Loreme RPS23, RPS23/R2, RPS23/S1, RPS23/R4, RPS23/R3 Configuration Handbook

...
E 1
PROGRAMMABLE
DC OVER CURRENT PROTECTION RELAY
LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3
Phone 03.87.76.32.51 - Telefax 03.87.76.32.52
Contact : Commercial@Loreme.fr - Technique@Loreme.fr
Download manual at : www.loreme.fr
RPS23
CONFIGURATION HANDBOOK
E 2 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr
Table of contents
DEVICE PRESENTATION ......................................................................................................................................... p3
CONFIGURATION .................................................................................................................................................... p3
1) Thermal protection configuration ............................................................................................................ p4
2) Relays configuration ................................................................................................................................. p5
3) Analog outputs configuration .................................................................................................................. p6
RS232 LINK SETTING ............................................................................................................................................. p7
FIRMWARE UPDATE ............................................................................................................................................... p8
EMC CONSIDERATION ........................................................................................................................................... p9
1) Introduction ............................................................................................................................................... p9
2) Recommendation of use .......................................................................................................................... p9
2.1) General remarks .......................................................................................................................... p9
2.2) Power Supply ............................................................................................................................... p9
2.3) Inputs / Outputs ........................................................................................................................... p9
WIRING ...................................................................................................................................................................... p10
FRONT FACE CONFIGURATION DIAGRAM ......................................................................................................... p11
SOMMAIRE
E 3
Device Presentation
The purpose of the RPS23 is to protect a load against DC over-current heating by the utilization of an inverse time cur­rent characteristic. The device has a mV DC voltage input, ranging from 0 to 2000 mV over 2 calibers (0/250 mV & 0/2000 mV), automatically selected according to the configuration of the nominal voltage. To measure a current, an ex­ternal shunt has to be used. The current measured and displayed is signed but the protection function is carried out on the absolute value of the measurement. The relay is entirely configurable via the front face keys and display. It can be equipped with 1 to 4 relays and 1 to 2 analog outputs. Relays 1 and 2 are affected to the thermal protection, relay 3 to nominal current overflow detection and relay 4 is the watchdog relay. The watchdog relay is normally closed and LED R4 is off. When a default is detected (internal measure error), the watchdog relay is open and LED R4 is ON. In normal operation, the RPS23 displays the value of the measured current (see configuration). When a default is de­tected, the device display the following messages:
- "Err" for sensor break or internal measure failure.
It is necessary to notice the differences between all the models:
RPS23: 1 relay (thermal protection). RPS23/R2: 2 relays (thermal protection). RPS23/R3: 3 relays (idem R2 + nominal current overflow alarm). RPS23/R4: 4 relays (idem R3 + watchdog). RPS23/S1: 1 insulated analog output RPS23/S2: 2 insulated analog outputs, independently configurable.
The technical data sheet is downloadable here: http://www.loreme.fr/fichtech/RPS23_eng.pdf
CONFIGURATION
Pressing the upper key permit to access the configuration.
For each rubric, a message is streaming on the display and the <YES> key permits to access the rubric and the <NO> key to skip it. For a choice selection, the <YES> key validate the choice and the <NO> key invalidate it or pass to the next choice.
During an adjustment procedure, the upper key increment the value and the lower key decrement the value and the re­lay 1 LED is flashing. All the parameters are limited excepted the nominal current (LOW or HIGH is displayed on over­flow). The adjustment procedure is terminated automatically after 4 seconds if no key is pressed.
The message "OK !" is displayed at the end of the configuration after all the parameters have been memorized. If the configuration is stopped before the message "OK !" appears, the newly configured parameters are not saved.
Connector for relays 1 & 2, outputs and power supply.
Power present LED.
4 digits display (current value)
Relay 1 alarm LED (thermal protection). Relay 2 alarm LED (thermal protection).
Relay 3 alarm LED (nominal current).
Relay 4 alarm LED (watchdog).
Cover
Connector for voltage input & relays 3, 4.
Configuration access
or
YES key
or
increment key (+)
NO key
or
decrement key (-)
RPS23
Stereo Jack for the RS232 link
SOMMAIRE
E 4 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr
Configuration via the front face
1) Thermal protection configuration
In this rubric, the user can set the different thermal protection parameters.
1.1) Nominal Voltage (mV)
The nominal voltage is the voltage trip point for the relay. It is used in the calculation of the trip time, and can be config­ured from 0 mV to 200 mV. Usually this value should be set to the value of the measurement shunt caliber. For example 50mV for a 50 mV / 500 A shunt. The scale of the input is equal to 10 times the nominal voltage. For example, for a nominal voltage = 50 mV, the input range will be 0/500 mV so the RPS23 will switch its input high caliber 0/2000 mV.
1.2) Nominal current (A)
This parameter is normally set to the current rating value of the measuring shunt. E.g. 500 A for a 50 mV / 500 A shunt. It may also be configured to the value of Unominal / Rshunt if the configured nominal voltage is not the nominal shunt voltage. It serves as a:
switching threshold for relay 3 (over current detection). display scale for displaying the current measurement. measurement scale for the calculation of the analog output.
1.3) Measure filter
In some noisy environment, it is necessary to filter the input signal. This parameter is the coefficient of the digital filter included in the device. By increasing the value, the response time of the filter is increased and thus the response time of the device. If the value is zero, there is no filtering. The parameter can be configured from 0 to 50 in 0.1 steps.
1.4) Thermal equations coefficients
The coefficients K, R, a, b, c used in the calculation of the thermal image are entirely configurable to adapt the relay to quiet any protection curve. The relay uses the equation 1 for heating and the equation 2 for cooling:
1) t = K x ( a / ((U / Unom)^b - 1) + c), for (U/ Unom)^b > 1.
2) t = K x R / ((U / Unom)^b - 1), for (U/ Unom)^b < 1.
1.4.1) K coefficient
The K coefficient can be configured from 0 to 50 in 0.1 steps.
1.4.2) R coefficient
The R coefficient is used in the cooling equation. It can be configured from 0 to 100 in 0.01 steps.
1.4.3) a coefficient
The a coefficient can be configured from 0 to 100 in 0.001 steps.
1.4.4) b coefficient
The b coefficient is the power factor of thermal equations. It can be configured from 0 to 3 in 0.001 steps.
1.4.5) c coefficient
The c coefficient can be configured from 0 to 10 in 0.001 step.
See table next page for some examples of coefficient values for different thermal protection.
Remark:
RPS23 Timing accuracy:
Within ±5% or ±300ms whichever is greater. This is true when the “measure filter” is set to 0. Increasing the “measure filter” parameter will increase the tripping time of the relay.
SOMMAIRE
E 5
2) Relays configuration
The relays 1 to 3 are independently configurable. Relay 1 and 2 goes into alarm state when the calculated thermal im­age exceeds the trip point and goes out of alarm when the thermal image falls below the trip point minus hysteresis. Relay 3 goes into alarm state when the measured current exceeds the nominal configured current and goes out of alarm when the current falls below the nominal current minus hysteresis.
For each relay, the programmable parameters are:
- The hysteresis,
- The security,
- The activation and de-activation delay.
The hysteresis is set in % of thermal trip point for relay 1 and 2, and in % of the nominal current for relay 3.
The security parameter allows to choose between the activation or the de-activation of the relay when alarm is activated:
- in positive security, relay is switched on when alarm is active, "work" contact is closed on alarm, opened out of alarm, "rest" contact is opened on alarm, closed out of alarm.
- in negative security, relay is switched on when alarm is inactive, "work" contact is opened on alarm, closed out of alarm, "rest" contact is closed on alarm, opened out of alarm.
The delay value, configurable from 0 to 30 s, determines the time above which alarm changes its state after event ap­pearance and disappearance. For each relay, the user can configure an activation delay and a deactivation delay.
Default factory setup is:
- Hysteresis = 2%,
- Positive security,
- Delays = 0 s.
Factory output default value
SOMMAIRE
E 6 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr
3) Analogs outputs configuration
In standard, the device has no output. It can, by /S1,/S2 options, provide 1 or 2 outputs. These outputs, insulated be­tween themselves, are independently configurable. Analog outputs configuration is presented through 2 rubrics:
- Output type:
- current output (mA),
- voltage output (V). And for each output type, the low and high scale.
- Output parameters:
- security value,
- limitation,
- response time.
The security value allows to set the output to a known state when there is a sensor breaking or a measure range over­flow. This value will be transferred to output.
The limitation allows to bound the output signal swing to the configured output scales for all input signal values. Only security value goes beyond this function.
The response time allows a smoothing of the output. It is adjustable from 0 to 60 s.
Default factory setup is:
- 4 to 20 mA current output,
- Security value = 22 mA,
- No limitation,
-Response time = 0 s.
Switched off Switched on
Inactive
Event
Alarm
Relay in + security
Relay in ­security
Delay
Delay before activation
Delay before de-activation
active
Switched off Switched on
Event time measure is reseted
after event disappearing
SOMMAIRE
E 7
RS232 link setting
Enter name for the new connection
Start a "hyper Terminal" connection :
- Click on "START" button Up to XP version
- Go to "Programs \ Accessories \ Communication \ Hyper Terminal"
- Click on "Hypertrm.exe" Or if the software was downloaded
- Go to "All programs \ HyperTerminal Private Edition"
- Click on "HyperTerminal Private Edition"
Choose:
- 9600 bauds
- 8 DATA bits
- no parity
- 1 stop bit
- XON/XOFF
The device can be configured or updated in terminal mode via an RS232 link.
Step 1: Driver installation for USB / RS232 adapter
- download driver at www.loreme.fr: http://www.loreme.fr/aff_produits.asp?rubid=53&langue=fr
- Click on executable file to install the driver,
- Plug the cable on a USB port, Windows install a new serial communication port COMx (x >= 4).
Note :
The use of the cable on another USB port don’t generates a new communication port.
Use of another adapter generates another communication port number (COMx) and re­quires the reconfiguration of the hyperterminal.
The terminal emulation software for PC « HyperTerminal » is resident in windows up to XP version. For later ver­sions, it is downloadable on : www.loreme.fr in download part ( http://www.loreme.fr/HyperTerm/htpe63.exe )
=> Run the downloaded software to install it.
1
Step 2: Setting of terminal emulation software (PC with windows).
2
3 4
5
Choose the communication port related to the adapter.
The PC is now in terminal mode, connect it to the device by plugging the RS232 cable. The measure is now dis-
played on the terminal. To access configuration, press ’C’ key.
6
7
Note: to modify the parameters of terminal mode whereas this one is already started, it is necessary, after having car­ried out the modifications, to close the terminal and to open it again so that the modifications are effective.
When leaving Hyper terminal, the following window will appear. By saving, the terminal session will start with the same configuration.
Thus, the shortcut will permit to communi­cate with all LOREME devices.
SOMMAIRE
E 8 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Technique@Loreme.fr
FIRMWARE update
To access to the firmware update function, you must first open an HyperTerminal session on a PC, connect the device to the PC with the RS232 link cable and then power on the device.
The following character is send to the terminal:
> <———————— The device sends this character then it waits the « F » key during 0.5 s.
If the user has pressed the « F » key in the allowed time, the following message is displayed in the HyperTerminal win­dows:
FIRMWARE LOADER Rev2 READY TO TRANSFER...
The device is now in the firmware load mode and is waiting for the firmware file. This file is provide by LOREME and contain the firmware code in Intel HEX format.
Select the « Transfer », « Send a text file ... » in the HyperTerminal menu. Select the directory and open the file. The HyperTerminal program begins to send the file to the device.
FIRMWARE LOADER Rev2 READY TO TRANSFER *********** <———————— The star characters appears to show the progress of the uploading.
At the end, the message « PROGRAMMING OK ! » is display if no errors occurs. Otherwise, these following message could be displayed:
- SERIAL COM ERROR ! Error during receipt.
- SERIAL TIMEOUT ! Waiting time of receipt elapsed (60 s).
- PROGRAMMING FAILED ! Programming error in the internal flash memory.
Attention
If an error occurs during the programming process, it is necessary to start again the whole procedure. A bad programming leads to an inoperative or bad operative device.
SOMMAIRE
E 9
1) Introduction To meet its policy concerning EMC, based on the Community directives 2014/30/EU & 2014/35/EU, the LOREME company takes into account the standards relative to this directives from the very start of the con­ception of each product. The set of tests performed on the devices, designed to work in an industrial environment, are made in accor­dance with IEC 61000-6-4 and IEC 61000-6-2 standards in order to establish the EU declaration of confor­mity. The devices being in certain typical configurations during the tests, it is impossible to guarantee the re­sults in every possible configurations. To ensure optimum operation of each device, it would be judicious to comply with several recommendations of use.
2) Recommendations of use
2.1 ) General remarks
- Comply with the recommendations of assembly indicated in the technical sheet (direction of assembly, spacing between the devices, ...).
- Comply with the recommendations of use indicated in the technical sheet (temperature range, protection index).
- Avoid dust and excessive humidity, corrosive gas, considerable sources of heat.
- Avoid disturbed environments and disruptive phenomena or elements.
- If possible, group together the instrumentation devices in a zone separated from the power and relay cir­cuits.
- Avoid the direct proximity with considerable power distance switches, contactors, relays, thyristor power groups, ...
- Do not get closer within fifty centimeters of a device with a transmitter (walkie-talkie) of a power of 5 W, be­cause the latter can create a field with an intensity higher than 10 V/M for a distance fewer than 50 cm.
2.2 ) Power supply
- Comply with the features indicated in the technical sheet (power supply voltage, frequency, allowance of the values, stability, variations ...).
- It is better that the power supply should come from a system with section switches equipped with fuses for the instrumentation element and that the power supply line be the most direct possible from the section switch.
- Avoid using this power supply for the control of relays, of contactors, of electrogates, ...
- If the switching of thyristor statical groups, of engines, of speed variator, ... causes strong interferences on the power supply circuit, it would be necessary to put an insulation transformer especially intended for instru­mentation linking the screen to earth.
- It is also important that the installation should have a good earth system and it is better that the voltage in relation to the neutral should not exceed 1V, and the resistance be inferior to 6 ohms.
- If the installation is near high frequency generators or installations of arc welding, it is better to put suitable section filters.
2.3 ) Inputs / Outputs
- In harsh conditions, it is advisable to use sheathed and twisted cables whose ground braid will be linked to the earth at a single point.
- It is advisable to separate the input / output lines from the power supply lines in order to avoid the coupling phenomena.
- It is also advisable to limit the lengths of data cables as much as possible.
EMC Consideration
SOMMAIRE
E 10 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-
Wirings
3.5 stereo
jack plug to
device
STANDARD LINK
IN FRONT FACE
9 pins
Sub-D to Terminal
mV input from: terminal A (+), terminal E (-) external shunt
Analog output 1: terminal K (+), terminal L (-) (Terminals K & shunt must be closed for voltage output) Analog output 2: terminal P (+), terminal N (-) (Terminals P & shunt must be closed for voltage output)
Relay 1: terminal R1 (rest), terminal T1 (work), terminal C1 (common) Relay 2: terminal R2 (rest), terminal T2 (work), terminal C2 (common) Relay 3: terminal T3, terminal C3 Relay 4: terminal T4, terminal C4
Power supply: terminal G, terminal H
SOMMAIRE
E 11
Front face configuration diagram
Next Page
NOMINAL (mV)
XXXX
( value adjustment
with UP/DOWN buttons)
000.0
PROTECTION CONFIG?
BP UP
Up button = Yes Down button = No
Yes
Yes
No
No
NOMINAL CURRENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
MEASURE FILTER
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
K COEFFICIENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
R COEFFICIENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
Next Page
SOMMAIRE
E 12 LOREME 12, rue des Potiers d'Etain - 57071 Metz 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: Commercial@Loreme.fr - Techni-
Next Page
Up button = Yes Down button = No
a COEFFICIENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
b COEFFICIENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
c COEFFICIENT
XXXX
( value adjustment
with UP/DOWN buttons)
Yes
No
SOMMAIRE
E 13
No
No
Yes
RELAY CONFIGURATION? RELAY x?
Yes
No
Yes
HYSTERESIS?
Value
Setting
Yes
No
POSITIVE
SECURITY?
NEGATIVE
SECURITY?
ACTIVATION DELAY?
Value
Setting
Yes
No
DEACTIVATION DELAY?
Value
Setting
Yes
No
Yes
OK ?
Yes
Yes
Yes
OUTPUT CONFIGURATION?
CURRENT?
VOLTAGE?
Low and high
scale
adjustment
block
OUTPUT LIMITATION?
OUTPUT x?
No
No
Yes
Yes
SECURITY VALUE?
RESPONSE TIME?
Value
Setting
Value
Setting
No
No
No
Yes / No
Loading...