Optional Equipment
Standard Features
Typical Specification
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
1/07-Printed in U.S.A.
• 120 VAC power for ease of installation
• Built in password protection
• Adjustable ignition and modulation start points
• LED indicator lights
• Digital display of system status: set point, lead
unit and status of last unit
• Unit signal output: 4-20mA
• Sequencing Options:
Manual, First ON/First OFF, or Automatic at selected
time periods from every hour to every seven days
• 4-20mA interface for outdoor or night setback
• Temperature display – Fahrenheit or Celsius
• Pump relay provided is energized when output is
required. It is adjustable for time delay
• Adjustable PID logic controls system loading/unloading
• System sensor can be located up to 500 feet
from the control module
• All settings and operating modes are stored permanently
and maintain their values if power is lost
• Requires only one sensor located in the common header
of all units
• System output can be used to activate a system pump,
damper, or other functions when a Power-Fin is active.
• Expandable, up to 12 units of heating
• Outdoor air sensor
Ordering Information
The sequencing control for proportional boilers shall be Lochinvar model number SMP having a capacity
for
stages to be used on Power-Fin units.
The control system shall provide:
A field adjustable set point from 100ºF to 240ºF; (Minimum inlet water temperature on Power-Fin 130ºF) Field adjustable reset
ratio from 1:4 to 4:1 (Outdoor temperature: Water temperature); Field adjustable integral offset to parallel shift the selected reset
curve in the range of -50ºF to 50ºF; Field adjustable outdoor temperature cutoff in the range of 30ºF to 75ºF and capable of
ON/OFF; Field adjustable number of stages, input from 1 to 4 stages; Optional control of up to 12 stage; Field adjustable rotation
among stages: Manual, First ON/First OFF, or Automatic at every selected time period from every hour to every 7 days; Four line
by twenty character VFD display of numbers and characters visible without ambient light; Thermistor type temperature sensors;
Field adjustable modulation start point from 25% to 100% of rated input; Field adjustable purge timer from 0 to 10 minutes of
delay between energizing a stage and the beginning of modulation; Field adjustable lag stage delay from 0 to 60 minutes;
Adjustable setback from 0ºF to 75ºF with external switch closure; NEMA-1 enclosure with key lock; Field adjustable standby
timer from 1 to 60 minutes to determine the delay period before standby stages are activated; Field adjustable system delay from
0 to 60 minutes; 120 VAC power supply to panel; Terminal strips for all field wiring connections.
Description Model Number Part Number
1-4 Unit Master Control Module PB/PF 501-1300 (M9) SMP2103
5-12 Unit Extention Module PB/PF 501-1300 (M9) SMP2104
Outdoor Air Sensor (optional) PB/PF 501-1300 (M9) SMP2102
HS-03 (Replaces HS-02 4/05)
Sequencing of up to 4 Units requires the following:
1 - SMP2103 Master Control Module
Sequencing of 5 - 12 units requires the following:
1 - SMP2103 Master Control Module
1 - SMP2104 Extension Module