Locknetics 390DEL, DEL 390-2 Installation And Programming Manual

390/390-2 DEL
MAGNETIC LOCKING SYSTEM
INSTALLATION AND PROGRAMMING
1
Form 39990 Rev. E 09/23/2005
575 Birch Street, Forestville, CT 06010
Phone (866) 322-1237 Fax (866) 322-1233
WWW. LOCKNETICS .COM
DELAYED EGRESS
MAGNETIC LOCKING SYSTEM
PLEASE READ ALL INSTRUCTIONS PRIOR TO INSTALLING THE ELECTROMAGNETIC LOCK.
HANDLE THE EQUIPMENT CAREFULLY, DAMAGING THE MATING SURFACES OF THE
ELECTROMAGNET OR THE ARMATURE MAY REDUCE LOCKING EFFICIENCY.
General Description............................................. 2
Technical Specifications.......................................2
Pre Installation Considerations............................3
Mechanical Installation.........................................4
Template Information............................................4
Wiring Information/Board Layout......................... 8
Terminal Layout/Dipswitch Settings..................... 9
100CAB/TR80/TR81 Hook-up..............................9
390-2 (Double Unit) Wiring Information.............. 10
Monitoring/Control Wiring and Examples.............11
Programming - General Information.................... 12
Code/iButton Functions........................................12
Keypad Initialization.............................................13
“System 7” iButton Programming.........................13
Erasing Memory................................................... 13
Time Delay Settings............................................. 14
Automatic Relock Time Delay..............................14
Nuisance Alert Time Delay...................................14
Door Propped Open Alarm (SEC)....................... 14
Anti Tamper Switch Information...........................15
Keypad Manual Programming............................. 16
iButton Manual Programming.............................. 18
TEP1 Initialization................................................ 18
Output Audible/Visual/Alarm Indication Table...... 18
Maintenance.........................................................21
Trouble Codes......................................................21
Error Codes.......................................................... 21
Overall Dimensions..............................................22
IMPORTANT! This manual is intended to be kept for programming, maintenance, and trouble shooting purposes. Do not dispose of after installation. Please present this manual to facility manager upon completion of installation.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
2
Form 39990 Rev. E 09/23/2005
TECHNICAL SPECIFICATIONS:
Dual Voltage: 12 or 24 volts AC or DC (Automatic Voltage Selection) Max. Current: 0.8 Amps @ 12 Volts (DC) 1.5 Amps @ 12Volts (AC)
0.5 Amps @ 24 Volts (DC) 1.0 Amps @ 24Volts (AC)
Outputs:
Alarm: (standard) N.O. 1.0 Amp resistive load at 30V DSM: (optional) SPDT 200 mA @ 12V, 100mA@ 24V
MBS: (optional) SPDT 1.0 Amp resistive load at 30V Audible: 91 dB @ 2 feet Mechanical Holding Force: 1650 pounds
1500 pounds
UL listings:
SA8954 Special Locking Arrangements R12092 Auxiliary Locks
GENERAL DESCRIPTION: The electromagnet mounts rigidly to the door frame header. The armature mounts to the door. The armature is designed to pivot about its center compensating for door misalignment. When the door is closed the energized magnet will bond with the armature, providing auxiliary locking force. If the opening is fire rated, the door must be secured positively with a mechanical latching device, in addition to the magnetic lock, in accordance with local authority having jurisdiction. Locknetics manufactures fire rated mechanical latching devices. The electroni­cally controlled 390 DEL and 390-2 DEL series magnetic locks described in this manual share the same access con­trol circuitry. With optional access control input devices (Locknetics keypads or iButton readers) the locks can hold up to 150 codes or iButtons standard for access, toggle, lockout, or special functions. Dry contact inputs allow for fire alarm tie in and remote release/reset capabilities. This manual covers the mechanical installation, wiring, and manual programming aspects of the locks. For computer programming, see information provided with the software package you will be using.
THIS MANUAL COVERS THE 390 DEL AND 390-2 DEL, DEL
AYED EGRESS MAGNETS:
Delayed egress is initiated by a “plunger” switch which is actuated by a spring-loaded armature plate. By setting dip­switches, an auxiliary switch, such as an exit device or pushbutton, can be used as well. (See dipswitch/terminal lay­out on page 9.) The nuisance delay can be set from 0-3 seconds in the standard unit (fixed at 1 second in the BOCA unit). The delay time is generally fixed at 15 seconds, but, with approval of the local authority having jurisdiction, can be set to 30 seconds in the standard unit.
DESCRIPTION OF OPTIONS: DSM: Door Status Monitor will provide status of door with or without power applied. MBS: Magnetic Bond Sensor will provide status of lock (locked or unlocked) with or without power applied. SEC: Security Alarm will close alarm relay contacts if the door is forced open or after it is propped open for a selec-
table time period. (See page12). Anti tailgate is also in effect: the door will relock as soon as it closes, even if the relock time delay has not yet transpired. BOCA: Some areas adhere to this life safety code for delayed egress. The nuisance delay is fixed at one second and the delayed egress time at 15 seconds. After delayed egress has been initiated and the door opened, the alarm will automatically reset after 30 seconds and the door will relock. If the door is opened within the 30 seconds the timer will begin again. ATR: Audit Trail Retrieval uses computer programming and interrogation of the lock to store and retrieve the past 100 events such as access, alarm, and reset functions and the time that they occur.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
3
Form 39990 Rev. E 09/23/2005
The electromagnet should be mounted as near to the frame strike jamb as possible to provide maximum holding force. Visually check the mounting location to assure that the unit will mount without interference.
LHR
RHR
Wiring for the electromagnet must enter the top of the unit through the wire access hole drilled in the frame header (see template). Be certain provisions can be made to bring the wire through the header into the top of the unit.
Frame conditions may require the use of filler plates and/or angle brackets. These items are available from Locknetics.
Use proper mounting screws for your door frame. For light-gauge metal door frames, self tapping screws may be used. If the door frame is heavy-gauge metal, machine screws may be necessary and the holes will have to be tapped.
Caution: It is very important to make sure that magnet is secured to the structure of the opening.
Armature mounting hardware is for door thickness of 1-3/4 inches. For doors thicker than 1-3/4” consult your Locknetics distributor for availability of sex nuts.
PRE-INSTALLATION CONSIDERATIONS
DELAYED EGRESS LOCKS: Local codes generally require the signage, provided with the product, to be posted on
or near the door. Consult local authority having jurisdiction prior to any installation involving the use of delayed egress products to ensure life safety compliance.
FRAME STRIKE JAM
PAN HEAD FLAT HEAD
MACHINE SCREWS
SELF-TAPPING
SCREWS
When mounting two locks on one opening with or without a mullion, treat each installation separately. Use the template for each leaf. If the installation involves a 390-2 (master/slave magnet set) see important wiring information on pages 10 and 11.
FOR SEX NUTS FOR USE ON DOORS OTHER THAN
1-3/4”
CONSULT DISTRIBUTOR.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
4
Form 39990 Rev. E 09/23/2005
INSTALLATION PROCEDURE
A. The door should be closed and latched. You should be at the "push" side. Locate the paper template and fold
it along the perforated line with the printed sides facing each other. Place the template against the frame stop and the door. Tape template in place.
B. On the frame stop mark the location of holes "A" from the template. For heavy gauge or reinforced frames, drill and tap for #10-24 thread. For standard frames, drill 5/32" dia. for #10 self tapping screws. Locate and drill the 3/4" dia. wire hole. (The 3/4" dia. hole is oversized to the 5/8" dia. mounting plate hole to allow the full range of adjustability.)
C. On the doors, mark the locations of all holes. Drill (2) 1/4" dia. holes per template for armature holder mount­ing screws. Armature mounting hole "B" is determined by the door type (see below).
1. PREP DOOR AND FRAME:
The paper template is the preferable way to prepare the door and frame. If for any reason it is not available, use the dimensions shown below to mark the centerlines of the holes. Note that the layout is not symmetrical with respect to
the centerline of the armature.
HOLLOW METAL
DOOR
WOOD
DOOR
REINFORCED METAL DOOR
2. DRILL 1/2”
DIA. HOLE INTO SKIN OF DOOR ON SEX NUT SIDE ONLY. DO NOT DRILL THROUGH DOOR
.
1. DRILL 11/32” DIA.
HOLE THROUGH DOOR.
DRILL AND TAP FOR 5/16-18 MACHINE SCREW.
HEX KEY
FLAT WASHER (WOOD DOORS ONLY)
STAR LOCKING
WASHER
TAPERED WASHER
SEX NUT
DRILL 1/2” DIA THRU HOLE.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
5
Form 39990 Rev. E 09/23/2005
3. TEMPORARILY ATTACH MOUNTING PLATE TO HEADER
Slotted holes and counterbore should face downward. Mount to the frame using (2) #10-24 x ½" pan head machine screws, or (2) #10 x 3/4" pan head self-tapping screws, and #10 flat washers. Tighten screws just tight enough to allow shifting the plate during adjustment.
STAR LOCKING
WASHER
TAPERED WASHER
ARMATURE
HOUSING
2. MOUNT ARMATURE TO DOOR
Assemble using hardware provided in the order shown. All hardware shown must be used except where noted. Note that the tapered washer must be
placed with the pointed side facing away from the door and toward the armature. It MUST be used for proper operation. Use hex key to tighten the arma-
ture mounting bolt. For solid core and hollow metal doors, gently tap sex nut into position with a rubber mallet before mounting armature assembly.
Proper use of hardware will allow armature to pivot slightly after securely tightening the mounting screw. This is normal, and necessary to allow arma­ture to mate properly with magnet.
CAUTION:
Failure to secure armature to door may result in seri­ous injury to door user. For proper operation, safety and security, sex nut / bolt assembly, washers and spacers must be assembled in the order illustrated and securely tightened 1/8 to 1/4 turn past hand tight.
FLAT WASHER
(WOOD DOORS
ONLY)
#8 SHEET METAL
SCREWS (2)
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
6
Form 39990 Rev. E 09/23/2005
4. TEMPORARILY MOUNT TEMPLATE OR MAGNET TO MOUNTING PLATE
NO
YES
GAP
NO
GAP
Using 1/4-20 flat head screws, temporarily secure the plastic or metal template to the mounting plate, carefully passing the wiring through the hole in the template.
GAP
NO
GAP
NO
YES
5. ALIGN MAGNET WITH ARMATURE
With door closed and latched push magnet assembly (or template) toward the armature by applying pressure on each end of the magnet until fully mated together, as shown below. Mark the position of the mounting plate. Remove mag­net from the mounting plate without moving the mounting plate. (If using template, tighten two pan head screws through holes in template before removing it.) Tighten the slotted hole screws without moving the mounting plate to assure proper alignment.
CAUTION: Do not press on the PC board while moving the magnet. This could cause damage.
PUSH HERE TO
CLOSE GAP
PUSH HERE TO
CLOSE GAP
Make sure that the hole in the template lines up with the socket cap screw in the armature.
3/16”
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
7
Form 39990 Rev. E 09/23/2005
ACCESS COVER
DSM/SEC/BOCA
SWITCH CONTACT
LEADS
WIRE ACCESS HOLES
CONTROL WIRING
ANTI
-TAMPER PLUGS
7. SECURE MAGNET TO MOUNTING PLATE
Install the electromagnet to the mounting plate by tightening the captured 1/4-20 x 2" socket head cap screws with a 3/16" hex key. Firmly tighten the screws. Pass wiring through hole in top of magnet and through access hole on circuit board side of magnet as shown below. If the unit has DSM and/or SEC and/or BOCAthere will be up to two switch contacts with plug-in leads mounted on the access cover. Pass these leads through the access hole on circuit board side of magnet. Secure access cover. Drive in anti-tamper plugs using a rubber mallet.
NOTE: Double units with SEC2 or BOCA2: Do not switch covers between units. The wiring on each cover is different and doing so will cause improper operation.
6. SECURE MOUNTING PLATE
Using the Mounting Plate as a template, drill the four remaining mounting holes. Tighten two 10-24 self tapping pan head screws
If using #10 self-tapping, flat-head screws drill 5/32" dia. holes and drive four screws tight.
If using #10-24 flat head machine screws, drill and tap for #10-24 threads and tighten four screws.
CAUTION: It is critical that the screws used secure the mounting plate to the structure of the frame.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
8
Form 39990 Rev. E 09/23/2005
DSM2 (SEC/BOCA OPTION INPUT) N
OTE THAT THE CONNECTOR WILL
ONLY FIT ONE WAY.
KEYPAD/REMOTE IBUTTON READER INPUT TERMINAL
(TB9)
DSM1 (DSM
OPTION INPUT)
N
OTE THAT THE CONNECTOR WILL
ONLY FIT ONE WAY
.
SW4
(
DIP SWITCHES 1-8)
LED
ATR CHIP
(
OPTIONAL)
HORN
PLUG FOR IBUTTON READER ON COVER
DELAYED EGRESS INPUT
SWITCH
(FACTORY
ADJUSTED - DO NOT
ATTEMPT TO ADJUST)
ATS
JUMPER SETTING SHOWN FOR SINGLE
LOCK APPLICATIONS
. FOR DOUBLE
LOCK
(390-2), SEE PAGE 10 FOR
JUMPER SETTING
.
ANTI TAMPER
SWITCH
SW-2
SW-3
8. MAKE WIRING CONNECTIONS AND SET DIPSWITCHES
Connect wiring to main terminal strip. If furnished, connect DSM1 and DSM2 to board as shown. Note that if the unit has only the DSM option, connect the plug into the DSM1 jack. If the unit has only the SEC and/or BOCA option, con­nect the plug into the DSM2 jack. If the unit is to be used with a keypad (and the required 100CAB adapter cable) or a TR80 or TR81 see the programming information starting on page 10. After wiring, time delay setting, initialization and programming have been completed, secure the cover onto the lock, making sure to connect the iButton reader (DEL models). See illustration on page 15.
See next page (9)for terminal layouts and dipswitch settings. Not all terminals will be used in all cases. Note that to get the correct outputs, the correct options must have been ordered and the dipswitches set properly.
IMPORTANT: DO NOTAPPLY POWER UNTIL ALL CONNECTIONS HAVE BEEN MADE AND DIPSWITCHES SET AND VERIFIED.
DELAYED EGRESS INITIATION:
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
9
Form 39990 Rev. E 09/23/2005
AUTOMATIC RELOCK ON POWER-UP/FIRE ALARM RESET
DOOR FORCED/PROPPED ALARM (SEC REQUIRED)
UNLOCK ALERT (HORN SOUNDS WHENEVER DOOR IS UNLOCKED
ANTI-TAILGATE (SEC REQUIRED)
1 2 3 4 5 6 7 8
TERMINAL LAYOUT TB1:
POWER INPUT
12/24 VOLTS
AC OR DC (AUTOMATIC SELECTION)
DO NOT
APPLY
120 VAC
FIRE ALARM
INPUT
APPLYA
NORMALLY CLOSED DRY CONTACT OR
A JUMPER IF
NOT
CONNECTED
TO FIRE
ALARM
AUXILIARY
INPUT
(SEE
DIPSWITCH
SETTINGS
BELOW)
C NO
ALARM
OUTPUT
(STANDARD)
CONTACTS
CHANGE
STATE
DURING
ALARM
CONDITION
RELEASE
INPUT
DRY CONTACT CLOSURE
WILL
RELEASE
LOCK FOR
THE TIME
DELAY
PERIOD (SEE
PAGE 14)
RESET
INPUT
DRY CONTACT
CLOSURE
RESETS LOCK
IN ALARM
CONDITION.
NO C NC
DSM OUTPUT
(OPTIONAL)
CONTACTS CHANGE
STATE WHEN DOOR IS
CLOSED.
C NC NO
MBS OUTPUT
(OPTIONAL)
CONTACTS CHANGE STATE WHEN MAGNET IS PROPERLY BONDED
TO ITS ARMATURE.
POOR BOND CAN BE
CAUSED BY LOW
VOLTAGE, MISALIGN-
MENT OR DAMAGED
MATING SURFACES.
DELAYED EGRESS TIME:
15 SECONDS 30 SECONDS
ON
DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH ONLY.
DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH OR
AUX. INPUT.
DELAYED EGRESS TRIGGERED BY PLUNGER SWITCH AND AUX. INPUT.
DELAYED EGRESS DISABLED.
DISABLED
ENABLED
DISABLED
ENABLED
DOOR WILL RELOCK AS SOON AS ITCLOSES - EVEN IF THE RELOCK TIME DELAY HAS NOT ENDED.
POWER MUST STILL BE APPLIED TO TERMINALS 1&2. CODE/iButton, PIR, OR LEGAL RELEASE INPUT MUST BE TRIGGERED. AV AILABLE ON ALL MODELS.
DISABLED
ENABLED
WHEN ENABLED, LOCK WILL ENERGIZE UPON REGAINING POWER OR AFTER A FIRE ALARM CONDITION CLEARS.
NUISANCE ALERT
DISABLED
ENABLED
HORN SOUNDS DURING NUISANCE ALERT.
TERMINAL LAYOUT TB9:
IF YOUR SYSTEM USES A KEYPAD/READER WITH A 100CAB ADAPTER CABLE OR A
TR80
OR TR81, CONNECT THE WIRES
AS SHOWN. KEYPADS WILL NEED TO BE INITIALIZED
. SEE KEYPAD OR IBUTTON
PROGRAMMING FOR FURTHER INFORMATION.
DIPSWITCH SW-4 SETTINGS:
Set the dipswitches as required for your system.
SW-4
WHITE
BLACK
RED
SW4-4:
SW4-5:
DISABLED
ENABLED
FORCED: ALARM SOUNDS UNTIL RESET BY CODE/iButton OR RESET INPUT ON TERM. 17&18. PROPPED: AFTER PRE-SET TIME (SEE PG. 14 ) ALARM SOUNDS UNTIL DOOR CLOSES AGAIN.
SW4-6:
SW4-7:
SW4-8:
SW4-3:
SW4-2:
SW4-1:
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
10
Form 39990 Rev. E 09/23/2005
TO POWER
SUPPLY/MONITORING
STATION.
WIRING BETWEEN
UNITS
MASTER UNIT
SLAVE UNIT
DSM
/SEC
WIRE ACCESS COVERS
390-2 (DOUBLE UNIT) INSTALLATION AND WIRING INFORMATION
The electronic 390 series has the capability of operating two locks with the “brain” of one. The lock with the central processing unit is referred to as the “master” unit while the dependent one is referred to as the “slave” unit. The system can be run on 12 or 24 volts AC or DC. It does not matter which lock is on the left or right of an opening.
There are three, 36 inch cables furnished standard with a double unit and one which comes with the SEC or BOCA options which are intended to connect the locks, using plug-in connectors, to each other. They may be extended if necessary. If the units have SEC2 or BOCA2 options there will be a fourth cable which connects to the DSM2 cables as shown.
J11
CONNECTOR
(SLAVE ATS/SEC)
J10 CONNECTOR (SLAVE MAGNET)
J11 CONNECTOR
(SLAVE ATS/SEC)
WHITE WIRE BETWEEN UNITS
WHITE WIRE FROM DSM
2
SWITCH ON
COVER
BLACK WIRE FROM DSM2
SWITCH ON
COVER
RED
& BLACK WIRES
FROM DSM
2 SWITCH ON
COVER
RED
& WHITE WIRES
FROM DSM
2 SWITCH ON
COVER
IBUTTON READER
CONNECTION CABLE
(
PLUGS INTO COVERS
)
J10 CONNECTOR
(SLAVE MAGNET)
NOTE: JUMPER MUST BE SET AS SHOWN FOR 390-2 MASTER UNITS.
STANDARD
DOUBLE UNIT
WIRING
ADDITIONAL WIRING FOR
SEC2/BOCA2
OPTION
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
11
Form 39990 Rev. E 09/23/2005
MONITORING AND CONTROL SYSTEM WIRING INFORMATION AND EXAMPLES
Shown below are basic wiring examples for supplying power, monitoring lock, door and alarm status as well as fire alarm, auxiliary, release/reset and timer inputs. Note that most national codes require that magnetic locks become unlocked whenever a fire alarm condition exists. Consult authority having jurisdiction prior to installation to assure compliance with all local and national codes.
WIRING TRICK
RESET INPUT
RELEASE INPUT
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
12
Form 39990 Rev. E 09/23/2005
PROGRAMMING: GENERAL INFORMATION
Programming the electronic 390 model electromagnetic locking systems can be done either by computer program­ming or manually, using the keypad, or TEP1 programmer. The standard unit can have up to 150 codes and/or iButtons. Their functions can be chosen using software or by manually adding the code/iButton and function (see “DEFINITION OF CODE/IBUTTON FUNCTIONS AND FACTORY DEFAULTS” below). When manual programming, it is critical to keep a record of the people and codes/iButtons which are issued to them along with their functions and PIN numbers (for iButtons). This will enable the ability to manage the access system properly. The units come from the factory with preset factory default code (described below). When the lock is reset (memory erased) it will return to factory default codes and any keypad (using the 100CAB) or TEP1 will need to be initialized again. Initializing a mas­ter iButton, TEP1, or changing the master code, or computer programming, will erase the factory default codes.
When programming with a computer, it is possible to enable or disable manual programming. If manual programming is enabled, and a code is entered manually, the Audit Trail Report will be corrupted. The time delay functions can be entered using computer programming or by buttons located on the PC board. The manual setting of time delays will still be possible even if manual programming of codes and/or iButtons is disabled via the computer.
Additional codes and iButtons can only be programming in with a computer. They cannot be manually programmed in. The exception to this is “System 7” programming in which up to 7 iButtons can be added. With System 7 program­ming, the unit must have or be attached to an iButton reader, or a Locknetics keypad that has an iButton reader. The iButtons can be entered into the reader on the cover (See page 13).
DEFINITION OF CODE/iButton FUNCTIONS AND FACTORY DEFAULTS:
MASTER 97531 Allows access to programming functions. Will not release lock. NORMAL 13579 Unlocks lock for relock time delay. Will reset lock in alarm condition.
ACCESS TOGGLE 135135 Unlocks the lock until same or another Toggle Code is entered. LOCKOUT 9115 “Freezes” the lock in its present condition, either locked or unlocked, until the same or
another Lockout Code/iButton is entered.
ONE-TIME ACCESS No factory default. This type of code/iButton will allow access only once.
It will then become deleted from memory.
SUPERVISED ACCESS No factory default. This type of code/iButton allows access only when used with
another Supervised Access Code/iButton. The second code/iButton must be entered within five seconds of the first one. The order that they are entered does not matter.
FACTORY DEFAULT
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
13
Form 39990 Rev. E 09/23/2005
TO CREATE MASTER iButton (FOR USE WITH COMPUTER PROGRAMMING)
The master iButton is used to initialize programming (like a password to access programming mode).
A. Set SW4 dipswitch #1 to ON (if it is off). B. Press and hold SW3 until two beeps are heard. C. Touch a iButton key to the reader within ten seconds. The lock will indicate acceptance with two beeps.
This will be the Master iButton.
D. Return SW4, #1 to its original position.
NOTES:
1. Refer to instructions included with the programmer/software that you will use to program for more information regarding programming.
2. The Master iButton is used for initiating programming. It will not unlock the door.
“SYSTEM 7” PROGRAMMING:
This procedure will allow up to seven iButtons to be programmed into a lock equipped with an iButton reader or Locknetics keypad with an iButton reader. iButtons will be of the Normal Access type and will unlock the unit for the relock time delay. The iButtons will also reset the lock if it is in an alarm condition.
A. Set SW4-1 to OFF (if it is on) B. Press and hold SW3 until you hear two beeps. Release SW3. C. Touch each of the iButtons to the reader. Two quick beeps will sound each time a key has been accepted. D. After entering up to seven iButtons wait 10 seconds for programming to end. One quick beep will indicate
that programming has ended.
E. Return SW4-1 to its original position, if required. NOTE: Whenever new “System 7” iButtons are entered, the old ones are erased. Also, whenever computer program­ming is done, or memory is erased, all “System 7” iButtons are erased.
ERASE MEMORY
Memory may be erased to conveniently return to default time delay settings or if an error was made.
A. Press and hold SW2 until a single beep is heard. Release SW2.
B. Quickly press SW2 three times, three beeps will sound.
C. Another 3 beeps will sound in about 10 seconds indicating the memory is erased. NOTES:
1. All programmed codes and iButtons will be erased. Factory default codes and time settings will be restored.
2. Keypads w/100CAB will need to be initialized again.
KEYPAD/100CAB INITIALIZATION (REQUIRED TO ENABLE KEYPAD TO FUNCTION)
It is necessary to initialize the keypad/100CAB any time that the memory is erased.
A. Set SW4 dipswitch #1 to ON. B. Press and hold switch SW3 for two quick beeps of the audible.. C. Push each button in order, starting with the 1-2 button, and including the *.
* Wait for LEDs to stop flashing before pushing next button.
* Waiting for longer than 7 seconds will terminate initialization.
D. After the last button is pressed, the audible will beep three times and the LEDs will
flash indicating that programming has ended.
E. Return SW4 dipswitch #1 to its original position.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
14
Form 39990 Rev. E 09/23/2005
SETTING TIME DELAYS MANUALLY:
AUTOMATIC RELOCK DELAY (factory default: 8 seconds)
The amount of time the lock is de-energized after release. Programmable 1-30 seconds.
A. Set SW4 dipswitch #6 to OFF (if it is on). B. Press and release SW2. The LED will begin flashing GREEN . C. Thereafter, press SW3 once for each second of relock delay desired.
(ex. 3 presses equals 3 seconds-15 presses equals 15 seconds-Up to 30 seconds)
Each SW3 activation will cause the LED to flash RED and the horn to beep . D. Press SW2 and the relock delay will be stored in non-volatile memory. E. Return SW4 dipswitch #6 to its original position.
NOTES: 1. Not pressing SW3 between pressing SW2 will set the relock time delay to zero seconds. This
will cause the lock not to unlock with a momentary contact closure or valid code or iButton.
2. Models with the SEC option include the anti-tailgate feature. If SW4-4 is on, the lock will relock immediately when the door closes even if the time delay has not yet expired.
NUISANCE DELAY (factory default: 3 second)
The amount of time the door must be pushed before triggering the DELAYED EGRESS CYCLE Programmable 0 - 3 seconds. (BOCA Units are fixed at 1 second.)
A. Press and release SW3, the LED will begin flashing RED. B. Thereafter, press SW2 once for each second of nuisance delay desired, up to
3 seconds maximum. Each SW2 activation will cause the LED to flash GREEN and the horn to beep .
C. Press SW3 and the nuisance delay will be stored in non-volatile memory.
NOTES: 1. To program nuisance delay to zero, eliminate Step B.
2. Setting nuisance delay to zero will allow the lock to go into delayed egress the instant that it is pushed upon. This may prove inconvenient in some applications.
DOOR PROPPED DELAY (Units with SEC option only) (factory default: 60 second)
The amount of time the door must be propped open (after normal release time delay has ended) before triggering the alarm. The alarm will clear as soon as the door closes again. Programmable 0 - 120 seconds.
A. Set SW4-6 to ON (if it is off). B. Press and release SW2, the LED will begin flashing YELLOW. C. Thereafter, press SW3 once for each second of propped delay desired, up to 120 seconds maximum.
Each SW3 activation will cause the RED LED to flash and the horn to beep . D. Press SW2 and the door prop delay will be stored in non-volatile memory. E. Leave SW4-6 ON to enable door propped alarm.
NOTES: 1. To program door propped delay to zero, eliminate Step B.
2. Setting the door propped delay to zero will cause the lock to go into alarm the instant that the normal time delay has ended, if the door is still open.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
15
Form 39990 Rev. E 09/23/2005
ANTI TAMPER SWITCH - IMPORTANT NOTE:
The electronic 390 models come standard with the ATS (Anti Tamper Switch). When the cover is removed, the alarm will sound. It can be reset either by momentarily shorting terminals 17 and 18, which is the reset input, or by entering a valid keypad code or iButton. If power is applied while the cover is off, the alarm will not sound. Putting the cover on or depressing the ATS switch will arm it. If the ATS switch is not working properly, check the setting of the jumper (see pages 8 & 10).
ANTI TAMPER
SWITCH
PLUGTOUCH READER INTO PC BOARD AND SECURE LOCK COVER
TERMINALS
17&18
ATS
JUMPER
MASTER
MASTER (OR SINGLE LOCK)
SLAVE
WIRING TO PASS THROUGH FRAME
PLUG THIS END INTO BOARD AS SHOWN
PLUG CABLE ENDS INTO PC BOARDS AS SHOWN
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
16
Form 39990 Rev. E 09/23/2005
TO ADD NORMAL ACCESS CODES -
Will unlock door for relock time delay period. Will also reset lock after an alarm condition.
Master Code *...3 *...New Code (3-8 digits) *...* (to end)
UP TO 150 NEW CODES CAN BE ADDED BY RETURNING HERE.
TO DELETE CODES Master Code *...5 *...Old Code *...* (to end)
MORE CODES CAN BE DELETED BY RETURNING HERE.
TO DELETE CODES WITH ALARM/ATR NOTICE: Codes will be not be allowed to function but will remain in memory. When the code is used, the lock will go into alarm, the alarm relay will close, the audible will sound and the LED will illuminate red. The door will not unlock. It will stay in alarm until a valid user code, iButton or reset input will silence the alarm. If the ATR option is pres­ent and the unit was programmed by computer, an access attempt will show in the audit trail.
Master Code *...55 *...Old Code *...* (to end)
MORE CODES CAN BE DELETED BY RETURNING HERE.
MANUAL PROGRAMMING - KEYPAD
When using a keypad to manually program a 390DEL, the keypad must first be initialized. It is a recommended that the factory default Master Code be changed. Doing so will delete all factory default codes and ensure the security of the system. After entering the Master code the LEDs on the keypad will flash. They will also flash each time that * is entered. Wait for the LED to stop flashing before entering the next sequence.
TO CHANGE MASTER CODE Master Code *...7 *...New Master Code (5-8 digits)*...New Master Code *
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
17
Form 39990 Rev. E 09/23/2005
TO ADD FUNCTION CODES (Note that a three digit function code sets the function of the user code)
Master Code *...33*...111*...New Access Code (3-8 digits) * ...* (to end)
UP TO 150 NEW CODES CAN BE ADDED BY RETURNING HERE.
OR
191*...New Toggle Code
OR
115*...New Lockout Code
OR
113*...New One-Time Access Code
OR
117*...New Supervised Access Code
TO CHANGE FUNCTION/CODES
Master Code *...11*...Old Code *... X Y Z *...New(or same) Code (3-8 digits) *...* (to end)
New or Same
3-digit function
code.See above.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
18
Form 39990 Rev. E 09/23/2005
TO ADD NORMAL ACCESS iButtons - Will unlock door for relock time delay period. Will also reset lock after
an alarm condition.
Master iButton...3 *...New PIN(3-8 digits)*...New Access iButton...* (to complete)
UP TO 150 NEW iButtons CAN BE ADDED BY RETURNING HERE.
MANUAL PROGRAMMING - iButtons
When manually programming the 390-2 DEL for iButtons, a TEP1 programmer must first be initialized. Only one pro­grammer can be initialized to a particular lock. A Master iButton must also be initialized at the same time as the pro­grammer and will be used to enter the programming mode. See steps below. After entering the Master iButton, the green LED on the iButton reader will flash. It will also flash each time that * is entered. Wait for the LED to stop flash­ing before entering the next sequence. The TEP1 programmer is intended to simulate a keypad.
PROGRAMMER INITIALIZATION TEP1
A. Set SW4 dipswitch #1 to ON. B. Press and hold switch SW2 for two quick beeps of the audible.. C. Touch a iButton key up to the reader. (This iButton will be initialized as a MASTER iButton.) D. Touch each iButton of the TEP1 to the reader in the following order(two beeps of the
audible will sound indicating acceptance of each key.)
* Wait for LEDs to stop flashing before touching next key or pushing next button.
* Waiting for longer than 7 seconds will terminate initialization.
E. After the last button is entered, the audible will beep three times and the LEDs will
flash indicating that programming has ended.
F. Return SW4 dipswitch #1 to its original position.
TO DELETE iButtons Master iButton...5 *...Old PIN*...* (to end)
MORE iButtons CAN BE DELETED BY RETURNING HERE.
TO DELETE iButtons (and with alarm/ATR notice): iButtons will not be allowed to function, but will remain in
memory. When the iButton is used, the lock will go into alarm, the alarm relay will close, the audible will sound and the LED will illuminate red. The door will not unlock. It will stay in alarm until a valid user code, iButton or reset input silences the alarm. When the ATR option is present and the unit was programmed by computer, an access attempt will show in the audit trail.
Master iButton...55 *...Old PIN*...* (to complete)
MORE iButtons CAN BE DELETED BY RETURNING HERE.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
19
Form 39990 Rev. E 09/23/2005
TO ADD FUNCTION iButtons (Note that a three digit function code sets the function of the user iButton)
Master iButton ...33*...111*...New PIN(3-8 digits)*...New Access iButton ...* (to end)
UP TO 150 NEW iButtons CAN BE ADDED BY RETURNING HERE.
OR
191*...New Toggle iButton
OR
115*...New Lockout iButton
OR
113*...New One-Time Access iButton
OR
117*...New Supervised Access iButton
TO CHANGE FUNCTION AND/OR PIN Master iButton ...11*...Old PIN*... X Y Z *...New(or same) PIN (3-8 digits) *...* (to end)
New or Same
3-digit function
code.See above.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
20
Form 39990 Rev. E 09/23/2005
The table below is intended to provide all possible indications and states which can be encoun­tered under normal operation. Note that some conditions or features are only available on certain models or when certain options are included.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
21
Form 39990 Rev. E 09/23/2005
TROUBLE SHOOTING:
Some common problems associated with the installation of the 390 series can be easily recognized and corrected:
Problem
: Possible Solution
:
Lock has power but won’t lock. Fire alarm not connected or open connection. SW4-7 not ON (set switch, LED (on lock) is Green. remove and re-apply power).
Won’t go into delayed egress. Check dipswitch settings (p.9). Armature washers not installed properly (p.5)
Magnet not properly aligned with armature. (p.6)
Goes into delayed egress upon powerup. Armature washers not installed properly (p.5)
Improper gap between magnet and armature (p.6) Lock can be pushed open with minimal resistance. Magnet/Armature/washers not installed properly (p.5-6). Lock “hums” or vibrates noisily when energized. Magnet/Armature/washers not installed properly (p.5-6). Lock “beeps” every several seconds. Low voltage alert. Check voltage at terminals 1&2. It must be 12.00 volts or
24.00 volts or slightly higher.
Won’t accept iButtons. iButton reader on cover not plugged in to board. (p.15) LED(s) flash once quickly. Relock delay set to 0 sec.(p.14)
Lock won’t accept programmed codes/iButtons. Relock time delay set to 0 sec. (p.14) LED(s) flash once quickly. Keypad not initialized (p.12).
MBS doesn’t change state when locked. Low voltage. Mechanical misalignment. Debris between lock and armature.
Armature/magnet not installed properly (p.5-6). DSM/SEC option not working properly. Armature holder not aligned with DSM/SEC switch(s). Switch not
plugged into correct jack (p.8)
MAINTENANCE
It is not recommended that the magnet be painted (unless ordered with in iridite primer). If the unit must be painted, it is important that the mating surfaces of the magnet and armature not be painted. The iButton reader and LED must not be painted either. The electromagnet and armature are plated for corrosion resistance and require little mainte­nance. For maximum performance the following service should be done to both the armature and electromagnet as required: Clean the mating surfaces of the electromagnet and armature with a non-abrasive cleaning pad, apply a light coating of silicon lubricant and wipe with a clean dry cloth.
ERROR CODES
NUMBER OF
FLASHES
ERROR NUMBER OF
FLASHES
ERROR
2
Code entered too long. Code length cannot exceed 8 digits.
6
Invalid command.
3
Memory full – too many codes/iButtons entered
7
Code does not exist. (For “Delete With Alarm/ATR” only)
4
Master code cannot be deleted, only changed.
8
Code too short. Minimum master code 5 digits. Minimum user code 3 digits.
9
Not a unique code/iButton.
5
Second entry of master code does not match first. Master code not changed.
10
Manual Programming disabled.
ERROR CODES:
If an error is made while manually programming a lock, an error code indication will be indicated at the iButton reader or keypad. The LED(s) will flash several times. Count the number of flashes and refer to the chart below for diagnosis.
390/390-2 DEL
MAGNETIC LOCKING SYSTEM
22
Form 39990 Rev. E 09/23/2005