is manual must only be used by a
quali ed heating installer / service
technician. Read all instructions,
including this manual and the
Outdoor Knight XL Service Manual,
before installing. Perform steps in
the order given. Failure to comply
could result in severe personal
injury, death, or substantial property
damage.
Revision Notes .................................................. Back Cover
Hazard defi nitions
e following de ned terms are used throughout this manual to bring attention to the presence of hazards of various risk levels
or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate
injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not
avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not
related to personal injury or property damage.
2
Please read before proceeding
WARNING
Installer – Read all instructions, including
this manual and the Outdoor Knight XL
Service Manual, before installing. Perform
steps in the order given.
When servicing boiler –
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
Outdoor Knight XL Installation & Operation Manual
NOTICE
WARNING
WARNING
User – is manual is for use only by
a qualified heating installer/service
technician. Refer to the User’s Information
Manual for your reference.
Have this boiler serviced/inspected by
a quali ed service technician, at least
annually.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
When calling or writing about the boiler
– Please have the boiler model and serial
number from the boiler rating plate.
Consider piping and installation when
determining boiler location.
Any claims for damage or shortage in
shipment must be led immediately
against the transportation company by the
consignee.
Factory warranty (shipped with unit) does
not apply to units improperly installed or
improperly operated.
Failure to adhere to the guidelines on this
page can result in severe personal injury,
death, or substantial property damage.
If the information in this manual is not
followed exactly, a re or explosion may
result causing property damage, personal
injury or loss of life.
is appliance MUST NOT be installed in
any location where gasoline or ammable
vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a near by phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
• Installation and service must be
performed by a quali ed installer,
service agency, or the gas supplier.
• To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation –
• Do not block ow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut o ,
do not turn o or disconnect electrical supply to
circulator. Instead, shut o the gas supply at a location
external to the appliance.
• Do not use this boiler if any part has been under water.
e possible damage to a ooded appliance can be
extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
Boiler water –
• oroughly ush the system to remove debris. Use
an approved pre-commissioning cleaner (see Start-Up
Section), without the boiler connected, to clean the system
and remove sediment. e high e ciency heat exchanger
can be damaged by build-up or corrosion due to sediment.
NOTE: Cleaners are designed for either new systems or
pre-existing systems. Choose accordingly.
• Continual fresh make-up water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat
transfer, overheats the stainless steel heat exchanger,
and causes failure. Addition of oxygen carried in by
makeup water can cause internal corrosion in system
components. Leaks in boiler or piping must be repaired
at once to prevent makeup water.
CAUTION
CAUTION
Do not use petroleum-based cleaning or
sealing compounds in the boiler system.
Gaskets and seals in the system may be
damaged. is can result in substantial
property damage.
Do not use “homemade cures” or “boiler
patent medicines”. Serious damage to the
boiler, personnel, and/or property may
result.
Freeze protection fl uids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are speci cally
formulated for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used in hydronic
systems.
3
Outdoor Knight XL Installation & Operation Manual
The Outdoor Knight XL - How it works...
1. Stainless steel heat exchanger
Allows system water to ow through specially designed
coils for maximum heat transfer, while providing protection
against ue gas corrosion. e coils are encased in a jacket that
contains the combustion process.
2. Combustion chamber access cover
Allows access to the combustion side of the heat exchanger
coils.
3. Blower
e blower pulls in air and gas through the venturi (item 5).
Air and gas mix inside the blower and are pushed into the
burner, where they burn inside the combustion chamber.
4. Gas valve
e gas valve senses the negative pressure created by the
blower, allowing gas to ow only if the gas valve is powered and
combustion air is owing.
5. Venturi
e venturi controls air and gas ow into the burner.
6. Flue gas sensor (limit rated - not shown)
is sensor monitors the ue gas exit temperature. e
control module will modulate and shut down the boiler if the
ue gas temperature gets too hot. is protects the ue pipe from
overheating.
7. Boiler outlet temperature sensor (housed with the
high limit sensor)
is sensor monitors boiler outlet water temperature (system
supply). If selected as the controlling sensor, the control
module adjusts boiler ring rate so the outlet temperature is
correct.
8. Boiler inlet temperature sensor
is sensor monitors return water temperature (system
return). If selected as the controlling sensor, the control
module adjusts the boiler ring rate so the inlet temperature is
correct.
9. Temperature and pressure gauge ( eld installed, not
shown)
Monitors the outlet temperature of the boiler as well as the
system water pressure.
10. Electronic LCD display
e electronic display consists of 4 buttons, a navigation dial
and a multiple line liquid crystal display.
11. Flue pipe assembly
Factory-supplied components for complete venting
system.
12. Burner (not shown)
Made with metal ber and stainless steel construction, the
burner uses pre-mixed air and gas and provides a wide range of
ring rates.
13. Water outlet (system supply)
A 1-1/2" or 2" NPT (depending on the model) water
connection that supplies hot water to the system.
14. Water inlet (system return)
A 1-1/2" or 2" NPT (depending on the model) water connection
that returns water from the system to the heat exchanger.
15. Gas connection pipe
readed pipe connection of 1". is pipe should be connected
to the incoming gas supply for the purpose of delivering gas to
the boiler.
16. SMART SYSTEM Control Module
e SMART SYSTEM Control responds to internal and
external signals and controls the blower, gas valve, and pumps
to meet the heating demand.
17. Manual air vent
Designed to remove trapped air from the heat exchanger
coils.
18. Air intake
Provides combustion air to the appliance.
19. Air Intake Cover
Provides protection from outdoor elements.
20. High voltage junction box
e junction box contains the connection points for the line
voltage power and all pumps.
21. Boiler drain port
Location from which the heat exchanger can be drained.
4
22. Low voltage connection board
e connection board is used to connect external low voltage
devices.
23. Low voltage wiring connections (plugs)
Conduit connection points for the low voltage connection
board.
24. Condensate drain connection
Connects the condensate drain line to a 1/2” PVC union.
25. Access cover - front
Provides access to the gas train and the heat exchanger.
26. Ignition electrode
Provides direct spark for igniting the burner.
27. Flame inspection window
e quartz glass window provides a view of the burner surface
and ame.
28. Gas shuto valve
Manual valve used to isolate the gas valve from the gas supply.
29. Relief valve
Protects the heat exchanger from an over pressure condition.
e relief valve provided with the unit is set at 50 PSI.
30. Flame sensor
Used by the control module to detect the presence of burner
ame.
31. Line voltage wiring connections (knockouts)
Conduit connection points for the high voltage junction box.
32. Top panel
Removable panel to gain access to the internal components.
33. Power switch
Turns 120 VAC ON/OFF to the boiler.
34. Leveling legs
Used to allow the heat exchanger to be leveled. is is needed
for the proper draining of the condensate from the combustion
chamber.
35. Air shroud (Model 501 only)
e air shroud controls air and gas ow into the burner.
36. Air pressure switch
e air pressure switch detects blocked ue/inlet conditions.
break the control circuit, shutting the boiler down.
37. Pump relay board
e pump relay board is used to connect the boiler, system and
DHW pumps.
38. Transformer (not shown)
e transformer provides 24V power to the integrated control.
39. High limit sensor (housed with the outlet temperature
sensor)
Device that monitors the outlet water temperature. If the
temperature exceeds its setting, the integrated control will break
the control circuit, shutting the boiler down.
40. Over-temp switch (located underneath vent cover not shown)
An electrical switch designed to shut down boiler operation in
the event the outer back of the heat exchanger, directly above the
ue connection exceeds 604°F (318°C). is is a one time
switch and could warrant a heat exchanger replacement. Check
the integrity of the rear refractory at the back of the upper coil if
the switch opens.
41. Vent Cover
Covers Over-temp switch and ue collar with ue sensor.
42. Flow switch
e ow switch is a safety device that ensures ow through
the heat exchanger during operation. is appliance is low
mass and should never be operated without ow. e ow
switch makes contact when ow is detected and allows the unit
to operate. If ow is discontinued during operation for any
reason the ow switch will break the control circuit and the
unit wll shut down.
43. Burner door temperature switch
An electrical switch designed to shut down boiler operation
in the event the combustion chamber access cover exceeds
500°F (260°C). is switch may only be reset by a quali ed
boiler service technician AFTER the underlying cause has been
identi ed and corrected. Check the integrity of the front
refractory on the inside of the combustion chamber access
cover if the switch opens.
Outdoor Knight XL Installation & Operation Manual
The Outdoor Knight XL - How it works... (continued)
Model 400
32
10
25
Front View - Model 400
20
36
8
4
29
7
39
13
21
24
43
IMG00405
4
IMG00406
33
30
26
Rear View - Model 400
20
2
27
22
37
16
1
3
34
17
IMG00407
Left Side (inside unit) - Model 400
Right Side (inside unit) - Model 400
5
Outdoor Knight XL Installation & Operation Manual
The Outdoor Knight XL - How it works...
Model 501
32
Rear View - Model 501
Models 601 - 801
41
15
IMG00408
35
15
19
28
4
29
7
39
43
33
17
IMG00409
Left Side (inside unit) - Model 501
20
Rear View - Models 601 - 801
16
22
4
18
8
1
34
21
IMG00324
24
2
Left Side (inside unit) - Models 601 - 801
3
5
10
30
43
IMG00324
6
Ratings
Outdoor Knight XL Installation & Operation Manual
Outdoor Knight XL Boiler
Other Specifi cations
AHRI Rating
Model Number
Note: Change “N” to
“L” for L.P. gas models.
OKN40080399370322
OKN501100500463402
OKN601120600566493
OKN701140700658572
OKN801160800748651
NOTICE
Min Max
Maximum allowed working pressure is located on the rating plate.
Input
MBH
(Note 4)
Gross
Output
MBH
(Note 1)
Notes:
1. e ratings are based on standard test procedures prescribed by the United States Department of Energy.
Net
AHRI
Ratings
Water,
MBH
(Note 2)
Boiler Water
Content
Gallons
3.41-1/2"1"4"
4.21-1/2"1"4"
4.22"1"4"
5.02"1"4"
5.72"1"4"
Water
Connections
Gas
Connections
Air Size
2. Net AHRI ratings are based on net installed radiation of su cient quantity for the requirements of the building and nothing
need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
3. Standard Outdoor Knight XL boilers are equipped to operate from sea level to 4,500 feet only with no adjustments. e boiler
will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet.
4. Ratings have been con rmed by the Hydronics Section of AHRI.
5. Outdoor Knight XL boilers comply with the requirements of CSD-1 Section CW-400 requirements as a temperature operation
control. e manual reset high limit provided with the Outdoor Knight XL is listed to UL353.
7
Outdoor Knight XL Installation & Operation Manual
1 Determine boiler location
Installation must comply with:
• Local, state, provincial, and national codes, laws, regulations,
and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1, when required.
• National Electrical Code.
NOTICE
WARNING
WARNING
WARNING
Table 1A - Ambient Temperature
ModelKit Number
OK 151/211
OA 151/200
OK/OA 2861001576725°F
OK/OA
501 - 801
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Gas supply piping
• Electrical power
2. - Keep venting areas free of obstructions.
- Keep area clean and free of combustible and ammable
materials.
- To avoid a blocked air inlet or blocked ue condition,
keep the outdoor air inlet and ue outlet clear or leaves,
debris, etc.
8
e Outdoor Knight XL gas manifold
and controls met safe lighting and other
performance criteria when the boiler
underwent tests speci ed in ANSI Z21.13 –
latest edition.
Outdoor models must be installed outdoors
only and must use the outdoor vent
assembly supplied by the manufacturer.
Personal injury or product damage may
result if any other venting is used or if an
outdoor model is used indoors. All covers,
doors and jacket panels must be properly
installed to ensure proper operation and
prevent a hazardous condition.
This product contains a condensate
management and disposal system that
may be subject to freezing if exposed
to sustained temperatures below 32°F.
Precautions should be taken to protect
the condensate trap and drain lines during
extended periods of outdoor temperatures
below 32°F. Consult the manufacturer
(and see Table 1A below) for an optional
condensate trap kit recommended for areas
which may experience temperatures below
32°F. Note: is condensate option is only
available for Models OK 151 - 286 and
501 - 801.
Model OK 400 is NOT suitable for
installation in areas which may experience
temperatures below 32°F.
Requirements
Minimum Allowable
Ambient Temperature
1001576715°F
100157673
10°F (OK/OA 501)
5°F (OK/OA 601 - 801)
CAUTION
CAUTION
CAUTION
CAUTION
WARNING
3. Check area around the boiler. Remove any combustible
materials, gasoline and other ammable liquids.
WARNING
4. If a new boiler will replace an existing boiler, check for
and correct system problems, such as:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Debris le from existing piping, if not ushed and
cleaned with an appropriate cleaner.
Do not install outdoor models directly on
the ground. You must install the outdoor
unit on a level concrete, brick, block, or
pressure-treated wood platform.
Do not locate unit so that high winds can
de ect o of adjacent walls, buildings
or shrubbery causing recirculation.
Recirculation of ue products may cause
operational problems, bad combustion or
damage to controls. Locate unit at least
3 feet (0.91m) from any wall or vertical
surface to prevent wind conditions from
a ecting performance.
e unit must not be installed in an area
that is enclosed by walls or a fence that
will block free wind movement around
the appliance. Free movement of wind
around the outdoor unit is required
to carry away the ue products and
provide combustion air. e ue outlet/
combustion air inlet of an outdoor unit
must not be installed closer than 10 feet
from an inside corner of an L-shaped
structure. Walls or enclosed fencing may
cause eddy currents which can recirculate
the ue products into the combustion
air inlet. Recirculation of ue products
may cause operational problems, bad
combustion or non-warrantable damage
to controls.
Locate the unit at least 3 feet (0.91m)
outside any overhang.
Do not install in locations where rain from
building runo drains will spill onto the
unit.
Do not locate the unit so that water
from sprinklers may spray directly onto
it. Water may damage controls or other
electrical components.
Do not install the unit under a deck.
Do not install the unit in a well, stairwell,
alcove, courtyard or other recessed area.
Do not install outdoor units on stack
frames. Failure to comply with the above
may result in severe personal injury, death
or substantial property damage.
Failure to keep boiler area clear and free
of combustible materials, gasoline, and
other ammable liquids and vapors can
result in severe personal injury, death, or
substantial property damage.
1 Determine boiler location (continued)
• is unit is not intended for installations where
temperatures may reach below 32°F (0°C). Exposure to
freezing temperatures will cause the system and boiler to
freeze and leak.
5. Check around the boiler for any potential air
contaminants that could risk corrosion to the boiler or
the boiler combustion air supply (see Table 1B). Prevent
combustion air contamination. Remove any of these
contaminants from the boiler area.
WARNING
DO NOT install units in rooms or
environments that contain corrosive
contaminants (see Table 1B). Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
Provide clearances:
Clearances from combustible materials
1. Hot water pipes—at least 1/4" (6 mm) from combustible
materials.
2. Jacket—minimum of 0" from right side and 14" from rear
side for proximity from combustible materials.
3. Vent—minimum of 1" from combustible materials.
Clearances for service access
1. If you do not provide the minimum clearances shown, it
may not be possible to service the boiler without removing
it from the space.
To prevent recirculation of the ue products into the
combustion air inlet, follow all instructions in this section.
Flue gas condensate can condense on exterior walls or on the
vent. Some discoloration or exterior building or unit surfaces
can be expected. Adjacent brick or masonry surfaces should
be protected with a rust resistant sheet metal plate.
Maintain a minimum of 24" clearance to the air inlet.
Locate the outdoor vent termination at least 48" (1.22m)
below and 48" (1.22m) horizontally from any window, door,
walkway or gravity air intake.
Locate the unit at least 10 feet (3.05m) away from any forced
inlet.
Multiple unit outdoor installations require 24" (1.22m)
clearance between each vent termination.
Clearances around outdoor installations can change with
time. Do not allow the growth of trees, shrubs or other plants
to obstruct the proper operation of the outdoor vent system.
e ue products discharged from the
ue outlet on the outdoor vent may be
very hot. Avoid touching or making other
direct contact with the ue gases or the
vent termination. ese components are
hot and direct contact can result in burns.
Flooring and foundation
Flooring
e Outdoor Knight XL is approved for installation on
combustible ooring.
WARNING
Under no circumstances is the manufacturer to be held
responsible for water damage in connection with this
appliance, or any of its components. If ooding is possible,
elevate the boiler su ciently to prevent water from reaching
the boiler.
Prevent combustion air contamination
Do not install unit in locations that can allow contamination
of combustion air. Refer to Table 1B for products and areas
which may cause contaminated combustion air.
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water so ening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric so eners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
Adhesives used to fasten building products and other
similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture re nishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Outdoor Knight XL Installation & Operation Manual
Do not install the boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death, or
substantial property damage.
9
2 Prepare boiler
Outdoor Knight XL Installation & Operation Manual
Remove boiler from wood pallet
1. A er removing the outer shipping carton from the
boiler, remove the parts box.
2. Remove the front door to access the lag bolts in front
of the unit (FIG. 2-1).
3. To remove the boiler from the pallet (a er removing
the front door):
a. Remove the two lag bolts from the wood pallet
inside the boiler (FIG. 2-1).
b. Detach the boiler from the lag bolts in the rear of the
unit, see FIG. 2-1.
NOTICE
Figure 2-1 Boiler Mounted on Shipping Pallet
Do not drop the boiler or bump the
jacket on the oor or pallet. Damage to
the boiler can result.
Install fl ue pipe assembly
Models 400 - 601
is unit is provided with all of the necessary venting
components. All components must be installed prior to
operation.
1. Locate all venting components from the installation kit
and carton.
2. Before connecting the vent pipe sections or components,
verify that the gasket is seated evenly inside the groove in
the female end of the elbow and ue adaptor (FIG. 2-2).
3. Remove the provided screws from the vent cover and use
them to install the vent strap (FIG. 2-2).
4. Insert the elbow into ue adaptor (FIG. 2-2).
CAUTION
5. Slide the vent pipe through the wall strap and insert it
into the elbow (FIG. 2-2).
6. Install the bird screen into the top of the vent.
Do NOT use grease or other lubricant
on the vent seals. Only water may be
used for this purpose. Grease or other
lubricant can make the seal brittle or
cause tearing of the seal surface which
can result in ue gas leakage.
1. Locate all venting components from the installation kit and
carton.
2. Before connecting the vent pipe sections or components,
verify that the gasket is seated evenly inside the
groove in the female end of the elbow and ue adapter
(FIG. 2-3).
3. Remove the vent cover from the back of the unit as shown in
FIG. 2-3.
4. Insert the elbow into the ue adapter and tighten the clamp
using a 5/16" nut driver (FIG. 2-3).
5. Re-install the vent cover removed in Step 3.
6. Remove the provided screws from the vent cover and use
them to install the wall strap (FIG. 2-3).
Outdoor Knight XL Installation & Operation Manual
CAUTION
7. Slide the vent pipe through the wall strap and insert it into the
elbow. Tighten the clamp (FIG. 2-3).
8. Install the termination into the top of the vent and tighten the
clamp.
Do NOT use grease or other lubricant on the
vent seals. Only water may be used for this
purpose. Grease or other lubricant can make
the seal brittle or cause tearing of the seal
surface which can result in ue gas leakage.
11
2 Prepare boiler
Gas conversions
Outdoor Knight XL Installation & Operation Manual
WARNING
For a boiler already installed, you must
turn o gas supply, turn o power and
allow boiler to cool before proceeding.
You must also completely test the boiler
a er conversion to verify performance
as described under Start-up, Section 10
of this manual. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
For the 400 Model you must install a
propane ori ce to operate the Outdoor
Knight XL on propane gas. Verify when
installing that the ori ce size marking
matches boiler size (Model 400 - 8.0 LP
ori ce stamping).
Models 501 - 801 do not require an ori ce
installation for propane operation, but
they will require a valve adjustment.
Model 400
1. Remove the top and front access covers from the unit
(tools required for removal).
2. Remove the three screws securing the venturi to the
blower. Note: When separating the venturi from the
blower, take care not to damage the O-ring inside the
blower (FIG. 2-4).
3. Remove the four star-drive screws securing the gas valve
to the venturi (FIG. 2-4).
4. Locate the propane ori ce disk from the conversion kit
bag.Verify that the stamping on the ori ce disk matches
the boiler size (Model 400 - 8.0 LP ori ce stamping).
5. Remove the existing ori ce from the O-ring in the side of
the gas valve and replace it with the ori ce from the kit.
Position and secure the ori ce in the valve as shown in
FIG. 2-4.
6. Reposition the gas valve against the venturi and replace
the star-drive screws (FIG. 2-4) securing the valve to the
venturi.
7. Inspect the O-ring inside the blower. Handle the O-ring
with care, do not damage. Reposition the venturi against
the blower and replace the screws securing the venturi to
the blower (FIG. 2-4).
8. A er installation is complete, attach the propane
conversion label (in the conversion kit bag) next to the
boiler rating plate. Attach the LP caution label (in the
conversion kit bag) to the le side of the unit in the lower
le corner.
9. Replace the top and front access covers.
WARNING
A er converting to LP, check combustion
per the Start-up procedure in Section 10
of this manual. Failure to check and verify
combustion could result in severe personal
injury, death, or substantial property damage.
DANGER
Model 400: Inspect the O-ring when the
blower is disassembled. e O-ring must
be in good condition and must be installed.
Failure to comply will cause a gas leak,
resulting in severe personal injury or death.
Figure 2-4 Installing Propane Orifi ce - Model 400
BLOWER
SCREWS
QTY. 4
O-RING
O-RING
BRASS ORIFICE
VENTURI
SCREWS
QTY. 3
GAS VALVE
12
2 Prepare boiler (continued)
Outdoor Knight XL Installation & Operation Manual
Model 501
1. Remove the top access cover from the unit (Philips Head
screwdriver required for removal).
2. Turn the adjustment screw on the gas valve clockwise until
it stops. en turn the adjustment screw counterclockwise
four and three quarter (4 3/4) turns (see FIG. 2-5).
3. Use a combustion analyzer to verify CO2 is within the range
of 9.6 – 10.5%. If not, adjust the screw counterclockwise
incrementally to raise CO2 and clockwise to lower CO2
(FIG. 2-5).
4. A er adjustment is complete, attach the propane conversion
label (in the conversion kit bag) next to the boiler rating
plate. Attach the LP caution label (in the conversion kit bag)
to the le side of the unit in the lower le corner.
5. Replace the top access cover.
WARNING
Figure 2-5 Gas Valve Adjustment - Model 501
A er converting to LP, check combustion
per the Start-up procedure in Section 10
of this manual. Failure to check and verify
combustion could result in severe personal
injury, death, or substantial property
damage.
WARNING
A er converting to LP, check combustion
per the Start-up procedure in Section
10 of this manual. Failure to check and
verify combustion could result in severe
personal injury, death, or substantial
property damage.
Figure 2-6 Gas Valve Adjustment - Models 601 - 801
COVER
ALLEN WRENCH
ADJUSTMENT SCREW
ALLEN WRENCH
ADJUSTMENT SCREW
Models 601 - 801
1. Remove the top access cover from the unit (Philips Head
screwdriver required for removal).
2. Remove the cover on top of the gas valve (FIG. 2-6).
3. Turn the adjustment screw on top of the gas valve clockwise
one and three quarter (1 3/4) turns on the 601 Model, one
and a half (1 1/2) turns on the 701 Model, and one turn on
the 801 Model (see FIG. 2-6).
4. Use a combustion analyzer to verify CO
of 9.6 – 10.5%. If not, adjust the screw counterclockwise
incrementally to raise CO2 and clockwise to lower CO2
(FIG. 2-6).
5. A er adjustment is complete, attach the propane conversion
label (in the conversion kit bag) next to the boiler rating
plate. Attach the LP caution label (in the conversion kit
bag) to the le side of the unit in the lower le corner.
6. Replace the gas valve cover along with the top access cover.
is within the range
2
Leveling the boiler
1. Set the boiler in place and check level.
a) Adjust legs if necessary to level boiler, see FIG. 2-7
below.
Figure 2-7 Leveling Legs on the Boiler
SCREWDRIVER
SLOT
LOWER
RAISE
13
Outdoor Knight XL Installation & Operation Manual
3 Hydronic piping
System water piping methods
e Outdoor Knight XL is designed to function in a closed
loop pressurized system not less than 12 psi (83 kPa) (Nonmetallic system piping must have an oxygen barrier to be
considered a closed loop). A temperature and pressure
gauge is included to monitor system pressure and outlet
temperature and should be located on the boiler outlet.
It is important to note that the boiler has a minimal amount
of pressure drop which must be gured in when sizing
the circulators. Each boiler installation must have an air
elimination device, which will remove air from the system.
Install the boiler so the gas ignition system components
are protected from water (dripping, spraying, etc.) during
appliance operation or basic service of circulator replacement,
valves, and others.
Observe a minimum of 1/4 inch (6 mm) clearance around all
un-insulated hot water pipes when openings around the pipes
are not protected by non-combustible materials.
Low water cutoff device
On a boiler installed above radiation level, some states and
local codes require a low water cuto device at the time of
installation.
Chilled water system
If the boiler supplies hot water to heating coils in air handler
units, ow control valves or other devices must be installed to
prevent gravity circulation of heater water in the coils during
the cooling cycle. A chilled water medium must be piped in
parallel with the heater.
Freeze protection
Freeze protection for new or existing systems must use
glycol that is specially formulated for this purpose. is
includes inhibitors, which prevent the glycol from attacking
the metallic system components. Make certain to check that
the system uid is correct for the glycol concentration and
inhibitor level. e system should be tested at least once
a year and as recommended by the producer of the glycol
solution. Allowance should be made for the expansion of the
glycol solution in the system piping.
WARNING
14
Use only inhibited propylene glycol
solutions, which are speci cally formulated
for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used
in hydronic systems.
General piping information
Basic steps are listed below along with illustrations on the
following pages (FIG.’s 3-7 through 3-11), which will guide
you through the installation of the Outdoor Knight XL
(reference FIG.’s 3-4A and 3-4B).
1. Connect the system return marked “Inlet”.
2. Connect the system supply marked “Outlet”.
3. Install purge and balance valve or shuto valve and drain
on system return to purge air out of each zone.
4. Install a back ow preventer on the cold feed make-up
water line.
5. Install a pressure reducing valve on the cold feed make-up
water line, (15 psi (103 kPa) nominal). Check temperature
and pressure gauge (shipped separately), which should
read a minimum pressure of 12 psi (83 kPa).
6. Consult the factory for a pump and/or pump cover. If a
eld-supplied pump is used, install per the manufacturer’s
speci cations in regard to indoor or outdoor location. An
outdoor rated pump is recommended.
7. Install a circulator as shown on the piping diagrams in this
section. Make sure the circulator is properly sized for the
system and friction loss.
8. Install an expansion tank on the system supply. Consult the
tank manufacturer’s instruction for speci c information
relating to tank installation. Size the expansion tank for the
required system volume and capacity.
9. Install an air elimination device on the system supply.
10. Install a drain valve at the lowest point of the system.
Note: e boiler cannot be drained completely of water
without purging the unit with an air pressure of 15 psi
(103 kPa).
11. is appliance is supplied with a relief valve sized in
accordance with ASME Boiler and Pressure Vessel Code,
Section IV (“Heating Boilers”). Pipe the discharge of the
safety relief valve to prevent injury in the event of pressure
relief. Pipe the discharge to a drain. Provide piping that is
the same size as the safety relief valve outlet. Never block
the outlet of the safety relief valve.
WARNING
12. Install a eld supplied strainer to prevent damage to
the heat exchanger caused by debris entering from the
system piping. When installing in a pre-existing system, a
strainer/ lter capable of removing debris le in the system
is recommended.
See the piping illustrations included in this section, FIG.’s
3-7 and 3-11 for suggested guidelines in piping the Outdoor
Knight XL.
NOTICE
e relief valve, tee and any other necessary
ttings are shipped in the install kit with the
boiler and are to be eld installed (FIG.’s
3-1 and 3-2).
Please note that these illustrations are
meant to show system piping concept only,
the installer is responsible for all equipment
and detailing required by local codes.
3 Hydronic piping (continued)
Outdoor Knight XL Installation & Operation Manual
Flow switch, relief valve and temperature
and pressure gauge installation
Basic steps are listed below to guide you through the
installation of the ow switch, relief valve, and temperature
and pressure gauge provided with the unit.
1. For Models 400 - 501 install the close nipple on the
outlet connection of the heat exchanger. Install the tee
with the 3/4 inch tting positioned vertically and on
the top as shown in FIG. 3-1. For Models 601 - 801
install the tee directly to the outlet connection of the
heat exchanger with the 3/4 inch tting positioned
vertically and on the top (see FIG. 3-2).
2. For Models 701 - 801 install the 3/4 inch close nipple
in the tee. Install the relief valve on the 3/4 inch close
nipple (FIG. 3-2). For Models 400 - 601 install the
relief valve directly into the 3/4 inch tting on the tee
(FIG. 3-1).
3. Install the close nipple on the downstream side of
the relief valve tee (FIG. 3-1).
4. Install the tee with the 1 inch tting positioned
vertically and on the top (FIG. 3-1).
5. Attach paddle #3 to the ow switch per the
manufacturer’s instructions.
6. Install the assembled ow switch into the 1 inch tting
of the tee installed in Step 4 (see FIG. 3-1).
7. Install a eld provided close nipple on the downstream
side of the ow switch (see FIG.’s 3-1 and 3-2).
8. Install a eld provided tee with the gauge tting
positioned vertically and on the top (FIG.’s 3-1 and
3-2)
9. Install the temperature and pressure gauge provided
with the unit into the top tting of the tee (a bushing
may be necessary) installed in Step 8 (FIG.’s 3-1 and
3-2).
Figure 3-1 Flow Switch, Relief Valve and Temperature and
Pressure Gauge Installation_Models 400 - 501
Figure 3-2 Flow Switch, Relief Valve and Temperature and
Pressure Gauge Installation_Models 601 - 801
NOTICE
Be sure to install the ow switch so
that the arrow on the ow switch is
pointing in the direction of the ow
(see FIG. 3-3).
15
3 Hydronic piping
Outdoor Knight XL Installation & Operation Manual
Flow switch adjustment
Refer to Table 3A for the proper setting of the sensitivity
screw. For reference, the position of the screw prior to setting
should be turned clockwise with a Phillips driver until it stops
(FIG. 3-3). Proceed to turn the screw counterclockwise the
amount of turns listed in Table 3A based on the model.
Consult the manufacturer’s instructions for wiring the ow
switch to your system.
Turn the sensitivity screw clockwise to
increase the ow rate required to activate
the switch. Turn the sensitivity screw
counterclockwise to decrease the ow rate
required to activate the switch.
Figure 3-3 Flow Switch Adjustment
SENSITIVITY SCREW
ADJUSTMENT
NORMALLY
OPEN
SENSITIVITY
ADJUSTMENT
Near boiler piping components
1. Boiler system piping:
Boiler system piping MUST be sized per the pipe
requirements listed in Table 3B. Reducing the pipe size
can restrict the ow rate through the boiler, causing
inadvertent high limit shutdowns and poor system
performance. Flow rates are based on 20 feet (6 m) of
piping, 4 - 90° elbows, and 2 - fully ported ball valves.
2. Boiler system circulating pump:
(Field supplied.) e boiler circulating pump should be
based on 20 feet (6 m) of piping, 4 - 90° elbows, and
2 - fully ported ball valves.
3. Domestic hot water circulating pump:
(Field supplied.) e pump MUST be sized to meet
the speci ed minimum ow requirements listed in
FIG.’s 3-5 and 3-6. Consult the indirect water heater
operating guide to determine ow characteristics for the
selected product used.
4. Variable speed boiler system circulator:
Outdoor Knight XL boilers are capable of controlling
a variable speed boiler system circulator. Variable speed
circulators MUST be sized to meet the speci ed minimum
ow requirements listed in FIG.’s 3-5 and 3-6 on page 16
at full speed.
5. Boiler isolation valves:
Field supplied. Full port ball valves are required. Failure
to use full port ball valves could result in a restricted ow
rate through the boiler.
GROUND
16
COMMON
NORMALLY
CLOSED
6. Check valves:
Field supplied. Check valves are recommended for
installation as shown in FIG.’s 3-7 through 3-11. Failure
to install check valves could result in a reverse ow
condition during pump(s) o cycle.
7. Domestic indirect hot water isolation valves:
Field supplied. Full port ball valves are required. Failure
to use full port ball valves could result in a restricted ow
rate through the boiler.
8. Anti-scald mixing valve:
Field supplied. An anti-scald mixing valve is
recommended when storing domestic hot water above
115°F (46°C).
9. Unions:
Field supplied. Recommended for unit serviceability.
10. Temperature and pressure gauge:
Factory supplied. e temperature and pressure gauge is
shipped loose. It is the responsibility of the contractor to
install the temperature and pressure gauge on the boiler
water outlet.
11. Pressure relief valve:
Factory supplied. e pressure relief valve is sized to
ASME speci cations.
3 Hydronic piping (continued)
Outdoor Knight XL Installation & Operation Manual
12. Boiler purge valve:
Field supplied. e boiler purge valve is used to
remove entrapped air from the heat exchanger during
start-up.
13. System temperature sensor:
Lochinvar supplies a system temperature sensor. e
sensor is to be installed in the heating loop downstream
from the boiler hot water piping and heating loop
junction. e sensor should be located far enough
downstream to sense system diluted water temperature.
14. Water Meter:
Field supplied. A water meter to monitor makeup water is
recommended. Makeup water volume should not exceed
5% of total system per year.
15. Y-Strainer:
Field supplied. Install a Y-strainer or equivalent multi purpose strainer just before the boiler pump at the inlet
of the heat exchanger. is item is used to remove system
debris from older hydronic systems and to protect newer
systems.
Circulator sizing
Figure 3-4B Near Boiler Piping w/Low Loss Header
WATER
METER
O
T
S
M
M
O
E
R
T
F
S
Y
S
FAST FILL VALVE
EXPANSION TANK
INDIRECT
DOMESTIC
M
O
R
HOT WATER
F
TANK
O
T
T
S
Y
LOW LOSS HEADER
(TYPICAL)
Y-STRAINER
FLOW CHECK
VALVE
BOILER PUMP
SYSTEM PUMP
SYSTEM SENSOR
AIR SEPARATOR
DRAIN
(TYPICAL)
AIR VENT VALVE
DRAIN
VALVE
M
E
e Outdoor Knight XL heat exchanger does have a pressure
drop, which must be considered in your system design. Refer
to the graphs in FIG’s 3-5 and 3-6 for pressure drop through
the Outdoor Knight XL heat exchanger.
Near boiler piping connections
Figure 3-4A Near Boiler Piping w/Y-Strainer
WATER
SYSTEM SENSOR
AIR SEPARATOR
SYSTEM PUMP
O
T
M
E
T
S
Y
S
BOILER PUMP
METER
Y-STRAINER
M
M
O
E
R
F
ST
Y
S
DOMESTIC HOT
WATER PUMP
O
R
F
O
T
DIR #2000548018 00
INDIRECT
M
DOMESTIC
HOT WATER
TANK
TO FLOOR
DRAIN
DIR #2000547995 00
Variable speed pump option
Variable speed pump setup
Before operation, ensure the following:
- Pump is set for an input signal of 0 - 10VDC
by the dip switches on the pump control
- Pump is set for external signal control
(if applicable)
- Pump is set for linear output (if applicable)
- If pump does not come equipped with a
0 - 10 VDC input option, an optional module
will be required from the vendor
SMART SYSTEM / Multi-temperature
loop control option
e Outdoor Knight XL boiler is capable of producing
up to three (3) set point temperatures to meet di erent
space heating demands. When using more than one
temperature demand it is necessary to protect the
lower temperature loop from overheating. To help
aid with this protection, Lochinvar o ers the MultiTemperature Loop Control Board Kit (100167843).
17
0
2
4
6
8
10
12
14
16
18
20
051015202530354045
KBN501
KBN400
0
10
20
30
40
50
60
0 102030405060708090
KBN801
KBN701
KBN601
3 Hydronic piping
Figure 3-5 Pressure Drop vs. Flow - Models 400 and 501
Pressure Drop vs Flow
(Includes Boiler Secondary Piping)
Pressure Drop (Feet of Head)
Flow Rate (GPM)
Outdoor Knight XL Installation & Operation Manual
O
O
Figure 3-6 Pressure Drop vs. Flow - Models 601 thru 801
Pressure Drop vs Flow
(Includes Boiler Secondary Piping)
Pressure Drop (Feet of Head)
Flow Rate (GPM)
Table 3B Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F
Model
4001 1/2"372130142611218
5011 1/2"4623371632132610
6012"5531442238183213
7012"6530522045163711
8012"7433602351184212
18
MINIMUM
PIPE
SIZE
TEMPERATURE RISE APPLICATIONS
20°F 25°F30°F35°F
GPMFT/HDGPMFT/HDGPMFT/HDGPMFT/HD
O
O
O
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.