INSTALLATION
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do so
could result in personal injury or property damage.
Heater must be installed by a qualified person in accordance with the National Electrical Code, NFPA 70.
1. Before installing, unpack and check your immersion heater for any
damage that may have occurred during shipment. Report any
claims to your carrier if damage has ocurred in shipment. Do not
operate damaged equipment. Consult factory for
instructions.
2. Check to ensure that the line voltage is the same as that stamped
on the nameplate. Verify wattage and capacity versus the requirements at installation site.
3. Do not bend the heating elements. If bending is necessary,
consult factory.
4. IMPORTANT: Mount the heater in the tank so that the liquid
level will always be above the effective heated portion of the
heater. If the heater is not properly submerged, it may overheat and
damage the heating elements (see Figure 1).
5. Where work will pass over or near equipment, additional protection
such as a metal guard may be needed.
6. Heater shall not be operated in sludge.
FIRE HAZARD. If the heater is not properly submerged, the heating elements will overheat and could
result in a fire or damaged equipment.
7. Install the heater using a high quality pipe sealing compound on the
threads. Screw the heater into the opening (Figure 2). Tighten sufficiently with wrench applied on the hex portion of the screwplug.
8. Closed Tank Installation
EXPLOSION HAZARD. When heating in closed vessels,
controls and back-up controls must be used to regulate build-up of temperature and/or pressure.
A. Horizontal Position (Figure 3)
A1. Place heater at an elevation so that natural circulation can
take place.
A2. Position outlet and inlet in a vertical plane, facing upward
to prevent air pockets. Be sure all trapped air is removed
from the closed tank. Bleed the air out of the liquid piping
system and heater enclosure prior to operation.
A3. IMPORTANT: Heater should never be located at the high-
est point of the liquid system. Provide expansion tank, if
necessary.
A4. Heater shall be supported if the immersion length is greater
than 36”.
FREEZE HAZARD. This unit may be equipped with a
thermowell for process control or over-temperature
control. Do not allow moisture to accumulate in thermowell. Freezing temperatures can cause damage
that my result in the heated medium leaking into terminal closure.
B. Vertical Position (Figure 4)
A drip loop is recommended to minimize passage of moisture from
condensation along wiring into terminal enclosure and connections.
9. To prevent moisture accumulation in cryogenic applications or
when heater is exposed to freezing temperatures:
A. Slope conduit away from enclosure (drip loop).
B. Seal all conduit openings to moisture/explosion resistant termi-
nal enclosure.
C. Insulate terminal enclosure.
D. Fill thermowell(s) with silicone, fluid when heater is mounted
with terminal enclosure up.
Note: Locate Heater as low as possible for maximum heated liquid storage
capacity. Heat does not move downward.
Figure 1 - Open Tank Installation
Expected Low Liquid
Level
This Portion of the Heater Above Liquid Level and
Exposed to Air Will Lead to Premature Burnout of Element
Expected Maximum
Sediment Level
RIGHT
WRONG
Heavy Tank Walls may be drilled and tapped - if thickness is sufficient to engage 3/4 of
threads.
Lighter Tank Walls must be equipped with suitable pipe coupling attached with proper
solder or weld material.
Care must be taken to insure the heated portion does not extend into the coupling area.
Approx. Cold End
(See Warning)
Figure 2 - Exploded View Screw Plug Mounting
2”