Lowell ACS2024-2C User Manual

ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
Installation Instructions
Rack rail mounting channel
Alternating colors indicate 2 separate circuits
White
Gray
White
Gray
● Twenty-four receptacles, 12 per circuit (adjacent recepta­cles on opposite circuit).
● Symmetrical design, recepta­cles can be oriented “up” or “down”.
● Power connections can be made from either end, or both ends for feed-through.
● Light colored receptacles for high visibility inside cabinets, alternating white and gray colors indicate separate cir­cuits.
● Dimensions: 70"x1.625"x1.5".
● Long cable ties provided for securing power supplies (see detail).
Nut
Screw
Mounting
clip
1) Install mounting clip to rack
rail mounting channel using hardware provided.
2) Align power strip with
mounting clips and snap into place.
Easy installation into Lowell cabinets
and racks with adjustable mounting rails.
Z-bracket in rear of cabinet
Nut
Mounting
clip
Screw
ACS-1524-2C (15A) ACS-2024-2C (20A)
Model Specifications
ACS-1524-2C ACS-2024-2C
15 Amp 20 Amp
24 outlets 24 outlets
125 VAC 125 VAC
70"L 70"L
1.5"W 1.5"W
1.625"D 1.625"D
P/N 16099
pg 1 of 2
Printed in U.S.A. © 10-09-08
1) Install mounting clip to rack
Z-bracket using hardware provided.
2) Align power strip with
mounting clips and snap into place.
Easy installation into Lowell cabinets
with fixed mounting rails.
Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A.
Ca ll 800.325.9 660 , 636 .25 7.3 400 • Fa x 636 .257.660 6 • Cl ic k www. low ell mfg.c om
Remove cover
Connect wires
(Two possible wiring options)
Remove knock-out(s) as needed
ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
Pull out pigtails and identify circuits
Circuit Two (white recept.)
Wht
Receptacle ground
Pull out pigtails, identify circuits.
NOTE: Factory installed push-in connectors suitable for SOLID wire ONLY. For stranded wire remove and discard push-in connectors and use wire nuts or other suitable connectors (not included).
Blk
Green
Wht
Red
Chassis ground (enclosure bonding)
Green
12-3 MC or equiv. with appropriate connector
Connect all grounds together
P/N 16099
pg 2 of 2
Printed in U.S.A. © 10-09-08
Multi-wire branch circuit (shared neutral)
Circuits must be on opposite phases to pre­vent neutral oveload.
Red
Chassis ground wire
Green
Blk
Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A. Cal l 800 .325. 966 0, 636. 257 .3400 • Fax 6 36. 257.6 606 • Click w ww.l owe llmfg .co m
Blk
Attach cover
Wht
Wht
connected to safety ground
Tuck wires inside chassis and re-install cover assembly
Independent circuits and isolated ground
12-3 MC or equiv. with appropriate connector
Red
Wht
Wht
Green
Blk
Wht
Pigtails at opposite end can be utilized as feed-through to connect additional power strip.
Green w/yellow strips
Isolated ground connected to
Green
receptacle ground wire