Lotus LTS-3HP Installation And Operation Manual

Installation and Operation Guide
Model #: LTS-3HP
3.5kW / 120V
Note: Restricted to sink applications only. Please read manual
completely prior to installing your unit to understand if this
unit is suitable for your application.
Safety Instructions
OVERVIEW
Atmor will not be liable for any damages because of failure to comply with the installation and operating instructions outlined in this manual or because of improper use. Improper use includes the use of this appliance to heat any liquid other than
Failure to comply with the installation and operating instructions or improper use voids the warranty. Never
water.
remove the unit’s cover unless the electricity is turned off.
01
The water heater must be installed by a licensed electrician and in compliance with all local electrical and building regulations.
04
The heater must be installed according to the installation instructions (see figures).
07
The plumbing installation requires metal or reinforced pipes that can withstand a minimum pressure of 8 bar. (Other types of pipes will cause damage.)
02
Caution: The appliance must be grounded.
05
The plumbing installation must be completed before the electrical installation.
08
Do not install the heater where it may be subjected to direct sunlight, rain and/ or a constant spray of water.
03
A dedicated circuit breaker must be installed on the power distribution panel.
06
The heater operates at a minimum water flow rate of
0.5 gallon/minute.
09
Always contact your local authorized licensed proffessional for service.
1
Technical Information
Circuit breaker
Model Wattage Voltage Amperage Phase
LTS-3HP 3.5 kW 120 27 1 30 10 AWG
Minimum water flow to activate unit: 0.5 GPM Nominal water volume: 0.11 gal (0.42l) Working pressure: 0.5 -8 bar (7 -115 psi) Tested pressure: 16 bar (230 psi) Water connections: 1/2” NPT Dimensions (in) (H x W x D): 7.2 x 11.8 x 4.3 Weight (Ib): 3.4
size
Model Guide - kW Output
Model 120V 110V
LTS-3HP 3.5 kW 3.0 kW
Wattage based on maximum voltage.
Required wire
size
2
Assembly Instructions
01
Connect the Pressure Relief Device (PRD) to the unit (Fig1) Note:
IMPORTANT – do not discard this step. A PRD must be installed.
Mount unit to wall with 4 screws at the marked points (Figure 4)
04
The appliance must be mounted horizontally, with water inlets and outlets at the bottom (Figure 5)
Connect the water inlet hose to the entry point of the heater (left side inlet), and connect the outlet hose to the water outlet. Use a hose that can withstand a minimum pressure of 4 bars. Using any other type of hose will cause damage (Figure 5).
05
Residential plumbing systems with unstable pressure or pressure above 5 bar require the application of a pressure stabilizer valve, set to 4 – 5 bars.
Do not install the appliance with water inlets and outlets at the top (Figure 6)
02
Remove the appliance covers (Figure 2).
03
1. Mount ground plate to wall.
2. Pull wires through.
3. Cut out hole in back of unit (Right/Left back) and pass wires through
(Figure 3)
06
3
N
L1G
1
Rubber
PRD
Cold Hot
2
*
3 4
3
3.5kW
G = Green or Yellow N = White L1 = Black
65
L1GGN
L1
N
4
07
Run the water flow for one minute to check for leakage before connecting to power.
Reattach the front cover of the heater and secure it with 4 screws and then slide the bottom gray cover
08
11 12
When installed outdoors, the heater must be placed in sealed waterproof electrical box.
Connect the power cable to the terminal block. Caution: The heater must be grounded. Reference figure *3 on page 4 and Electrical diagram on page 6
1009
Make sure that the appliance is filled with water before connecting power. (Repeat step 7)
Do not install the heater where it may be subject to direct sunlight.
13
5
It is recommended that the appliance electrical connections be tested once a year by a qualified technician.
Electrical Diagram
3.5kW (120V)* - Install Line 1 (L1), E(G)-Ground, N (Neutral)
1
L1
E(G)
N
1. Terminal block
2. Thermal cut-out with reset
3. Thermal cut-out
4. Light
5. Switch On / Off
6. Relay
7. Heating element
8. Read sensor
* 3.5kW/120V = 3.0kW/110V
6
Operation Guide
Flow Rate Chart
35º F Temp Rise - 0.6 GPM 45º F Temp Rise - 0.5 GPM
Troubleshooting
PROBLEM ISSUE POSSIBLE CAUSE SOLUTION
Water not hot enough.
Water too hot. Not enough water flowing through the heater.
Too much water flowing through the heater.
Reduction in the ambient temperature.
Water Pressure below of
0.5 bar (7 psi).
Electrical Malfunction.
Increase in the ambient temperature.
7
Reduce the flow rate of the water via the outlet tap.
Switch to higher temperature setting.
Check if the main water line stop valve is fully open and that there are no other restrictions in the water supply line.
Have the Heater unit check by a qualified eIectrician or contact your local authorized distributor.
Increase the flow rate via the outlet tap.
Switch to lower temperature setting.
Loading...
+ 16 hidden pages