VENTING OPTIONS
Armor X2 VENTING OPTIONS
JOB NAME_______________________________________________________ LOCATION_______________________________________________________ ARCH./ENG.______________________________________________________ WHOLESALER ___________________________________________________ MECH. CONTRACTOR_____________________________________________ MODEL NUMBER__________________________________________________ NOTES__________________________________________________________ ________________________________________________________________
VERTICAL VENT WITH COMBUSTION AIR FROM THE ROOFTOP Category IV – Direct Vent Vertical
Vents vertically up to 100 equivalent feet and directly draws combustion air 100
equivalent feet from the rooftop.
Vent and Air Intake diameters are 6” and/or 7” based on model. See page 4 for table
showing model sizes with matching pipe diameters and maximum pipe lengths.
Vent material may be PVC, CPVC, Polypropylene or AL29-4C Stainless Steel. All Vent
connections, joints and seams MUST be sealed airtight.
Air Intake material may be PVC, CPVC, Polypropylene or ABS plastic pipe; Galvanized
Steel Vent pipe or Type “B” Double-Wall vent. All Air Intake connections, joints and seams MUST be sealed airtight.
When venting with PVC, the first 10 equivalent feet from the boiler MUST be CPVC.  Vent material and air intake material are supplied locally.
Submittal Sheet
AWXV-Sub-01a
Non-Metallic
Two Pi
e
HORIZONTAL VENT WITH COMBUSTION AIR FROM THE SIDEWALL Category IV – Direct Vent Horizontal
Vents horizontally up to 100 equivalent feet and directly draws combustion air 100
equivalent feet from the sidewall.
Vent and Air Intake diameters are 6” and/or 7” based on model. See page 4 for table
showing model sizes with matching pipe diameters and maximum pipe lengths.
Vent material may be PVC, CPVC, Polypropylene or AL29-4C Stainless Steel. All Vent
connections, joints and seams MUST be sealed airtight.
Air Intake material may be PVC, CPVC, Polypropylene or ABS plastic pipe; Galvanized
Steel Vent pipe or Type “B” Double-Wall vent. All Air Intake connections, joints and seams MUST be sealed airtight.
When venting with PVC, the first 10 equivalent feet from the boiler MUST be CPVC.  Sidewall vent and air intake terminations are provided by Lochinvar. Vent material and
air intake material are supplied locally.
Non-Metallic Two Pipe
Use “Snorkel” termination as seen above or For Stainless Steel sidewall termination, use Sidewall Vent/Air Termination Kit provided specify special Stainless Steel Vent Kit, with every SYNC boiler. KIT30028 (6” kit) or KIT30029 (7” kit).