Lochinvar WB-050 User Manual

KNIGHT® WALL MOUNT BOILER PRODUCT SUMMARY
(WB) 50,000 - 210,000 BTU/HR
WB-050 WB-080 WB-105 WB-150 WB-210
WATER
GALLON CAPACITY 0.6 0.6 0.7 1.3 1.7 HEATING SURFACE (SQ. FT.) 7.3 7.3 9.1 16.4 21.8 WATER CONNECTIONS 1” 1” 1” 1” 1” DRAIN 3/4” 3/4” 3/4” 3/4” 3/4” 20°F ΔT WATER FLOW (GPM) 5.1 7.5 9.8 14.0 19.6 HEAD LOSS (FT. OF HD.) 11.0 24.0 27.0 20.0 29.0 35°F ΔT WATER FLOW (GPM) 2.9 4.2 5.5 7.9 11.0 HEAD LOSS (FT. OF HD.) 4.1 7.3 9.8 10.0 10.1 MAX. WORKING PRESSURE (PSI) 160 160 160 160 160 # OF RELIEF VALVES 1 1 1 1 1 RELIEF VALVE SIZE 3/4” 3/4” 3/4” 3/4” 3/4” RELIEF VALVE RATING (MBH) 510 510 510 510 510 RELIEF VALVE PRESSURE RATING (PSI) 30 30 30 30 30
GAS
INLET CONNECTION 1/2” 1/2” 1/2” 1/2” 1/2” MAX. INLET PRESSURE, NAT 10.5” w.c. 10.5” w.c. 10.5” w.c. 10.5” w.c. 10.5” w.c. MIN. INLET PRESSURE, NAT 4.0” w.c. 4.0” w.c. 4.0” w.c. 4.0” w.c. 4.0” w.c. MAX. INLET PRESSURE, LP 13.0” w.c. 13.0” w.c. 13.0” w.c. 13.0” w.c. 13.0” w.c. MIN. INLET PRESSURE, LP 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. BTU/HR INPUT 50,000 80,000 105,000 150,000 210,000 BTU/HR OUTPUT (HIGH FIRE) 45,000 72,000 97,000 135,000 190,000 BTU/HR OUTPUT (LOW FIRE) 9,000 14,400 19,400 27,000 38,000
ELECTRICAL
VOLTAGE/HEATER 120 120 120 120 120 VOLTAGE/CONTROL 24 24 24 24 24 TOTAL AMPS 0.5 0.5 0.5 1.0 1.2 # OF ELECTRICAL CONNECTIONS 1 1 1 1 1
DIMENSIONS
HEIGHT 29-1/4” 29-1/4” 29-1/4” 29-1/4” 29-1/4” WIDTH 18-1/2” 18-1/2” 18-1/2” 18-1/2” 18-1/2” DEPTH 15-3/4” 15-3/4” 15-3/4” 20-3/4” 25”
SERVICE CLEARANCES
FRONT 24” 24” 24” 24” 24” BOTTOM 24” 24” 24” 24” 24” RIGHT SIDE 0” 0” 0” 0” 0” LEFT SIDE 24” 24” 24” 24” 24” TOP 6” 6” 6” 6” 6”
DIRECT VENTING
SIZE 2” 2” 2” 3” 3” VENT CATEGORY IV IV IV IV IV VENT MATERIAL PVC PVC PVC PVC PVC
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
WB-PS-03 (Replaces WB-PS-02 06/08)
www.Lochinvar.com
06/08-Printed in U.S.A.
Loading...