Lochinvar STU150 Installation Manual

Page 1
STU-I-O Rev A
Installation & Operation
Manual
Models: STU150 - 940
WARNING
Save this manual for future reference.
IMG00044
This manual must only be used by a qualified heating installer / service technician. Read all instructions before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Page 2
Contents
HAZARD DEFINITIONS .................................................... 2
PLEASE READ BEFORE PROCEEDING ........................ 3
1. GENERAL INFORMATION
Operating Restrictions ........................................................ 4
Tank Shipment................................................................... 4
Components .................................................................... 4-6
Spherical Heat Exchanger................................................. 7
2. PRE-INSTALLATION
Locating the Tank ............................................................... 8
Recommended Clearances ................................................ 8
3. SOLAR CONNECTIONS
Spherical Pressure Drop Calculations............................... 9
Piping Diagrams ............................................................... 10
4. DOMESTIC SIDE PIPING
Basic Domestic Piping ..................................................... 11
Domestic Water Piping for Distant Fixtures ..................... 11
Recirculation Lance .......................................................... 12
Recirculation Lance Pressure Drop Chart ....................... 12
Direct Piping to Cold Water Inlet ...................................... 13
Multiple Tank Domestic Water Piping .............................. 13
Anti-Scald Mixing Valves ...................................................13
Domestic Coil Pressure Drop Chart................................ 14
Temperature and Pressure (T&P) Relief Valve .......... 15-16
Table 4E - Minimum Relief Valve (ASME Rating) 15
Piping Diagrams........................................................... 17-19
5. BOILER SIDE PIPING
Multiple Tank Connections ............................................... 20
Piping Diagrams ........................................................ 20 - 21
6. STARTUP AND MAINTENANCE
System Startup ................................................................. 22
Maintenance Schedule ................................................ 22-23
Winterizing the System ............................................... 23
To Drain/Flush the System ......................................... 23
7. PERFORMANCE DATA
Performance Data Charts ........................................... 24-27
REVISION NOTES ............................................ Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
2
Page 3
Please read before proceeding
Installation & Operation Manual
WARNING
NOTICE
WARNING
Installer – Read all instructions before installing. Perform steps in the order given.
Have this storage tank serviced/inspected by a qualified service technician, at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
When calling or writing about the appliance – Please have the model and serial number from the tank rating plate.
Consider piping and installation when determining appliance location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Factory warranty (shipped with appliance) does not apply to appliances improperly installed or improperly operated.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING
Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage.
When servicing the Strato-Therm+ –
• To avoid severe burns, allow the appliance to cool before performing maintenance.
Appliance operation –
• Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
APPROXIMATE TIME / TEMPERATURE
RELATIONSHIPS IN SCALDS
120°F More than 5 minutes 125°F 1 1/2 to 2 minutes 130°F About 30 seconds 135°F About 10 seconds 140°F Less than 5 seconds 145°F Less than 3 seconds 150°F About 1 1/2 seconds 155°F About 1 second
Hot Water Can Scald!
Water heated to temperatures for clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury.
• Children, elderly, and infirm or physically handicapped persons are more likely to be permanently injured by hot water. Never leave them unattended in a bathtub or shower. Never allow small children to use a hot water tap or draw their own bath.
If anyone using hot water in the building fits the above description, or if state laws or local codes require certain water temperatures at hot water taps, you must take special precautions:
Use lowest possible temperature setting.
• Install some type of tempering device, such as an automatic mixing valve, at hot water tap or water heater. Automatic mixing valve must be selected and installed according to valve manufacturer’s recommendations and instructions.
Water passing out of drain valves may be extremely hot. To avoid injury:
Make sure all connections are tight.
Direct water flow away from any person. Protection Must Be Taken Against Excessive Temperature and Pressure!
--Installation of a Temperature & Pressure (T&P) relief valve is required.
3
Page 4
Installation & Operation Manual
1 General information
The Lochinvar Strato-Therm+ solar stratified tank (FIG. 1-1, page 5) is designed to use a solar collector system, in conjunction with a back-up heat source, to generate domestic hot water. This solar tank consists of a spherical heat exchanger attached to an unlined tank containing a corrugated 316L stainless steel coil. Tank components and specifications are detailed in FIG.’s 1-1 and 1-2 (pages 5 and 6), as well as Tables 1A - 1D.
Solar heated water is pumped through the spherical heat exchanger to heat the water in the tank. A backup heat source is used to maintain desired tank temperature in the event that solar heated water is not available. The tank may be used to heat domestic potable water which runs through the stainless steel coil. In addition to generating domestic hot water, this tank can have many other applications including indirect pool heating and space heating. Consult the factory if your specific application is not covered in this manual. The tank is not intended for use in gravity water heating applications.
Operating Restrictions:
Maximum domestic hot water temperature is 194°F.
Maximum boiler water temperature is 210°F.
Maximum working pressure for the vessel is 125 psig.
Tank shipment
Tanks taller than 7.5 feet will be shipped horizontally. Four shipping legs are used to secure the tank to a pallet, and holes are provided in the top cover for access to lifting lugs. The shipping legs should be removed when the tank is removed from the shipping crate.
Use field-supplied insulation to pack the shipping and lug compartments, then use the factory provided covers to conceal compartments upon final installation.
Table 1A
Strato-Therm+
Tank Component Materials
Component Material
Tank Steel SA414-G
Coil 316L Stainless Steel
Insulation Polyurethane Foam
Jacket Pre-paint Sheet Metal
Table 1B
Spherical Heat Exchanger
Component Materials
Component Material
Housing Steel S 235 JR
Heat Exchanger Coil Copper
Insulation Polyurethane Foam
Jacket Polypropylene
4
Page 5
1 General information (continued)
Figure 1-1 Strato-Therm+ solar stratified tank components
HEAT SOURCE
THERMOMETER
BACKUP HEAT
SOURCE SENSOR
SPHERICAL
HEAT EXCHANGER
Installation & Operation Manual
DOMESTIC WATER OUTLET
DOMESTIC WATER
STAINLESS STEEL COIL
BACKUP
HEAT SOURCE
SUPPLY
BACKUP
HEAT SOURCE
SOLAR
SENSOR
IMG00078
RETURN
DOMESTIC
WATER
INLET
Table 1C
Strato-Therm+ Tank and Coil Specifications
Stainless
Steel
Coil
Surface
Area (ft2)
Tank
Water
Volume
(gal.)
Domestic
Water
Volume
(gal.)
Full
Weight
(lbs)
Model
Tank
Diameter
(in.)
Jacket
Diameter
(in.)
Domestic
Water
Inlet/ Outlet (NPT)
Boiler
Supply/
Return
(NPT)
Stainless
Steel
Coil
Length
(ft.)
STU150 24 28 1" 2" 82 69 125 12.0 1715
STU200 28 32 1" 2" 98 83 175 14.5 2300
STU257 30 34 1" 2" 98 83 225 14.5 2875
STU350 36 40 1" 2" 98 83 325 14.5 3775
STU423 36 40 1" 2" 115 97 400 16.0 4650
STU504 42 46 1" 2" 121 103 475 17.0 5475
STU650 48 52 1" 2" 131 111 625 20.0 7050
STU752 48 52 1" 2" 131 111 725 20.0 8100
STU940 48 52 1" 2" 131 111 900 20.0 10000
5
Page 6
1 General information
Figure 1-2 Strato-Therm+ tappings
Installation & Operation Manual
I
H
J
K
L
M
N
P
O
IMG00088
G
F
E
D
C
B
A
Strato-Therm+ Elements
A
Drain Valve
B
Domest Water Inlet
C
Low Temp Water Return
D
High Temp Water Return
E
Backup Heat Source Return
F
Space Heat Supply
G
Backup Heat Source Supply
H
Relief Valve / Air Vent
I
Domestic Hot Water Outlet
J
Heat Source Thermometer
K
Backup Heat Source Sensor
L
Sensor (Optional)
M
Sensor (Optional)
N
Solar Sensor
O
Spherical Exchanger, Inlet (Red Label)
P
Spherical Exchanger, Outlet (Blue Label)
Model
STU150
STU200
STU257
STU350
STU423
STU504
STU650
STU752
STU940
6
Table 1D
Tapping Measurements
A
(in.)
2 1/4 12 1/4 21 1/4 28 3/4 33 50 3/4 55 1/4 71 76 3/4 3 1/2 3 1/2
3 1/2 12 3/4 22 3/4 33 38 1/2 55 1/4 59 1/2 76 80 1/4 4 1/4 4 1/4
2 1/4 17 34 1/2 42 1/2 49 63 1/2 67 3/4 87 92 3/4 8 1/2 8 1/2
3 1/4 18 3/4 37 46 1/2 53 62 66 1/4 87 1/4 92 1/4 10 10
3 1/4 18 1/2 40 1/4 52 58 1/4 76 1/2 80 3/4 100 105 1/4 10 10
2 1/2 19 1/2 33 1/2 42 1/4 49 60 1/4 64 3/4 87 92 1/2 11 1/2 11 1/2
2 21 1/2 36 3/4 44 1/2 51 61 1/4 65 3/4 88 94 13 1/2 13 1/2
2 22 38 1/4 50 57 1/2 70 3/4 75 100 105 3/4 10 1/2 10 1/2
2 22 49 63 70 1/2 89 93 1/2 124 130 13 1/2 13 1/2
B
(in.)
C
(in.)
D
(in.)
E
(in.)
F
(in.)
G
(in.)
H
(in.)
I
(in.)
O
(in.)
P
(in.)
Page 7
1 General information (continued)
Installation & Operation Manual
Spherical heat exchanger
The Strato-Therm+ uses a copper finned tube spherical heat exchanger to provide optimum solar stratified charging. The spherical exchanger helps maintain optimal use of solar energy for hot water and space heating. The multi-functional design improves efficiency in every system. Insulated with polyurethane foam, the spherical heat exchanger and tank maintain a space-saving design with minimal heat loss. Refer to FIG. 1-3 and Tables 1E and 1F for additional spherical heat exchanger information and measurements.
Figure 1-3 Spherical heat exchanger w/ tank
B
Table 1E
Tank with Spherical Measurements
Model
STU150 SHX40000 44 1/2 28
STU200 SHX40000 48 1/4 32
STU257 SHX40001 50 1/4 34
STU350 SHX40001 56 1/4 40
STU423 SHX40002 56 1/4 40
STU504 SHX40002 62 1/4 46
STU650 SHX40003 71 1/4 52
STU752 SHX40003 71 1/4 52
STU940 SHX40004 71 1/4 52
Spherical
Model
A
(in.)
(in.)
B
A
IMG00054
Table 1F
Spherical Heat Exchanger Specifications
Tank
Model
SHX40000 8 1/2 14 61 0.75" 28 0.55 7.9 8.45
SHX40001 8 1/2 14 61 0.75" 42 0.65 7.8 8.45
SHX40002 8 1/2 14 61 1" 59 1.1 7.35 8.45
SHX40003 11 3/4 17 61 1.25" 102 2.0 15.8 17.8
SHX40004 11 3/4 17 80 1.25" 102 2.0 15.8 17.8
Diameter
(in)
Jacket
Diameter
(in)
Jacket
Height
(in)
Solar
Inlet
Return
(NPT)
HEX
Surface
Area
(ft2)
HEX
Water
Volume
(gal)
Tank
Water
Volume
(gal)
Total
Water
Volume
(gal)
7
Page 8
2 Pre-installation
Installation & Operation Manual
1. The installation must conform to the instructions in this manual and all applicable local, state, provincial, and national codes, laws, regulations, and ordinances. Installations in Canada must conform to B149.2 Installation Code.
2. Ensure that the domestic water supply to the stainless steel coil has physical and chemical characteristics that fall within the limits shown in Table 2A. Where questions exist as to the composition of the water on the job site, a qualified water treatment expert should be consulted.
CAUTION
3. Read and understand all installation requirements in this manual.
Water with characteristics outside the limits shown in Table 2A may severely shorten the life of the domestic water coil due to corrosion. Damage in such cases is not covered under warranty.
Table 2A
Water Chemistry Requirements
Domestic potable water must have characteristics falling within the following limits:
Characteristic Min. Max.
pH 6.5 9.5
Chloride (PPM) -- 200
Locating the Tank
1. Choose a location for the Strato-Therm+ centralized to the piping system. You must also locate the Strato-Therm+ where it will not be exposed to freezing temperatures. Additionally, you will need to place the appliance so that the controls, drain, and inlet/outlets are easily accessible. This appliance must not be installed outdoors, as it is certified as an indoor appliance, and must also be kept vertical on a level surface.
2. Table 1C on page 5 shows the weight of all the tanks filled with water. Ensure that the location chosen for the tank is capable of supporting the weight.
CAUTION
3. The tank may be located some distance from the heat source provided that the pump is designed to to provide enough flow for both units to perform properly. The further the distance from the tank to the heat source, the longer the response time will be to provide sufficient heat to the tank. Insulate piping between the heat source and the tank.
This appliance must be placed where leakage from the relief valve, leakage from the related piping, or leakage from the tank or connections, will not result in damage to the surrounding areas, or to the lower floors of the building. A water heater should always be located in an area with a floor drain or installed in a drain pan suitable for water heaters. Lochinvar shall not be held liable for any such water damage.
WARNING
Failure to properly support the tank could result in property damage or personal injury.
Recommended Clearances
The installation location must provide adequate clearances for servicing and proper operation of the appliance. A 12-inch vertical clearance is recommended from the top of the appliance. A zero clearance is allowed for the sides of the appliance. However, boiler and servicing clearances must be figured when locating the appliance.
8
Page 9
0
5
10
15
20
25
30
02468101214
Pressure Drop, psi
Flow Rate, gpm
STU150
STU200 / SHX40000
STU257
STU350 / SHX40001
STU423
STU504 / SHX40002
STU650
STU752 / SHX40003
STU940 /
SHX40004
Installation & Operation Manual
3 Solar connections
A solar thermal system consists of several components selected to work together to convert solar energy into hot water for various applications. A controller is used to turn on a pump when the fluid in the solar collectors is warmer than the water in the Strato­Therm+ tank. The pump will transport hot fluid from the collector to the heat exchanger and replace it with cooler fluid returning. The collectors, pump station and heat exchanger are connected with supply and return piping that is insulated to minimize heat losses (FIG. 3-1, page 10). The system is equipped with over-temperature and over-pressure devices that prevent unsafe operating conditions. When multiple heat exchangers are used, they should connected in reverse-return arrangement (FIG. 3-2, page 10). This will help ensure that solar heated water is distributed evenly between the heat exchangers. Pressure drop and maximum operating values for the Strato-Therm+ spherical heat exchanger are listed in Tables 3A - 3C.
Installation and commissioning must be carried out by a licensed contractor. Take appropriate safety measures when carrying out any installation work on the roof and observe all relevant accident prevention regulations. It is the installer’s responsibility to comply with the building and installation codes in effect and all regulations that apply to the operation of a solar hot water system.
MODEL
STU150
STU200
STU257
STU350
STU423
STU504
STU650
STU752
STU940
Table 3A
Spherical Heat Exchanger
Pressure Drop Values
PRESSURE DROP PSI)
SPHERICAL
MODEL
SHX40000 0.20 0.68 2.29 4.66 7.71 11.39 15.67 20.52
SHX40001 0.24 0.81 2.71 5.52 9.13 13.49 18.56 24.31
SHX40002 0.07 0.23 0.78 1.59 2.64 3.90 5.36 7.02
SHX40003 0.03 0.09 0.30 0.61 1.01 1.50 2.06 2.70
SHX40004 0.03 0.09 0.30 0.61 1.01 1.50 2.06 2.70
1
GPM2 GPM4GPM6GPM8GPM10GPM12GPM14GPM
Table 3C
Spherical Heat Exchanger Pressure Drop Chart
Table 3B
Spherical Maximum Operating
Conditions
Copper Heat
Exchanger
Temperature 230°F 230°F
Pressure 145 psi 125 psi
Tank
9
Page 10
3 Solar connections
Installation & Operation Manual
Figure 3-1 Solar System Piping
TEMPERATURE GAUGE
SOLAR PUMP
STATION / CONTROLLER
COLLECTOR
(TYPICAL)
SOLAR

PRESSURE
RELIEF VALVE
FILL AND
FLUSH VALVE
EXPANSION
TAN K
SOLAR AIR RELEASE VENT (OPTIONAL)
TEMPERATURE
GAUGE
SPHERICAL
HEAT EXCHANGER
SOLAR
SENSOR
IMG00040
Figure 3-2 Solar System Piping with Multiple Heat Exchangers
SOLAR AIR
RELEASE VENT
EXPANSION
TAN K
(OPTIONAL)
TEMPERATURE
GAUGE
SOLAR
COLLECTOR
TEMPERATURE
GAUGE
(TYPICAL)
SOLAR PUMP
STATION /
CONTROLLER

PRESSURE
RELIEF VALVE
T&P
RELIEF
VALV E
SPHERICAL
HEAT EXCHANGER
SOLAR
SENSOR
IMG00094
10
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Page 11
4 Domestic side piping
Installation & Operation Manual
Basic domestic piping
Figure 4-4 on page 17 shows typical domestic water and space heating piping for a Strato-Therm+ tank. The stainless steel coil requires properly sized piping and a properly sized pump to maintain adequate domestic hot water delivery. Refer to Tables 4D and 4E on page 14 and 15 for domestic coil pressure drop. The functions of the components shown are as follows:
a. Shut-off valves (recommended) - Used to isolate the appliance for servicing.
b. Backflow Preventer (required by some codes) - Used to prevent water from backing out of the indirect coil and into the main potable water supply in the event that inlet water pressure drops.
c. Expansion Tank (required for thermal expansion) - Tank absorbs the increased volume caused by heating water.
Use an expansion tank designed for use on domestic water systems. Refer to the expansion tank manufacturer’s instructions for proper sizing and use.
NOTICE
d. Shock Arrestor (required by some codes) - Used to allow water to accelerate or decelerate without a sudden change in pressure.
If an expansion tank is used, do not put any valves between the expansion tank and tank inlet.
Domestic water piping for distant fixtures
In some cases the furthest fixture may be located far from the tank. This may result in an unacceptable delay before hot water reaches these distant fixtures. Even if all the fixtures are located relatively close to the tank, it may be desired that hot water be instantly available to all fixtures.
To prevent delays, return circulation piping with a check valve that allows flow to the domestic hot water outlet. This should be installed on each branch circuit at the farthest fixture or device, so that hot water is supplied upon demand. Traditional recirculation piping is illustrated in FIG. 4-1, page 12.
Because hot water is always circulating in the hot water branch, the entire branch should be insulated to prevent excessive heat loss.
When a hot water recirculation system is used there are two piping arrangements that can be applied to the Strato-Therm+. The first arrangement is for use in systems with up to 2 gal/ min circulation and requires the purchase of a recirculation lance assembly (FIG. 4-5, page 18). The second arrangement is for use in systems with greater than 2 gal/min circulation that require higher performance and temperature (FIG. 4-6, page 18).
e. Circulation Pump (recommended) - Used to circulate and maintain hot water within the piping system.
f. Check Valve (required by some codes) - Used to allow water to flow in only one direction, preventing back-flow.
g. Drain (required) - Used to drain the tank for inspection or servicing.
h. Mixing valve (required) - Used to mix hot water with cold water to ensure constant, safe outlet temperatures.
i. Unions (optional) - Used to disconnect the tank in the unlikely event that this is necessary for service.
NOTICE
Be sure to field-install plugs or caps on any tank tappings that are not in use.
11
Page 12
4 Domestic side piping
0
1
2
3
4
5
6
0.0 0.5 1.0 1.5 2.0 2.5
Installation & Operation Manual
Recirculation lance
Recirculation systems with up to 2 gal/min circulation require the use of a recirculation lance assembly (TUB30000) (FIG. 4-1). The lance is a stainless steel tube that is inserted directly into the hot water connection of the tank and into the stainless steel coil. As part of a continuous, slow-moving loop, warm water is circulated directly back into the coil, via the lance, maintaining tank stratification. Reference FIG. 4-5 on page 18 for typical recirculation lance piping.
Table 4A
Recirculation Lance Pressure Drop Values
Flow Rate (gpm) Pressure Drop (psi)
0.2 0.07
0.4 0.25
0.6 0.5
0.8 0.83 1 1.22
1.2 1.68
1.32 1.98
1.4 2.2
1.6 2.78
1.8 3.41 2 4.11
2.2 4.85
Figure 4-1 Recirculation lance assembly
RECIRCULATION
WATER LINE
1/2" NPT
REDUCER
BUSHING
RECIRCULATION
LANCE
HOT WATER
1 1/2" NPT
1 1/2" NPT
DOMESTIC
1" NPT
1 1/2" NPT
NIPPLE
1 1/2" NPT
STAINLESS STEEL
REDUCER BUSHING
STAINLESS STEEL
1" NPT NIPPLE
1" NPT DOMESTIC HOT WATER TUBE
1" NPT
1 1/2" NPT
T&P
RELIEF
VALVE
BRASS NIPPLE
1" NPT
1 1/2" NPT
DOMESTIC
HOT WATER
IMG00013
Table 4B
Recirculation Lance Pressure Drop Chart
PRESSURE, PSI
12
FLOW RATE, GPM
Page 13
4 Domestic side piping (continued)
Installation & Operation Manual
Direct piping to cold water inlet
When a re-circulation lance is not used, it is acceptable to connect a building recirculation loop directly to the cold water inlet of the Strato-Therm+ when flows are greater than 2 gal/ min returning to the tank. This method of building recirulation will use the entire indirect coil to heat the recirulation loop. See Figure 4-6 on page 18 for typical piping arrangement.
Multiple tank domestic water piping
Multiple tank installations must be done in the reverse-return arrangement. This helps maintain the same flow and pressure drop through the coil of each tank. Because the pressure drop through tank coils varies from size to size, it is recommended not to mix tanks with different coil sizes within the same zone. Multiple tank domestic piping is illustrated in FIG. 4-7 on page 19.
When high volume supply of hot water at a constant outlet temperature is required, the Strato-Therm+ can be paired with a large capacity storage tank (FIG. 4-8, page 19). In this configuration the Strato-Therm+ will be able to meet high demands with its instantaneous delivery rate. An Aquastat control is used to control the water temperature between the two tanks with a circulation pump. If a building recirculation system is installed, the return water is brought back to the storage tank so as not to disturb the stratification of the Strato-Therm+.
Anti-scald mixing valves
Anti-scald valves used with water heaters are also called tempering valves or mixing valves. An anti-scald valve mixes cold water with the outgoing hot water to assure that hot water reaching a building fixture is at the correct temperature.
NOTICE
The temperature of water going to the fixtures may be more carefully controlled through the use of a thermostatic mixing valve. This device blends a controlled amount of cold water with the hot water leaving the tank so that water at a more constant temperature exits the mixing valve. Anti-scald mixing valve piping is illustrated in FIG.’s 4-4 thru 4-8, pages 17 - 19. Always consult the mixing valve manufacturer’s instructions and guidelines for correct piping and usage.
WARNING
WARNING
ASSE1017 and ASSE1070 certified mixing valves are required.
Hot water can scald! To avoid scalding potential, mixing valves must be selected and installed according to valve manufacturer’s instructions and recommendations. Mixing valves should be installed by a licensed contractor.
An anti-scald mixing valve does not eliminate the risk of scalding.
* Feel water before bathing or showering.
* If anti-scald or anti-chill protection is required, use devices specifically designed for such service. Install these devices in accordance with their manufacturer’s instructions.
13
Page 14
4 Domestic side piping
0
5
10
15
20
0 5 10 15 20 25 30 35
Pressure, psi
Flow Rate, gpm
STU150
STU200
STU257 STU350
STU423
STU504
STU650
STU752 STU940
Domestic Coil Pressure Drop Values
MODEL
STU150 0.1 0.6 1.6 2.8 4.4 6.2 8.3 10.7 13.3 14.7
STU200 STU257 STU350
STU423 0.1 0.8 2.0 3.6 5.6 7.9 10.6 13.6 16.9 18.7
STU504 0.1 0.8 2.1 3.7 5.8 8.2 11.0 14.2 17.7 19.5
STU650 STU752 STU940
2
GPM
6
GPM
10
GPM
0.1 0.7 1.8 3.2 5.0 7.1 9.5 12.2 15.1 16.7
0.1 0.9 2.2 4.0 6.2 8.8 11.7 15.1 18.7 20.7
Table 4C
PRESSURE DROP
14
GPM
GPM22GPM26GPM30GPM34GPM36GPM
18
(PSI)
Installation & Operation Manual
Table 4D
Domestic Coil Pressure Drop Chart
14
Page 15
4 Domestic side piping (continued)
Installation & Operation Manual
Temperature & Pressure (T&P) Relief Valve
WARNING
The T&P relief valve is installed in the vertical position and mounted in the outlet of the indirect coil as shown in FIG. 4-2. Do not place a valve between the relief valve and the coil. To prevent water damage, the discharge from the relief valve shall be piped to a suitable floor drain for proper drainage when relief occurs. Do not install reducing couplings or other restrictions in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once per year.
For protection against excessive temperatures and pressure, install temperature and pressure protective equipment required by local codes. A T&P relief valve must be certified by a nationally recognized testing laboratory that maintains periodic inspection of listed equipment or materials. The equipment and materials must meet the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, as well as the standard CAN1-4.4, Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum Relief Valves. The combination T&P relief valve shall be marked with a maximum set pressure, not to exceed the maximum working pressure of the water heater. It shall also have an hourly rated discharge capacity not less than shown in Table 4E.
Figure 4-2 Relief valve
PRESSURE
RELIEF VALVE
(FIELD SUPPLIED)
NOTICE
Verify that the combination temperature and pressure relief valve complies with local codes. If the combination T&P relief valve does not comply with local codes, replace it with one that does. Follow the installation instructions in this section.
Do not place a valve between the combination T&P relief valve and the tank.
Minimum Domestic Coil Relief Valve
Model
Table 4E
ASME
Btu/hr
Pressure
psi
T&P RELIEF
VALV E
(PROVIDED)
Lochinvar
Part No.
IMG00105
Pressure Only (POV) Relief Valve
A connection is provided for a pressure relief valve on the top of the tank. The tank containing the hydronic water shall have a pressure only relief valve in addition to the T&P relief valve installed in the stainless steel coil. The POV should be sized in accordance with the maximum working pressure of the tank and the BTU output of the backup heat source. It is recommended to have a relief valve sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV “Heating Boilers”. ASME states in Section VIII, Division 1, paragraph UG-125 (a) “All pressure vessels within the scope of this division, irrespective of size or pressure, shall be provided with pressure relief devices in accordance with the requirements of UG-125 through UG-137.”
STU150 - STU940 2,610,000 125 RLV20015
15
Page 16
4 Domestic side piping
Installation & Operation Manual
Standard Installation
Connect a factory-supplied straight tee, reducing bushing and close nipple to the coil opening provided. Install the T&P relief valve vertically (FIG. 4-3). Install a field-supplied POV into the nipple provided.
T&P Relief Valve and POV Discharge Piping
Relief valve discharge piping MUST be:
- made of material serviceable for a temperature of 250°F or greater
- directed so that hot water flows away from all persons
- directed to a suitable place for disposal
- installed so as to allow complete draining of the T&P relief valve and discharge line
- terminated within 6" of the floor
Relief valve discharge piping MUST NOT be:
- excessively long. Using more than two (2) elbows or 15 feet of piping can reduce discharge capacity
- directly connected to a drain (Refer to local codes)
- subject to freezing
WARNING
Do not install any valve between the relief valve and its connection or on the relief valve discharge piping. Improper placement and piping of relief valve can cause severe personal injury, death or substantial property damage.
Figure 4-3 Relief valve Assembly
T&P RELIEF
VALV E
1” NPT
CLOSE NIPPLE
1 - 1/2” NPT
STRAIGHT TEE
1 - 1/2” X 1” NPT
REDUCER BUSHING
HOT WATER
OUTLET
1” NPT
STAINLESS STEEL
CLOSE NIPPLE
IMG00012
CAUTION
WARNING
The T&P relief valve or POV is not intended for constant duty, such as relief of pressure due to repeated normal system expansion. Correct this condition by installing a properly sized expansion tank in a domestic water system. Refer to the expansion tank manufacturer’s installation instructions for proper sizing.
Failure to install and maintain a new, listed and properly sized relief valve will relieve the manufacturer from any claim which might result from excessive temperature and pressure.
16
Page 17
4 Domestic side piping (continued)
Figure 4-4 Domestic Piping with Hydronic Heating
Installation & Operation Manual
BACKFLOW
PREVENTER
BALL VALVE
(TYPICAL)
PRESSURE REDUCING
AIR
SEPARATOR
VALVE
SYSTEM SUPPLY
SENSOR
(WHEN USED)
PRESSURE
GAUGE
ZONE CIRCULATORS
(TYPICAL)
EXPANSION
TANK
MIXING
VALVE
LOW TEMP
ZONE
SPACE HEAT SUPPLY
HIGH TEMP RETURN
LOW TEMP RETURN
HIGH TEMP
ZONE #1
TEMPERATURE
BACKUP
HEAT SOURCE
GAUGE
HIGH TEMP
ZONE #2
CIRCULATION
MIXING
VALVE
PUMP
SHOCK
ARRESTOR
RECIRCULATION
LINE
CHECK
VALVE
DOMESTIC
HOT WATER
SHUTOFF
VALVE
DOMESTIC
COLD WATER
NOTICE
DRAIN
IMG00042
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
17
Page 18
4 Domestic side piping
Figure 4-5 Recirculation Lance Piping: Flow Up to 2 gal/min
CIRCULATION
PUMP
RECIRCULATION
LINE
RECIRCULATION
LANCE
SHOCK
ARRESTOR
Installation & Operation Manual
SHUTOFF
VALV E
DOMESTIC
HOT WATER
TEMPERATURE
GAUGE
BACKUP HEAT
SOURCE SENSOR
Figure 4-6 Recirculation Piping: Flow Over 2 gal/min
CIRCULATION
PUMP
RECIRCULATION
LINE
TEMPERATURE
GAUGE
MIXING
VALV E
IMG00043
MIXING
VALV E
SHOCK
ARRESTOR
CHECK
VALV E
HOT WATER
SHUTOFF
VALV E
DOMESTIC
COLD WATER
DOMESTIC
HEAT SOURCE
18
BACKUP
SENSOR
NOTICE
CHECK
VALV E
DOMESTIC
COLD WATER
IMG00089
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Page 19
4 Domestic side piping (continued)
Installation & Operation Manual
Figure 4-7 Multiple Tank Domestic Piping
RECIRCULATION
LINE
TEMPERATURE
GAUGE
BACKUP
HEAT SOURCE
SENSOR
CIRCULATION PUMP
ARRESTOR
MIXING
VALV E
SHOCK
DOMESTIC
HOT WATER
SHUTOFF
VALV E
CHECK
VALV E
DOMESTIC
COLD WATER
Figure 4-8 Domestic Piping with Storage Tank
BUILDING
RETURN LINE
DOMESTIC
WATER OUTLET
DOMESTIC
WATER INLET
CIRCULATION
PUMP
IMG00087
SHOCK
ARRESTOR
MIXING
VALV E
AQUASTAT
(TO CONTROL
CIRCULATION
SENSOR
PUMP)
IMG00093
DOMESTIC
HOT WATER
SHUTOFF
VALV E
CHECK
VALV E
DOMESTIC
COLD WATER
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
19
Page 20
Installation & Operation Manual
5 Boiler side piping
Figures 5-1 and 5-2 show typical boiler piping for single and multi-tank situations. A pressure relief valve must be installed on each boiler and each tank, as regulations require. The tank pressure relief valve should be sized to meet the working pressure of the tank according to local codes.
Multiple tank connections (boiler side)
Boiler piping works most efficiently when it is done in the reverse-return application. This method uses more piping than direct return systems, but the pressure drop and boiler flow are more balanced throughout each tank. To ensure even charging and discharging of each tank, it is recommended that only tanks of the same size are placed in the same manifold. It is recommended that each tank be equipped with its own isolation valves, unions and drains so that one tank may be removed from the system, if necessary.
Figure 5-1 Backup Heat Source Connection
PRESSURE
RELIEF VALVE
TEMPERATURE
GAUGE
BACKUP
HEAT SOURCE
SENSOR
NOTICE
FILL
VALV E
AIR
SEPARATOR
Y-STRAINER
(TYPICAL)
CHECK
VALV E
PRESSURE
BOILER
CIRCULATOR
T&P
GAUGE
DRAIN
RELIEF
VALV E
IMG00086
BACKUP
HEAT SOURCE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
20
Page 21
5 Boiler side piping (continued)
Figure 5-2 Multiple Tank Backup Heat Source Connection
PRESSURE
RELIEF VALVE
TEMPERATURE
GAUGE
BACKUP
HEAT SOURCE SENSOR
AIR SEPARATOR
Installation & Operation Manual
PRESSURE
RELIEF VALVE
BOILER CIRCULATOR
BACKUP
HEAT SOURCE
NOTICE
FILL
VALV E
EXPANSION
TAN K
Y-STRAINER
(TYPICAL)
CHECK
VALV E
TEMPERATURE /
PRESSURE
GAUGE
DRAIN
IMG00091
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
21
Page 22
6 Startup and maintenance
Installation & Operation Manual
System startup
1. Make sure the system is free of leaks and that air is purged from the system.
CAUTION
2. Many soldering fluxes contain Zinc Chloride which can cause severe corrosion damage to stainless steel. After completing all domestic water connections, flush the Strato-Therm+ tank and indirect coil thoroughly before leaving the installation. This is particularly important if the Strato-Therm+ will be unused for an extended period of time after installation. Flush the storage tank by drawing at least three times its volume from the tank.
3. Make sure that each zone valve or circulator operates when, and only when, its thermostat calls for heat. Let each zone operate long enough to purge any remaining air from the system.
Refer to the heat source and solar Installation and Operation Manuals for additional start-up information.
Fix any leaks found before proceeding further. Leakage from the heat source and solar piping can result in severe damage to the system.
Maintenance Schedule
The Lochinvar Strato-Therm+ solar tank is an extremely simple device and as such requires very little maintenance. There are, however, several items which should be inspected on an annual or as needed basis to ensure a reliable supply of hot water:
* Ensure that the boiler and solar water piping are free of leaks.
* If there is an oil lubricated circulator in the system, make sure it is lubricated as called for by the circulator manufacturer.
* Make sure that the heat source is maintained in accordance with the manufacturer’s instructions.
* If a water treatment system is required to keep the water chemistry within the parameters shown in Table 2A (see Section 2 - Pre-Installation), make sure that this system is properly maintained.
Annual service by a qualified service technician should include the following:
Any procedure required by local codes.
Verify system pressure. Air venting procedure may require
adding water to bring boiler system up to pressure, typically 12 psig minimum.
Manually operate T&P relief valve at least once a year. This will release some hot water.
WARNING
Verify that expansion tank pressure is equal to system pressure.
Move operating lever to open position for a few seconds and then move it back, allowing it to snap closed. After the T&P relief valve is operated, if it continues to release water, close the cold water inlet to the water heater immediately. Follow the draining instructions, and replace the T&P relief valve. If the T&P relief valve weeps periodically, it may be due to thermal expansion. Do not plug the T&P relief valve or discharge piping. In this case, ensure that the expansion tank is properly sized and charged to the appropriate pressure.
DANGER
Before operating a T&P relief valve, make sure no one is in front of or around the T&P relief valve discharge piping. Hot discharge water can cause severe personal injury or substantial property damage.
Plugging the T&P relief valve or discharge piping can cause excessive pressure in the water heater, resulting in severe personal injury, death, or substantial property damage.
22
Page 23
6 Startup and maintenance (continued)
Installation & Operation Manual
Follow instructions on circulator to oil, if required.
Check mixing valve, valves, pipes, and fittings for leaks.
Check function of the field-installed controls and valves.
See component manufacturer’s instructions.
Review owner’s maintenance responsibilities and their frequencies, including any not listed in the following section.
Owner monthly maintenance to include:
Visually check valves, pipes, and fittings for leaks. Call a qualified service technician to repair leaks.
Winterizing the system
Drain the tank and coil if it will be off and exposed to freezing temperatures. Freezing water will expand and damage the water heater.
If the tank, spherical heat exchanger and heat source water contain sufficient antifreeze, then only the domestic coil water needs to be drained.
If the tank, spherical heat exchanger and heat source
water do not contain sufficient antifreeze, they must be drained in addition to domestic water.
If antifreeze is used in the heat source water, check the concentration. Heat source water (including additives) must be practically non-toxic, having a toxicity rating or class of 1, as listed in the “Clinical Toxicology of Commercial Products”. A maximum 50/50 mixture of inhibited propylene glycol is recommended. Follow the antifreeze manufacturer’s instructions.
WARNING
Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death, or substantial property damage.
To drain/flush the system
1. Turn OFF main electrical power to the tank, solar collectors and any other heat source connected to the tank.
2. Turn OFF the main manual gas shutoff for any heat source connected to the tank.
3. Turn OFF electrical power to the circulating pump (if used).
4. Close off the boiler or heat source inlet connection.
5. Ensure that the drain (located on the bottom of the tank) is routed to a floor drain with adequate capacity to allow the tank to be flushed.
6. Open the drain valve and allow the incoming cold water “Boiler Return” to flush the soft sediment out of the bottom of the storage tank.
CAUTION
7. Observe the color of the water initially discharged from the tank drain. This water will generally be milky or slightly discolored by the sediment discharge. Allow the drain to run until the water runs clear.
8. Close the drain valve on the tank.
9. Open the hot water relief/air valve on the top of the tank.
10. Turn ON main electrical power for the heat source, solar collectors, tank and circulating pump.
11. Turn ON gas supply to the heat source(s).
12. Observe heat source and solar piping to ensure that all components are functioning properly.
Hot water will be released under pressure. Avoid contact with hot discharge water to prevent the risk of severe scald injury.
Hot Water Can Scald!
Water heated to temperatures for clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury.
• Children, elderly, and infirm or physically handicapped persons are more likely to be permanently injured by hot water. Never leave them unattended in a bathtub or shower. Never allow small children to use a hot water tap or draw their own bath.
If anyone using hot water in the building fits the above description, or if state laws or local codes require certain water temperatures at hot water taps, you must take special precautions:
Use lowest possible temperature setting.
• Install some type of tempering device, such as an automatic mixing valve, at hot water tap or water heater. Automatic mixing valve must be selected and installed according to valve manufacturer’s recommendations and instructions.
Water passing out of drain valves may be extremely hot. To avoid injury:
Make sure all connections are tight.
Direct water flow away from any person. Protection Must Be Taken Against Excessive Temperature and Pressure!
--Installation of a Temperature & Pressure (T&P) relief valve is required.
23
Page 24
Installation & Operation Manual
7 Performance data
Table 7A
First Hour Ratings at Maximum Coil Capacity
180°F Boiler Input 140°F Boiler Input
140°F Mixed DHW 115°F Mixed DHW 115°F Mixed DHW
Max. Capacity
Model
STU150 16 1035 23 1516 15 997
STU200 19 1244 27 1774 18 1125
STU257 19 1365 27 1965 18 1250
STU350 19 1550 27 2223 18 1395
STU423 27 1690 36 2451 26 1600
STU504 28 1816 36 2569 27 1783
STU650 31 2036 36 2737 28 1952
STU752 31 2042 36 2869 28 1983
STU940 31 2072 36 3011 28 2032
Flow Rate
(gpm)
First Hour
Rating
gal/hr
Max. Capacity
Flow Rate
(gpm)
First Hour
Rating
gal/hr
Max. Capacity
Flow Rate
(gpm)
First Hour
Rating
gal/hr
Table 7B
Standby Heat Loss
Model
STU150 0.61
STU200 0.52
STU257 0.44
STU350 0.39
STU423 0.31
STU504 0.30
STU650 0.27
STU752 0.25
STU940 0.23
Heat Loss
°F/hr
24
Page 25
716,548
716,548
716,548
716,548
716,548
716,548
716,548
716,548
Installation & Operation Manual
7 Performance data (continued)
Table 7C
Maximum Coil Capacity 180°F Boiler Input, 115°F DHW
Boiler Heat Input - Btu/hr
Flow Rate Tank Size
gpm gal/hr 150 200 257 350 423 504 650 752 940
2 120 84,592 84,592 84,592 84,592 84,592* 84,592* 84,592* 84,592* 84,592* 3 180 89,569 89,569 89,569 89,569 89,569* 89,569* 89,569* 89,569* 89,569* 4 240 119,425 119,425 119,425 119,425 119,425* 119,425* 119,425* 119,425* 119,425* 5 300 149,281 149,281 149,281 149,281 149,281* 149,281* 149,281* 149,281* 149,281* 6 360 179,137 179,137 179,137 179,137 179,137* 179,137* 179,137* 179,137* 179,137* 7 420 208,993 208,993 208,993 208,993 208,993* 208,993* 208,993* 208,993* 208,993* 8 480 238,849 238,849 238,849 238,849 238,849* 238,849* 238,849* 238,849* 238,849*
9 540 268,706 268,706 268,706 268,706 268,706* 268,706* 268,706* 268,706* 268,706* 10 600 298,562 298,562 298,562 298,562 298,562* 298,562* 298,562* 298,562* 298,562* 11 660 328,418 328,418 328,418 328,418 328,418* 328,418* 328,418* 328,418* 328,418* 12 720 358,274 358,274 358,274 358,274 358,274* 358,274* 358,274* 358,274* 358,274* 13 780 388,130 388,130 388,130 388,130 388,130* 388,130* 388,130* 388,130* 388,130* 14 840 417,986 417,986 417,986 417,986 417,986* 417,986* 417,986* 417,986* 417,986* 15 900 447,843 447,843 447,843 447,843 447,843* 447,843* 447,843* 447,843* 447,843* 16 960 477,699 477,699 477,699 477,699 477,699* 477,699* 477,699* 477,699* 477,699* 17 1020 507,555 507,555 507,555 507,555 507,555* 507,555* 507,555* 507,555* 507,555* 18 1080 537,411 537,411 537,411 537,411 537,411* 537,411* 537,411* 537,411* 537,411* 19 1140 567,267 567,267 567,267 567,267 567,267* 567,267* 567,267* 567,267* 567,267* 20 1200 597,123 597,123 597,123 597,123 597,123* 597,123* 597,123* 597,123* 597,123* 21 1260 626,980 626,980 626,980 626,980 626,980* 626,980* 626,980* 626,980* 626,980* 22 1320 656,836 656,836 656,836 656,836 656,836* 656,836* 656,836* 656,836* 656,836* 23 1380 686,692 686,692 686,692 686,692 686,692* 686,692* 686,692* 686,692* 686,692* 24 1440 25 1500 746,404 746,404 746,404 746,404* 746,404* 746,404* 746,404* 746,404* 26 1560 776,260 776,260 776,260 776,260* 776,260* 776,260* 776,260* 776,260* 27 1620 806,117 806,117 806,117 806,117* 806,117* 806,117* 806,117* 806,117* 28 1680 835,973* 835,973* 835,973* 835,973* 835,973* 29 1740 865,829* 865,829* 865,829* 865,829* 865,829* 30 1800 895,685* 895,685* 895,685* 895,685* 895,685* 31 1860 925,541* 925,541* 925,541* 925,541* 925,541* 32 1920 955,397* 955,397* 955,397* 955,397* 955,397* 33 1980 985,254* 985,254* 985,254* 985,254* 985,254* 34 2040 1,015,110* 1,015,110* 1,015,110* 1,015,110* 1,015,110* 35 2100 1,044,966* 1,044,966* 1,044,966* 1,044,966* 1,044,966* 36 2160 1,074,822* 1,074,822* 1,074,822* 1,074,822* 1,074,822*
* Denotes value based on use of a mixing valve.
716,548
716,548
716,548
716,548*
716,548*
716,548*
716,548*
716,548*
NOTE: - Values based on 55°F domestic cold water input
- Values obtained using boiler heat input only
- Maximum coil threshold was set at 36 gpm
25
Page 26
Installation & Operation Manual
7 Performance data
Table 7D
Maximum Coil Capacity 180°F Boiler Input, 140°F DHW
Boiler Heat Input - Btu/hr
Flow Rate Tank Size
gpm gal/hr 150 200 257 350 423 504 650 752 940
2 120 84,389 84,389 84,389 84,389 84,389 84,389 84,389 84,389 84,389 3 180 126,583 126,583 126,583 126,583 126,583 126,583 126,583 126,583 126,583 4 240 168,778 168,778 168,778 168,778 168,778 168,778 168,778 168,778 168,778 5 300 210,972 210,972 210,972 210,972 210,972 210,972 210,972 210,972 210,972 6 360 253,167 253,167 253,167 253,167 253,167 253,167 253,167 253,167 253,167 7 420 295,361 295,361 295,361 295,361 295,361 295,361 295,361 295,361 295,361 8 480 337,556 337,556 337,556 337,556 337,556 337,556 337,556 337,556 337,556
9 540 379,750 379,750 379,750 379,750 379,750 379,750 379,750 379,750 379,750 10 600 421,944 421,944 421,944 421,944 421,944 421,944 421,944 421,944 421,944 11 660 464,139 464,139 464,139 464,139 464,139 464,139 464,139 464,139 464,139 12 720 506,333 506,333 506,333 506,333 506,333 506,333 506,333 506,333 506,333 13 780 548,528 548,528 548,528 548,528 548,528 548,528 548,528 548,528 548,528 14 840 590,722 590,722 590,722 590,722 590,722 590,722 590,722 590,722 590,722 15 900 632,917 632,917 632,917 632,917 632,917 632,917 632,917 632,917 632,917 16 960 675,111 675,111 675,111 675,111 675,111 675,111 675,111 675,111 675,111 17 1020 717,306 717,306 717,306 717,306 719,036 719,036 719,036 719,036 18 1080 759,500 759,500 759,500 759,500 761,332 761,332 761,332 761,332 19 1140 801,694 801,694 801,694 801,694 803,629 803,629 803,629 803,629 20 1200 843,889 843,889 843,889 843,889 843,889 21 1260 886,083 886,083 886,083 886,083 886,083 22 1320 928,278 928,278 928,278 928,278 928,278 23 1380 970,472 970,472 970,472 970,472 970,472 24 1440 1,012,667 1,012,667 1,012,667 1,012,667 1,012,667 25 1500 1,054,861 1,054,861 1,054,861 1,054,861 1,054,861 26 1560 1,097,055 1,097,055 1,097,055 1,097,055 1,097,055 27 1620 1,139,250 1,139,250 1,139,250 1,139,250 1,139,250 28 1680 1,181,444 1,181,444 1,181,444 1,181,444 29 1740 1,223,639 1,223,639 1,223,639 30 1800 1,265,833 1,265,833 1,265,833 31 1860 1,308,028 1,308,028 1,308,028
NOTE: - Values based on 55°F domestic cold water input
- Values obtained using boiler heat input only
26
Page 27
Installation & Operation Manual
7 Performance data (continued)
Table 7E
Maximum Coil Capacity 140°F Boiler Input, 115°F DHW
Boiler Heat Input - Btu/hr
Flow Rate Tank Size
gpm gal/hr 150 200 257 350 423 504 650 752 940
2 120 84,592 84,592 84,592 84,592 84,592 84,592 84,592 84,592 84,592 3 180 89,569 89,569 89,569 89,569 89,569 89,569 89,569 89,569 89,569 4 240 119,425 119,425 119,425 119,425 119,425 119,425 119,425 119,425 119,425 5 300 149,281 149,281 149,281 149,281 149,281 149,281 149,281 149,281 149,281 6 360 179,137 179,137 179,137 179,137 179,137 179,137 179,137 179,137 179,137 7 420 208,993 208,993 208,993 208,993 208,993 208,993 208,993 208,993 208,993 8 480 238,849 238,849 238,849 238,849 238,849 238,849 238,849 238,849 238,849
9 540 268,706 268,706 268,706 268,706 268,706 268,706 268,706 268,706 268,706 10 600 298,562 298,562 298,562 298,562 298,562 298,562 298,562 298,562 298,562 11 660 328,418 328,418 328,418 328,418 328,418 328,418 328,418 328,418 328,418 12 720 358,274 358,274 358,274 358,274 358,274 358,274 358,274 358,274 358,274 13 780 388,130 388,130 388,130 388,130 388,130 388,130 388,130 388,130 388,130 14 840 417,986 417,986 417,986 417,986 417,986 417,986 417,986 417,986 417,986 15 900 447,843 447,843 447,843 447,843 447,843 447,843 447,843 447,843 447,843 16 960 477,699 477,699 477,699 477,699 477,699 477,699 477,699 477,699 17 1020 507,555 507,555 507,555 507,555 507,555 507,555 507,555 507,555 18 1080 537,411 537,411 537,411 537,411 537,411 537,411 537,411 537,411 19 1140 567,267 567,267 567,267 567,267 567,267 20 1200 597,123 597,123 597,123 597,123 597,123 21 1260 626,980 626,980 626,980 626,980 626,980 22 1320 656,836 656,836 656,836 656,836 656,836 23 1380 686,692 686,692 686,692 686,692 686,692 24 1440 716,548 716,548 716,548 716,548 716,548 25 1500 746,404 746,404 746,404 746,404 746,404 26 1560 776,260 776,260 776,260 776,260 776,260 27 1620 806,117 806,117 806,117 806,117 28 1680 835,973 835,973 835,973
NOTE: - Values based on 55°F domestic cold water input
- Values obtained using boiler heat input only
27
Page 28
Revision Notes: Revision A (ECO C09107)
initial release.
10/11 - Printed in U.S.A.
STU-I-O Rev A
Loading...