ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
Installation Instructions
Models Features Installation
Rack rail mounting channel
Alternating colors
indicate 2 separate
circuits
White
Gray
White
Gray
● Twenty-four receptacles, 12
per circuit (adjacent receptacles on opposite circuit).
● Symmetrical design, receptacles can be oriented “up” or
“down”.
● Power connections can be
made from either end, or both
ends for feed-through.
● Light colored receptacles for
high visibility inside cabinets,
alternating white and gray
colors indicate separate circuits.
● Dimensions: 70"x1.625"x1.5".
● Long cable ties provided for
securing power supplies (see
detail).
Nut
Screw
Mounting
clip
1) Install mounting clip to rack
rail mounting channel using
hardware provided.
2) Align power strip with
mounting clips and snap
into place.
Easy installation into Lowell cabinets
and racks with adjustable mounting rails.
Z-bracket in rear of cabinet
Nut
Mounting
clip
Screw
ACS-1524-2C (15A) ACS-2024-2C (20A)
Model Specifications
ACS-1524-2C ACS-2024-2C
15 Amp 20 Amp
24 outlets 24 outlets
125 VAC 125 VAC
70"L 70"L
1.5"W 1.5"W
1.625"D 1.625"D
P/N 16099
pg 1 of 2
Printed in U.S.A. © 10-09-08
1) Install mounting clip to rack
Z-bracket using hardware
provided.
2) Align power strip with
mounting clips and snap
into place.
Easy installation into Lowell cabinets
with fixed mounting rails.
Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A.
Ca ll 800.325.9 660 , 636 .25 7.3 400 • Fa x 636 .257.660 6 • Cl ic k www. low ell mfg.c om
Remove cover
Connect wires
(Two possible wiring options)
Remove knock-out(s) as needed
ACS1524-2C, ACS2024-2C Series
15/20A Hardwired Mutli-Circuit AC Power Strips - ETL Listed
Pull out pigtails and
identify circuits
Circuit Two
(white recept.)
Wht
Receptacle
ground
Pull out pigtails, identify circuits.
NOTE: Factory installed push-in connectors suitable for SOLID wire ONLY. For stranded wire remove
and discard push-in connectors and use wire nuts or other suitable connectors (not included).
Blk
Green
Wht
Red
Chassis ground
(enclosure bonding)
Green
12-3 MC or equiv. with
appropriate connector
Connect all
grounds together
P/N 16099
pg 2 of 2
Printed in U.S.A. © 10-09-08
Multi-wire branch circuit (shared neutral)
Circuits must be on opposite phases to prevent neutral oveload.
Red
Chassis ground wire
Green
Blk
Lowell Manufacturing Company • 100 Integram Drive • Pacific, Missouri 63069 U.S.A. Cal l 800 .325. 966 0, 636. 257 .3400 • Fax 6 36. 257.6 606 • Click w ww.l owe llmfg .co m
Blk
Attach cover
Wht
Wht
connected to safety
ground
Tuck wires inside chassis and
re-install cover assembly
Independent circuits and isolated ground
12-3 MC or equiv. with
appropriate connector
Red
Wht
Wht
Green
Blk
Wht
Pigtails at opposite end can be
utilized as feed-through to
connect additional power strip.
Green w/yellow strips
Isolated ground
connected to
Green
receptacle ground
wire