Lochinvar Standard Hi-Power Installation Manual

1
INSTALLATION AND SERVICE MANUAL
SHP-I&S-02
COMMERCIAL ELECTRIC WATER HEATERS
52, 82, 119 Gallon, 9 kW - 54kW Input Models
FIG. 1 Front View Vertical Round Models
Installation and service must be performed by Qualified Service Personnel Only.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
1. Excessive water hardness causing a lime/scale build-up in the heater and/or on the immersion heating elements is not the fault of the equipment and is not covered under the manufacturer's warranty. (See Water Treatment and Water Chemistry)
2. Do not energize electrical system before the heater is completely filled with water. Damage caused to the immersion heating elements by dry fire is not covered under the manufacturer's warranty. Follow start up procedure in the manual.
3. Water heater corrosion and component failure caused by air-borne chemical vapors is not covered under the manufacturer's warranty.
4. Corrosion damage caused by current leakage due to improper grounding of electrical systems or electronic components to the storage tank and related piping is not covered by the manufacturer's warranty.
5. Under no circumstance will the manufacturer be liable for consequential damages resulting from the installation or use of this equipment.
6. Correct installation procedure and local codes must be adhered to.
SPECIAL INSTRUCTIONS
TO OWNER
NOTE:
Retain this manual for future reference.
WARNING:
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency or the electric utility.
This manual supplies information for the installation, operation and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation.
CHECKING EQUIPMENT
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the water heater, which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify carrier.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. THE POSSIBLE DAMAGE TO A FLOODED APPLIANCE CAN BE EXTENSIVE AND PRESENT NUMEROUS SAFETY HAZARDS. ANY APPLIANCE THAT HAS BEEN UNDER WATER MUST BE REPLACED.
2
WARNING:
CONTENTS
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Checking the Equipment . . . . . . . . . . . . . . . . . . . . . . . . .1
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation Requirements
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Drain Pan Requirements . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Tank Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cathodic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Electrical Service
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Wire Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Jacket Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Standard and Optional Controls . . . . . . . . . . . . . . . . . . .7
Components and Controls
Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Fuses and Fuse Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Surface Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Immersion Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Temperature Regulation . . . . . . . . . . . . . . . . . . . . . . . . .10
Risk of Scald Warnings . . . . . . . . . . . . . . . . . . . . . . . . . .10
Temperature Limit Control . . . . . . . . . . . . . . . . . . . . . .11
Immersion Heating Elements . . . . . . . . . . . . . . . . . . . .12
Start-Up Procedure
Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Filling the Water Heater . . . . . . . . . . . . . . . . . . . . . . . . .12
Start-Up Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Shutdown Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Maintenance
T&P Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Water Chemistry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Flushing the Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Sediment Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Scale Removal - Elements . . . . . . . . . . . . . . . . . . . . . . . .15
Trouble Shooting
Not Enough Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . .16
Water Is Too Hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Water Heater Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
OWNER WARNING:
The information contained in this manual is intended for use by qualified professional installers, service technicians or the electric utility. Consult your local expert for proper installation or service procedures.
IMPORTANT:
Consult and follow local Electrical Codes, Building and Fire Regulations and other Safety Codes that apply to this installation. Consult local codes officials and electric utility company to authorize and inspect all field installed electrical connections.
CAUTION
Be sure to turn off power when working on or near the electrical system of the water heater. Never touch electrical components with wet hands or when standing in water. When replacing fuses, always use the correct size for the circuit. Do not test electrical system before the water heater is completely filled with water. Follow the start-up procedure.
WARNING:
To minimize the possibility of serious personal injury, fire or damage to your appliance, never violate the following safety rules.
1. Always keep the area around your appliance free of combustible materials, gasoline, and other flammable liquids and vapors.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the access to your appliance.
3
CODES
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Electrical Code, NFPA 70. When the appliance is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.
APPROVALS
This complete appliance is design certified and Listed by Underwriters Laboratories as a commercial storage electric water heater. This water heater bears the UL certification for the United States as tested under the Standard for Electric Booster and Commercial Storage Tank Water Heaters, UL1453 and C-UL in Canada as tested under the Standard for Construction and Test of Electric Storage Tank Water Heaters, CAN/CSA-C22.2 No. 110-M90.
INSTALLATION PROCEDURE
LOCATION OF UNIT
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit, or any of its components.
2. Insure that the appliance is located near an acceptable drain so that the vessel can be properly drained when performing service or maintenance. The drain must
also
provide adequate drainage in the event of leakage from the tank or related piping. The drain must prevent water damage to the adjacent area and lower floors of the structure.
3. The appliance must be installed so that the electrical components are protected from water (dripping, spraying, etc.) during appliance operation and service (replacing of fuses, elements, etc.)
4. Appliances located in a garage or parking structure shall be installed so that the jacket and all piping shall be located or protected so that it is not subject to physical damage by a moving vehicle.
5. The appliance must be installed on a level floor. Shim the base as necessary if leveling is required.
6. The floor on which the appliance is installed must be capable of supporting the total weight of the water heater when completely filled with water. Combustible floor locations may be used. Maintain required clearances from combustible surfaces.
7. The appliance must not be installed on carpet.
8. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
9. Locate the appliance as close as possible to the point of major hot water usage, the water piping and branch electrical circuit wiring.
10. Insulate water piping to control heat loss and possible condensation.
11. The appliance must be located in an area that is not subject to freezing. The ambient temperature of the space where the appliance is installed must not go below 32°F (0°C) or above 104°F (40°C).
CAUTION
This water heater, as well as all water heaters will eventually leak. Installation of the water heater should be accomplished in such a manner that if the tank, piping or any connections should leak, the flow of water will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan must be installed under the water heater. Drain pans may be fabricated or purchased from your plumbing wholesaler. The drain pan must be piped to an adequate drain. Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater.
4
CLEARANCES FROM
COMBUSTIBLE CONSTRUCTION
FIG. 2 Clearances from Combustible Construction
TABLE - A
CLEARANCES FROM
COMBUSTIBLE CONSTRUCTION:
Right Side - 0" Rear - 0" Left Side - 0" Front - 18" (45cm) for service access to controls and heating elements Top - 12" (30cm) suggested for service access to piping and water connection Hot Water Pipes 1" (25.4mm)
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the electrical components, water pipe connections, piping and other auxiliary equipment, as well as the appliance.
Multiple appliances may be installed in a modular water heater installation. Multiple appliances may be installed side by side with no clearance between the sides of adjacent appliance. This appliance is approved for zero clearance from side combustible surfaces and no service access is required from the sides on most models.
MOUNTING
The water heater should be mounted to the floor following applicable architectural and local code requirements or accepted standards for the specific site and model purchased. In areas prone to seismic activity, it is recommended that the water heater be mounted to the floor according to recommended procedures for the site. In some geographic areas, additional strapping or braces may be required, consult local codes for specific requirements. Proper mounting will help to make the water heater less susceptible to seismic damage.
FIG. 3 Water Connections
WATER CONNECTIONS
NOTE:
Before making any connections to the cold water inlet or hot water outlet, insure that all piping is clean and free of material or scale. This can usually be accomplished by "blowing out the pipe." Any foreign material or scale entering the water heater can adversely affect operation and performance.
NOTE:
When using copper tubing, solder tubing to an adapter before attaching to the threaded nipple connection provided on the water heater. Soldering directly to the threaded connection may harm a lining in the nipple or damage the tank lining.
5
INLET AND OUTLET CONNECTIONS
For ease of service, install unions on the cold water inlet and hot water outlet of the water heater. The cold water inlet connection is located on the lower left front side of the water heater. A manual shutoff valve should be installed upstream on the cold water source as an isolation device. The hot water outlet connection is located on the top center of the water heater. A manual shutoff valve should be installed downstream on the hot water outlet source as an isolation device in case the water heater must be disconnected from the system.
STORAGE TANK
This appliance uses a glass lined steel storage tank to store the heated water for use. The storage tank is constructed in accordance with the requirements of the Underwriters Laboratory Listing for a commercial electric water heater. The tank is furnished with threaded connections for cold water inlet, hot water outlet, a relief valve and a drain connection. The storage tank has a hand hole for ease of inspection, cleanout and service. The interior of the storage tank is glass lined and fired to 1600˚F (871˚C) to insure a molecular fusing of glass and steel to protect the steel base metal against corrosion. A magnesium anode is standard to help prevent dissipation of the tank material by electrolytic action.
RELIEF VALVE
This water heater is supplied with a temperature and pressure relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV. Some water heaters may be supplied with an optional pressure only relief valve. The relief valve(s) is installed in the vertical position and mounted in the tapping provided in the storage tank. No valve is to be placed between the relief valve, and the water heater. To prevent water damage, the discharge from the relief valve must be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year. A relief valve that fails to completely reseat and continues to discharge water must be immediately replaced with a new, properly sized, temperature and pressure relief valve.
CAUTION
Avoid contact with hot discharge water. Insure that no one is in front of or around the relief valve discharge line. Make sure that the extremely hot water manually discharged from the relief valve will not cause bodily injury or property damage.
THERMAL EXPANSION
OF WATER
A relief valve that discharges periodically may be due to thermal expansion in a closed system. Many water systems are equipped with pressure reducing valves, check valves or back flow preventers which may cause the water system to be closed. As water is heated it will expand in volume due to thermal expansion. The system must make allowance for this expansion. If an expansion tank is not provided in the system, water pressure may increase to the point where the water heater's temperature and pressure relief valve opens to relieve the excess pressure. The temperature and pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected. Do not plug or cap the relief valve discharge! A properly sized expansion tank is typically installed in the potable water system to relieve the pressure built up by thermal expansion of heated water. Consult your local plumbing contractor and plumbing wholesaler for assistance in properly selecting an expansion tank for your system.
As the water heater operates, there may be noises generated by the expansion and contraction of the metal parts of the water heater and related piping. These noises may occur during periods of heat up or cool down. They do not represent harmful or dangerous conditions.
CATHODIC PROTECTION
Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be open for several minutes at a sink close to the water heater before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.
Loading...
+ 11 hidden pages