This manual must only be used
by a qualified heating installer
/ service technician. Read all
instructions in this manual before
installing. Perform steps in the
order given. Failure to comply
could result in severe personal
injury, death, or substantial
property damage.
Ladder Diagram (Standard)_Combi Only ..................................... 95
Wiring Diagram (Standard)_Combi Only ..................................... 96
Ladder Diagram (Standard)_Boiler Only .......................................97
Wiring Diagram (Standard)_Boiler Only .......................................98
Revision Notes .................................................................... Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or
to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate
injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not
avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not
related to personal injury or property damage.
Please read before proceeding
FIRE TUBE
™
Installation & Service Manual
WARNING
NOTICE
WARNING
WARNING
Installer – Read all instructions, in this
manual before installing. Perform steps
in the order given.
User – This manual is for use only
by a qualified heating installer/
service technician. Refer to the User’s
Information Manual for your reference.
Have this boiler serviced/inspected by
a qualified service technician, at least
annually.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
When calling or writing about the boiler
– Please have the boiler model and serial
number from the boiler rating plate.
Consider piping and installation when
determining boiler location.
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by
the consignee.
Factory warranty (shipped with unit) does
not apply to units improperly installed or
improperly operated.
Failure to adhere to the guidelines on this
page can result in severe personal injury,
death, or substantial property damage.
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
This appliance MUST NOT be installed in
any location where gasoline or flammable
vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
WARNING
DO NOT install units in rooms or
environments that contain corrosive
contaminants (see Table 1A on page 10).
Failure to comply could result in severe
personal injury, death, or substantial
property damage.
When servicing boiler –
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
• To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut off,
do not turn off or disconnect electrical supply to
circulator. Instead, shut off the gas supply at a location
external to the appliance.
• Do not use this boiler if any part has been under water.
The possible damage to a flooded appliance can be
extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
Boiler water –
• Thoroughly flush the system to remove debris. Use
an approved pre-commissioning cleaner (see Start-Up
Section), without the boiler connected, to clean the
system and remove sediment. The high efficiency heat
exchanger can be damaged by build-up or corrosion
due to sediment.
NOTE: Cleaners are designed for either new systems or
pre-existing systems. Choose accordingly.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are specifically
formulated for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used in hydronic
systems.
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a near by phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
• Installation and service must be
performed by a qualified installer,
service agency, or the gas supplier.
3
™
FIRE TUBE
Installation & Service Manual
The Noble Fire Tube - How it works...
1. Heat exchanger
Allows system water to flow through specially designed
coils for maximum heat transfer, while providing
protection against flue gas corrosion. The coils are
encased in a jacket that contains the combustion process.
2. Blower
The blower pulls in air and gas through the venturi (item
5). Air and gas mix inside the blower and are pushed into the
burner, where they burn inside the combustion chamber.
3. Gas valve
The gas valve senses the negative pressure created by the
blower, allowing gas to flow only if the gas valve is
powered and combustion air is flowing.
4. Venturi
The venturi controls air and gas flow into the burner.
5. Flue gas sensor (limit rated)
This sensor monitors the flue gas exit temperature. The control
module will modulate and shut down the boiler if flue gas
temperature gets too hot. This protects the flue pipe from
overheating.
6. Boiler outlet temperature sensor (limit rated)
This sensor monitors boiler outlet water temperature (system
supply). The control module will adjust boiler firing rate so the
outlet temperature is correct.
7. Boiler inlet temperature sensor
This sensor monitors return water temperature (system
return).
8. Temperature and pressure gauge (field installed, not
shown)
Monitors the outlet temperature of the boiler as well as the
system water pressure.
9. Electronic LCD display
The electronic display consists of five (5) buttons, and a liquid
crystal display. The display is used to make adjustments and
read boiler status.
10. Flue pipe adapter
Allows for the connection of the vent pipe system to the
boiler.
11. Burner (not shown)
Made with metal fiber and stainless steel construction,
the burner uses pre-mixed air and gas and provides a
wide range of firing rates.
12. Boiler water outlet
The boiler water outlet is the boiler water connection for water
leaving the boiler and entering the system.
13. Domestic Hot Water (DHW) water outlet (Combi Only)
The DHW water outlet is the water connection for domestic water
leaving the boiler and entering the system.
14. Boiler water inlet
The boiler water inlet is the boiler water connection for water
entering the boiler from the system.
15. Domestic Hot Water (DHW) water inlet (Combi Only)
The DHW water inlet is the water connection for domestic water
entering the boiler from the system.
16. Gas connection pipe
Threaded pipe connection of 1/2". This pipe should be
connected to the incoming gas supply for the purpose of
delivering gas to the boiler.
17. Boiler control module
The boiler control responds to internal and external signals
and controls the blower, gas valve, and pumps to meet the
demand.
18. Air intake adapter
Allows for the connection of the air intake pipe to
the boiler.
19. High voltage junction box
The junction box contains the connection points for the line
voltage power and all pumps.
20. Low voltage connection board
The connection board is used to connect external low voltage
devices.
21. Low voltage wiring connections
Conduit connection points for the low voltage
connection board.
22. Condensate drain connection
The condensate drain connection provides a connection
point to install a condensate drain line.
23. Front access cover
Provides access to all internal components.
24. Ignition / flame sense electrode
Used by the control module to detect the presence of burner
flame.
25. Flame inspection window
The quartz glass window provides a view of the burner
surface and flame.
26. Relief valve
Protects the heat exchanger from an over pressure condition.
The relief valve provided with the unit is set at 50 psi on Combi
models and 30 psi on Boiler models.
27. Line voltage wiring connections (inside junction box)
Conduit connection points for the high voltage junction box.
28. Air pressure switch
The air pressure switch detects blocked conditions.
29. Transformer
The transformer provides 24V power to the integrated control.
30. Pump (Combi Only)
Provides flow through the unit for space heating and domestic
water applications. Serves as the boiler and DHW pump.
31. Diverter valve (Combi Only)
Diverts boiler water from the heating loop to the DHW heat
exchanger.
32. DHW Flow switch (Combi Only)
The DHW flow switch detects a DHW draw and signals the
boiler to fire.
33. Domestic Hot Water (DHW) sensor (Combi Only)
This sensor monitors DHW water temperature.
The control module will adjust boiler firing rate so the
DHW temperature is correct.
34. Condensate trap
The condensate trap is sized for a 3/4" PVC outlet connection
pipe. Note: The Noble Combi trap is factory installed whereas the Noble Boiler trap is factory supplied, but field
installed.
4
™
FIRE TUBE
Installation & Service Manual
The Noble Fire Tube - How it works... (continued)
NOTICE
18
2
23
9
Front Outside View
The Noble Combi Boiler is shown throughout the manual unless otherwise noted.
Bottom View - Boiler Only
10
26
16
LEFTRIGHT
FRONT
19
BACK
13
12
16
DIR #2000528036
LEFTRIGHT
Bottom View - Combi Only
FRONT
21
14
12
22
21
15
14
19
DIR #2000528036 00
5
28
29
BACK
22
1
27
DIR #2000528036 00
Front Inside View
Side_Rear View
5
Ratings
A
S
M
E
H
FIRE TUBE
™
Installation & Service Manual
LOW LEAD CONTENT
AHRI Rating
Model Number
Note: Change “N”
to “L” for L.P. gas
models.
NKB80N8.380746495.0
NK(B,C)110N111101028995.0
NK(B,C)150N1515013912195.0
NK(C)199N2019918516195.0
NOTICE
Input
MBH
(Note 5)
Min
Max
Maximum allowed working pressure is located on the rating plate.
Heating
Capacity
MBH
(Note 2, 7)
Notes:
1. As an Energy Star Partner, the manufacturer has determined
that Noble Fire Tubes meet the Energy Star guidelines for
energy efficiency.
2. The ratings are based on standard test procedures prescribed
by the United States Department of Energy.
3. Net AHRI ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.
4. Noble Fire Tubes require special gas venting. Use only the
vent materials and methods specified in the Noble Fire Tube
Installation and Service Manual.
5. Standard Noble Fire Tubes are equipped to operate from sea
level to 4,500 feet only with no adjustments. The boiler will
de-rate by 4% for each 1,000 feet above sea level up to 4,500
feet.
6. High altitude Noble Fire Tubes are equipped to operate from
3,000 to 9,600 feet. e boiler will de-rate 1.7% between
5,000 to 9,600 feet. For any units installed past 9,600 feet
there is an additional de-rate of 4% per 1,000 feet beyond
9,600 feet per the National Fuel Gas Code. Appliances
con gured for high altitude shall not be installed below 3000
feet.
The operation given in this manual remains the same as the
standard boilers. A high altitude label (as shown in FIG. A)
is also affixed to the unit.
De-rate values are based on proper combustion calibration
and
CO2’s adjusted to the recommended levels.
For installations above 9,600 feet, please consult the factory.
Net
AHRI
Ratings
Water,
MBH
(Note 3, 7)
6
AFUE
%
(Note 1, 7)
Other Specifications
SH Water
Boiler Water
Content Gallons
1.21"--1/2"3"
1.41"3/4"1/2"3"
2.01"3/4"1/2"3"
2.71"3/4"1/2"3"
Connections
NPT = Combi
Sweat = Boiler
7. Ratings have been confirmed by the Hydronics Institute,
Section of AHRI.
8. The manual reset high limit provided with the Noble Fire
Tube is listed to UL353.
UNIT EQUIPPED FOR
HIGH ALTITUDE
3,000 FT. TO 9,600 FT.
Figure A High Altitude Label Location (Combi Only)
Note: Combi models approved for high altitude. Not
available on Boiler models.
DHW Water
Connections
Combi Only
Gas
Connections
Vent/Air
Size
(Note 4)
1 Determine boiler location
FIRE TUBE
™
Installation & Service Manual
Installation must comply with:
• Local, state, provincial, and national codes, laws,
regulations, and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• National Electrical Code.
• For Canada only: B149.1 Installation Code, CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
NOTICE
The Noble Fire Tube gas manifold and
controls met safe lighting and other
performance criteria when the boiler
underwent tests specified in ANSI Z21.13
– latest edition.
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the
appliance. The pan must not restrict combustion air
flow. Under no circumstances is the manufacturer to be
held responsible for water damage in connection with
this appliance, or any of its components.
3. Check area around the boiler. Remove any combustible
materials, gasoline and other flammable liquids.
WARNING
4. The Noble Fire Tube must be installed so that gas control
system components are protected from dripping or
spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check for
and correct system problems, such as:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing system
and boiler to freeze and leak.
• Debris left from existing piping, if not flushed and
cleaned with an appropriate cleaner.
6. Check around the boiler for any potential air
contaminants that could risk corrosion to the boiler or
the boiler combustion air supply (see Table 1A on page
10). Prevent combustion air contamination. Remove
any of these contaminants from the boiler area.
WARNING
Failure to keep boiler area clear and free
of combustible materials, gasoline, and
other flammable liquids and vapors can
result in severe personal injury, death, or
substantial property damage.
DO NOT install units in rooms or
environments that contain corrosive
contaminants (see Table 1A on page 10).
Failure to comply could result in severe
personal injury, death, or substantial
property damage.
WARNING
WARNING
This appliance is certified as an indoor
appliance. Do not install the appliance
outdoors or locate where the appliance will
be exposed to freezing temperatures or to
temperatures that exceed 100°F.
Failure to install the appliance indoors
could result in severe personal injury,
death, or substantial property damage.
This appliance requires a special venting
system. The vent connection to the
appliance is made of CPVC. Field supplied
vent fittings must be cemented to the CPVC
fitting on the boiler. Use only the vent
materials, primer, and cement specified in
the manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.
Closet and alcove installations
A closet is any room the boiler is installed in which is less
than 93 cubic feet for NKC110 models, and 102 cubic feet
for NKC150 - 199 models, and 69 cubic feet for NKB80 - 150
models.
An alcove is any room which meets the criteria for a closet
with the exception that it does not have a door.
Example: Room dimensions = 4 feet long, 3 feet wide, and
7 foot ceiling = 4 x 3 x 7 = 84 cubic feet. This would be
considered a closet for a Noble Fire Tube.
WARNING
For closet and alcove installations as
shown in FIG.’s 1-1 and 1-2, CPVC,
polypropylene or stainless steel vent
material must be used inside the structure.
The two ventilating air openings shown in
FIG. 1-1 are required for this arrangement.
Failure to follow this warning could result
in fire, personal injury, or death.
Provide clearances:
Clearances from combustible materials
1. Hot water pipes—at least 1/4" from combustible materials.
2. Vent pipe – at least 1" from combustible materials.
3. See FIG.’s 1-1 and 1-2 on page 8 for other clearance
minimums.
Clearances for service access
1. See page 9 for recommended service clearances. If you
do not provide the minimum clearances shown, it may
not be possible to service the boiler without removing it
from the space.
For closet installations, CPVC,
polypropylene, or stainless steel
vent material MUST BE used in
a closet structure due to elevated
temperatures. Failure to follow
this warning could result in fire,
personal injury, or death.
Note: Service clearances are recommendations only.
WARNING
For alcove installations, CPVC,
polypropylene, or stainless steel
vent material MUST BE used in
an alcove structure due to elevated
temperatures. Failure to follow
RIGHT
0" MINIMUM
this warning could result in fire,
personal injury, or death.
1"
OPEN DOOR
BOTTOM
0"
MINIMUM
1/4"MINIMUM CLEARANCE
AROUND HOT WATER PIPES
FRONT
6"
MINIMUM
DIR #2000534544 00
Note: Service clearances are recommendations only.
8
FIRE TUBE
1 Determine boiler location (continued)
™
Installation & Service Manual
NOTICE
Recommended clearances for service access
- Front ............................................................................. 24"
- Left ................................................................................ 12"
- Right ............................................................................. 12"
If you do not provide the recommended
service clearances shown, it may not be
possible to service the boiler without
removing it from the space.
Provide air openings to room:
Boiler alone in boiler room
1. No air ventilation openings into the boiler room are
needed when clearances around the Noble Fire Tube
are at least equal to the SERVICE clearances shown in
FIG.’s 1-1 and 1-2. For spaces that do NOT supply this
clearance, provide two openings as shown in FIG. 1-1.
Each opening must provide one square inch free area
per 1,000 Btu/hr of boiler input.
Boiler in same space with other gas or oil-fired
appliances
1. Follow the National Fuel Gas Code (U.S.) or CSA
B149.1 (Canada) to size/verify size of the combustion/
ventilation air openings into the space.
WARNING
2. Size openings only on the basis of the other appliances
in the space. No additional air opening free area is
needed for the Noble Fire Tube because it takes its
combustion air from outside (direct vent installation).
The space must be provided with
combustion/ventilation air openings
correctly sized for all other appliances
located in the same space as the Noble
Fire Tube.
Do not install the boiler in an attic.
Failure to comply with the above
warnings could result in severe personal
injury, death, or substantial property
damage.
Wall mounting location
Ensure the wall for which the boiler is intended to be
mounted is comprised of either, cement, brick, block, or
wooden studs spaced 16" apart from center. Ensure the
wall is capable of supporting at least 200 pounds.
If flooding is possible, elevate the boiler sufficiently to
prevent water from reaching the boiler.
Ensure the boiler is installed in a location that minimizes
the risk of water damage due to valves, pumps, etc.
Residential garage installation
Precautions
Take the following precautions when installing the appliance in
a residential garage. If the appliance is located in a residential
garage, it should be installed in compliance with the latest
edition of the National Fuel Gas Code, ANSI Z223.1 and/or
CAN/CGA-B149 Installation Code.
• Appliances located in residential garages and in
adjacent spaces that open to the garage and are not part
of the living space of a dwelling shall be installed so that
all burners and burner ignition devices are located not
less than 18 inches (46 cm) above the floor.
• The appliance shall be located or protected so that it is
not subject to physical damage by a moving vehicle.
Vent and air piping
The Noble Fire Tube requires a special vent system, designed for
pressurized venting.
The boiler is to be used for either direct vent installation or for
installation using indoor combustion air. When room air is
considered, see Section 3, General Venting. Note prevention of
combustion air contamination below when considering vent/
air termination.
Vent and air must terminate near one another and may be
vented vertically through the roof or out a side wall, unless
otherwise specified. You may use any of the vent/air piping
methods covered in this manual. Do not attempt to install the
Noble Fire Tube using any other means.
Be sure to locate the boiler such that the vent and air piping can
be routed through the building and properly terminated. The
vent/air piping lengths, routing and termination method must
all comply with the methods and limits given in this manual.
Prevent combustion air contamination
Install air inlet piping for the Noble Fire Tube as described in
this manual. Do not terminate vent/air in locations that can
allow contamination of combustion air. Refer to Table 1A,
page 10 for products and areas which may cause contaminated
combustion air.
WARNING
You must pipe combustion air to the boiler
air intake. Ensure that the combustion air will
not contain any of the contaminants in Table
1A, page 10. Contaminated combustion air
will damage the boiler, resulting in possible
severe personal injury, death or substantial
property damage. Do not pipe combustion
air near a swimming pool, for example.
Also, avoid areas subject to exhaust fumes
from laundry facilities. These areas will
always contain contaminants.
9
1 Determine boiler location
FIRE TUBE
™
Installation & Service Manual
Table 1A Corrosive Contaminants and Sources
Products to avoid:
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
Adhesives used to fasten building products and other
similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
When using an existing vent system to
install a new boiler:
WARNING
Check the following venting components before installing:
• Material - For materials listed for use with this appliance,
see Section 3 - General Venting.
• Size - To ensure proper pipe size is in place, see Table 3A.
Check to see that this size is used throughout the vent
system.
• Manufacturer - For a polypropylene or stainless steel
application, you must use only the listed manufacturers
and their type product listed in Tables 3E and 3G for CAT
IV positive pressure venting with flue producing
condensate.
• Supports - Non-combustible supports must be in place
allowing a minimum 1/4" rise per foot. The supports
should adequately prevent sagging and vertical slip,
by distributing the vent system weight. For additional
information, consult the vent manufacturer’s
instructions for installation.
• Terminations - Carefully review Sections 3 through 5 to
ensure requirements for the location of the vent and air
terminations are met and orientation of these fit the
appropriate image from the Sidewall or Vertical
options listed in the General Venting Section. For
stainless steel vent, only use terminations listed in Table
3H for the manufacturer of the installed vent.
Failure to follow all instructions can result
in flue gas spillage and carbon monoxide
emissions, causing severe personal injury
or death.
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
10
• Seal - With prior requirements met, the system should be
tested to the procedure listed in parts (c) through (f) of
the Removal of an Existing Boiler Section on page 11.
With polypropylene and stainless steel vent, seal and connect
all pipe and components as specified by the vent manufacturer
used; with PVC/CPVC vent, see the Installing Vent or Air
Piping Section on page 18.
WARNING
If any of these conditions are not met,
the existing system must be updated or
replaced for that concern. Failure to
follow all instructions can result in flue gas
spillage and carbon monoxide emissions,
causing severe personal injury or death.
™
FIRE TUBE
Installation & Service Manual
1 Determine boiler location (continued)
When removing a boiler from existing common vent system:
DANGER
WARNING
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected
to the common venting system placed in operation, while the
other appliances remaining connected to the common venting
system are not in operation.
a. Seal any unused openings in the common venting system.
b. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, or other deficiencies, which
could cause an unsafe condition.
c. Test vent system – Insofar as is practical, close all building
doors and windows and all doors between the space in
which the appliances remaining connected to the common
venting system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
Do not install the Noble Fire Tube into a
common vent with any other appliance.
This will cause flue gas spillage or appliance
malfunction, resulting in possible severe
personal injury, death, or substantial
property damage.
Failure to follow all instructions can result
in flue gas spillage and carbon monoxide
emissions, causing severe personal injury
or death.
g. Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When resizing any portion of the
common venting system, the common venting system
should be resized to approach the minimum size as
determined using the appropriate tables in Part 11
of the National Fuel Gas Code, ANSI Z223.1/NFPA
and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
d. Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
e. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that each appliance remaining
connected to the common venting system properly vents
when tested as outlined herein, return doors, windows,
exhaust fans, fireplace dampers, and any other gas-burning
appliance to their previous conditions of use.
11
2 Prepare boiler
Remove boiler from wood pallet
1. After removing the outer shipping carton from the
boiler, remove the parts box.
2. To remove the boiler from the pallet:
a. Remove the two (2) lag bolts securing the
bottom of the unit to the pallet.
b. Lift the boiler off the wall bracket mounted to
the pallet (FIG. 2-1).
CAUTION
CAUTION
Figure 2-1 Boiler Mounted on Shipping Pallet
3. Remove the two (2) lag bolts securing the wall bracket to the
wood pallet. Be certain not to lose the wall bracket as it will
be needed for securing the boiler to the wall (FIG. 2-4).
NOTICE
Gas conversions
WARNING
You must install a propane venturi to operate the Noble
Fire Tube on propane gas. Verify when installing that the
venturi label marking matches the boiler size. Refer to the
Replacement Parts List for the appropriate LP Conversion Kit
applicable to your unit's size and serial number.
Do not attempt to use the water pipe
fittings or gas pipe to lift the boiler.
Do not attempt to lift the boiler using the
gas pipe as a handle.
REMOVE SHIPPING
(WALL) BRACKET
DO NOT DISCARD.
WILL BE NEEDED TO
SECURE THE BOILER
TO THE WALL.
DIR #2000528206 00
Do not drop the boiler. Damage to the
boiler can result.
For a boiler already installed, you must
turn off gas supply, turn off power and
allow boiler to cool before proceeding.
You must also completely test the boiler
after conversion to verify performance as
described under Start-up, Section 10 of
this manual.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.
™
FIRE TUBE
Installation & Service Manual
1. If boiler is already installed, you must turn off the gas
supply, turn off the power, and allow the boiler to cool
before proceeding.
2. Remove the front access cover from the unit (no tools
required for removal).
3. Using a 5/16" nut driver, loosen the rachet clamp securing
the air intake fitting to the venturi assembly. Slide the
rubber boot off the venturi.
4. Using an adjustable wrench, loosen the union between the
gas valve adapter and the venturi assembly. Remove the
gasket between the gas piping and venturi (FIG. 2-2).
5. Using a 3 mm Allen wrench, remove the three (3) screws
securing the venturi to the fan assembly and proceed to
remove the natural gas venturi from the unit, making sure
not to damage the blower O-ring gasket (FIG. 2-2).
6. Install the air shutter.
a. Disconnect the wiring from the fan and remove the
bolts securing the fan to the heat exchanger top plate.
b. Remove the fan and gasket, and install the air shutter
provided in the kit. Note: On NKC110 models, the air
shutter MUST be installed in the proper direction.
Install the air shutter so that the hole in the corner is
oriented towards the back right corner of the unit
(opposite the front door and gas piping).
c. Replace all torn or damaged gaskets. Reassemble the
fan assembly and reconnect the wiring harnesses
before operation.
7. Install the propane venturi and verify the following:
a. The UP arrow on the plastic housing is pointing
upward.
b. The threaded connection for the gas piping is facing
towards the LEFT of the unit.
8. Reassemble the unit by following the previous steps in
reverse order, taking care to ensure that the venturi adapter
gasket is seated properly before tightening the nut on the
venturi. NOTE: Replace any torn or damaged gasket(s) that
may have been damaged or torn during installation.
9. After installation is complete, fill out the gas conversion
label (in the conversion kit bag) and affix it to the unit to the
right of the control display as shown in FIG. 2-3.
10. Replace the front access cover removed in Step 2 and
resume operation.
DANGER
When removing the natural gas venturi,
inspect the gasket at the gas connection
and the O-ring at the blower. These
gaskets must be in good condition and
must be installed. Failure to comply
will cause a gas leak, resulting in severe
personal injury or death.
12
FIRE TUBE
™
Installation & Service Manual
2 Prepare boiler (continued)
WARNING
Figure 2-2 Remove Natural Gas Venturi
Figure 2-3 Gas Conversion Label Location
After converting to LP, check combustion
per the Start-up procedure in Section 10
of this manual. Failure to check and
verify combustion could result in severe
personal injury, death, or substantial
property damage.
NATURAL GAS
VENTURI
DISCONNECT
GAS PIPING
AIR SHUTTER
DIR #2000534767 00
GAS CONVERSION LABEL
(AFFIX TO UNIT AS SHOWN)
DIR #2000536093 00
2. Mount the wall bracket using the 2 1/4" lag bolts
provided. Make sure the top edge of the bracket is away
from the wall. Ensure the bracket is level when mounted.
Extreme care is needed to ensure the bolts are secured in
the center of the studs.
3. Hang the boiler on the bracket and secure the bottom of
the boiler with two (2) additional lag bolts provided.
WARNING
The boiler is too heavy for a single person
to lift. A minimum of two people is
needed for mounting the boiler onto the
bracket.
Mounting to a concrete wall:
1. Mount the wall bracket using the two (2) wedge anchor
bolts provided with the bracket (FIG. 2-4). To mount the
wedge anchor bolts, drill a 1/4" diameter hole 1 1/8" deep
and insert anchor. Hang the bracket from the anchor and
secure with the two nuts provided. Make sure the top edge
of the bracket is away from the wall. Ensure bracket is level
when mounted.
Note: If wall thickness does not allow a 1 1/8" deep hole,
field supplied hardware suitable for the application should be
provided.
2. Hang the boiler on the bracket and secure the bottom of the
boiler with two (2) remaining anchors, following the
instructions above.
Mounting to a metal studded wall:
1. The wall mount bracket is designed for a stud spacing of 16
inches from center (FIG. 2-4). For other stud spacing a
solid mounting surface must be provided by the installer.
WARNING
Do not mount the boiler to a hollow wall. Be
sure to mount the boiler to the studs only.
2. Mount the wall bracket using two (2) field supplied toggle
bolts capable of supporting 100 pounds each. Ensure the
top edge of the bracket is away from the wall. Ensure the
bracket is level when mounted. Extreme care is needed to
ensure the bolts are secured in the center of the studs.
3. Hang the boiler on the bracket and secure the bottom of the
boiler with two (2) field supplied toggle bolts.
Mounting the boiler
See page 9 of this manual for boiler mounting location
instructions.
NOTICE
Mounting to a wood studded wall:
1. The wall mount bracket is designed for a stud spacing of
16 inches from center (FIG. 2-4). For other stud spacing
a solid mounting surface must be provided by the
installer.
WARNING
The Noble Fire Tube is not intended for
floor installation.
Do not mount the boiler to a hollow wall.
Be sure to mount the boiler to the studs
only.
Figure 2-4 Mounting the boiler
FASTENERS
APPROPRIATE
FOR WALL TYPE
QTY: 4
WALL:
WOOD OR METAL STUDS
ON 16" CENTERS -ORMASONRY / POURED CONCRETE
MOUNTING BRACKET
(FACTORY SUPPLIED)
DIR #2000528235 00
13
3 Generalventing
Direct venting options - Sidewall Vent
FIRE TUBE
™
Installation & Service Manual
DIR #2000534593 00
Figure 3-1 Two-Pipe Sidewall Termination - See
page 22 for more details
Direct venting options - Vertical Vent
DIR #2000534592 00
Figure 3-2 PVC/CPVC Concentric Sidewall
Termination - See page 25 for more details
DIR #2000534588 00
Figure 3-3 Two-Pipe Vertical
Termination - See page 28 for more
details
14
DIR #2000534590 00
Figure 3-4 PVC/CPVC Concentric
Vertical Termination - See page 30
for more details
DIR #2000534587 00
Figure 3-5 Vertical Vent, Sidewall
Air
3 Generalventing (continued)
Install vent and combustion air piping
FIRE TUBE
™
Installation & Service Manual
DANGER
WARNING
WARNING
NOTICE
WARNING
CAUTION
The Noble Fire Tube must be vented and
supplied with combustion and ventilation
air as described in this section. Ensure the
vent and air piping and the combustion
air supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section 1
of this manual.
Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.
Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.
This appliance requires a special venting
system. Use only approved PVC, CPVC,
polypropylene or stainless steel pipe and
fittings listed in Tables 3D, 3E, and 3G for
vent pipe, and fittings. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
DO NOT mix components from different
systems. The vent system could fail,
causing leakage of flue products into the
living space. Mixing of venting materials
will void the warranty and certification of
the appliance.
Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
For closet and alcove installations, CPVC,
polypropylene or stainless steel material
MUST BE used in a closet/alcove structure.
Failure to follow this warning could result
in fire, personal injury, or death.
Improper installation of venting systems
may result in injury or death.
The Noble Fire Tube vent and air piping can be installed
through the roof or through a sidewall. Follow the procedures
in this manual for the method chosen. Refer to the information
in this manual to determine acceptable vent and air piping
length.
You may use any of the vent/air piping methods covered in
this manual. Do not attempt to install the Noble Fire Tube
using any other means.
You must also install air piping from outside to the boiler
air intake adapter unless following the Optional Room Air
instructions on page 17 of this manual. The resultant
installation is direct vent (sealed combustion) .
Air intake/vent connections
1. Combustion Air Intake Connector (FIG. 3-6)
- Used to provide combustion air directly to the unit from
outdoors. A fitting is provided on the unit for final
connection. Combustion air piping must be supported
per guidelines listed in the National Mechanical Code,
Section 305, Table 305.4 or as local codes dictate.
2. Vent Connector (FIG.'s 3-6 thru 3-10) - Used to provide a
passageway for conveying combustion gases to the
outside. A transition fitting is provided on the unit for
final connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.
Figure 3-6 Near Boiler Air Piping
AIR
NOTICE
WARNING
Follow the instructions in Section 1, page
11 of this manual when removing a boiler
from an existing vent system.
Do not connect any other appliance to the
vent pipe or multiple boilers to a common
vent pipe. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
DIR #2000528317 00
15
3 General venting
FIRE TUBE
™
Installation & Service Manual
Sizing
The Noble Fire Tube uses model specific combustion air
intake and vent piping sizes as detailed in Table 3A below.
Table 3A Air Intake/Vent Piping Sizes
Model2" Max Vent/Air3" Max Vent/Air
80 - 110100 feet100 feet
15060 feet100 feet
199N/A100 feet
NOTICE
Minimum / Maximum allowable combustion
air and vent piping lengths are as follows:
Combustion Air = 7 equivalent feet minimum / 100 equivalent
feet maximum
Increasing or decreasing combustion air
or vent piping sizes is not authorized
unless otherwise specified in this manual.
The appliance output rating will reduce by
up to 1.5% for each 25 feet of vent length.
Kit
Number
Equivalent Vent
Length
Vent
Size
WARNING
NOTICE
Sealing of Type “B” double-wall vent material or galvanized
vent pipe material used for air inlet piping on a sidewall or
vertical rooftop Combustion Air Supply System:
a. Seal all joints and seams of the air inlet pipe using either
Aluminum Foil Duct Tape meeting UL Standard 723 or
181A-P or a high quality UL Listed silicone sealant such as
those manufactured by Dow Corning or General Electric.
b. Do not install seams of vent pipe on the bottom of
horizontal runs.
c. Secure all joints with a minimum of three (3) sheet metal
screws or pop rivets. Apply Aluminum Foil Duct Tape or
silicone sealant to all screws or rivets installed in the vent
pipe.
d. Ensure that the air inlet pipes are properly supported.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and
sealed with the pipe manufacturer’s recommended solvents
and standard commercial pipe cement for the material used.
The PVC, CPVC, ABS, or Flex Duct air inlet pipe should
use a silicone sealant to ensure a proper seal at the appliance
connection and the air inlet cap connection. Dryer vent or
flex duct should use a screw type clamp to seal the vent to
the appliance air inlet and the air inlet cap. Proper sealing of
the air inlet pipe ensures that combustion air will be free of
contaminants and supplied in proper volume.
When a sidewall or vertical rooftop combustion air supply
system is disconnected for any reason, the air inlet pipe
must be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.
Using air intake materials other than those
specified can result in personal injury,
death or property damage.
The use of double-wall vent or insulated
material for the combustion air inlet pipe is
recommended in cold climates to prevent
the condensation of airborne moisture in
the incoming combustion air.
Materials
Air inlet pipe materials:
The air inlet pipe(s) must be sealed. Choose acceptable
combustion air inlet pipe materials from the following list:
PVC, CPVC, Polypropylene or ABS
Galvanized steel vent pipe with joints and seams sealed as
specified in this section.
Type “B” double-wall vent with joints and seams sealed as
specified in this section.
AL29-4C, stainless steel material to be sealed to
specification of its manufacturer.
*Plastic pipe may require an adapter (not provided) to
transition between the air inlet connection on the appliance
and the plastic air inlet pipe.
16
DANGER
Failure to properly seal all joints and seams
as required in the air inlet piping may
result in flue gas recirculation, spillage
of flue products and carbon monoxide
emissions causing severe personal injury
or death.
3 Generalventing (continued)
Optional room air
NOTICE
Commercial applications utilizing the Noble Fire Tube may
be installed with a single pipe carrying the flue products to
the outside while using combustion air from the equipment
room. In order to use the room air venting option the
following conditions and considerations must be followed.
• The unit MUST be installed with the appropriate
room air kit (Table 3C).
• The equipment room MUST be provided with
properly sized openings to assure adequate
combustion air. Please refer to instructions provided
with the room air kit.
• There will be a noticeable increase in the noise level
during normal operation from the inlet air opening.
• Using the room air kit makes the unit vulnerable to
combustion air contamination from within the
building. Please review Section 1, Prevent
Combustion Air Contamination, to ensure proper
installation.
• Vent system and terminations must comply with the
standard venting instructions set forth in this
manual.
Optional room air is intended for
commercial applications. Combustion air
piping to the outside is recommended for
residential applications.
™
FIRE TUBE
Please read the information given in Table 1A, page 10,
listing contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
combustion air and vent to another location, per this manual.
WARNING
WARNING
Installation & Service Manual
If the boiler combustion air inlet is located
in a laundry room or pool facility, for
example, these areas will always contain
hazardous contaminants.
To prevent the potential of severe personal
injury or death, check for areas and products
listed in Table 1A, page 10 before installing
the boiler or air inlet piping.
If contaminants are found, you MUST:
• Remove contaminants permanently.
—OR—
• Relocate air inlet and vent
terminations to other areas.
WARNING
Table 3C Optional Room Air Kit
Air contamination
Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds.
When these chemicals pass through the boiler, they can form
strong acids. The acid can eat through the boiler wall, causing
serious damage and presenting a possible threat of flue gas
spillage or boiler water leakage into the building.
When utilizing the single pipe method,
provisions for combustion and ventilation
air must be in accordance with Air for
Combustion and Ventilation, of the
latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest
edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and
Equipment, or applicable provisions of the
local building codes.
Model Kit NumberAir Size
80 - 1501001576142"
80 - 1991001576153"
17
3 Generalventing
PVC/CPVC:
This product has been approved for use with the PVC/CPVC
vent materials listed in Table 3D.
Use only the vent materials, primer, and
cement specified in Table 3D to make the
vent connections. Failure to follow this
warning could result in fire, personal injury,
or death.
Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.
All PVC vent pipes must be glued, properly
supported, and the exhaust must be pitched
a minimum of a 1/4 inch per foot back to the
boiler (to allow drainage of condensate).
Insulation should not be used on PVC
or CPVC venting materials. The use of
insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
For installations using 2" vent, the first seven
(7) equivalent feet of vent must be CPVC
(field supplied). See examples below.
When transitioning from 2" to 3" vent
diameter, a 2" pipe section and 2" to 3"
increaser are required to be CPVC when
PVC/CPVC vent is used.
™
FIRE TUBE
Installation & Service Manual
1. Work from the boiler to vent or air termination. Do
not exceed the lengths given in this manual for the air
or vent piping.
2. Cut pipe to the required lengths and deburr the inside
and outside of the pipe ends.
3. Chamfer outside of each pipe end to ensure even
cement distribution when joining.
4. Clean all pipe ends and fittings using a clean dry rag.
(Moisture will retard curing and dirt or grease will
prevent adhesion.)
5. Dry fit vent or air piping to ensure proper fit up before
assembling any joint. The pipe should go a third to
two-thirds into the fitting to ensure proper sealing after
cement is applied.
6. Priming and Cementing:
a. Handle fittings and pipes carefully to prevent
contamination of surfaces.
b. Apply a liberal even coat of primer to the fitting
socket and to the pipe end to approximately 1/2"
beyond the socket depth.
c. Apply a second primer coat to the fitting socket.
d. While primer is still wet, apply an even coat of
approved cement to the pipe equal to the depth of
the fitting socket along with an even coat of
approved cement to the fitting socket.
e. Apply a second coat of cement to the pipe.
f. While the cement is still wet, insert the pipe into
the fitting, if possible twist the pipe a 1/4 turn as
you insert it. NOTE: If voids are present,
sufficient cement was not applied and joint could
be defective.
g. Wipe excess cement from the joint removing ring
or beads as it will needlessly soften the pipe.
Figure 3-7 Near Boiler PVC/CPVC Venting
Table 3D PVC/CPVC Vent Pipe, and Fittings
Approved PVC/CPVC Vent Pipe and Fittings
ItemMaterialStandard
PVC Schedule 40, 80ANSI/ASTM D1785
Vent pipe
PVC - DWVANSI/ASTM D2665
CPVC Schedule 40, 80ANSI/ASTM F441
PVC Schedule 40ANSI/ASTM D2466
Vent fittings
PVC Schedule 80ANSI/ASTM D2467
CPVC Schedule 80ANSI/ASTM F439
PVC - DWVANSI/ASTM D2665
Pipe Cement /
Primer
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE
PVCANSI/ASTM D2564
CPVCANSI/ASTM F493
NOTE: In Canada, CPVC and PVC vent pipe, ttings and cement/
primer must be ULC-S636 certi ed.
18
VENT
AIR
DIR #2000528318 00
3 Generalventing (continued)
FIRE TUBE
™
Installation & Service Manual
Polypropylene:
This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.
All terminations must comply with listed options in this
manual and be a single-wall vent offering.
For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.
When determining equivalent combustion air and vent length
for polypropylene single-wall piping:
Flexible polypropylene
For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations (FIG. 3-8).
Figure 3-8 Near Boiler Flexible Polypropylene Venting
CHIMNEY
CAP
B
A
Duravent 3”
“A” DIM
3” RIGID
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
Centrotherm 3”
“A” DIM
3” RIGID
10 FT
20 FT
30 FT
40 FT
50 FT
60 FT
70 FT
80 FT
90 FT
“B” DIM
3” FLEX
60 FT
53 FT
47 FT
40 FT
33 FT
27 FT
20 FT
13 FT
7 FT
“B” DIM
3” FLEX
45 FT
40 FT
35 FT
30 FT
25 FT
20 FT
15 FT
10 FT
5 FT
4” FLEX
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
4” FLEX
90 FT
80 FT
70 FT
60 FT
50 FT
40 FT
30 FT
20 FT
10 FT
NOTICE
The installer must use a specific vent
starter adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3F for
approved vent adapters.
NOTICE
All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-9).
WARNING
Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
WARNING
Use only the adapters and vent system listed
in Tables 3E and 3F. DO NOT mix vent
systems of different types or manufacturers,
unless listed in this manual. Failure to
comply could result in severe personal injury,
death, or substantial property damage.
NOTICE
Installations must comply with applicable
national, state, and local codes. For
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.
NOTICE
Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.
Figure 3-9 Near Boiler Polypropylene Venting Model 199
*NOTES: 1) FLEX PIPE MAY ONLY BE RUN IN A VERTICAL ORIENTATION
2) ALL VENT LENGTHS REPRESENTED IN ABOV E CHARTS ARE
EQUIVALENT LENGTHS.
3) SECTION A IS EQUIVALENT FEET OF RIGID PIPE, WHICH MAY
INCLUDE 45 AND 90° ELBOWS. PLEASE SEE SIZING SECTION
FOR DETERMINING EQUIVALENT FEET.
IMG00840
Table 3E Polypropylene Vent Pipe and Fittings
Approved Polypropylene Vent Manufacturers
MakeModel
Centrotherm Eco Systems
Duravent (M & G Group)
PolyPro Single-Wall / PolyPro Flex
InnoFlue SW/Flex
Table 3F Approved Polypropylene Terminations and Adapters
Centrotherm InnoFlue SWDuravent Polypro
Model
80 - 199
* These parts are only needed if the alternate sidewall termination assembly is used.
JOINT CONNECTOR REQUIRED
AT ALL COMPONENT CONNECTIONS
OF VENT SYSTEM
CENTROTHERM PVC ADAPTER
(SEE TABLE 3F FOR MORE DETAILS)
DIR #2000528329 00
Sidewall Adapter* Joint ConnectorSidewall Kit*
19
3 Generalventing
FIRE TUBE
™
Installation & Service Manual
Stainless steel vent:
This product has been approved for use with stainless steel
using the manufacturers listed in Table 3G.
WARNING
NOTICE
NOTICE
Use only the materials, vent systems, and
terminations listed in Tables 3G and 3H.
DO NOT mix vent systems of different
types or manufacturers. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
The installer must use a specific vent
starter adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3H for
approved vent adapters.
Installations must comply with applicable
national, state, and local codes. Stainless
steel vent systems must be listed as a
UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.
NOTICE
Installation of a stainless steel vent system
should adhere to the stainless steel vent
manufacturer’s installation instructions
supplied with the vent system.
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure
no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method,
see manufacturer’s instructions.
Table 3H Approved Stainless Steel Terminations and Adapters
ProTechHeat FabZ Flex
FasNSealSaf-T VentZ-Vent
Model
80 - 199
**Boiler
Adapter
300715
(Intake Air)
Flue
Termination
FSBS3
FSRC3(R.C)
Intake
Air
Termination
303889--
*Boiler
Adapter
Flue
Termination
9392
5300CI
Intake
Air
Termination
9314TERM--
**Boiler
Adapter
Flue
Termination
2SVSTP03
2SVSRCX03
Intake Air
Termination
2SVSTEX0390
*The stainless steel venting option is only available in 3" vent diameters.
20
4 Sidewall directventing
-
FIRE TUBE
™
Installation & Service Manual
Vent/air termination – sidewall
WARNING
WARNING
Determine location
Locate the vent/air terminations using the following
guidelines:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page
16 of this manual.
2. You must consider the surroundings when terminating
the vent and air:
a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.
b. The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.
c. Prevailing winds could cause freezing of
condensate and water/ice buildup where flue
products impinge on building surfaces or plants.
d. Avoid possibility of accidental contact of flue
products with people or pets.
e. Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.
Figure 4-1A PVC/CPVC/Polypropylene Sidewall
Termination of Air and Vent w/Field Supplied Fittings
FROM BOILER
VENT PIPE
CONNECTION
Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death,
or substantial property damage.
A gas vent extending through an exterior
wall shall not terminate adjacent to a wall
or below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
TO BOILER
INTAKE AIR
CONNECTION
BIRD SCREEN
12” MIN
15” MAX
If using the sidewall termination:
3. The air piping must terminate in a down-turned elbow
as shown in FIG. 4-1A. This arrangement avoids
recirculation of flue products into the combustion air
stream.
4. The vent piping must terminate in an elbow pointed
outward or away from the air inlet, as shown in FIG. 4-1A.
WARNING
Do not exceed the maximum lengths of
the outside vent piping shown in FIG.
4-1A. Excessive length exposed to the
outside could cause freezing of condensate
in the vent pipe, resulting in potential boiler
shutdown.
When venting out a sidewall using PVC, CPVC, or
Polypropylene vent materials, an optional sidewall vent
termination kit can be ordered (reference Table 4A for kit
numbers).
Table 4A Alternate Sidewall Vent Kit
Model
Kit
Number
Air
Size
Vent
Size
Centerline
Width
80 - 1501001576092"2"5 5/8"
80 - 1991001576103"3"5 5/8"
Figure 4-1B Alternate PVC/CPVC/ Polypropylene
Sidewall Termination of Air and Vent
Figure 4-1D Alternate Venting Arrangement - Typical
Stainless Steel Sidewall Termination of Air and Vent w/
Field Supplied Fittings
TO BOILER
INTAKE AIR
CONNECTION
FROM
BOILER
VENT PIPE
CONNECTION
BIRD SCREEN
GRADE OR SNOW LINE
5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,
pages 21 and 22. Also maintain the following:
a. Vent must terminate:
• At least 6 feet from adjacent walls.
• No closer than 12 inches below roof overhang.
• At least 7 feet above any public walkway.
• At least 3 feet above any forced air intake within
10 feet.
• No closer than 12 inches below or horizontally
from any door or window or any other gravity air
inlet.
b. Air inlet must terminate at least 12 inches above
grade or snow line; at least 12 inches below the vent
termination (FIG. 4-1B); and the vent pipe must not
extend more than 24 inches vertically outside the
building.
c. Do not terminate closer than 4 feet horizontally
from any electric meter, gas meter, regulator, relief
valve, or other equipment. Never terminate above or
below any of these within 4 feet horizontally.
6. Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.
12" MIN
COUPLING
12” MIN
BIRD SCREEN
12”
MIN
12" MIN
Figure 4-2A Clearance to Gravity Air Inlets w/Field
Supplied Fittings
12”
MIN
BIRD
SCREEN
(TYPICAL)
12”
MIN
12”
MIN
Figure 4-2B Clearance to Gravity Air Inlets using an
Optional Vent Kit
12"
MIN.
VENT / AIR
TERMINATION
12"
MIN.
12"
MIN.
Figure 4-3A Clearance to Forced Air Inlets using an
Optional Vent Kit
VENT / AIR
TERMINATION
7' MIN. ABOVE ANY
PUBLIC WALKWAY
IF LESS
THAN 10’
36"
MIN.
FORCED AIR
INLET
Figure 4-3B Clearance to Forced Air Inlets w/Field
Supplied Fittings
IF LESS
THAN 10’
36”
MIN
FORCED AIR
INLET
BIRD
SCREEN
7’ MIN ABOVE ANY
PUBLIC WALKWAY
(TYPICAL)
22
4 Sidewall direct venting (continued)
FIRE TUBE
™
Installation & Service Manual
Prepare wall penetrations
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the vent
pipe outer diameter:
• 3½ inch hole for 2 inch vent pipe
• 4½ inch hole for 3 inch vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole as shown in FIG. 4-4A.
3. Use the sidewall termination plate as a template for
correct location of hole centers.
4. Follow all local codes for isolation of vent pipe when
passing through floors or walls.
5. Seal exterior openings thoroughly with exterior caulk.
Figure 4-5A Multiple Vent Terminations w/Field Supplied
Fittings (must also comply with Figure 4-1A)
Figure 4-5B Alternate Multiple Vent Terminations (must
also comply with Figure 4-1B)
12" MIN. BETWEEN EDGE OF AIR
INLET AND ADJACENT VENT OUTLET
VENT
AIR
GALVANIZED
THIMBLE
SIDEWALL
TERMINATION PLATE
ELBOW
BIRD SCREEN
Multiple vent/air terminations
1. When terminating multiple boilers terminate each vent/
air connection as described in this manual (FIG. 4-5A).
WARNING
2. Place wall penetrations to obtain minimum clearance
of 12 inches between edge of air inlet and adjacent vent
outlet, as shown in FIG. 4-5A for U.S. installations. For
Canadian installations, provide clearances required by
CSA B149.1 Installation Code.
3. The air inlet of a Noble Fire Tube is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent boiler vents.
All vent pipes and air inlets must terminate
at the same height to avoid possibility
of severe personal injury, death, or
substantial property damage.
VENT / AIR
TERMINATION
23
FIRE TUBE
™
4 Sidewall direct venting
Sidewall termination – optional concentric vent
Description and usage
The manufacturer offers optional concentric combustion air
and vent pipe termination kits (Factory Kit #100140480 - 3"
or #100140485 - 2"). Both combustion air and vent pipes
must attach to the termination kit. The termination kit must
terminate outside the structure and must be installed as shown
below in FIG. 4-6.
The required combustion vent pipe and fittings are listed in
Table 3B, on page 16 of this manual.
Figure 4-6 Concentric Sidewall Termination
3. Cut one (1) hole (5 inch diameter for #100140480
installations or 4 inch diameter for #100140485 installations)
into the structure to install the termination kit.
4. Partially assemble the concentric vent termination kit.
Clean and cement using the procedures found in these
instructions.
a. Cement the Y concentric fitting to the larger kit pipe
(FIG. 4-7).
b. Cement the rain cap to the smaller diameter kit pipe
(FIG. 4-7).
Figure 4-7 Kit Contents
Installation & Service Manual
Sidewall termination installation
1. Determine the best location for the termination kit (see
FIG. 4-6).
2. Reference the Determine Location Section on page 21 of
this manual for general termination considerations.
Figure 4-9 Rain Cap to Vent Pipe Alternate Assembly
Instead of cementing the smaller pipe to
the rain cap, a field-supplied stainless steel
screw may be used to secure the two (2)
components together when field disassembly
is desired for cleaning (see FIG. 4-9).
When using the alternate screw assembly
method, drill a clearance hole in the rain
cap and a pilot hole in the vent pipe for
the screw size being used. Failure to drill
adequate holes may cause cracking of PVC
components, allowing combustion products
to be recirculated. Failure to follow this
warning could result in personal injury or
death.
Do not operate the appliance with the rain
cap removed or recirculation of combustion
products may occur. Water may also collect
inside the larger combustion air pipe and
flow to the burner enclosure. Failure to
follow this warning could result in product
damage or improper operation, personal
injury, or death.
5. Install the Y concentric fitting and pipe assembly through
the structure’s hole.
NOTICE
6. Install the rain cap and small diameter pipe assembly into
the Y concentric fitting and large pipe assembly. Ensure
small diameter pipe is bottomed and cemented in the Y
concentric fitting.
7. Secure the assembly to the structure as shown in FIG.
4-10 using field-supplied metal strapping or equivalent
support material.
NOTICE
NOTICE
NOTICE
Do not allow insulation or other materials
to accumulate inside the pipe assembly
when installing through the hole.
Ensure termination location clearance
dimensions are as shown in FIG. 4-6.
If assembly needs to be extended to
allow sidewall thickness requirement, the
two (2) pipes supplied in the kit may
be replaced by using the same diameter,
field-supplied SDR-26 PVC (D2241) pipe.
Do not extend dimension D more than 60
inches (see FIG. 4-8).
If assembly needs to be reduced, dimension
D can be as short as possible.
25
™
FIRE TUBE
Installation & Service Manual
4 Sidewall direct venting
Sidewall termination – optional concentric vent
Figure 4-10 Concentric Vent Sidewall Attachment
CAUTION
8. Cement appliance combustion air and vent pipes to the
concentric vent termination assembly. See FIG. 4-10 for
proper pipe attachment.
9. Operate the appliance one (1) heat cycle to ensure
combustion air and vent pipes are properly connected to
the concentric vent termination connections.
DO NOT use field-supplied couplings to
extend pipes. Airflow restriction will occur
and may cause intermittent operation.
Multiventing sidewall terminations
When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see FIG.
4-11). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 4-11. It is important that vent terminations be made as
shown to avoid recirculation of flue gases.
26
12"
MINIMUM
VENT
COMBUSTION
AIR
Figure 4-11 Concentric Vent and Combustion Air Termination
5 Vertical direct venting
/
Vent/air termination – vertical
FIRE TUBE
™
Installation & Service Manual
WARNING
Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death
or substantial property damage.
Determine location
Locate the vent/air terminations using the following
guidelines:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page
16 of this manual.
2. Prepare the vent termination and the air termination
elbow (FIG. 5-1A) by inserting bird screens.
3. The vent must terminate at least 3 feet above the highest
place in which the vent penetrates the roof and at least
2 feet above any part of a building within 10 horizontal
feet.
4. The air piping must terminate in a down-turned 180°
return pipe no further than 2 feet from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.
5. The vent piping must terminate in an up-turned coupling
as shown in FIG. 5-1A. The top of the coupling must
be at least 1 foot above the air intake. When the vent
termination uses a rain cap as illustrated in FIG. 5-1B
maintain at least 36" (914 mm) above the air inlet. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than
2 feet (.6 m) apart and with the vent termination at least
1 foot for PVC and 3 feet for stainless steel, above the air
intake.
6. Maintain the required dimensions of the finished
termination piping as shown in FIG. 5-1A.
7. Do not extend exposed vent pipe outside of building
more than shown in this document. Condensate could
freeze and block vent pipe.
Figure 5-1A PVC/CPVC/Polypropylene Vertical
Termination of Air and Vent
ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” OF VENT
PIPE
BIRD SCREEN
(TYPICAL)
VENT
COUPLING
(FIELD SUPPLIED)
VENT OUTLET
12” MINIMUM
ABOVE AIR INLET
COMBUSTION
AIR
6” MINIMUM
ABOVE ROOF
SNOW LINE
Figure 5-1B Stainless Steel Vertical Termination of Air
and Vent
ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” (610 MM)
OF VENT PIPE
BIRD SCREEN
(TYPICAL)
6" (152 MM) MINIMUM
ABOVE ROOF /
SNOW LINE
VENT OUTLET
36” (914 MM) MINIMUM
ABOVE AIR INLET
VENT
COMBUSTION
AIR
8. Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.
WARNING
Rooftop vent and air inlet terminations
must terminate in the same pressure
zone, unless vertical vent sidewall air is
set up, reference this section, page 28 and
Section 4 - Air Intake Clearances.
27
5 Vertical direct venting
Vent/air termination – vertical
FIRE TUBE
™
Installation & Service Manual
Prepare roof penetrations
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the
vent pipe outer diameter:
• 3½ inch hole for 2 inch vent pipe
• 4½ inch hole for 3 inch vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole.
3. Space the air and vent holes to provide the minimum
spacing shown in FIG. 5-1A, page 27.
4. Follow all local codes for isolation of vent pipe when
passing through floors, ceilings, and roofs.
5. Provide flashing and sealing boots sized for the vent pipe
and air pipe.
Figure 5-2 Vertical Terminations with Multiple Boilers
Figure 5-3 Alternate Vertical Terminations with Multiple
Boilers
Multiple vent/air terminations
1. When terminating multiple boilers, terminate each vent/
air connection as described in this manual (FIG. 5-2).
WARNING
2. Place roof penetrations to obtain minimum clearance of
12 inches between edge of air intake elbow and adjacent
vent pipe of another boiler for U.S. installations (see
FIG. 5-2). For Canadian installations, provide clearances
required by CSA B149.1 Installation Code.
3. The air inlet of a Noble Fire Tube is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent boiler vents.
Terminate all vent pipes at the same height
and all air pipes at the same height to
avoid possibility of severe personal injury,
death, or substantial property damage.
28
™
FIRE TUBE
Installation & Service Manual
5 Vertical direct venting (continued)
Vertical termination – optional concentric vent
Description and usage
The manufacturer offers an optional concentric combustion
air and vent pipe termination kit. Both combustion air
and vent pipes must attach to the termination kit. The
termination kit must terminate outside the structure and
must be installed as shown in FIG. 5-4.
Field supplied pipe and fittings are required to complete
the installation.
The required combustion air and vent pipe fittings are
listed in Table 3B, on page 16 of this manual.
Vertical termination installation
1. See Section 5, Vertical Direct Venting - Determine
Location (where applicable).
Figure 5-4 Concentric Vertical Termination
2. Cut one (1) hole (5 inch diameter for #100140480 installations
or 4 inch diameter for #100140485 installations) into the
structure to install the termination kit.
3. Partially assemble the concentric vent termination kit.
Clean and cement following the cleaning procedures in
these instructions.
a. Cement the Y concentric fitting to the larger
diameter kit pipe (see FIG. 4-7, page 24).
b. Cement rain cap to the smaller diameter kit pipe (see
FIG. 4-7, page 24).
NOTICE
WARNING
Instead of cementing the smaller pipe to
the rain cap, a field supplied stainless steel
screw may be used to secure the two (2)
components together when field disassembly
is desired for cleaning (see FIG. 4-9, page
25).
When using the alternate screw assembly
method, drill a clearance hole in the rain
cap and a pilot hole in the vent pipe for
the screw size being used. Failure to drill
adequate holes may cause cracking of PVC
components, allowing combustion products
to be recirculated. Failure to follow this
warning could result in personal injury or
death.
Figure 5-5 Do Not Install U-Bend to Rain Cap
29
™
FIRE TUBE
Installation & Service Manual
5 Vertical direct venting
Vertical termination – optional concentric vent
WARNING
Do not operate the appliance with
the rain cap removed or recirculation
of combustion products may occur.
Water may also collect inside the larger
combustion air pipe and flow to the
burner enclosure. Failure to follow this
warning could result in product damage
or improper operation, personal injury,
or death.
4. Install the Y concentric fitting pipe assembly through the
structure’s hole and field supplied roof boot/flashing.
NOTICE
Do not allow insulation or other materials
to accumulate inside the pipe assembly
when installing through the hole.
5. Secure the assembly to the roof structure as shown
below in FIG. 5-6 using field supplied metal strapping or
equivalent support material.
Figure 5-6 Concentric Vent Roof Installation
CAUTION
DO NOT use field-supplied couplings to
extend pipes. Airflow restriction will occur.
6. Install the rain cap and the small diameter pipe assembly
into the roof penetration assembly. Ensure the small
diameter pipe is cemented and bottomed in the Y concentric
fitting.
7. Cement the appliance combustion air and vent pipes to
the concentric vent termination assembly. See FIG. 5-6 for
proper pipe attachment.
8. Operate the appliance through one (1) heat cycle to ensure
combustion air and vent pipes are properly connected to
the concentric vent termination connections.
Multi-venting vertical terminations
When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see
FIG. 5-7). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 5-7. It is important that vent terminations be made as
shown to avoid recirculation of flue gases.
Figure 5-7 Concentric Vent and Combustion Air Vertical
Termination
NOTICE
NOTICE
Ensure termination height is above the
roof surface or anticipated snow level (12
inches in U.S.A. or 18 inches in Canada) as
shown in FIG. 5-4, page 29.
If assembly is too short to meet height
requirement, the two (2) pipes supplied
in the kit may be replaced by using the
same diameter, field supplied SDR-26 PVC
(D2241) pipe. Do not extend dimension
D more than 60 inches (see FIG. 4-8, page
25).
12” (18” FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24” ABOVE ROOF.
12”
MINIMUM
COMBUSTION
AIR (TYPICAL)
30