625"D
Rack rail mounting channel
Mounting
clip
Nut
Screw
1) Install mounting clip to rack
rail mounting channel using hardware provided.
2) Align power strip with
mounting clips and snap into place.
1) Install mounting clip to rack
Z-bracket using hardware provided.
2) Align power strip with
mounting clips and snap into place.
Easy installation into Lowell cabinets
and racks with adjustable mounting rails.
Easy installation into Lowell cabinets
with fixed mounting rails.
Mounting
clip
Nut
Screw
Z-bracket in rear of cabinet
● Twenty-four receptacles, 12 per circuit (adjacent recepta­cles on opposite circuit).
● Symmetrical design, recepta­cles can be oriented “up” or “down”.
● Power connections can be made from either end, or both ends for feed-through.
● Light colored receptacles for high visibility inside cabinets, alternating white and gray colors indicate separate cir­cuits.
● Dimensions: 70"x1.625"x1.5".
● Long cable ties provided for securing power supplies (see detail).
ACS-1524-2C (15A) ACS-2024-2C (20A)
Alternating colors indicate 2 separate circuits
White
Gray
White
Gray
Remove cover
Remove knock-out(s) as needed
Pull out pigtails and identify circuits
Multi-wire branch circuit (shared neutral)
Tuck wires inside chassis and re-install cover assembly
Pigtails at opposite end can be utilized as feed-through to connect additional power strip.
Connect wires (Two possible wiring options)
Independent circuits and isolated ground
Attach cover
Circuits must be on opposite phases to pre­vent neutral oveload.
12-3 MC or equiv. with appropriate connector
12-3 MC or equiv. with appropriate connector
Isolated ground connected to receptacle ground wire
Chassis ground wire connected to safety ground
Connect all grounds together
ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
P/N 16099
pg 2 of 2
Printed in U.S.A. © 10-09-08
Circuit Two (white recept.)
Chassis ground (enclosure bonding)
Red
Green
Wht
Wht
Blk
Green
Receptacle ground
Pull out pigtails, identify circuits.
NOTE: Factory installed push-in connectors suitable for SOLID wire ONLY. For stranded wire remove and discard push-in connectors and use wire nuts or other suitable connectors (not included).
Green
Green w/yellow strips
Blk
Red
Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A. Cal l 80 0. 32 5. 96 60 , 636. 25 7. 34 00 • Fax 636. 25 7. 66 06 • C li ck www.l ow el lm fg .c om
Green
Red
Green
Blk
Blk
Wht
Wht
Wht
Wht
Wht