Lochinvar LVN04040 User Manual

POWER VENTED GAS
WATER HEATER
Submittal Sheet
LVN-Sub-04a
POWER VENTED RESIDENTIAL GAS WATER HEATERS
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ARCH./ENGR.____________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ TYPE GAS ______________________________________________________________________ Btu/hr INPUT____________________________________________________________________ RECOVERY RATE IN GPH_______________________________________@________ °F RISE GALLON CAPACITY_____________________________________________________________ NOTES
Standard Features
• Power Vented Exhaust System
• FVIR Compliant
• Side Wall or Vertical Venting
• Electronic Gas Control
• Low NOx Burner, less than 40ng/j NOx
• Non-CFC Foam Insulation
• Glass-Lined Steel Tank
• Tank Saver Anode
• Factory Installed Heat Trap
• Adjustable Thermostat w/ Overheat Protection
• Temperature & Pressure Relief Valve
• Brass Drain Valve
• 6 Year Limited Tank and Parts Warranty* (See warranty for details)
• 10 Year Extended Warranty Available
residential applications only
* 1 year limited tank and parts warranty when installed
in commercial applications
Optional Equipment
Place an X in the box by all options that apply
10 Year Extended Warranty Kit
residential applications only
Dimensions and Specifications:
B
F
TOP VIEW
6 Ft. POWER CORD
WATER
CONNECTIONS
FACTORY SUPPLIED
1/2" GAS CONNECTION
C
D A
Max. Vent Length (Total equivalent feet)
2” 3” 4”
LVN040 40 40 120 160 LVN050 40 40 120 160 LVN040 50 40 120 160 LVN050 50 40 120 160 LVN050 65 N/A 80 120 LVN075 80 N/A 30 100 LVN040 40ES 40 120 160 LVN050 40ES 40 120 160
E
Model Gal. Btu/hr GPH @ 1st Hr. Energy Gas Blower Water Ship. Number Cap. Input 90°F Rise Rating Factor A B C D E F Conn. Diam. Conn. Wt.
Power Vent Models LVN040 40 40 40,000 44 69 0.65 63” 18-1/2” 49” 55” 13” 8” 1/2” 2”, 3” or 4” 3/4” 157 LVN050 40 50 40,000 44 83 0.65 65” 20” 50-1/4” 56-3/4” 13” 8” 1/2” 2”, 3” or 4” 3/4” 177 LVN040 50 40 50,000 53 80 0.65 63” 20-1/2” 49” 55” 13” 8” 1/2” 2”, 3” or 4” 3/4” 166 LVN050 50 50 50,000 53 83 0.65 65” 22” 50-1/4” 56-3/4” 13” 8” 1/2” 2”, 3” or 4” 3/4” 186 LVN050 65 50 62,500 66 114 0.65 65” 22” 50-1/4” 56-3/4” 13” 8” 1/2” 3” or 4” 3/4” 186 LVN075 80 74 80,000 86 N/A N/A 66” 25-1/2” 50-1/4” 57” 15” 16” 1/2” 3” or 4” 1” 245 Energy Star Power Vent Models LVN040 40ES 40 40,000 44 70 0.67 63” 20-1/2” 49” 55” 13” 8” 1/2” 2”, 3” or 4” 3/4” 166 LVN050 40ES 50 40,000 44 83 0.67 65” 22” 50-1/4” 56-3/4” 13” 8” 1/2” 2”, 3” or 4” 3/4” 186
Notes: Replace “N” with “L” to indicate LP gas model Models fired above 75,000Btu/Hr are certified to ANSI Z21.10.3 and are not required to meet the FVIR Standard. Performance data is based on manufacturer test results.
Certified for Potable Water and Space Heating Applications
This water heater is suitable for water heating and space heating. Toxic chemicals, such as those used for boiler water treatment shall NEVER be introduced into this system. This water heater may NEVER be connected to any existing heating system or components previously used with non-potable water heating appliances.