Lomanco IB-8 User Manual

OMANCO
®
8" Turbine Vent
Model IB-8 Installation Instructions
1
turbine turns freely. If necessary, minor adjustment may be made by gently prying lowest point of turbine upward to remove any wobble.
4
shingles. Secure with nails at top, sides and bottom.
Before installing, check to see that
Slide top half of flashing under
2
rafters and mark hole to be cut. Locate rafters by tapping roof. 8" turbine base, model VP-8, is sold separately.
5
screws on the barrel; rotate and adjust until the top sits in vertical and level position.
Set the base in position; loosen
Cut hole as marked. Seal around
3
entire perimeter of hole with roofing cement.
6
tighten as shown with screw, included with 8" turbine base, model VP-8.
Place locking clamp across seam and
7
base/elbow connection seam on inside with roofing cement. Seal locking clamp holes and all exposed nails with roofing cement.
Seal the adjusting seam and the
LIMITED WARRANTY
Lomanco, Inc. warrants this product for five (5) years against defects due to workmanship, parts or mechanical failure. For warranty service, the defective product must be sent, freight prepaid, to Lomanco, Inc., 2102 West Main Street, Jacksonville, AR, 72076. If the unit is found to be defective, it will be replaced with a new unit at no charge and returned, freight prepaid. This warranty does not include replacement due to destructive storms. ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE ALSO LIMITED IN DURATION TO FIVE (5) YEARS; CONSEQUENTIAL DAMAGES TO PROPERTY RESULTING FROM A BREACH OF ANY WARRANTY MENTIONED HEREIN ARE EXPRESSLY EXCLUDED. Some states do not allow limitations on how long an implied warranty last or do not allow exclusion or limitations of consequential damages, so the above limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
GUARANTEE APPLIES TO RESIDENTIAL ATTIC USE ONLY AS AN EXHAUST VENT IN A BALANCED
VENTILATION SYSTEM.
GUARANTEE IS VOID IF USED ON FIREPLACE, CHIMNEY, STOVEPIPE OR ANY APPLICATION OTHER
THAN AS INTENDED BY LOMANCO.
8
base. Line up the predrilled holes in the brackets and elbow and fasten with sheet metal screws.
Position the turbine head on the
1.800.643.5596 • Lomanco, Inc. • www.lomanco.com
9
that turbine vent turns freely. NOTE: This turbine vent can be installed on exisiting galvanized or aluminum turbine bases of appropriate size.
After installing, check again to see
Tools Needed:
• Screwdriver
• Level
• Jig Saw
• Putty Knife
• Utility Knife
• Drill
• Hammer
• Tape Measure
20450_1212
OMANCO
®
How To Locate and Space
IB-8 Turbine Vent
1/4
Back of House
1/4
Proper Spacing With Two
Turbine Vents Installed
Turbine vents should be located near the peak of the roof on the rear slope, exposed to the wind from all directions. When installing two, place each one ¼ of the total length of the roof peak from each end of the house.
Example: On a 40' roof, each turbine vent should be 10' from each end of the house.
Turbine vents should be located near the peak of the roof on the rear slope, exposed to the wind from all directions. When installing three, one should be installed 1/6 of the total length of the roof peak from each end of the house and one should be installed in the center.
Example: On a 60' roof, the two outside turbine vents should be 10' from each end of the house – and the center one should be 30' from either end of the house.
1/6 CENTER 1/6
Back of House
Proper Spacing With Three
Turbine Vents Installed
A Properly Ventilated Attic Must
Have Intake and Exhaust Vents
DO’S AND DON’TS FOR
ATTIC VENTILATION.
DO install all Exhaust Ventilation at the SAME
HEIGHT within a common attic area.
Installation of exhaust vents at more than one level on a roof allows the upper exhaust vent to wrongly pull air in from lower exhaust vent rather than from the sot Intake Vents.
DON’T install exhaust vents at dierent heights. DON’T install Ridge Vents down the hip. DO install ONLY ONE TYPE of Exhaust
Ventilation within a common attic area. Exhaust Vents pull air from the easiest Intake source. The use of two or more types of exhaust vents such as Power Vents with Roof Vents or Gable Vents with Ridge Vents or Roof Vents could make one of these vents act as intake instead of pulling air from the sot vents.
DON’T mix dierent types of exhaust vents. DO install a BALANCED SYSTEM of Intake and
Exhaust Ventilation. 50% Intake and 50% Exhaust is a balanced system. Improper intake may lead to snow or rain inltration into the exhaust vents.
Stale, Moist Air Out
Front of House
Back of House
Insulation
IMPORTANT Do not cover turbine vents in colder months. Turbine vents will help remove damaging moisture present in all attics. If this moisture is not removed, it could condense and ruin your insulation.
Make Sure Insulation Material Does Not Block intake Vents
Intake Sot Ventilator
Fresh Air In
1.800.643.5596 • Lomanco, Inc. • www.lomanco.com
20450_1212
Loading...