Lochinvar SYNC 1.0 User Manual

Installation & Operation Manual
Models: 1.0 - 1.3 - 1.5
This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the SYNC Service Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Save this manual for future reference.
SYNC-I-O Rev C
2
Contents
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
HAZARD DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PLEASE READ BEFORE PROCEEDING . . . . . . . . . . . . 3
THE SYNC -- HOW IT WORKS . . . . . . . . . . . . . . . . . . . . 4-5
RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1. DETERMINE BOILER LOCATION
Closet and Alcove Installations . . . . . . . . . . . . . . . . . . . . . 7
Provide Air Openings to Room . . . . . . . . . . . . . . . . . . . . . 9
Flooring and Foundation . . . . . . . . . . . . . . . . . . . . . . . . . 9
Vent and Air Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Prevent Combustion Air Contamination . . . . . . . . . . . . . . . 9
Corrosive Contaminants and Sources . . . . . . . . . . . . . . . 10
Removing a Boiler from Existing Common Vent . . . . . . . 10
Remove Boiler from Wood Pallet . . . . . . . . . . . . . . . . . . . 11
Combustion and Ventilation Air Requirements . . . . . . . . 11-12
2. GENERAL VENTING
Direct Venting Options - Sidewall . . . . . . . . . . . . . . . . . . 13
Direct Venting Options - Vertical . . . . . . . . . . . . . . . . . . . .13
Vertical Vent Optional Room Air . . . . . . . . . . . . . . . . . . . 14
Horizontal Vent Optional Room Air . . . . . . . . . . . . . . . . . 14
Install Vent and Combustion Air Piping . . . . . . . . . . . . . . 15
PVC / CPVC Vent Piping Materials . . . . . . . . . . . . . . 15
Requirements for Installation in Canada . . . . . . . . . . . . . 15
PVC/CPVC Air Intake/Vent Connections . . . . . . . . . . . . . 16
Stainless Steel Vent and Air Piping . . . . . . . . . . . . . . . . . 17
Min./Max. Combustion Air & Vent Piping Lengths . . . . . . 18
Removing from Existing Vent . . . . . . . . . . . . . . . . . . . . . 18
Vent and Air Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3. SIDEWALL DIRECT VENTING
Vent/Air Termination - Sidewall . . . . . . . . . . . . . . . . . . . . 19-22
Determine Location . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Prepare Wall Penetrations . . . . . . . . . . . . . . . . . . . . . 21
Termination and Fittings . . . . . . . . . . . . . . . . . . . . . . . 22
4. VERTICAL DIRECT VENTING
Vent/Air Termination - Vertical . . . . . . . . . . . . . . . . . . . . . 23-24
Determine Location . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Prepare Roof Penetrations . . . . . . . . . . . . . . . . . . . . . 23
Termination and Fittings . . . . . . . . . . . . . . . . . . . . . . . 23-24
Multiple Vent/Air Terminations . . . . . . . . . . . . . . . . . . 24
Optional Room Air . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5. HYDRONIC PIPING
System Water Piping Methods . . . . . . . . . . . . . . . . . . . . 25
Low Water Cutoff Device . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chilled Water System . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General Piping Information . . . . . . . . . . . . . . . . . . . . . . . 25
Circulator Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Near Boiler Piping Connections . . . . . . . . . . . . . . . . . . . 26
Near Boiler Piping Components . . . . . . . . . . . . . . . . . . . 28-30
6. GAS CONNECTIONS
Connecting Gas Supply Piping . . . . . . . . . . . . . . . . . . . . 31
Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Pipe Sizing for Natural Gas . . . . . . . . . . . . . . . . . . . . 32
Natural Gas Supply Pressure Requirements . . . . . . . 32
Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Pipe Sizing for Propane Gas . . . . . . . . . . . . . . . . . . . 32
Propane Supply Pressure Requirements . . . . . . . . . . 32
Check Inlet Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . 33-34
Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Gas Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 34
7. FIELD WIRING
Line Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . 35
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . 36
Wiring of the Cascade . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8. CONDENSATE DISPOSAL
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9. STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-45
10. OPERATING INFORMATION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-48
Cascade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-49
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-52
Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
11. MAINTENANCE
Maintenance & Annual Startup . . . . . . . . . . . . . . . . . . 54-59
12. DIAGRAMS
Ladder Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60-61
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Revision Notes . . . . . . . . . . . . . . . . . . . . . . . . . Back Cover
Installation & Operation Manual
Please read before proceeding
Installer – Read all instructions, including this manual and the SYNC Service Manual, before installing. Perform steps in the order given.
User – This manual is for use only by a qualified heating installer/service technician. Refer to the User’s Information Manual for your reference.
Have this boiler serviced/inspected by a qualified service technician, at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage.
When servicing boiler –
• To avoid electric shock, disconnect electrical supply before performing maintenance.
• To avoid severe burns, allow boiler to cool before performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut off,
do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
• Do not use this boiler if any part has been under water.
The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Boiler water –
• Thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
• Do not use petroleum-based cleaning or sealing
compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
• Do not use “homemade cures” or “boiler patent
medicines”. Serious damage to the boiler, personnel, and/or property may result.
• Continual fresh make-up water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion in system components. Leaks in boiler or piping must be repaired at once to prevent the need for makeup water.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
3
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING
NOTICE
WARNING
WARNING
Installation & Operation Manual
4
The SYNC - How it works...
1. Access cover - front
Provides access to the gas train and the heat exchanger.
2. Air intake adapter
Allows for the connection of the PVC air intake pipe to the boiler.
3. Air pressure switches
The air pressure switches detect blocked flue/vent conditions.
4. Air shrouds (1.0 Model only)
The air shrouds control air and gas flow into the burners.
5. Automatic air vents
Designed to remove trapped air from the heat exchanger coils.
6. Blowers
The blowers pull in air and gas through the venturis (item
35). Air and gas mix inside the blowers and are pushed into the burners, where they burn inside the combustion chamber.
7. Boiler drain port
Location from which the heat exchangers can be drained.
8. Boiler inlet temperature sensors
These sensors monitor system return water temperature. If selected as the controlling sensor, the control module adjusts the boiler firing rate so the inlet temperature matches the set point.
9. Boiler outlet temperature sensors
These sensors monitor boiler outlet water temperature. If selected as the controlling sensor, the control module adjusts boiler firing rate so the outlet temperature matches the set point.
10. Burners (not shown)
Made with metal fiber and stainless steel construction, the burners use pre-mixed air and gas and provide a wide range of firing rates.
11. Condensate drain connection
Connects the condensate drain line to a 1/2" PVC union.
12. Control modules
The control modules respond to internal and external signals and control the blowers, gas valves, and pumps to meet the heating demand.
13. Electronic display
Digital controls with touch screen technology and full color display.
14. Flame inspection windows
The quartz glass windows provide a view of the burner surfaces and flames.
15. Flame sensors
Used by the control module to detect the presence of burner flame.
16. Flap valves
Prevents recirculation of flue products when only one burner is running.
17. Flue gas sensors
These sensors monitor the flue gas exit temperature. The control modules will modulate and shut down the boiler if the flue gas temperature gets too hot. This protects the flue pipe from overheating.
18. Flue pipe adapter
Allows for the connection of the PVC vent pipe system to the boiler.
19. Gas connection pipe
Threaded 1½" pipe connection. This pipe should be connected to the incoming gas supply for the purpose of delivering gas to the boiler.
20. Gas shutoff valves (inside unit)
Manual valves used to isolate the gas valves from the burners.
21. Gas shutoff valve (outside unit)
Manual valve used to isolate the gas valve from the gas supply.
22. Gas valves
The gas valves sense the negative pressure created by the blowers, allowing gas to flow only if the gas valves are powered and combustion air is flowing.
23. Heat exchanger access covers
Allows access to the combustion side of the heat exchanger coils.
24. High gas pressure switches
Switches provided to detect excessive gas pressure.
25. High limits
Devices used to monitor the outlet water temperature. If the temperature exceeds its setting, they will break the control circuit, shutting the boiler down.
26. Ignition electrodes
Provides direct spark for igniting the burners.
27. Line voltage junction box
The junction box contains the connection points for the line voltage power and all pumps.
28. Line voltage wiring connections (knockouts)
Conduit connection points for the high voltage junction box.
29. Low gas pressure switch
Switch provided to detect low gas pressure.
30. Low voltage connection board
The connection board is used to connect external low voltage devices.
31. Low voltage wiring connections (knockouts)
Conduit connection points for the low voltage connection board.
32. Low water cutoff device (LWCO)
Device used to ensure adequate water is supplied to the boiler and in the event of inadequate water levels, will ensure the boiler will shut down.
33. Power switch
Turns 120 VAC ON/OFF to the boiler.
34. Pump relay boards
The pump relay boards are used to connect the boiler, system and Hot Water Generator (HW) pumps.
35. Relief valve
Protects the heat exchangers from an over pressure condition. The relief valve will be set at 50 PSI.
36. Reset switch
Reset switch for the low water cutoff. Hold for 10 seconds to reset.
37. Stainless steel heat exchangers
Allows system water to flow through specially designed coils for maximum heat transfer, while providing protection against flue gas corrosion. The coils are encased in a jacket that contains the combustion process.
38. Temperature and pressure gauge
Monitors the outlet temperature of the boiler as well as the system water pressure.
39. Test switch
Test switch for the low water cutoff. Hold for 10 seconds to test.
40. Top panel
Removable panel to gain access to the internal components.
41. Venturis
The venturis control air and gas flow into the burners.
42. Water inlets
Two 2" NPT water connections that return water from the system to the heat exchangers.
43. Water outlets
A 2½" NPT water connection that supplies hot water to the system.
Installation & Operation Manual
Left Side (inside unit)
6
23
5
26
14
24
15
29
Right Side (inside unit)
The SYNC - How it works... (continued)
5
Models 1.0 - 1.3 - 1.5
Front View
Rear View
40
13
1
27
28
18
19
21
12
42
30
17
31
3
34
16
8
9
43
1.0 Model Only
2
37
38
4
22
32
39
36
11
35
22
7
33
25
20
41
24
6
Installation & Operation Manual
Ratings
SYNC
I=B=R Rating
Model Number
Note: Change “N” to
“L” for L.P. gas models.
Input MBH
(Note 4)
Min Max
Gross
Output
MBH
(Note 1)
Net
I=B=R
Ratings
Water,
MBH
(Note 2)
SBN1000 100 1000 941 818
SBN1300 130 1300 1237 1076
SBN1500 150 1500 1444 1256
Other Specifications
Appliance
Water Content Gallons
Outlet Water
Inlet
Water
Gas
Connections
Air
Size
Vent
Size
(Note 3)
8.4 2½" (2) - 2" 1½" 6" 6"
10.0 2½" (2) - 2" 1½" 6" 6"
11.4 2½" (2) - 2" 1½" 6" 6"
Maximum allowed working pressure is located on the rating plate.
NOTICE
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
3. SYNC boilers require special gas venting. Use only the vent materials and methods specified in the SYNC Installation and Operation Manual.
4. Standard SYNC boilers are equipped to operate from sea level to 4,500 feet only with no adjustments. The boiler will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet.
5. High altitude SYNC boilers are equipped to operate from 3,000 to 12,000 feet only with no field adjustments. The boiler will de-rate by 2% for each 1,000 feet above 3,000 feet. High altitude models are manufactured with a different control module for altitude operation, but the operation given in this manual remains the same as the standard boilers. A high altitude label (as shown in FIG. A) is also affixed to the unit.
6. Ratings have been confirmed by the Hydronics Institute, Section of AHRI.
UNIT EQUIPPED FOR
3,000 FT. TO 12,000 FT.
HIGH ALTITUDE
Figure A High Altitude Label Location
7
Installation & Operation Manual
Installation must comply with:
• Local, state, provincial, and national codes, laws, regulations, and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required.
• National Electrical Code.
• For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
WARNING
This appliance is certified as an indoor appliance. Do not install the appliance outdoors or locate where the appliance will be exposed to freezing temperatures or to temperatures that exceed 100°F (37.8°C).
Failure to install the appliance indoors could result in severe personal injury, death, or substantial property damage.
1 Determine boiler location
The SYNC gas manifold and controls met safe lighting and other performance criteria when the boiler underwent tests specified in ANSI Z21.13 – latest edition.
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
3. Check area around the boiler. Remove any combustible
materials, gasoline and other flammable liquids.
Closet and alcove installations
This appliance requires a special venting system. Use only the vent materials, primer and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
For closet and alcove installations as shown in FIG.’s 1-1 and 1-2, CPVC or stainless steel vent material must be used inside the structure. The ventilating air openings shown in FIG.’s 1-1 and 1-2 are required for this arrangement. Failure to follow this warning could result in fire, personal injury, or death.
WARNING
NOTICE
WARNING
Failure to keep boiler area clear and free of combustible materials, gasoline, and other flammable liquids and vapors can result in severe personal injury, death, or substantial property damage.
4. The SYNC must be installed so that gas control system
components are protected from dripping or spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check for
and correct system problems, such as:
• System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing system and boiler to freeze and leak.
Provide clearances:
Clearances from combustible materials
1. Hot water pipes—at least 1" (25 mm) from combustible materials.
2. Vent pipe – at least 1" (25 mm) from combustible materials.
3. See FIG.’s 1-1 and 1-2 on page 8 for other clearance minimums.
Clearances for service access
1. See FIG.’s 1-1 and 1-2 on page 8 for recommended
service clearances. If you do not provide the minimum clearances shown, it may not be possible to service the boiler without removing it from the space.
WARNING
A closet is any room the boiler is installed in which is less than 778 cubic feet for SB1000 models, 847 cubic feet for SB1300 models, and 914 cubic feet for SB1500 models.
An alcove is any room which meets the criteria for a closet with the exception that it does not have a door.
Example: Room dimensions = 9 feet long, 9 feet wide, and 9 foot ceiling = 9 x 9 x 9 = 729 cubic feet. This would be considered a closet for a SYNC Boiler.
Installation & Operation Manual
8
Figure 1-2 Alcove Installation - Minimum Required Clearances
Figure 1-1 Closet Installation - Minimum Required Clearances
WARNING
For closet installations, CPVC or stainless steel material MUST BE used in a closet structure due to elevated temperatures. Failure to follow this warning could result in fire, personal injury, or death.
RECOMMENDED SERVICE CLEARANCES:
Front - 30" (762 mm) Top - 24" (610 mm) Left Side - 24" (610 mm) Rear - 24" (610 mm)
1 Determine boiler location
RECOMMENDED SERVICE CLEARANCES:
Front - 30" (762 mm) Top - 24" (610 mm) Left Side - 24" (610 mm) Rear - 24" (610 mm)
WARNING
For alcove installations, CPVC or stainless steel material MUST BE used in an alcove structure due to elevated temperatures. Failure to follow this warning could result in fire, personal injury, or death.
1" (25 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
AND VENT PIPE
0"
LEFT
24" (610 MM)
REAR
1" (25 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
AND VENT PIPE
4" (330 MM)
TOP
VENTILATING*
AIR OPENING
CLOSED DOOR
VENTILATING* AIR OPENING
6" (152 MM)
0"
RIGHT
6" (152 MM)
FRONT
*AREA OF EACH OPENING: 1 SQ. INCH PER 1000 BTU PER HOUR INPUT WITH A MINIMUM OF 100 SQ. INCHES
0"
LEFT
24" (610 MM)
13" (330 MM)
TOP
OPEN FRONT
REAR
0"
RIGHT
6" (152.40 MM)
FRONT
Installation & Operation Manual
9
1 Determine boiler location (continued)
Provide air openings to room:
The SYNC alone in boiler room
1. No air ventilation openings into the boiler room are needed when clearances around the SYNC are at least equal to the SERVICE clearances shown in FIG.’s 1-1 and 1-2. For spaces that do NOT supply this clearance, provide two openings as shown in FIG. 1-1. Each opening must provide one square inch free area per 1,000 Btu/hr of boiler input.
2. Combustion air openings are required when using the Room Air Option on page 24 of this manual.
The SYNC in same space with other gas or oil-fired appliances
1. Follow the National Fuel Gas Code (U.S.) or CSA B149.1 and B149.2 (Canada) to size/verify size of the combustion/ventilation air openings into the space.
The space must be provided with combustion/ventilation air openings correctly sized for all other appliances located in the same space as the SYNC.
Do not install the boiler in an attic.
Failure to comply with the above warnings could result in severe personal injury, death, or substantial property damage.
2. Size openings only on the basis of the other appliances in the space. No additional air opening free area is needed for the SYNC because it takes its combustion air from outside (direct vent installation).
Do not install the boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death, or substantial property damage.
If flooding is possible, elevate the boiler sufficiently to prevent water from reaching the boiler.
Flooring and foundation
Flooring
The SYNC is approved for installation on combustible flooring, but must never be installed on carpeting.
Vent and air piping
The SYNC requires a special vent system, designed for pressurized venting.
You must also install air piping from outside to the boiler air intake adapter. The resultant installation is direct vent (sealed combustion). Note prevention of combustion air contamination below when considering vent/air termination.
Vent and air must terminate near one another and may be vented vertically through the roof or out a side wall. You may use any of the vent/air piping methods covered in this manual. Do not attempt to install the SYNC using any other means.
Be sure to locate the boiler such that the vent and air piping can be routed through the building and properly terminated. The vent/air piping lengths, routing and termination method must all comply with the methods and limits given in this manual.
Prevent combustion air contamination
Install air inlet piping for the SYNC as described in this manual. Do not terminate vent/air in locations that can allow contamination of combustion air. Refer to Table 1A, page 10 for products and areas which may cause contaminated combustion air.
Ensure that the combustion air will not contain any of the contaminants in Table 1A, page 10. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death or substantial property damage. Do not pipe combustion air near a swimming pool, for example. Also, avoid areas subject to exhaust fumes from laundry facilities. These areas will always contain contaminants.
WARNING
WARNING
WARNING
Installation & Operation Manual
10
Products to avoid:
Spray cans containing chloro/fluorocarbons Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers Hydrochloric acid/muriatic acid
Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms Adhesives used to fasten building products and other
similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction Remodeling areas
Table 1A Corrosive Contaminants and Sources
When removing a boiler from existing common vent system:
Do not install the SYNC into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death, or substantial property damage.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
a. Seal any unused openings in the common venting system. b. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deficiencies, which could cause an unsafe condition.
c. Test vent system – Insofar as is practical, close all building
doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at the draft hood relief opening after 5 minutes
of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that each appliance remaining
connected to the common venting system properly vents when tested as outlined herein, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
g. Any improper operation of the common venting system should
be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code.
DANGER
WARNING
1 Determine boiler location
Remove boiler from wood pallet
1. After removing the outer shipping carton from the boiler, remove the parts package (packaged parts inside the jacket of the boiler).
2. To remove the boiler from the pallet:
a. Remove the front door of the boiler. b. Remove the two lag bolts from the wood pallet
inside the boiler (FIG. 1-3).
c. Detach the boiler from the lag bolts in the rear of
the unit, see FIG. 1-3.
Do not drop the boiler or bump the jacket on the floor or pallet. Damage to the boiler can result.
Figure 1-3 Boiler Mounted on Shipping Pallet
NOTICE
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
LAG BOLTS
(QTY. 3)
REAR
LAG BOLTS
(QTY. 3)
FRONT
Installation & Operation Manual
1 Determine boiler location (continued)
11
Combustion and ventilation air requirements for appliances drawing air from the equipment room
Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The equipment room MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation.
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent connections, water pipe connections, piping and other auxiliary equipment, as well as the appliance. The clearance labels on each appliance note the same service and combustible clearance requirements as shown in this manual.
Multiple appliances may be installed in a modular boiler installation. Multiple appliances may be installed side by side with no clearance between adjacent appliances because this appliance is approved for zero clearance from combustible surfaces and no service access is required from the sides.
Consult the Ve n ti n g section of this manual for specific installation instructions for the appropriate type of venting system that you will be using.
Figure 1-4_Combustion Air Direct from Outside
(b) Ventilation air opening, with a minimum free
area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be located within 12" (30 cm) of the top of the enclosure.
Figure 1-5_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the equipment room, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11 cm
2
per kW) of input (see FIG. 1-5).
Figure 1-6_Combustion Air from Interior Space
1. If air is taken directly from outside the building with no duct, provide two permanent openings to the equipment room (see FIG. 1-4):
(a) Combustion air opening, with a minimum free
area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be located within 12" (30 cm) of the bottom of the enclosure.
3. If air is taken from another interior space, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22 cm
2
per kW) of input, but not less than 100 square inches (645 cm
2
) (see FIG. 1-6).
IF NECESSARY
FOR TIGHT
CONSTRUCTION
Figure 1-7_Combustion Air from Outside - Single Opening
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-7).
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
Model
Number
FIG. 1-4 FIG. 1-5 FIG. 1-6 FIG. 1-7
*Outside Air from
2 Openings Directly from
Outdoors
*Outside Air from
2 Ducts Delivered from
Outdoors
**Inside Air from
2 Ducts Delivered from
Interior Space
*Outside Air from 1 Opening Directly from Outdoors, in
2
To p
Opening, in
2
Bottom
Opening, in
2
To p
Opening, in
2
Bottom
Opening, in
2
To p
Opening, in
2
Bottom
Opening, in
2
1.0
250
(1613 cm2)
250
(1613 cm2)
500
(3226 cm2)
500
(3226 cm2)
1000
(6452 cm2)
1000
(6452 cm2)
333
(2149 cm2)
1.3
325
(2097 cm2)
325
(2097 cm2)
650
(4194 cm2)
650
(4194 cm2)
1300
(8388 cm2)
1300
(8388 cm2)
433
(2794 cm2)
1.5
375
(2420 cm2)
375
(2420 cm2)
750
(4839 cm2)
750
(4839 cm2)
1500
(9678 cm2)
1500
(9678 cm2)
500
(3226 cm2)
All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers.
CAUTION
Under no circumstances should the equipment room ever be under negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.
The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be corrected immediately.
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system.
Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN B149.1 or B149.2. Check all local code requirements for combustion air.
12
1 Determine boiler location
Installation & Operation Manual
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the water heater only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.
*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).
Where two openings are provided, one must be within 12" (30cm) of the ceiling and one must be within 12" (30cm) of the floor of the equipment room. Each opening must have net free area as specified in the chart below (Table 1B). Single openings shall commence within 12" (30cm) of the ceiling.
Installation & Operation Manual
PVC/CPVC Two Pipe
See Figure 3-1A
Stainless Steel
Two Pipe
See Figure 3-2
Direct venting options - Sidewall Vent
2 General venting
13
PVC/CPVC
Two Pipe
See Figure 4-1
Stainless Steel
Two Pipe
See Figure 4-2
Direct venting options - Vertical Vent
Installation & Operation Manual
2 General venting
Vertical Vent Optional Room Air
PVC/CPVC
Room Air
See Figure 4-5
Stainless Steel
Room Air
See Figure 4-5
14
Horizontal Vent Optional Room Air
PVC/CPVC
Room Air
See Figure 4-5
Stainless Steel
Room Air
See Figure 4-5
Installation & Operation Manual
2 General venting (continued)
PVC/CPVC vent piping materials
Use only the materials listed in Table 2A on page 16 for vent pipe, and fittings. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 or B149.2 for Canadian installations.
Install vent and combustion air piping
DANGER
The SYNC must be vented and supplied with combustion and ventilation air as described in this section. Ensure the vent and air piping and the combustion air supply comply with these instructions regarding vent system, air system, and combustion air quality. See also Section 1 of this manual.
Inspect finished vent and air piping thoroughly to ensure all are airtight and comply with the instructions provided and with all requirements of applicable codes.
Failure to provide a properly installed vent and air system will cause severe personal injury or death.
All PVC vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the boiler (to allow drainage of condensate).
This appliance requires a special venting system. Use only the vent materials, primer, and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
WARNING
NOTICE
WARNING
WARNING
For closet and alcove installations, CPVC material MUST BE used in a closet/alcove structure. Failure to follow this warning could result in fire, personal injury, or death.
NOTICE
15
For all installations, the first ten (10) equivalent feet of vent must be CPVC or stainless steel (see FIG.’s 2-1A and 2-1B below). Failure to follow this warning could result in fire, personal inury, or death.
WARNING
Figure 2-1A CPVC Starter Vent - Horizontal
Figure 2-1B CPVC Starter Vent - Vertical
Requirements for installation in Canada
1. Installations must be made with a vent pipe system certified to ULC-S636.
IPEX is an approved vent manufacturer in Canada supplying vent material listed to ULC-S636.
2. The first three (3) feet of plastic vent pipe from the appliance flue outlet must be readily accessible for visual inspection.
3. The components of the certified vent system must not be interchanged with other vent systems or unlisted pipe/fittings. For concentric vent installations, the inner vent tube must be replaced with field supplied certifiedvent material to comply with this requirement.
CPVC PIPE
CPVC PIPE
CPVC ELBOW
CPVC ELBOW
5'
CPVC PIPE
5'
Installation & Operation Manual
2 General venting
PVC/CPVC air intake/vent connections
1. Combustion Air Intake Connector (FIG. 2-2) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
2. Vent Connector (FIG. 2-2) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
Figure 2-2 Near Boiler PVC/CPVC Venting
Air inlet pipe materials:
The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list:
PVC, CPVC or ABS Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet) Galvanized steel vent pipe with joints and seams sealed as specified in this section. Type “B” double-wall vent with joints and seams sealed as specified in this section.
*Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the appliance and the plastic air inlet pipe.
WARNING
Using vent or air intake materials other than those specified, failure to properly seal all seams and joints or failure to follow vent pipe manufacturer’s instructions can result in personal injury, death or property damage. Mixing of venting materials will void the warranty and certification of the appliance.
NOTICE
The use of double-wall vent or insulated material for the combustion air inlet pipe is recommended in cold climates to prevent the condensation of airborne moisture in the incoming combustion air.
Sealing of Type “B” double-wall vent material or galvanized vent pipe material used for air inlet piping on a sidewall or vertical rooftop Combustion Air Supply System:
a. Seal all joints and seams of the air inlet pipe using either
Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant such as those manufactured by Dow Corning or General Electric.
b. Do not install seams of vent pipe on the bottom of
horizontal runs.
c. Secure all joints with a minimum of three sheet metal
screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.
d. Ensure that the air inlet pipes are properly supported.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used. The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe should use a silicone sealant to ensure a proper seal at the appliance connection and the air inlet cap connection. Dryer vent or flex duct should use a screw type clamp to seal the vent to the appliance air inlet and the air inlet cap. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.
16
Table 2A PVC, Vent Pipe, and Fittings
All vent pipe materials and fittings must comply with the following:
Item Material
Standards for installation in:
United States Canada
Vent pipe and fittings
PVC schedule 40 ANSI/ASTM D1785
CPVC and PVC venting must be ULC-S636 Certified.
IPEX is an approved manufacturer in Canada
supplying vent material listed to ULC-S636.
PVC-DWV ANSI/ASTM D2665
CPVC schedule 40 ANSI/ASTM F441
Pipe cement/primer
PVC ANSI/ASTM D2564
IPEX System 636
Cements & Primers
CPVC ANSI/ASTM F493
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE
VENT
PVC/CPVC ADAPTER
FACTORY INSTALLED
AIR
Installation & Operation Manual
2 General venting (continued)
Stainless steel air intake/vent connections
1. Combustion Air Intake Connector (FIG. 2-3) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
2. Vent Connector (FIG. 2-3) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
Figure 2-3 Near Boiler Stainless Steel Venting
Stainless steel vent and air piping
This product has been approved for use with stainless steel FasNseal vent systems manufactured by Dura-vent. Lochinvar offers a matching stainless steel sidewall vent termination kit, see Table 3A on page 19.
Use only the materials, vent systems, and terminations listed in Table 2B. DO NOT mix vent systems. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Installations must comply with local codes. Stainless steel vent systems must be listed as a UL-1738 approved system for the United States and a ULC-S636 approved system for Canada.
NOTICE
Installation of a stainless steel vent system should adhere to the installation instructions supplied with the vent system.
NOTICE
The installer must use a specific vent starter adapter supplied by the vent manufacturer to adapt to different vent systems. See Table 2B for approved vent adapters.
NOTICE
STAINLESS STEEL VENT TERMINATION KITS
Kit Part Number Model Component Description
KIT30028 SB 1000 - 1500
6" PVC x 6" Stainless Steel
Adapter
6" Stainless Steel Vent
Termination
6" Stainless Steel Air Inlet
KIT30029 SB 1300 - 1500
6" PVC x 6" Stainless Steel
Adapter
6" Stainless Steel x 7"
Stainless Steel Adapters (2)
7" Stainless Steel Vent
Termination
7" Stainless Steel Air Inlet
Table 2B Approved Stainless Steel Terminations and Adapters
When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.
DANGER
Failure to properly seal all joints and seams as required in the air inlet piping may result in flue gas recirculation, spillage of flue products and carbon monoxide emissions causing severe personal injury or death.
The SYNC uses model specific combustion air intake and vent piping sizes as detailed in Tables 2C and 2D on page 18.
Increasing or decreasing combustion air or vent piping to sizes not specified in this manual is not authorized.
NOTICE
PVC/CPVC or ABS is acceptable air inlet pipe material.
NOTICE
17
REMOVE PVC/CPVC VENT CONNECTOR WHEN INSTALLING STAINLESS STEEL
Installation & Operation Manual
Vent, air piping and termination:
The SYNC vent and air piping can be installed through the roof or through a sidewall. Follow the procedures in this manual for the method chosen. Refer to the information in this manual to determine acceptable vent and air piping length.
Air contamination
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.
Please read the information given in Table 1A, page 10, listing contaminants and areas likely to contain them. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per this manual.
If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.
To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A, page 10 before installing the boiler or air inlet piping.
If contaminants are found, you MUST:
• Remove products permanently. —OR—
• Relocate air inlet and vent
terminations to other areas.
Removing from existing vent
Follow the instructions in Section 1, page 10 of this manual when removing a boiler from an existing vent system.
Vent and air piping
Vent and air system:
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 or B149.2 for Canadian installations.
You must also install air piping from outside to the boiler air intake adapter. The resultant installation is direct vent (sealed combustion).
You may use any of the vent/air piping methods covered in this manual. Do not attempt to install the SYNC using any other means.
DO NOT mix components from different systems. The vent system could fail, causing leakage of flue products into the living space. Use only PVC or CPVC pipe and fittings, with primer and cement specifically designed for the material used.
NOTICE
WARNING
WARNING
WARNING
2 General venting
Note: When using a 7" vent or air pipe, a field supplied increaser is required.
When determining equivalent combustion air and vent length, add 5 feet (1.5m) for each 90° elbow and 3 feet (.9 m) for each 45° elbow.
EXAMPLE: 20 feet (6 m) of PVC pipe + (4) 90° elbows + (3) 45° elbows = 49 equivalent feet (15 m) of piping.
18
Model
Air Intake
Diameter
Air Intake
Min. Length
Air Intake
Max. Length
Vent
Diameter
Vent
Min. Length
Vent
Max. Length
Input
De-Rate per
25 feet of Vent
SB 1000 6" 12' 100' 6" 12' 100' 1.25%
SB 1300 6" 12' 100' 6" 12' 50' 2.90%
SB 1300 7" 12' 100' 7" 12' 100' 0.95%
SB 1500 6" 12' 100' 6" 12' 50' 3.30%
SB 1500 7" 12' 100' 7" 12' 100' 1.65%
Table 2C Direct Vent Minimum / Maximum Allowable Air / Vent Lengths
Model
Vent
Diameter
Vent
Min. Length
Vent
Max. Length
Input De-Rate per
25 feet of Vent
SB 1000 6" 12' 100' 0.63%
SB 1300 6" 12' 100' 1.45%
SB 1500 6" 12' 100' 1.65%
Table 2D Room Air Minimum / Maximum Allowable Air / Vent Lengths
Installation & Operation Manual
3 Sidewall direct venting
Vent/air termination – sidewall
Follow instructions below when determining vent location to avoid possibility of severe personal injury, death, or substantial property damage.
A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 or B149.2 for Canadian installations.
Determine location
Locate the vent/air terminations using the following guidelines:
1. The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 18 of this manual.
2. You must consider the surroundings when terminating
the vent and air: a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air conditioning equipment or be objectionable.
b. The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the plume could obstruct window views.
c. Prevailing winds could cause freezing of condensate
and water/ice buildup where flue products impinge on building surfaces or plants.
d. Avoid possibility of accidental contact of flue
products with people or pets.
e. Do not locate the terminations where wind eddies
could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.
WARNING
WARNING
NOTICE
WARNING
Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.
Figure 3-1A PVC/CPVC Sidewall Termination of Air and Vent
f. Do not terminate above any door or window.
Condensate can freeze, causing ice formations.
g. Locate or guard vent to prevent condensate
damage to exterior finishes.
WARNING
Sidewall vent and air inlet terminations must terminate in the same pressure zone.
Do not exceed the maximum lengths of the outside vent piping shown in FIG.’s 3-1B and 3-1C. Excessive length exposed to the outside could cause freezing of condensate in the vent pipe, resulting in potential boiler shutdown.
WARNING
If using the alternate sidewall termination:
3. The air piping must terminate in a down-turned elbow as shown in FIG. 3-1B. This arrangement avoids recirculation of flue products into the combustion air stream.
4. The vent piping must terminate in an elbow pointed outward or away from the air inlet, as shown in FIG.3-1B.
Figure 3-1B Alternate Sidewall Termination of Air and Vent w/Field Supplied Fittings
Model Kit Number Vent Size
1.0 - 1.5
KIT30028
(Stainless Steel)
6 inch vent
1.3 - 1.5
KIT30029
(Stainless Steel)
7 inch vent
Table 3A Sidewall Vent Kits
19
Note: Available in 6" diameter only.
POSSIBLE ORIENTATIONS
FROM BOILER
VENT PIPE
CONNECTION
TO BOILER INTAKE AIR
CONNECTION
VENT / AIR
TERMINATION
GRADE OR
SNOW LINE
12"
MIN
TO
OVER-
HANG
12" MIN
Installation & Operation Manual
3 Sidewall direct venting
Vent/air termination – sidewall
5. Maintain clearances as shown in FIG.’s 3-1A thru 3-4B, pages 19 and 20. Also maintain the following: a. Vent must terminate:
• At least 6 feet (1.8 m) from adjacent walls.
• No closer than 12 inches (305 mm) below roof overhang.
• At least 7 feet (2.1 m) above any public walkway.
• At least 3 feet (.9 m) above any forced air intake within 10 feet (3 m).
• No closer than 12 inches (305 mm) below or horizontally from any door or window or any other gravity air inlet.
b. Air inlet must terminate at least 12 inches (305 m)
above grade or snow line; at least 12 inches (305 mm) below the vent termination; and the vent pipe must not extend more than 24 inches (610 mm) vertically outside the building as shown in FIG.’s 3-1B and 3-1C.
c. Do not terminate closer than 4 feet (1.2 m)
horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet (1.2 m) horizontally.
6. Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
VENT / AIR
TERMINATION
12"
MIN.
12"
MIN.
12"
MIN.
Figure 3-2A Clearance to Gravity Air Inlets
Figure 3-3A Clearance to Forced Air Inlets
Figure 3-1C Alternate Stainless Steel Sidewall
Termination w/Field Supplied Fittings
PVC/CPVC or ABS is acceptable air inlet pipe material.
NOTICE
12” (305 MM)
MIN
BIRD
SCREEN
(TYPICAL)
12” (305 MM)
MIN
12” (305 MM)
MIN
Figure 3-2B Alternate Clearance to Gravity Air Inlets w/Field Supplied Fittings
20
TO BOILER INTAKE AIR CONNECTION
FROM BOILER VENT PIPE CONNECTION
12" (305 MM) MIN
15" (381 MM) MAX
12" (305 MM) MIN
IF LESS
THAN 10’
VENT / AIR
TERMINATION
7' MIN. ABOVE ANY
PUBLIC WALKWAY
36"
MIN.
FORCED AIR
INLET
Installation & Operation Manual
3 Sidewall direct venting (continued)
Figure 3-4A Sidewall Termination Assembly (PVC/CPVC)
Prepare wall penetrations
1. Use the factory supplied wall plate as a template to locate the vent and air intake holes and mounting holes.
Air pipe penetration: a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
Vent pipe penetration: a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
• 7½ inch hole for 6 inch vent pipe
• 8½ inch hole for 7 inch vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors into the wall.
2. Install the vent and air intake piping through the wall into the vent plate openings. Seal all gaps between the pipes and wall. Use RTV silicone sealant to seal the air pipe. Use the cement/primer listed in Table 2A on page 16 to seal the vent pipe.
3. Mount and secure the vent plate to the wall using stainless steel screws. Seal around the plate to the wall assuring no air gaps.
4. Assemble the vent cap to the vent plate (see FIG. 3-4A). Insert the stainless steel screws into the vent cap screw hole openings and securely attach the vent cap to the vent plate.
5. Seal all wall cavities.
Prepare wall penetrations (Alternate Field Supplied Options)
1. Air pipe penetration (see FIG. 3-4B): a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration (see FIG. 3-4B): a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
• 7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe
• 8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole (when required by local codes).
3. Use a sidewall termination plate as a template for correct location of hole centers.
4. Follow all local codes for isolation of vent pipe when passing through floors or walls.
5. Seal exterior openings thoroughly with exterior caulk.
Figure 3-4B Alternate Sidewall Termination Assembly PVC/CPVC or Stainless Steel
36” (914 MM)
MIN
7’ (2.1 M) MIN ABOVE ANY
PUBLIC WALKWAY
IF LESS
THAN 10’ (3 M)
FORCED AIR
INLET
BIRD
SCREEN
(TYPICAL)
Figure 3-3B Alternate Clearance to Forced Air Inlets w/Field Supplied Fittings
21
AIR PIPING
VENT PIPING
WALL PLATE
GALVANIZED
THIMBLE
VENT PLATE
VENT CAP
SIDEWALL
TERMINATION PLATE
VENT
PIPING
GALVANIZED THIMBLE
(WHEN REQUIRED BY LOCAL CODES)
ELBOW
AIR PIPING
BIRD SCREEN
ELBOW
BIRD SCREEN
Installation & Operation Manual
22
3 Sidewall direct venting
Termination and fittings
1. The air termination coupling must be oriented at least 12 inches above grade or snow line as shown in FIG. 3-1A, page 19.
2. Maintain the required dimensions of the finished termination piping as shown in FIG. 3-1A, page 19.
3. If using a stainless steel sidewall termination do not extend exposed vent pipe outside of the building more than what is shown in this document. Condensate could freeze and block vent pipe.
4. PVC/CPVC terminations are designed to accommodate any wall thickness of standard constructions per the directions found in this manual.
5. Stainless steel terminations are designed to penetrate walls with a thickness up to 9.25 inches of standard construction.
All vent pipes and air inlets must terminate at the same height to avoid possibility of severe personal injury, death, or substantial property damage.
Multiple vent/air terminations
1. When terminating multiple SYNC boilers terminate each vent/air connection as described in this manual (FIG. 3-5A).
2. Place wall penetrations to obtain minimum clearance of 12 inches (305 mm) between vent pipe and adjacent air inlet elbow, as shown in FIG. 3-5A for U.S. installations. For Canadian installations, provide clearances required by CSA B149.1 or B149.2 Installation Code.
3. The air inlet of a SYNC is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents.
WARNING
12" MIN. BETWEEN EDGE OF AIR
INLET AND ADJACENT VENT OUTLET
VENT / AIR
TERMINATION
VENT
AIR
Figure 3-5A Multiple Vent Terminations (must also comply with Figure 3-1A)
VENT
12” (305 MM) MIN 15” (381 MM) MAX
12” (305 MM) MIN. BETWEEN EDGE OF AIR PIPE AND ADJACENT VENT PIPE
AIR
Figure 3-5B Alternate Multiple Vent Terminations w/Field Supplied Fittings (must also comply with Figure 3-1B)
Installation & Operation Manual
23
4 Vertical direct venting
Vent/air termination – vertical
Prepare roof penetrations
1. Air pipe penetration: a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration: a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:
• 7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe
• 8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole (when required by local codes).
3. Space the air and vent holes to provide the minimum spacing shown in FIG.’s 4-1 and 4-2.
4. Follow all local codes for isolation of vent pipe when passing through floors, ceilings, and roofs.
5. Provide flashing and sealing boots sized for the vent pipe and air pipe.
Termination and fittings
1. Prepare the vent termination coupling and the air
termination elbow (FIG.’s 4-1 and 4-2) by inserting the bird screens provided with the boiler.
2. The air piping must terminate in a down-turned 180° return bend as shown in FIG.’s 4-1 and 4-2. Locate the air inlet pipe no further than 2 feet (.6 m) from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream.
Figure 4-1 PVC/CPVC Vertical Termination of Air and Vent
5. Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
WARNING
Rooftop vent and air inlet terminations must terminate in the same pressure zone.
Figure 4-2 Stainless Steel Vertical Termination of Air and Vent
Follow instructions below when determining vent location to avoid possibility of severe personal injury, death or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 or B149.2 for Canadian installations.
WARNING
NOTICE
WARNING
Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.
Determine location
Locate the vent/air terminations using the following guidelines:
1. The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 18 of this manual.
2. The vent must terminate at least 3 feet above the highest place in which the vent penetrates the roof and at least 2 feet above any part of a building within 10 horizontal feet.
3. The air piping must terminate in a down-turned 180° return pipe no further than 2 feet (.6 m) from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream.
4. The vent piping must terminate in an up-turned coupling as shown in FIG. 4-1. The top of the coupling must be at least 1 foot above the air intake. When the vent termination uses a rain cap as illustrated in FIG. 4-2 maintain at least 36" (914 mm) above the air inlet. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (.6 m) apart and with the vent termination at least 1 foot above the air intake.
ALTERNATE INTAKE LOCATIONS: INTAKE PIPES MAY BE LOCATED ANYWHERE WITHIN 24" (610 MM) OF VENT PIPE
ALTERNATE INTAKE LOCATIONS: INTAKE PIPES MAY BE LOCATED ANYWHERE WITHIN 24” (610 MM) OF VENT PIPE
BIRD SCREEN
(TYPICAL)
6" (152 MM) MINIMUM
ABOVE ROOF /
SNOW LINE
VENT OUTLET
36” (914 MM) MINIMUM
ABOVE AIR INLET
VENT
COM,BUSTION AIR
BIRD SCREEN (TYPICAL)
COUPLING (FIELD SUPPLIED)
VENT OUTLET 12" MINIMUM ABOVE AIR INLET
VENT
6" (152 MM) MINIMUM ABOVE ROOF / SNOW LINE
COMBUSTION AIR
Installation & Operation Manual
4 Vertical direct venting
Multiple vent/air terminations
1. When terminating multiple SYNC boilers, terminate each vent/air connection as described in this manual (FIG. 4-3).
Terminate all vent pipes at the same height and all air pipes at the same height to avoid recirculation of flue products and the possibility of severe personal injury, death, or substantial property damage.
2. Place roof penetrations to obtain minimum clearance of 12 inches (305 mm) between edge of air intake elbow and adjacent vent pipe of another boiler for U.S. installations (see FIG. 4-3). For Canadian installations, provide clearances required by CSA B149.1 or B149.2 Installation Code.
3. The air inlet of a SYNC boiler is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents.
12" (305 MM) MINIMUM VERTICALLY FROM VENT OUTLET TO ANY AIR INLET
12" (305 MM) MINIMUM FROM EDGE OF AIR INTAKE PIPE TO ADJACENT VENT PIPE FROM ANOTHER BOILER
AIR
AIR
VENT
VENT
Figure 4-3 Vertical Terminations with Multiple Boilers
VENT
VENT
AIR
AIR
12" (305 MM) MINIMUM VERTICALLY FROM VENT OUTLET TO ANY AIR INLET
Figure 4-4 Alternate Vertical Terminations with Multiple Boilers
WARNING
Room air
Figure 4-5 Room Air Installation
3. The vent piping must terminate in an up-turned coupling as shown in FIG. 4-1. The top of the coupling must be at least 1 foot (.3 m) above the air intake. When the vent termination uses a rain cap as illustrated in FIG. 4-2 maintain at least 36" (914 mm) above the air inlet. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (.6 m) apart and with the vent termination at least 1 foot (.3 m) above the air intake.
4. Maintain the required dimensions of the finished termination piping as shown in FIG.’s 4-1 and 4-2.
5. Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.
24
The SYNC boiler may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room.
Follow the requirements in the General Venting, Sidewall Direct Venting, and Vertical Direct Venting sections for vent material specifications, vent length requirements, and vent termination requirements.
Combustion and ventilation air must be supplied to the equipment room per the requirements on pages 11 and 12 of this manual for proper operation of the SYNC boiler when utilizing the single pipe method.
NOTICE
FOR DIRECT VENT SYSTEMS REMOVE AIR INLET COVER AND INSTALL RUBBER COUPLING FOR PVC / CPVC VENT SYSTEMS OR STAINLESS STEEL ADAPTER FOR STAINLESS STEEL VENT SYSTEMS
Installation & Operation Manual
5 Hydronic piping
System water piping methods
The SYNC is designed to function in a closed loop pressurized system not less than 12 psi (83 kPa). A temperature and pressure gauge is included to monitor system pressure and outlet temperature and should be located on the boiler outlet.
It is important to note that the boiler has a pressure drop which must be figured in when sizing the circulators. Each boiler installation must have an air elimination device, which will remove air from the system. Install the boiler so the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation or basic service of circulator replacement, valves, and others.
Observe a minimum of 1 inch (25 mm) clearance around all un-insulated hot water pipes when openings around the pipes are not protected by non-combustible materials.
Low water cutoff device
An electronic low water cutoff is provided as standard equipment on all models. The low water cutoff should be inspected every 6 months.
Chilled water system
If the boiler supplies hot water to heating coils in air handler units, flow control valves or other devices must be installed to prevent gravity circulation of heater water in the coils during the cooling cycle. A chilled water medium must be piped in parallel with the heater.
Freeze protection
Freeze protection for new or existing systems must use glycol that is specially formulated for this purpose. This includes inhibitors, which prevent the glycol from attacking the metallic system components. Make certain to check that the system fluid is correct for the glycol concentration and inhibitor level. The system should be tested at least once a year and as recommended by the producer of the glycol solution. Allowance should be made for the expansion of the glycol solution in the system piping.
General piping information
Basic steps are listed below along with illustrations on the following pages (FIG.’s 5-5 and 5-6), which will guide you through the installation of the SYNC (reference FIG. 5-1).
1. Connect the system returns marked “Inlet”, make sure to install with pipe sealant compound.
2. Connect the system supply marked “Outlet”, make sure to install with pipe sealant compound.
3. Install purge and balance valve or shutoff valve and drain on system return to purge air out of each zone.
4. Install a backflow preventer on the cold feed make-up water line.
5. Install a pressure reducing valve on the cold feed make-up water line, (15 psi (103 kPa) nominal). Check temperature and pressure gauge (shipped separately), which should read a minimum pressure of 12 psi (83 kPa).
6. Install the circulators as shown on the piping diagrams in this section. Make sure the circulators are properly sized for the system and friction loss. Install check valves with each boiler circulator.
7. Install an expansion tank on the system supply. Consult the tank manufacturer’s instruction for specific information relating to tank installation. Size the expansion tank for the required system volume and capacity.
8. Install an air elimination device on the system supply.
9. Install a drain valve at the lowest point of the system.
Note:
The boiler cannot be drained completely of water without purging the unit with an air pressure of 15 psi (103 kPa).
10. This appliance is supplied with a relief valve sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV (“Heating Boilers”). The safety relief valve is installed at the factory and is located on the rear of the boiler. Pipe the discharge of the safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet. Never block the outlet of the safety relief valve.
11. On any pre-existing system, it is good practice to install a field supplied strainer to prevent damage to the heat exchanger.
See the piping illustrations included in this section, FIG.’s 5-5 and 5-6 for suggested guidelines in piping the SYNC.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Use only inhibited propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
WARNING
NOTICE
25
Installation & Operation Manual
Circulator sizing
The SYNC heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graph in FIG. 5-4 for pressure drop through the SYNC heat exchanger.
Near boiler piping connections
Figure 5-1 Near Boiler Piping
5 Hydronic piping
26
DRAIN (TYPICAL)
SYSTEM SUPPLY SENSOR (NOTICE: A SYSTEM SUPPLY SENSOR MUST BE INSTALLED FOR PROPER BOILER OPERATION.)
ISOLATION VALVE
(TYPICAL)
SYSTEM PUMP
TEMPERATURE GAUGE
BOILER PUMP
MODULE 1
MODULE 2
BOILER PUMP
CHECK VALVE (TYPICAL)
RELIEF VALVE
TO FLOOR DRAIN
Installation & Operation Manual
Figure 5-3 Pump Configuration
5 Hydronic piping (continued)
27
Hot Water Generator pump sizing
The SYNC has two (2) heat exchanger modules that require two (2) individual pumps for proper installation in the boiler loop and an additional two (2) pumps for the Hot Water Generator loop.
Hot Water Pump Head Loss = Ft. of Head for Module 1 (at required flow) + Ft. of Head for the Hot Water Generator (at 2 X the flow of Module 1)
Example:
Boiler: SB1500 A ΔT of 30° requires a flow through each module of 51 GPM. The module head loss is 18 ft. of head (see Table 5A).
Coupled with a Lochinvar Hot Water Generator with a 8-42 (diameter-length) tube bundle the calculated pressure drop is
1.2 Ft. of Head at 102 GPM.
Hot Water Pump Head Loss = 18 Ft/Hd (51 GPM) + 1.2 Ft/Hd (102 GPM) = 19.2 Ft/Hd
A pump will need to be selected to flow 51 GPM with a head loss of 19.2 Ft/Hd.
Figure 5-2 Boiler Schematic
T
O SYSTEM
FROM SYSTEM
HOT WATER
GENERATOR
MODULE 2 BOILER PUMP
MODULE 1 HOT WATER PUMP
102 GPM
MODULE 2 HOT WATER PUMP
51 GPM
102 GPM
51 GPM
MODULE 1 BOILER PUMP
AIR COVER
FROM SYSTEM
OK
TO BOILER
INLETS
FROM SYSTEM
NO
TO BOILER
INLETS
Installation & Operation Manual
It is required that near boiler piping systems utilize Primary/Secondary configurations as shown in FIG.’s 5-5 and 5-6 only. The use of other near boiler piping configurations could result in improper building and system flow rates leading to inadvertent boiler high limit shutdowns and poor system performance.
Near boiler piping components
1. Boiler piping:
Boiler system piping MUST be sized per the pipe requirements listed in Table 5A. Reducing the pipe size can restrict the flow rate through the boiler, causing inadvertent high limit shutdowns and poor system performance.
2. Boiler circulating pump:
Field supplied. The boiler circulating pump MUST be sized to meet the specified minimum flow requirements listed in FIG. 5-4.
3. Hot Water Generator circulating pump:
Field supplied. The pump MUST be sized to meet the specified minimum flow requirements listed in FIG. 5-4. Consult the indirect boiler operating guide to determine flow characteristics for the selected product used.
4. Boiler isolation valves:
Field supplied. Full port ball valves are required. Failure to use full port ball valves could result in a restricted flow rate through the boiler.
5. Check valves:
Field supplied. Check valves are required for installation as shown in FIG.’s 5-5 and 5-6. Failure to install check valves could result in a reverse flow condition during pump(s) off cycle.
6. Domestic indirect hot water isolation valves:
Field supplied. Full port ball valves are required. Failure to use full port ball valves could result in a restricted flow rate through the boiler.
7. Anti-scald mixing valve:
Field supplied. An anti-scald mixing valve is recommended when storing domestic hot water above 115°F (46°C).
8. Unions:
Field supplied. Recommended for unit serviceability.
9. Pressure relief valve:
Factory supplied. The pressure relief valve is sized to ASME specifications.
10. System temperature sensor:
Lochinvar supplies a system temperature sensor. The sensor is to be installed in the heating loop downstream from the boiler hot water piping and heating loop junction. The sensor should be located far enough downstream to sense system diluted water temperature.
NOTICE
Pump sizing and flow requirements are based on 20 feet (6 m) of piping, 4 - 90° elbows, and 2 - fully ported ball valves.
NOTICE
5 Hydronic piping
28
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
TEMPERATURE RISE APPLICATIONS
Model
MINIMUM PIPE
SIZE
20°F 25°F 30°F 35°F
GPM FT/HD GPM FT/HD GPM FT/HD GPM FT/HD
1000 2" 55 31 44 22 38 18 32 13 1300 2" 65 30 52 20 45 16 37 11 1500 2" 74 33 60 23 51 18 42 12
0
10
20
30
40
50
60
0 102030405060708090
SB1500
SB1300
SB1000
Pressure Drop vs Flow
Flow Rate (GPM) - Single Module Only
Pressure Drop (Feet of Head) - Single Module Only
Figure 5-4 Pressure Drop vs. Flow
Table 5A Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F
Installation & Operation Manual
5 Hydronic piping (continued)
Figure 5-5 Single Boiler - Primary/Secondary Piping
NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in operation to prevent short cycling and high limit issues.
29
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
FROM SYSTEM
HOT WATER
GENERATOR
BALL VALVE
(TYPICAL)
AIR SEPARATOR
DRAIN POINT
(TYPICAL)
SYSTEM SUPPLY
SENSOR
SYSTEM CIRCULATOR
PRESSURE GAUGE
TO SYSTEM
BACK FLOW PREVENTER
MAKE UP
WATER
PRESSURE REDUCING
(VALVE)
EXPANSION
TAN K
WATER GENERATOR
CIRCULATOR
(TYPICAL)
MODULE 1
BOILER PUMP
BOILER PUMP
MODULE 2
FLOW CHECK
VALVE (TYPICAL)
DRAIN
UNION (TYPICAL)
TEMPERATURE /
PRESSURE GAUGE
PRESSURE RELIEF
VALV E
Installation & Operation Manual
SYSTEM
CIRCULATOR
AIR
SEPARATOR
MAKE UP
WATER
DRAIN POINT
(TYPICAL)
SYSTEM SUPPLY
SENSOR
BALL VALVE
(TYPICAL)
MODULE 1 BOILER PUMP
PRESSURE RELIEF
VALV E
FLOW CHECK
VALVE (TYPICAL)
PRESSURE REDUCING
(VALVE)
EXPANSION
TAN K
UNION (TYPICAL)
TEMPERATURE/
PRESSURE GAUGE
DRAIN (TYPICAL)
BACK FLOW PREVENTER
PRESSURE GAUGE
MODULE 2 BOILER PUMP
FROM SYSTEM
TO SYSTEM
Figure 5-6 Multiple Boilers - Primary/Secondary Piping
Model
Number of Units
2 3 4 5 6 7 8
Manifold Pipe Sizes in Inches (mm)
1000
4 (102) 5 (127) 6 (152) 6 (152) 8 (203) 8 (203) 8 (203)
1300
5 (127) 5 (127) 6 (152) 8 (203) 8 (203) 8 (203) 8 (203)
1500
5 (127) 6 (152) 6 (152) 8 (203) 8 (203) 8 (203) 10 (254)
5 Hydronic piping
NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in operation to prevent short cycling and high limit issues.
30
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
Installation & Operation Manual
6 Gas connections
Connecting gas supply piping
1. Refer to FIG. 6-1 to pipe gas to the boiler. a. Install ground joint union for servicing, when
required.
b. In Canada – When using manual main shutoff
valves, it must be identified by the installer.
2. Install sediment trap / drip leg.
Figure 6-1 Gas Supply Piping
3. Support piping with hangers, not by the boiler or its accessories.
Do not check for gas leaks with an open flame – use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage.
4. Purge all air from the gas supply piping.
5. Before placing the boiler in operation, check the boiler and its gas connection for leaks. a. The appliance must be disconnected from the gas
supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5 kPa).
c. The appliance and its gas connection must be leak
tested before placing it in operation.
The gas valve and blower will not support the weight of the piping. Do not attempt to support the weight of the piping with the boiler or its accessories. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
WARNING
6. Use pipe sealing compound compatible with propane gases. Apply sparingly only to male threads of the pipe joints so that pipe dope does not block gas flow.
Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or substantial property damage.
WARNING
31
MANUAL SHUTOFF
VALV E
(FACTORY SUPPLIED)
GAS SUPPLY
UNION
SEDIMENT TRAP / DRIP LEG
Installation & Operation Manual
6 Gas connections
Use two wrenches when tightening gas piping at boiler (FIG. 6-2), using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components.
Figure 6-2 Inlet Pipe with Backup Wrench
Natural gas supply pressure requirements
1. Pressure required at the gas valve inlet pressure port:
• Maximum 14 inches w.c. (3.5 kPa) with no flow (lockup) or with boiler on.
• Minimum 5 inches w.c. (1.25 kPa) for 1.0 models with gas flowing (verify during boiler startup).
• Minimum 4 inches w.c. (.99 kPa) for 1.3 - 1.5 models with gas flowing (verify during boiler startup).
2. Install 100% lockup gas pressure regulator in supply line if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any time. Adjust lockup regulator for 14 inches w.c. (3.5 kPa) maximum.
Propane Gas:
Pipe sizing for propane gas
1. Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator.
Propane Supply Pressure Requirements
1. Adjust propane supply regulator provided by the gas supplier for 14 inches w.c. (3.5 kPa) maximum pressure.
2. Pressure required at gas valve inlet pressure port:
• Maximum 14 inches w.c. (3.5 kPa)with no flow (lockup) or with boiler on.
• Minimum 8 inches w.c. (1.9 kPa) with gas flowing (verify during boiler startup).
Maximum inlet gas pressure must not exceed the value specified. Minimum value listed is for the purposes of input adjustment.
WARNING
WARNING
NOTICE
WARNING
Ensure that the high gas pressure regulator is at least 10 feet (3 m) upstream of the appliance.
Check boiler rating plate to determine which fuel the boiler is set for. SYNC boilers CAN NOT be field converted. Failure to comply could result in severe personal injury, death, or substantial property damage.
32
WARNING
Check boiler rating plate to determine which fuel the boiler is set for. SYNC boilers CANNOT be field converted. Failure to comply could result in severe personal injury, death, or substantial property damage.
Natural gas:
Pipe sizing for natural gas
1. Refer to Table 6A for pipe length and diameter. Based on rated boiler input (divide by 1,000 to obtain cubic feet per hour). a. Table 6A is only for natural gas with specific gravity
0.60 inches, with a pressure drop through the gas piping of 0.5 inches w.c.
b. For additional gas pipe sizing information, refer to
ANSI Z223.1 (or B149.1 or B149.2 for Canadian installations).
USE BACK UP WRENCH TO
PREVENT PIPE FROM ROTATING
Installation & Operation Manual
Table 6A Natural Gas Pipe Size Chart
The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load.
If you experience a pressure drop greater than 1 inch w.c. (249 Pa), the meter, regulator, or gas line is undersized or in need of service. Perform the steps below when checking inlet gas supply:
1. Turn the main power switch to the “OFF” position.
2. Shut off gas supply at the manual gas valve in the gas piping to the appliance.
3. Remove the 1/8" pipe plug on the flange to the field supplied gas shutoff valve and install a suitable 1/8" fitting (field supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the 1/8" fitting is installed as shown in FIG. 6-3.
4. Slowly turn on the gas supply at the field installed manual gas valve.
5. Turn the power switch to the “ON” position.
6. Adjust the temperature set point on the control panel of the SMART TOUCH control module to call for heat.
7. Observe the gas supply pressure as the burner fires at 100% of rated input. Percent of burner input will be displayed on the Burner Screen.
8. Ensure inlet pressure is within specified range. Minimum and maximum gas supply pressures are specified in this section of the manual.
9. If gas supply pressure is within normal range and no adjustments are needed, proceed on to Step 11.
10. If the gas pressure is out of range, contact the gas utility, gas supplier, qualified installer or service agency to determine the necessary steps to provide proper gas pressure to the control.
11. Turn the power switch to the “OFF” position.
12. Shut off the gas supply at the manual gas valve in the gas piping to the appliance.
13. Remove the manometer from the pressure tap on top of the gas valve. Remove the 1/8" (3 mm) field supplied fitting and reinstall the pipe plug removed in Step 3.
NOTICE
CSA or UL listed flexible gas connections are acceptable, but you must exercise caution to ensure that the line has adequate capacity to allow your boiler to fire at full rate. Consult with local codes for proper installation or service procedures.
DO NOT adjust or attempt to measure gas valve outlet pressure. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
WARNING
TABLE - 6A
GAS PIPING SIZE CHART
Nominal
Iron Pipe
Size
Inches
Length of Pipe in Straight Feet
Maximum Capacity of Pipe in Thousands of
Btu/hr for gas
pressures of
14 Inches Water
Column (0.5
PSIG) or less and
a pressure drop
of 0.5 Inch Water
Column (Based
on NAT GAS,
1025 Btu/hr per
Cubic Foot of
Gas and 0.60
Specific Gravity)
10 20 30 40 50 60 70 80 90 100 125 150 175 200
2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
2 4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3 11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4 23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Check inlet gas supply
33
6 Gas connections (continued)
Installation & Operation Manual
WARNING
Do not check for gas leaks with an open flame -- use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage.
14. Turn on the gas supply at the manual gas valve.
15. Turn the power switch to the “ON” position.
16. Adjust the temperature set point on the control panel of the SMART TOUCH control module to the desired water temperature so the appliance will call for heat.
17. Check burner performance by cycling the system while you observe burner response. The burner should ignite promptly. Flame pattern should be stable. Turn system off and allow burner to cool, then cycle burner again to ensure proper ignition and flame characteristics.
Gas Pressure
The gas pressure must remain between 4 inches w.c. (.99 kPa) minimum (5 inches w.c. for 1.0 models) and 14 inches w.c. (3.5 kPa) maximum for Natural gas and between 8 inches w.c. (1.9 kPa) minimum and 14 inches w.c. (3.5 kPa) maximum for LP gas during standby (static) mode and while in operating (dynamic) mode. If an in-line regulator is used, it must be a minimum of 10 feet (3 m) from the SYNC boiler. It is very important that the gas line is properly purged by the gas supplier or utility company. Failure to properly purge the lines or improper line sizing, will result in ignition failure.
The problem is especially noticeable in NEW LP installations and also in empty tank situations. This can also occur when a utility company shuts off service to an area to provide maintenance to their lines.
Gas valve replacement
The gas valve MUST NOT be replaced with a conventional gas valve under any circumstances. As an additional safety feature, this gas valve has a flanged connection to the venturi and blower.
Figure 6-3 Inlet Gas Supply Check
DO NOT adjust or attempt to measure gas valve outlet pressure. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
Failure to follow all precautions could result in fire, explosion, or death!
WARNING
WARNING
6 Gas connections
34
Installation & Operation Manual
7 Field wiring
ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler must be replaced, use only type 105°C wire or equivalent.
Boiler must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 – latest edition.
Installation must comply with:
1. National Electrical Code and any other national, state, provincial, or local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.
Line voltage connections
1. Connect 120 VAC power wiring to the line voltage terminal strip in the junction box, as shown in FIG. 7-1.
2. Provide and install a fused disconnect or service switch (15 amp recommended) as required by the code (see FIG. 7-1).
3. When connecting hot water generator pumps connect the wiring to the line voltage terminal strip as shown in FIG. 7-1. Maximum current is 1.8 amps, install a field supplied contactor.
4. To activate a system pump, wire as shown in FIG. 7-1. Dry contacts are sized for 1.5 hp/120V, 3 hp/240V or 30 amps.
5. To activate a louver, connect to the dry contacts provided. Contacts are rated for 5 amps, 120V.
Figure 7-1 Line Voltage Field Wiring Connections
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
WARNING
NOTICE
CAUTION
35
120V SUPPLY
NEUTRAL W
GROUND G
LINE
MODULE 1
HOT WATER
GENERATOR
MODULE 2 HOT WATER GENERATOR
SYSTEM PUMP
MODULE 1
BOILER PUMP
MODULE 2
BOILER PUMP
BK
SERVICE SWITCH
W
G
L
W
G L
BK
G
W
BK
G
W
BK
BK
G
W
PUMP CONTACTOR
L2/W G
L1
Installation & Operation Manual
Low voltage connections
1. Route all low voltage wires through the knockouts in the rear of the boiler, as shown in FIG. 7-2.
2. Connect low voltage wiring to low voltage connection board as shown in FIG. 7-3 on page 38 of this manual and the boiler wiring diagram.
Figure 7-2 Routing Field Wiring
7 Field wiring
Enable
1. Connect the room thermostat or boiler enable contacts (isolated contact only) to terminals R and W, as shown in FIG. 7-3.
2. If a thermostat is used, install the thermostat on the inside wall away from influences of drafts, hot or cold water pipes, lighting fixtures, television, sunlight, or fireplaces.
3. Thermostat anticipator (if applicable): a. If connected directly to boiler, set for 0.1 amps. b. If connected to relays or other devices, set to match
total electrical power requirements of connected devices. See device manufacturers’ specifications and thermostat instructions for details.
Outdoor temperature sensor
1. Connect the outdoor temperature sensor (FIG. 7-3) to the Outdoor Sensor terminals on the connection board to enable outdoor reset operation of the SYNC.
2. Mount the sensor on an exterior wall, shielded from direct sunlight or flow of heat or cooling from other sources.
3. Route sensor wires through a knockout at the rear of the boiler (see FIG. 7-2).
Hot Water Generator (HW) thermostat
1. Connect the HW tank thermostat to the Tank Thermostat terminals on the connection board (FIG. 7-3).
Hot Water Generator (HW) tank
sensor
1. By installing a HW tank sensor, the SMART TOUCH control can perform the tank thermostat function. The SMART TOUCH control automatically detects the presence of this sensor, and generates a HW call for heat when the tank temperature drops 6°F (3°C) below the tank set point, and finishes the call for heat when the tank temperature reaches the tank set point.
2. A TST2032 sensor MUST be used with any indirect tank. Failure to use the correct sensor will result in the tank temperature being either above or below the set point. Connect the correct sensor to the Tank Sensor terminals
(see FIG. 7-3).
Louver proving switch
1. Louvers are used to provide combustion air for the room air option. A louver proving switch should be installed on the appropriate terminals and verified prior to operation (see FIG. 7-3).
Flow switch (field supplied)
1. Flow switches are designed to prevent a no flow situation.
2. A flow switch may be used to guarantee flow through the boiler before allowing it to fire. When used, the SYNC boiler requires a flow switch to be installed on each inlet.
3. Remove the jumper wires from the terminals on the connection board and connect these terminals to the normally open contacts on the flow switches (FIG. 7-3).
36
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE
WIRING KNOCKOUTS
LOW VOLTAGE
CONNECTION BOARD
Installation & Operation Manual
7 Field wiring (continued)
System supply sensor
1. By installing the system supply sensor into the supply of the primary loop, the temperature of the system supply can be controlled. The SMART TOUCH control automatically detects the presence of this sensor, and controls the boiler firing rate to maintain the system supply temperature to the set point.
2. Connect these terminals to the system supply sensor (FIG. 7-3).
Boiler management system
1. An external control may be connected to control either the firing rate or the set point of the boiler. Connect the 0 - 10 VDC terminals to the 0 - 10 VDC output of the external control. The SMART TOUCH control can be enabled using the Enable output (see page 36) or using the voltage applied to the 0 - 10 VDC input. Reference the SYNC Service Manual for more details.
2. Make sure the ground terminal is connected to the ground output terminal of the external control, and the 0 - 10 VDC terminal is connected to the 0 - 10 VDC terminal of the external control.
Runtime contacts
The SMART TOUCH control closes a set of dry contacts whenever the burner is running. This is typically used by Building Management Systems to verify that the boiler is responding to a call for heat.
Alarm contacts
The SMART TOUCH control closes another set of contacts whenever the boiler is locked out or the power is turned off. This can be used to turn on an alarm, or signal a Building Management System that the boiler is down. Note that these contacts will close momentarily at the end of each call for heat or at least every 24 hours.
Wiring of the cascade
When wiring the boilers for Cascade operation, select one boiler as the Leader boiler. The remaining boilers will be designated as Members. See page 45 “Configuration of the Cascade” for a detailed explanation of this procedure.
Connect the system supply sensor and outdoor air sensor (if used) to the Leader boiler. For the Cascade system to work properly the system supply sensor must be installed.
The location of the system supply sensor should be downstream of the boiler connections in the main system loop (FIG.’s 5-5 and 5-6). The system supply sensor should be wired to the Low Voltage Connection Board at the terminals marked for the system supply sensor (see FIG. 7-3). The Leader control will use the water temperature at the system supply sensor to control the operation of the Cascade.
If outdoor air reset is desired, the outdoor air sensor should be wired to the Low Voltage Connection Board at the terminals marked for the outdoor air sensor on the Leader boiler (FIG. 7-3). If the outdoor air sensor is connected, the Leader control will calculate the water temperature set point based on the programmed reset curve parameters. If the outdoor air sensor is not connected, the Leader control will maintain the fixed water temperature set point that is programmed into the control.
If a Thermostat or Zone Control enable output is available, it should be wired to the Low Voltage Connection Board on the Leader boiler at the terminals marked Enable (FIG. 7-3). If the boilers are to run continuously, connect a jumper wire between the R and W terminals at the Enable input. This will initiate a call for heat on the Cascade. If the SMART TOUCH control is being controlled by a Boiler Management System (BMS), a call for heat may be initiated by the voltage applied to the 0 - 10 VDC input.
Communication between the Leader boiler and the Member boilers is accomplished by using shielded, 2-wire twisted pair communication cable. Connect one of the twisted pair wires to terminal A on each of the Low Voltage Connection boards, and the other wire of the twisted pair to terminal B on each of the Low Voltage Connection Boards. Connect the shield wires to one of the shield ground terminals on the Low Voltage Connection Boards (FIG. 7-3). If more than two boilers are on the Cascade, daisy chain the wiring from the Sequencing terminals on the second boiler to the Sequencing terminals on the third boiler, then from the third to the forth, and so on. The connections between boilers can be made in any order, regardless of the addresses of the boilers. Try to keep each cable as short as possible.
37
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
NOTICE
DO NOT INSTALL THE SYSTEM SUPPLY SENSOR INTO THE SYSTEM RETURN.
Installation & Operation Manual
7 Field wiring
Figure 7-3 Low Voltage Field Wiring Connections
38
MOD BUS
LBL20052 REV B
ENABLE
1 ALARM
2 CONTACTS
3 RUN TIME
SHIELD
B
A
4 CONTACTS
5 LOUVER
6 PROVING
7 MODULE 2
8 FLOW SWITCH
9 MODULE 1
15 SHIELD GND
13 R
11 TANK
10 FLOW SWITCH
12 THERMOSTAT
14 W
16 A
17 B
18 SHIELD GND
19 (+)
0 - 10V INPUT
21 SYSTEM
20 (-)
22 SENSOR
23 OUT DOOR
24 SENSOR
26 SENSOR
25 TANK
CASCADE
30 SHIELD GND
27 SHIELD GND
29 A
28 B
SHIELD
TO NEXT BOILER
A
B
BUILDING
MANAGEMENT
SYSTEM
LOUVER
PROVING
SWITCH
MODULE 2
MODULE 1
A
B
SHIELD
FROM PREVIOUS BOILER
THERMOSTAT
CONTROL
EXTERNAL
SYSTEM SENSOR
TAN K
TST2032
TST2303
OUTDOOR SENSOR
TST2032
TAN K S EN SO R
Installation & Operation Manual
8 Condensate disposal
Condensate drain
1. This boiler is a high efficiency appliance that produces condensate.
2. The rear of the boiler has a 1/2 inch (12.7 mm) PVC union for connection of a 1/2 inch (12.7 mm) PVC pipe (FIG. 8-1).
3. Slope condensate tubing down and away from the boiler into a drain or condensate neutralizing filter. Condensate from the SYNC will be slightly acidic (typically with a pH from 3 to 5). Install a neutralizing filter if required by local codes.
A Neutralizer Kit (FIG. 8-1) is available from the factory (KIT3046).
4. Install the 1/2 inch (12.7 mm) PVC tee assembly (shipped with the unit) as shown in FIG. 8-1.
5. Leave the top of the 1/2 inch (12.7 mm) tee OPEN. This is needed as a vacuum break.
6. Do not expose condensate line to freezing temperatures.
Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with ASTM D1785 or D2845. Cement and primer must comply with ASME D2564 or F493. For Canada use CSA or ULC certified PVC or CPVC pipe, fittings, and cement.
7. A condensate removal pump is required if boiler is below drain. When installing a condensate pump, select one approved for use with condensing boilers and furnaces. The pump should have an overflow switch to prevent property damage from condensate spillage. The switch should be wired to the auxiliary device proving switch terminals on the low voltage connection board.
NOTICE
NOTICE
To allow for proper drainage on large horizontal runs, a second line vent may be required and tubing size may need to increase to 1 inch (25 mm).
The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, condensate can exit from the boiler tee, resulting in potential water damage to property.
Figure 8-1 Condensate Disposal
39
1/2" (12.7 mm) PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
1/2" (12.7 mm) PVC UNION
(FACTORY SUPPLIED)
FLOOR DRAIN
OR DRAIN PAN
NEUTRALIZER KIT
Installation & Operation Manual
9 Start-up
Check/control water chemistry
Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and gaskets in the system could occur, resulting in substantial property damage.
Hardness less than 7 grains
1. Consult local water treatment companies for hard water areas (above 7 grains hardness).
Chlorine concentration less than 200 ppm
1. Do not fill boiler or operate with water containing chlorine in excess of 200 ppm.
2. Filling with chlorinated fresh water should be acceptable since drinking water chlorine levels are much lower.
3. Do not use the boiler to directly heat swimming pool or spa water.
Test/replace freeze protection fluid
1. For systems using freeze protection fluids, follow fluid manufacturer’s instructions.
2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time. Follow all fluid manufacturer’s instructions.
Freeze protection (when used)
1. Determine freeze protection fluid quantity using system
water content, following fluid manufacturer’s instructions. Boiler water content is listed on page 6. Remember to include expansion tank water content.
2. Local codes may require a backflow preventer or actual
disconnect from city water supply.
3. When using freeze protection fluid with automatic fill,
install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing concentration to drop, reducing the freeze protection level.
Fill and test water system
1. Fill system only after ensuring the water meets the requirements of this manual.
2. Close manual and automatic air vents and boiler drain valve.
3. Fill to correct system pressure. Correct pressure will vary with each application.
a. The minimum cold water fill pressure for a
commercial system is 12 psi (82.7 kPa).
b. Pressure will rise when boiler is turned on and
system water temperature increases.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.
Purge air from water system
1. Purge air from system:
2. Open automatic air vent (diaphragm-type or bladder­type expansion tank systems only) one turn.
3. Open other vents: a. Starting on the lowest floor, open air vents one at a
time until water squirts out.
b. Repeat with remaining vents.
4. Refill to correct pressure.
4. At initial fill and during boiler startup and testing, check system thoroughly for any leaks. Repair all leaks before proceeding further.
WARNING
CAUTION
40
Installation & Operation Manual
9 Start-up (continued)
Check for gas leaks
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the top access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.
DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
Propane boilers only – Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
Check thermostat circuit(s)
1. Disconnect the two external wires connected to the enable terminals on the connection board.
2. Connect a voltmeter across these two incoming wires. Close each thermostat, zone valve, and relay in the external circuit one at a time and check the voltmeter reading across the incoming wires.
3. There should NEVER be a voltage reading.
4. If a voltage does occur under any condition, check and correct the external wiring. (This is a common problem when using 3-wire zone valves.)
5. Once the external boiler enable wiring is checked and corrected if necessary, reconnect the external thermostat circuit wires to the connection board. Allow the boiler to cycle.
Inspect/fill condensate system
Inspect/check condensate lines and fittings
1. Inspect the condensate drain line, condensate PVC fittings and condensate trap.
Fill condensate trap with water
1. Remove the PVC cap retaining screw from the PVC cap (FIG. 9-1).
2. Remove the 2 inch PVC cap with the switch located at the top of the trap (FIG. 9-1).
3. Fill with fresh water until the water begins to pour out of the drain.
4. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
5. Replace the retaining screw.
The condensate trap (FIG. 9-1) must be filled with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.
Figure 9-1 Condensate Trap
WARNING
WARNING
WARNING
WARNING
41
PVC TEE ASSEMBLY (FACTORY SUPPLIED)
2" PVC CAP WITH BLOCKED DRAIN SWITCH
RETAINING SCREW
CONDENSATE FROM HEAT EXCHANGER
TO FLOOR DRAIN
Installation & Operation Manual
9 Start-up
Final checks before starting the boiler
Read the SYNC Service Manual to familiarize yourself
with SMART TOUCH control module operation. Read this manual, page 43 for proper steps to start boiler.
Verify the boiler and system are full of water and all
system components are correctly set for operation.
Verify the preparation procedures of Section 9, pages 40
and 41 have been completed.
Fill the vent condensate trap with water (removing the
retaining screw in order to remove the 2 inch (50.8 mm) PVC cap with the switch located at the top of the trap). Replace the cap. Press the cap onto the trap until the cap makes contact with the drain. Replace the retaining screw.
Verify electrical connections are correct and securely
attached.
Inspect vent piping and air piping for signs of
deterioration from corrosion, physical damage or sagging. Verify air piping and vent piping are intact and correctly installed per this manual.
Start the boiler
1. Read and follow the Operating instructions in FIG. 9-2, page 43.
If boiler does not start correctly
1. Check for loose connections, blown fuse or service switch off?
2. Is external limit control (if used) open? Is boiler water temperature above 200°F (93°C)?
3. Is thermostat set below room temperature?
4. Is gas turned on at meter or boiler?
5. Is incoming gas pressure less than 4 inches w.c. (.99 kPa)?
If none of the above corrects the problem, refer to the Troubleshooting Section of the SYNC Service Manual.
Check system and boiler
Check water piping
1. Check system piping for leaks. If found, shut down the boiler and repair immediately. (See WARNINGS on pages 40 and 41 (startup) regarding failure to repair leaks.)
2. Vent any remaining air from the system using manual vents. Air in the system will interfere with circulation and cause heat distribution problems and noise.
Check vent piping and air piping
1. Check for gastight seal at every connection, seam of air piping, and vent piping.
Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
Check gas piping
1. Check around the boiler for gas odor following the procedure on page 31 of this manual (connecting gas supply piping).
If you discover evidence of any gas leak, shut down the boiler at once. Find the leak source with a bubble test and repair immediately. Do not start the boiler again until corrected. Failure to comply could result in severe personal injury, death, or substantial property damage.
Check flame and combustion
1. Turn the main power off to the boiler by placing the “On/Off” switch in the OFF position.
2. Remove the flue temperature sensors from the flue pipe connections. Note:
Combustion measurements will be
made at this point.
3. Turn the main power on to the boiler by placing the “On/Off” switch in the ON position.
WARNING
WARNING
42
Installation & Operation Manual
Figure 9-2 Operating Instructions
9 Start-up (continued)
43
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury, or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automatically lights the burner. Do not to light the burner by hand.
B. BEFORE OPERATING smell all around
the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WH AT TO DO I F YO U SM ELL G AS
Do not try to light any appliance.
Do not touch any electric switch; do
not use any phone in your building.
try
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light t he burne r by hand.
5. Remove front door.
6. Turn gas shutoff valves counterclockwise to “OFF”. Handle will be perpendicular to pipe. Do not force.
7. Wait five (5) minutes to clear out any gas. If you then smell gas, in the safety information above this label. If you don’t smell gas, go to next step.
STOP! Follo w “B”
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to turn the gas control knob.
Never use tools. If the ha ndle wil l not tu rn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
8. Turn gas shutoff valve clockwise to “ON”. Handle will be p arallel to pipe.
9. Install top cover.
10. Turn on all electric power to appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove front door.
4. Turn gas shut off valves counterclockwise to “OFF”. Handle will be perpe ndicular to pipe. Do not force.
5. Install front door.
LBL20053 REV A
Installation & Operation Manual
9 Start-up
Check flame and combustion (continued)
4. Navigate to the Service Mode Screen from the Status Screen by pressing the MAIN button and then the SERVICE MODE button.
5. On the Service Screen place the Primary Module into operation by selecting Module 1 with the SELECT button and turning the module on by pressing the ON/OFF button (OFF indicates that the module is off and ON indicates that the module should be firing).
6. Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor.
Note:
The Primary Module is the top module; please
ensure the probe is in the top flue sensor location.
7. Once the module has modulated up to full fire measure the combustion. The values should be in the range listed in Table 9A below. CO levels should be less than 200 ppm for a properly installed unit. If the combustion is not within range reference the Troubleshooting Section in the SYNC Service Manual for possible causes and corrective actions.
Set space heating operation
Verify space heat circulator mode
The Space Heating Mode controls the system pump (if connected), and both boiler pumps. When the SMART TOUCH control receives a space heating call for heat, it turns on the system pump. If the boiler is not heating an indirect HW (Hot Water) tank, it also turns on the boiler pump. After the space heating call for heat ends, the system pump continues to run for a short period of time. If the boiler pump was running, it continues to run for a short period of time as well. These pump delays are factory set to 30 seconds. If different delays are desired, the appropriate parameters in the control must be changed. See the SYNC Service Manual for a detailed explanation of this procedure.
Set space heating set point temperature
During normal operation, space heating set point temperatures can be adjusted from the Set Points Menu. Press the following buttons to navigate to the Set Points Menu from the Status Screen:
1. To change a set point, press the SELECT button next to the user set point parameter.
2. The first time the user set point parameter is accessed, you will be required to enter the user password. The user password is 0704.
3. Using the keypad, enter the password and then press the OK button. If the password is not entered correctly, the screen will revert to the Parameter List Screen and you will not be able to adjust the set point. If a digit has been entered incorrectly, press the left arrow key on the keypad to back the digit up. If the password has been entered correctly, the Parameter Change Screen will appear. The Parameter Change Screen will display the set point being changed, the previous setting of the set point, and adjustment buttons.
4. To adjust the set point, press the + or - buttons to change the value being displayed.
5. Once the set point has been adjusted to the desired setting press the APPLY button to change the set point and return to the Parameter List Screen.
Table 9A Flue Products Chart
8. Once the Primary Module analysis is complete, test the safety shutoff device by turning the manual shutoff valve to the OFF position and ensuring that the Primary Module shuts down and registers an alarm. Open the manual shutoff valve, reset the control, and return to Service Mode.
9. Repeat the same procedure for the Secondary Module by selecting Module 2 while on the Service Mode Screen. Be certain to insert the probe from the combustion analyzer into the Secondary Module flue temperature sensor location.
10. Turn the main power off to the boiler and replace the
flue temperature sensor into the flue pipe connection.
11. Place the boiler back into normal operation.
You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Natural Gas Propane
CO
2
O
2
CO
2
O
2
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%
44
>> >>
Installation & Operation Manual
6. If no other changes are necessary, press the BACK button to return to the Parameter List Screen.
7. Once all the necessary adjustments have been made, press the BACK button to return to the Setup Screen.
8. Press the SAVE button to program all changes made to the set points and return to the Status Screen. Leaving the Setup Screen without pressing the SAVE button will erase the changes made to the set points and change them back to their previous settings.
Note:
The SAVE button must be pressed to ensure proper programming of the controls. Failure to press the SAVE button will require all changes to be reprogrammed.
Set Hot Water Generator (HW) operation
Verify HW circulator mode
The HW Mode is programmed to heat an indirect hot water tank. When a tank thermostat or a tank sensor initiates a call for heat, the SMART TOUCH control will turn on the HW pumps and turn off the boiler pumps (if running). If the system pump is running, it will remain on. When the HW call for heat ends, and there is no space heating call for heat, the HW pumps will continue to run for a period of time. This pump delay is set at the factory to 30 seconds. If a shorter or longer delay is desired, the appropriate parameter in the control must be changed. See the SYNC Service Manual for a detailed explanation of this procedure. If there is an active space heating call for heat, then the boiler pumps will be turned on and the HW pumps will be turned off.
Set HW target temperature
When in the HW Mode, the control will modulate to maintain the outlet temperature to a set point. This set point is set at the factory to 180°F. If a different set point is desired, the appropriate parameter in the control must be changed. See the SYNC Service manual for a detailed explanation of this procedure.
Set clock
To program the clock, access the night setback parameter by pressing the following buttons:
The SMART TOUCH control has a built-in clock that it uses for its night setback feature and for logging events. This clock must be set when the boiler is installed, and anytime the boiler has been powered off for more than one month. Use the following procedure to set the clock:
1. To set the clock, press the SELECT button in the upper right-hand corner of the display. The date and time are displayed as “Day dd/mm/yy hh:mm”. Day = day of the week (1 = Monday, 2 = Tuesday, etc.), dd = date, mm = month, yy = year, hh = hour, mm = minutes (24 hour time; 2:30PM = 14:30).
NOTICE
The internal clock does not adjust for Daylight Savings Time and therefore, will require a manual adjustment.
Configuration of the cascade
When installed in a Cascade system, the individual controls must be programmed for cascade operation. To program the cascade parameters, access the Cascade Menu found in the Setup Menu by pressing the following buttons:
Note:
The CASCADE button on the Main Menu will only
display the current status of the cascade.
1. Once in the Cascade Setup Menu select the appropriate parameter by pressing the SELECT button.
2. The first time the cascade setup parameters are accessed,
you will be required to enter the service password. Enter the service password as described in the SYNC Service Manual.
3. Once the password has been entered correctly, the
Parameter Change Screen will appear. The Parameter Change Screen will display the parameter being changed, the previous setting of the parameter, and adjustment buttons.
4. To adjust the parameter, press the + or - buttons to change
the value being displayed.
5. Make the correct adjustments and then press the APPLY button.
6. Once all the parameters have been adjusted press the BACK button. This will return you to the Setup Menu.
7. Press the SAVE button to program all controls.
Note:
The SAVE button must be pressed to ensure proper programming of the controls. Failure to press the SAVE button will require all changes to be reprogrammed.
9 Start-up
>> >>
45
2. Using the keypad, adjust the date and time by working from left to right. If a digit has been entered incorrectly, press the left arrow key on the keypad to back the digit up. If no change is necessary, press the BACK button to return to the Parameter List Screen. Once the correct date and time have been entered press the OK button on the display to program the date and time into memory and return to the Parameter List Screen.
>> >>
Installation & Operation Manual
General
How the boiler operates
The SYNC uses advanced stainless steel heat exchangers and electronic control modules that allow fully condensing operation. The blowers pull in air and push flue products out of the boiler through the heat exchangers and flue piping. The control modules regulate blower speed to control the boiler firing rate. The gas valve senses the amount of air flowing into the boiler and allows only the right amount of gas to flow.
How the control modules operate
The SYNC boiler is equipped with two (2) SMART TOUCH control modules. The control modules work in synchronization to meet the heat demand of the system.
The SMART TOUCH control modules receive input from boiler sensors and external inputs. The control modules activate and control the blowers and gas valves to regulate heat input and switches the boiler, Hot Water Generator (HW), and system pumps on and off as needed. The user programs the modules to meet system needs by adjusting control parameters. These parameters set operating temperatures and boiler operating modes. Boiler operation is based on system temperature.
Control inputs and outputs
Room thermostat / zone control
This input tells the boiler to provide water for space heating.
Hot Water Generator (HW) tank thermostat
This input tells the boiler to provide water for heating an indirect HW tank.
0 - 10V input (set point or power)
The SYNC can be controlled by a Building Management System (BMS) using a 0 - 10 VDC signal. The control can be configured by the installer to use this signal to either control set point or firing rate.
HW priority
The SMART TOUCH control module allows connection of a HW thermostat to the low voltage connection board. When the HW thermostat calls for heat, the modules activate the HW pumps, shuts down the boiler pumps, and immediately sets the target outlet water temperature to 180°F (82.2°C). This provides automatic priority heat allocation to the HW Generator for maximum response and recovery. The HW pumps continue for 30 seconds after the heating cycle to deliver the most possible heat.
Controlling sensor
The control module is programmed to use the outlet sensor as the control sensor by default. If a system supply sensor is connected, the control automatically uses it as the control sensor.
Anti-cycling
After a space heating demand has been satisfied, the control will delay the next space heating call for a set time period (time is adjustable by the installer). The time delay will be bypassed if the inlet water temperature drops too far during the delay.
Boiler, system, and HW pump control
When a space heating call for heat starts and no HW call is on, the system and boiler pumps are turned on. As long as the space heating call for heat is on, the system pump will remain on. If a HW call for heat is on, the boiler pumps will wait to turn on until just before the HW pumps turn off. After the space heating call for heat ends, both pumps will run for an additional period of time.
When a HW call for heat starts, the HW pumps are turned on. If a space heating call for heat was on, the boiler pumps will turn off a few seconds after the HW pumps turn on.
Louver
A dry contact is provided to open and close louvers whenever the SYNC boiler requires combustion air from inside the room. Connect the Louver End Switch to the Louver Proving Switch input on the Low Voltage Connection Board.
Temperature control
Modulation
The SYNC is capable of modulating its firing rate from a minimum of 10% to a maximum of 100%. The firing rate is dictated by the call for heat (i.e., space heating or hot water generation), the heating load, and various other temperature limitations.
10 Operating information
46
Installation & Operation Manual
10 Operating information (continued)
Gradient limiting
If during operation of the boiler the outlet water temperature is rising too quickly, the control will reduce the firing rate to its lowest setting.
Outdoor air reset
If an outdoor air sensor is connected, the control module will calculate the set point based on the programmed reset curve. The installer can change the slope of the reset curve by several adjustable parameters. The user can limit the maximum set point for the system using the space heating set point.
Boost function
If outdoor air reset is active, and a space heating demand has been active continuously for a set period of time (time adjustable by installer) and there has been no HW demands, the control will increase the set point by a fixed number of degrees (adjustable by installer). This process will continue until the space heating demand ends, the set point reaches the programmed set point or a maximum of 20 increases has occurred. Once the system heat demand is satisfied, the set point will revert to the value determined by the reset curve.
Night setback
The controller may be programmed to reduce the space heating set point during a certain time each day. A start and stop time can be programmed for each day of the week.
Flame current support
To prevent nuisance shutdowns when the boiler is firing at minimum rates, the control will increase the firing rate when the flame signal drops too low.
Protection features
Outlet temperature, flue temperature, and temperature rise limiting
The outlet temperature is monitored by the boiler outlet temperature sensor. When the outlet temperature exceeds 185°F, the unit will reduce the fan speed. If the outlet water temperature exceeds 195°F (90°C) the control will shut the unit down until it cools off.
The control module monitors the flue temperature by a sensor located in the flue exhaust. If the flue temperature exceeds 215°F (102°C) the control will reduce the maximum fan speed. If the flue temperature exceeds 240°F (115°C) the control will shut the unit down. The unit will restart automatically once the flue temperature drops 25°F (14°C) and the minimum off time has expired.
The control monitors the temperature difference between the inlet and the outlet sensor. If this difference exceeds 55°F (13°C) the control will reduce the fan speed. If the temperature difference exceeds 60°F (15°C) the control will shut the unit down. The unit will restart automatically once the temperature difference has dropped below 55°F (31°C) and the minimum off time has expired.
Freeze protection
DO NOT install the boiler in a room likely to freeze.
The following integral feature of the SMART TOUCH control module provides some protection for the boiler only -- not for the system.
• The SMART TOUCH control module provides freeze-up protection as follows when the boiler water temperature drops below 45°F (7°C):
Below 45°F (7°C), the boiler and system pumps operate constantly.
Below 37°F (3°C), the boiler turns on.
Boiler and pumps turn off if boiler water temperature rises above 45°F (7°C).
This feature of the SMART TOUCH control module does not eliminate the possibility of freezing. The installation must still use recognized design, installation and maintenance practice to prevent freeze potential for the boiler and system.
CAUTION
47
Installation & Operation Manual
10 Operating information
Monitor external limits
Connections are provided on the connection board for external limits such as flow switch and a louver proving switch. The SMART TOUCH control will shut off the burner and inhibit relighting whenever any of these external limits open.
Run-time and alarm outputs
The boiler provides dry contacts for indicating when the boiler is running, and when it is unable to operate.
Run-time and cycle counting
The control uses two timers to monitor the total hours of burner operation. One timer monitors the time the boiler is firing under 50% of rate. The other timer monitors the time the boiler is firing over 50% rate.
The control uses four (4) ignition counters to monitor the amount of boiler cycles. The first counter counts all ignitions of the control. The second counter counts only ignition attempts that have failed. The third and fourth counters are the same as the first and second respectively, but can be reset by the installer.
Service reminder
The control can be programmed for service reminder notification. This notification will become active when either a set time frame has expired, or a set amount of running hours or cycles has expired (all adjustable by the installer). The display will alternate the standard text on the display screen with Service Due every 5 seconds. The service reminder notification can be reset by the installer.
Error logging
The control will hold in memory the last 10 error codes as well as the last 10 turn-off functions. The date and time of the occurrence will be recorded as well. Only the 10 most current occurrences will be held in memory.
Boiler temperature regulation
Operating temperature (target)
The SMART TOUCH control module senses water temperature and regulates boiler firing and firing rate to achieve a target temperature. The target temperature can be set between 70°F (21°C) and 190°F (88°C).
• Target temperature is fixed when the outdoor sensor is not installed.
Target temperature is calculated as described below under “Outdoor Reset Operation” and “Target Temperature Boost” when the outdoor sensor is connected.
48
High limit operations
When outlet temperature exceeds 200°F (93.3°C), high limit action occurs. The boiler shuts down until the outlet water cools down.
Low water cutoff protection
1. A low water cutoff device with test and reset functionality is provided in the boiler as standard equipment.
Flow sensing device
1. The SMART TOUCH control module uses temperature sensing of both supply and return temperatures of the heat exchanger. If the flow rate is too low or the outlet temperatures too high, the control module modulates down and will shut the boiler off. This ensures boiler shutdown in the event of low flow conditions.
Outdoor reset operation, if used
Target temperature with outdoor reset
This feature improves the system’s efficiency as the outdoor temperature warms up.
See the SYNC Service Manual to change the settings.
Reset curve
The reset curve looks at outdoor air temperature and adjusts the set point.
Cascade
When multiple boilers are installed, they can be wired together in a cascade sequence. A maximum of eight boilers can be controlled from a single control. In this application one boiler would be designated as the Leader control and all others would be designated as Member controls.
Once the Leader boiler receives a call for heat from the Enable input or 0 - 10 VDC input, the control will determine what the set point will be. If outdoor air reset is desired, connect the outdoor air sensor to the terminals on the Low Voltage Connection Board on the Leader boiler. The set point will be calculated based on the programmed reset curve parameters. See the SYNC Service Manual to program the reset curve. If outdoor air reset is not desired, do not connect the outdoor air sensor. A fixed temperature set point can be programmed into the control.
NOTICE
If a mechanical flow switch is required to meet local code requirements the SYNC boiler can be equipped with field supplied switches on each inlet. Please reference page 36 of this manual for more information.
Installation & Operation Manual
If the water temperature at the system supply sensor is less than the set point + the turn-off offset - the off-on differential, then the control will initiate a call for heat on the Cascade (see the SYNC Service Manual for an explanation of the offset and differential). The Leader will energize the lead boiler on the Cascade. For a new startup this will be the Leader boiler.
The boiler will fire at its ignition speed and will then modulate its firing rate to maintain the set point. If the first boiler reaches 100% of its firing rate, the Leader will calculate at what point the second boiler could fire at 10% of its firing rate. At this point, the Leader will fire the second boiler on the Cascade. For a new startup, this would be the first Member boiler. The boiler will fire at its ignition speed and will then modulate its firing rate to maintain the set point.
If the set point still cannot be met, the Leader will continue firing more Members until either the heat demand is met or all boilers on the Cascade are firing. As the heat demand decreases, the last boiler on will modulate down to 10% of its firing rate. Once the demand for that boiler is zero, it will shut down. As the heat demand decreases further, the second to last boiler will modulate down and shut off. This will continue until the demand is satisfied and all boilers are shut off.
HW operation with cascade
For HW operation any boiler(s) in the Cascade can be selected to provide heat for a HW call. Select a boiler to be designated as the HW boiler. Connect the HW thermostat or sensor to the terminals on the Low Voltage Connection Board marked for the HW Thermostat or sensor. When the boiler receives a HW call, the Leader control will take that boiler out of the Cascade sequence. If another boiler is available, the Leader will start it up to take its place.
The HW boiler will adjust its set point to the programmed HW set point and will adjust its firing rate to maintain this. Once the HW call has been satisfied, the Leader control will place that boiler back into the Cascade sequence.
Night Setback operation with cascade
Night Setback operation of the boilers within the Cascade is available. Programming of the Night Setback will be done through the Leader boiler. Refer to the SYNC Service Manual for information regarding Night Setback.
Sequence of the cascade
To equalize the run time of all boilers on the Cascade, the firing sequence will automatically be changed at set intervals.
For the first 24 hours after initializing the Cascade, the sequence will be changed every hour. After that the sequence will be changed once every 24 hours. The switching on/off sequence will be as follows:
DAY SWITCHING ON SEQUENCE
Day 1 L-M1-M2-M3-M4-M5-M6-M7
Day 1 + 1 hour M2-M3-M4-M5-M6-M7-L-M1
Day 1 + 2 hours M4-M5-M6-M7-L-M1-M2-M3
49
10 Operating information (continued)
Installation & Operation Manual
10 Operating information
Sequence of operation
1.
Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for a space heating call, HW pump relay output for a HW call).
2.
The control confirms that the low water cutoff and flow switch (optional) contacts are closed.
3.
The control starts the blower and closes the louver contacts to begin the Pre-Purge cycle.
4.
The control confirms that the blower comes up to the desired speed, the flap valve opens, and the air pressure switch, gas pressure switch (optional), louver proving switch (optional), and blocked drain switch contacts close.
5.
Once the Pre-Purge cycle is complete, the control lowers the blower speed, initiates sparking of the ignition electrode, and opens the gas valve.
6.
After a short wait, the control stops sparking and checks for the presence of flame current through the spark and flame sense electrodes.
7.
If the control does not detect flame current, the control will lockout indefinitely, until the RESET button on the touch screen LCD is pressed.
8.
If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set point temperature.
9.
If the current call for heat is for space heating and a HW call for heat becomes active, the control will turn on the HW pump relay output, then turn off the boiler pumps. It will then modulate the blower speed in order to maintain the outlet temperature to the desired HW outlet set point temperature.
10.
If the first module in the boiler is unable to maintain the desired set point temperature, the second module in the boiler will be started, using much of the same sequences as described above. Once both modules are firing, the controls will work in synchronization to maintain the desired set point temperature. If the heat load should decrease sufficiently, the second module will be shut down, much like the sequences described below.
11.
Once both the space heating and HW calls for heat are satisified, the control will turn off the gas valve and begin the Post-Purge cycle. Any pumps that are running will begin their respective Pump Delay cycles.
12.
At the end of the Post-Purge cycle, the louver contacts will open.
13.
The control verifies that the blower stops running and the flap valve closes.
14.
At the end of the Pump Delay cycle(s), the pump(s) will be turned off.
Note: This unit is equipped with two (2) independent, but synchronized combustion systems. The primary (top) combustion system will fire first. If the demand cannot be met by one (1) combustion system the same sequence of operation will be followed to bring the secondary combustion system online.
50
51
Installation & Operation Manual
SYNC control module
Figure 10-1 Status Screen
The Status Screen displays boiler status, Cascade addresses, outlet water temperature, inlet water temperature, system temperature, and tank temperature.
The boiler can be changed by pressing the ON/OFF button. The Details Screen and Main Menu Screen can be accessed by pressing the appropriate button.
10 Operating information (continued)
When the ON/OFF switch is turned to the ON position, the first screen visible on the LCD display will be the Status Screen. This screen displays the current status of the SYNC boiler. The following items can be viewed or interacted with on the Status Screen:
On/Off button - Pressing this button allows the boiler to be placed in either Manual Shutdown Mode or Standby Mode.
Boiler Status - This line shows the current operating status of the SYNC boiler. Displayed items are as follows:
• Manual Shutdown - The boiler will not respond to either a system call or a hot water generation call.
• Standby - The boiler has not received a system call or hot water generation call.
• SH Call for Heat - The boiler has received a system heat call.
• SH Pump Delay - The boiler has satisfied a system heat call and the boiler pumps are running for a fixed time to remove any residual heat.
• HW Storage - The boiler has received a hot water generation call.
• HW Pump Delay - The boiler has satisfied a hot water generation call and the hot water generator pumps are running for a fixed time to remove any residual heat.
• SH BMS - The boiler has received a call for heat from a 0-10 VDC BMS control.
• Service Set Point Met - While in Service Mode, the water temperature at either the outlet sensor or the system sensor has exceeded 185°F.
• HW Outlet Set Point Met - The outlet water temperature has exceeded the HW Generator Set Point parameter.
• OA Shutdown - The outside air temperature has exceeded the Outdoor Shutdown Set Point parameter.
• SH Set Point Met - The water temperature as measured by the system supply sensor has exceeded the User Set Point parameter or if the optional Outdoor Air Sensor was used, the calculated set point based on the Outdoor Reset parameters.
• Anti-Cycle Delay - The boiler has satisfied a system heat call, but has received another system heat call before the anti-cycling time parameter has elapsed.
• Cascade ComError - A communication error has occurred between the Module 1 and Module 2 control modules or between the Leader and Member boilers.
10 Operating information
52
Installation & Operation Manual
Boiler Configuration - This line shows the current configuration of the two control modules inside the unit.
Outlet Water Temperature - This is a calculated temperature based on the readings of the outlet temperatures of the two (2) heat exchangers.
System Water Temperature - This is the water temperature as measured by the system supply sensor located in the downstream piping.
Inlet Water Temperature - This is a calculated temperature based on the inlet temperature readings from the two (2) heat exchangers.
Hot Water Tank Temperature - This is the temperature as measured by the tank sensor in the hot water storage tank.
Time - The time is displayed in the upper right-hand corner of the display. It is displayed in 24 hour format. Reference the Night Setback parameters on page 25 for information regarding adjusting the date and time.
Details button - Pressing this button brings up the Details Screen. This screen shows the status of the various safeties, inputs, and outputs to each control module. Reference the Details Screen section in the SYNC Service Manual for more information regarding this screen.
Main button - Pressing this button brings up the Main Screen. From this screen navigation to eight (8) other screens is possible. Reference the Main Screen section on page 53 of this manual for more information regarding this screen.
53
Installation & Operation Manual
10 Operating information (continued)
Figure 10-2 Main Menu Screen
Use the Main Menu Screen (FIG. 10-2) to access the screens necessary to set temperatures, operating conditions, and monitor boiler operation.
The SYNC is equipped with a SMART TOUCH control system. All menu options are accessed by touching the screen with your finger or a stylus from a PDA.
The Main Screen allows navigation to eight (8) additional screens which are used to set temperatures, operating conditions, and monitor boiler operation. These screens are as follows:
• Setup - Allows access to seven (7) other screens for the adjustment of the control parameters.
• Cascade - Shows the status of multiple boilers connected together in a cascade arrangement.
• Temps - Shows the temperatures measured by the individual sensors connected to the boiler.
• Burners - Shows the status of the two (2) independent burner systems used in the boiler.
• Building - Shows the information from a Building Integration System using Modbus Protocols.
• Graphs - Allows the selection of items to be graphed on a chart.
• History - Shows the operating and fault history of the two (2) control modules.
• Service Mode - Allows the installer to control the fan speed of the individual control modules for the purposes of combustion analysis. Service Mode will override all other heat demands, however, all safeties will remain intact.
Navigation to the Main Screen can be accomplished by pressing the MAIN button at the bottom of the page.
Reference the SYNC Service Manual for more information regarding the eight (8) accessible screens.
Time - The time is displayed in the upper right-hand corner of the display. It is displayed in 24 hour format. Reference the night setback parameters in the SYNC Servie Manual for information regarding adjusting the date and time.
Status button - Pressing this button displays the Status Screen. This screen shows the current status of the SYNC boiler. Reference pages 51 - 52 for more information regarding this screen.
54
Installation & Operation Manual
11 Maintenance
Maintenance and annual startup
Table 11A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
• Address reported problems, if any
• Inspect interior; clean and vacuum if necessary;
• Clean condensate trap and fill with fresh
water
• Check for leaks (water, gas, flue,
condensate)
• Verify flue and air lines in good condition
and sealed tight
• Check system water pressure/system
piping/expansion tank
• Check control settings
• Check ignition and flame sense
electrodes (sand off any deposits; clean and reposition)
• Check wiring and connections
• Perform start-up checkout and
performance verification per Section 9.
• Flame inspection (stable, uniform)
• Flame signal (at least 10 microamps at high fire)
• Clean the heat exchanger if flue
temperature is more than 54°F (30°C) above return water temperature.
If combustion or performance indicate need:
• Clean heat exchanger
• Remove and clean burner using compressed air only
• Clean the blower wheel
ANNUAL START-UP
Owner maintenance
(see the SYNC User’s Information Manual for
instructions)
Daily
• Check boiler area
• Check pressure/temperature gauge
Monthly
• Check vent piping
• Check air piping
• Check air and vent termination
screens
• Check relief valve
• Check condensate drain system
• Check automatic air vents
Every
6 months
• Test low water cutoff
• Reset button (low water cutoff)
• Check boiler piping (gas and
water) for leaks
• Operate relief valve
End
of season
months
• Shut boiler down (unless boiler used for domestic hot water)
55
Installation & Operation Manual
11 Maintenance (continued)
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the boiler designated in Table 11A and explained on the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect boiler area
1. Verify that boiler area is free of any combustible materials, gasoline and other flammable vapors and liquids.
2. Verify that air intake area is free of any of the contaminants listed in Section 1 of this manual. If any of these are present in the boiler intake air vicinity, they must be removed. If they cannot be removed, reinstall the air and vent lines per this manual.
Inspect boiler interior
1. Remove the front access cover and inspect the interior of the boiler.
2. Vacuum any sediment from inside the boiler and components. Remove any obstructions.
Clean condensate trap
1. Inspect the condensate drain line, condensate PVC fittings, and condensate trap.
2. Remove the PVC cap retaining screw from the PVC cap (FIG. 11-1).
3. Remove the 2 inch PVC cap with the switch located at the top of the trap (FIG. 11-1).
4. Remove any sediment in the trap.
5. Fill with fresh water until the water begins to pour out of the drain.
6. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
7. Replace the retaining screw.
Eliminate all system or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 6 ­Gas Connections.
Check all piping for leaks
The condensate trap must be filled with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.
WARNING
WARNING
WARNING
WARNING
WARNING
Figure 11-1 Condensate Trap
PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
TO FLOOR
DRAIN
2” PVC CAP WITH
BLOCKED DRAIN SWITCH
RETAINING
SCREW
CONDENSATE FROM
HEAT EXCHANGER
56
Installation & Operation Manual
11 Maintenance
Flue vent system and air piping
1. Visually inspect the entire flue gas venting system and air piping for blockage, deterioration or leakage. Repair any joints that show signs of leakage. Verify that air inlet pipe is connected and properly sealed.
2. Verify that boiler vent discharge and air intake are clean and free of obstructions.
Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.
Check water system
1. Verify all system components are correctly installed and
operational.
2. Check the cold fill pressure for the system. Verify it is
correct (must be a minimum of 12 psi (82.7 kPa)).
3. Watch the system pressure as the boiler heats up (during
testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove
air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
Check expansion tank
1. Expansion tanks provide space for water to move in and
out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See Section 5 - Hydronic Piping for suggested best location of expansion tanks and air eliminators.
Check boiler relief valve
1. Inspect the relief valve and lift the lever to verify flow.
Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 5 - Hydronic Piping before proceeding further.
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the boiler until a new relief valve has been installed.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
WARNING
WARNING
WARNING
57
Installation & Operation Manual
11 Maintenance (continued)
Inspect ignition and flame sense electrodes
1. Remove the ignition and flame sense electrodes from the boiler heat exchanger access covers.
2. Remove any deposits accumulated on the ignition/flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones.
3. Replace ignition/flame sense electrodes, making sure the gaskets are in good condition and correctly positioned.
Check ignition ground wiring
1. Inspect boiler ground wire from the heat exchanger access cover to ground terminal strip.
2. Verify all wiring is in good condition and securely attached.
3. Check ground continuity of wiring using continuity meter.
4. Replace ground wires if ground continuity is not satisfactory.
Check all boiler wiring
1. Inspect all boiler wiring, making sure wires are in good condition and securely attached.
Check control settings
1. Set the control module display to Parameter Mode and check all settings. See Section 1 of the SYNC Service Manual. Adjust settings if necessary. See Section 1 of the SYNC Service Manual for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
Perform start-up and checks
1. Start boiler and perform checks and tests specified
in Section 9 - Start-up.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
Check burner flame
1. Inspect flame through observation window.
2. If the flame is unsatisfactory at either high fire or low fire, turn off boiler and allow boiler to cool down. Remove the burners and clean them thoroughly using a vacuum cleaner or compressed air. Do not use compressed air to clean burners if performed inside a building.
3. Remove the burners, reference FIG. 11-2.
4. When replacing the burners, ensure gaskets are in good condition and positioned correctly (FIG. 11-2).
Figure 11-2 Burner Assembly
DOOR FIBER
BURNER DOOR
BURNER DOOR
HEX NUT (6)
BURNER
STABILITOR
AIR/GAS GASKET
FLAPPER VALVE
SCREW (5X)
FLAPPER VALVE
FLAME SENSE
SCREW (2X)
IGNITER
FLAME SENSE
IGNITER GASKET
FLAME SENSE
GASKET
IGNITER SCREW (2X)
58
Installation & Operation Manual
11 Maintenance
Check flame signal
1. At high fire the flame signal shown on the display should be at least 10 microamps.
2. A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode.
3. See Section 3 - Troubleshooting in the SYNC Service Manual for other procedures to deal with low flame signal.
Review with owner
1. Review the SYNC User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the SYNC User’s Information Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
Cleaning boiler heat exchanger
1. Shut down boiler:
• Follow the “To Turn Off Gas to Appliance” instructions for the boiler in Section 9 - Startup.
• Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.
2. Allow time for the boiler to cool to room temperature if it has been firing.
3. Remove the blower assemblies (gas air/arm) from the heat exchanger access covers. Set bolts aside.
4. Remove the nuts securing the heat exchanger access covers to the heat exchangers and set aside.
5. Remove the heat exchanger access covers, cover gaskets and chamber insulation assemblies.
The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on page 59 of this manual. Failure to comply could result in severe personal injury.
6. Use a vacuum cleaner to remove any accumulation on the
boiler heating surfaces. Do not use any solvent.
7. Finish cleaning using a clean cloth dampened with warm
water.
8. Install access cover gaskets, chamber insulation assemblies
and covers.
9. Secure nuts on the studs. DO NOT overtighten.
10. Re-install the blower assemblies (gas air/arm) using the
bolts set aside in Step 3.
11. Close isolation valves on piping to isolate boiler from
system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler.
12. When the boiler has been flushed, restore boiler to
operation.
13. Perform start-up and check-out procedures in Section 9 -
Start-up.
WARNING
59
Installation & Operation Manual
11 Maintenance (continued)
Handling ceramic fiber materials
REMOVAL OF COMBUSTION CHAMBER LINING
The combustion chamber door insulation in this product contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).”:
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the boiler and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately. Breathing: Fresh air.
WARNING
60
Installation & Operation Manual
12 Diagrams
Figure 12-1 Ladder Diagram_Part 1
BOX DEPICTS
OPTIONAL ITEMS
LOW VOLTAGE 120 VAC
HIGH VOLTAGE
LOUVER RELAY 1
INLET
SENSOR
OUTLET
SENSOR
SENSOR
GAS VALVE
BLOWER
SPARK
ROD
FLUE
FLAP
VALVE
HI-LIMIT
BLOCKED
DRAIN
AUTO RESET
HIGH LIMIT
AIR PRESSURE
SWITCH
X2-2
X2-1
1
2
4
5
TR1
X1-7
FLAME ROD
X5-5
X5-13
X5-6
X5-12
MODULE 1 CONTROL
24V
GAS VALVE
RELAY
X8
LOUVER RELAY 2
GAS VALVE
SENSOR
OUTLET
SENSOR
SENSOR
BLOWER
SPARK
ROD
INLET
FLUE
FLAP
VALVE
AIR PRESSURE
HI-LIMIT
AUTO RESET
HIGH LIMIT
FLAME ROD
SWITCH
X2-2
X2-1
1
2
4
5
TR1
X1-7
X6-8
X5-7
X5-7
X5-4
X5-14
X5-8
X5-1
X5-9
X5-2
X5-3
X5-10
X5-5
X5-13
X5-6
X5-12
MODULE 2 CONTROL
X8
X5-7
24V
X5-4
X5-14
X6-8
X5-8
X5-1
X5-9
X5-2
X5-3
X5-10
GAS VALVE
RELAY
CAUTION HIGH VOLTAGE SPARK LEAD
CONNECTION BOARD
CN3
SHIELD
CASCADE
RS485
SHIELD
TANK
SENSOR
OUTDOOR
SENSOR
SYSTEM SENSOR
EXTERNAL
10VDC
CONTROL
SHIELD
MOD BUS
RS485
SHIELD
NOTES:
1. Where possible, switches are shown with out utilities (gas, water or electricity) conn ected to the unit. As such, actual switch states may vary from those shown on diagrams depending upon whether utilities are connected or a fault condition is present.
2. See wiring diagram for addit ional notes.
CN3-16
CN3-15
CN3-14
CN3-13
CN3-12
CN3-11
CN3-10
CN3-9
CN3-8
CN3-7
CN3-6
-
CN3-5
+
CN3-4
CN3-3
CN3-2
CN3-1
CN4-3
CN4-1
CN4-2
CN4-4
CN4-6
CN4-5
CN4-8
CN4-7
CN4-9
CN4-10
MOD BUS
KIT
X4-2
X4-4
X4-6
X4-5
X4-8
X4-7
X4-9
X4-10
4
X4-3
X4-1
CAUTION HIGH VOLTAGE SPARK LEAD
MODULE 1MODULE 1
X4
X4-3
X4-1
X4-2
X4-4
MODULE 2
X4
LADDER DIAGRAM LBL20058 REV C
61
Installation & Operation Manual
12 Diagrams (continued)
Figure 12-2 Ladder Diagram_Part 2
BOX DEPICTS
OPTIONAL ITEMS
120 VAC
24 VAC
120VAC
TERMINAL STRIP 120V SUPPLY "L"
ON / OFF SWITCH
X1-6
BOILER PUMP
RELAY
DHW PUMP
RELAY
SYSTEM PUMP
RELAY
BLOWER
RELAY
X1-4
X1-2
X1-1
12
3
BLOWER
X1-5
X6-8
X6-3
F5
X5-7
X6-7
NEUTRAL
TERMINAL STRIP 120V SUPPLY "N"
JUNCTION
BOX
X1-8
CONNECTION
BOARD
5A
F4
3.5A
F2
3.5A
F3
1.25A
MODULE 1 CONTROL
GROUND
JUNCTION BOX
120 VAC
LOW VOLTAGE
HIGH VOLTAGE
5
9
X6-2
NOTES:
1. Where possible, switches are shown without utilities (gas, water or electricity) connected to t he unit. As such, actual switch states may vary from those shown on diagrams depending upon whether utilities are connected or a fault condition i s present.
2. See wiring diagram for additional notes.
BOILER
PUMP
BOILER
PUMP
SYSTEM
PUMP
MODULE 1
BOILER PUMP
RELAY
SYSTEM PUMP
RELAY
MODULE 1
BOILER
PUMP
CONTACTS
MODULE 2
BOILER
PUMP
CONTACTS
SYSTEM
PUMP
CONTACTS
L1
N / L2
120 VAC
24 VAC
ON / OFF SWITCH
X1-6
BOILER PUMP
RELAY
DHW PUMP
RELAY
SYSTEM PUMP
RELAY
BLOWER
RELAY
X1-4
X1-2
X1-1
12
3
BLOWER
X6-8
F5
X5-7
X6-7
JUNCTION
BOX
X1-8
5A
F4
3.5A
F2
3.5A
F3
1.25A
MODULE 2 CONTROL
X6-2
MODULE 2
BOILER PUMP
RELAY
JUNCTION BOX
LWCO
J3-2
7
11
13
LWCO
J3-4
LOUVER
PROVING
MODULE 1
FLOW
SWITCH
MODULE 2
FLOW SWITCH
HW
THERMOSTAT
ENABLE
CONNECTION
BOARD
MODULE 1 CONTROL
X6-10
MODULE 2 CONTROL
X6-9
X6-1
X6-6
X6-10
X6-9
LADDER DIAGRAM LBL20046 REV C
LOW GAS
PRESSURE
SWITCH
MODULE 2 CONTROL
X6-5
MODULE 1
CONTROL
X6-5
MODULE 1 HIGH GAS
PRESSURE
SWITCH
DHW PUMP
RELAY
(FIELD SUPPLIED)
DHW
PUMP
DHW
PUMP
DHW
PUMP
CONTACTS
(FIELD SUPPLIED)
X1-3
X1-3
J3-5
J3-6
RUN TIME
CONTACTS
RUN TIME
CONTACTS
ALARM
CONTACTS
X3-2
X3-4
X3-1
X3-3
X3-2 X3-4
X3-1
X3-3
3
JUNCTION BOX
MODULE 1 HIGH GAS
PRESSURE
SWITCH
MODULE 2
HIGH GAS
PRESSURE
SWITCH
CN1-4
CN1-12
CN1-13
6
10
8
12
14
4
3
1
2
CN1-7
CN1-8
CN1-10
CN1-15
CN1-11
CN1-3
CN1-6
CN1-5
CN1-6
TEST SWITCH
PROBE
J3-3
LOUVER
CONTACTS
62
Installation & Operation Manual
12 Diagrams
Figure 12-3 Wiring Diagram
SHIELD
CASCADE
RS485
SHIELD
TANK
SENSOR
OUTDOOR
SENSOR
SYSTEM
SENSOR
EXTERNAL CONTROL
SHIELD
MOD BUS
RS485
SHIELD
ENABLE
THERMOSTAT
THERMOSTAT
MODULE 2
FLOW
SWITCH
MODULE 1
FLOW
SWITCH
LOUVER
PROVING
RUNTIME
CONTACTS
ALARM
ALARM
CONTACTS
CONTACTS
CAUTION HIGH VOLTAGE SPARK LEAD
-
10VDC
+
TANK
TANK
PC INTERFACE
CONNECTION BOARD
CN3
CN3-16
CN4
CN3-15
CN3-14
CN3-13
CN3-12
CN3-11
CN3-10
CN3-9
CN3-8
CN3-7
CN3-6
CN3-5
CN1
CN3-4
CN3-3
CN1-10
CN3-2
CN1-2
CN3-1
CN1-9
CN1-11
CN2-14
CN2-13
CN1-3
CN2-12
CN1-4
CN2-11
CN1-5
CN2-10
CN1-6
CN2-9
CN1-13
CN2-8
CN1-14
CN2-7
CN1-12
CN2-6
CN1-15
CN2-5
CN1-16
CN2-4
CN1-8
CN2-3
CN1-7
CN2-2
CN2-1
CN1-1
CN2
LOW VOLTAGE 120 VAC
X1-4
X1-2
X1-3
X1-6
X1-5
X1-8
X1-1
X5-5 X5-13
X5-6 X5-12
X5-4 X5-10
X5-7
X5-14
X5-3 X5-8
X5-1
X5-2
X5-9
X6-8
X2-2
X2-1
X1-7
HIGH VOLTAGE
BOARD
BR
PR
Y
BK
W
GR
R
W
132
BLOWER
1245
3
R
T
W
BK OR
GY
PR
PR
BK
RD
W
Y
BK
Y
W/RD
BLOCKED
DRAIN
CONTACTS
RELAY
K1
K2
K3
ON/OFF SWITCH
G
LOUVER
R1
OPTIONAL ITEMS
R2
PR
PR
BR
BR
OR
OR
AUTO RESET LIMIT
HI-LIMIT
BOX DEPICTS
JUNCTION
BOX
GND
APS
SPARK
ROD
GND
GND
LOUVER
LOUVER RELAY 1
RELAY 1
FLAP VALVE
INLET SENSOR
OUTLET SENSOR
FLUE SENSOR
FLAME ROD
LOUVER
MODULE 1 BOILER PUMP
SYSTEM PUMP
MODULE 2 SYSTEM PUMP
HW PUMP RELAY
L
120V SUPPLY
GND
N
GAS VALVE
G
X3
X5
MOD2 PC
INTERFACE
MOD BUS
KIT
GY
W
PK
T
BR
OR
PK
RD
RD
PR
PR
4 CONDUCTORS
MOD1 PC INTERFACE
MODULE 1
CONTROL
X8
X4
PK
X6-2
BL
X6-7
GY
X6-6
W
X6-1
T
X6-9
X6-5
OR/BK
X6-10
PR
X3-2
RD
X3-4
PR
X3-1
RD
X3-3
WIRING DIAGRAM LBL20045 REV D
LOW WATER CUTOFF
BOARD
MODULE 2 CONTROL
X8
X4
LOW GAS
PRESSURE SWITCH
HIGH GAS
PRESSURE 1
HIGH GAS
PRESSURE 2
X6-5
T
TEST
SWITCH
J3-1
J3-1 J3-2 J3-3 J3-4 J3-5 J3-6
J2-1 J2-2 J2-3
Notes:
1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a minimum of 105°C. Exceptions: Replacement high voltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components.
3. Actual connector block loc ations may vary from tho se shown on diagrams. Refe r to actual components fo r proper connector block locations when using diagrams to troubleshoot unit.
PROBE
OR/BK
BK
BL
RESET
OR
CAUTION HIGH VOLTAGE SPARK LEAD
OR/BK
X6-9
X6-10
PR
X3-2
RD
X3-4
PR
X3-1
RD
X3-3
PR
X1-2
X1-2
BR
X1-4
GY
X1-3
W
X1-5
BK
X1-6
GR
X1-8
RD
X1-1
X5-5 X5-13
X5-6 X5-12
X5-4
X5-10
X5-7
X5-14
X5-3
X5-8
X5-1
X5-2
X5-9
X6-8
X2-2
X2-1
X1-7
T/BK
OR/BK
GR/BK
BL/BK
PR/BK
BK/RD
RD/BK
W/BK
BK
R
W
G
132
BLOWER
3
12 45
RD
W
BK
AUTO RESET LIMIT
PK
Y/BK
Y
SPARK
ROD
RD/W
HI-LIMIT
GAS VALVE
G
FLAME ROD
APS
LOUVER RELAY 2
FLAP VALVE
INLET SENSOR
OUTLET SENSOR
FLUE SENSOR
Notes
63
Revision Notes: Revision A (ECO #C02428) initial release.
Revision B (ECO #C03046) reflects the addition of FIG. 5-3 on page 27, the addition of a pressure gauge to FIG. 5-6 on page 30, edits made to FIG. 7-1 on page 35, edits made to the Low Water Cutoff Protection section on page 48 along with the addition of the Flow Sensing Device section.
Revision C (ECO #C03223) reflects edits made to the high altitude section on page 6.
SYNC-I-O Rev C
3/09
Loading...