8 OPERATING CODES/TROUBLESHOOTING
60
8 OPERATING CODES/TROUBLESHOOTING
8.1 OVERVIEW AND OPERATING CODES/TROUBLESHOOTING
Table 8.1 – TABLE OF OPERATING CODES generated by the S61 electronic board (rmware version 3.026)
CODES DESCRIPTION TRIP CONDITIONS RESET METHOD
E 400
FAULT ON RESET CIRCUIT OF FLAME
CONTROL UNIT
Fault on reset circuit of ame control unit. Contact authorised Technical Assistance.
u 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
High temperature detected by limit thermostat
on body of generator
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
u_01 code active for 1 hour, or u_01 code generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 402 FUMES THERMOSTAT
High temperature detected by exhaust fumes
thermostat
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 402 FUMES THERMOSTAT
u_02 code active for 1 hour, or u_02 code generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
E 405 HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient temperature sensor.
Reset occurs automatically when the condition that generated the
code ceases.
u 406 LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient temperature sensor.
Reset occurs automatically when the cause ceases or when the unit
is switched o.
u 407 GENERATOR TEMPERATURE HIGH Temperature detected by generator’s probe HIGH.
Reset occurs automatically when the condition that generated the
code ceases.
E 407 GENERATOR TEMPERATURE HIGH
Permanence of u_07 for 1 hour, or intervention of
u_07 for 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
E 408 FLAME CONTROL UNIT ERROR
E_12 on unit and condenser inlet temperature
increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
u 410 INSUFFICIENT HOT WATER FLOW
Insucient water ow (the circulator is on and
the owmeter measure a low water ow).
Reset occurs automatically when correct water ow is restored.
E 410 INSUFFICIENT HOT WATER FLOW
u_10 code is repeated, or code u_10 is active for
1 hour.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
Insucient rotation of oil pressure pump. Reset occurs automatically 20 minutes after the Code is generated.
E 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
u_11 code generated twice in 2 hours of
operation.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 412 FLAME CONTROL UNIT ARREST Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again
(new ignition attempt), or if the code persists for 5 minutes.
E 412 FLAME CONTROL UNIT ARREST Flame arrest signal.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 20). If the code persists, contact authorised
Technical Assistance.
E 416
HOT OUTLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on outlet hot
water temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 417
COLD INLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on inlet water
temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 420
CONDENSER INLET TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser
inlet temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 422 WATER FLOWMETER FAULT Water owmeter fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 423 AIR/GAS MIXTURE SENSOR FAULT Air gas mixture sensor fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 424
FUMES TEMPERATURE SENSOR
FAU LT
Fumes temperature sensor fault
Reset occurs automatically when the condition that generated the
code ceases.
E 424
FUMES TEMPERATURE SENSOR
FAU LT
Presence of E_24 for 5 seconds
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 425
CONDENSATE DISCHARGE
CLOGGED
Condensate discharge clogged
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 426
GENERATOR FIN TEMPERATURE
SENSOR MALFUNCTION
Generator n temperature sensor malfunction
Reset occurs automatically when the condition that generated the
code ceases.
E 426
GENERATOR FIN TEMPERATURE
SENSOR MALFUNCTION
Presence of u_26 for 5 seconds
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 428
GAS SOLENOID VALVE EXCITED
DURING FLAME CONTROLLER
ARREST
The ame controller is arrested (E_12) but the gas
solenoid valve is excited. In this case the ame
controller is de-excited (E_12 resets).
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Gas solenoid valve is o for 5 seconds (with
central ame control unit on).
Reset occurs automatically if the gas solenoid valve switches on
again within 10 minutes (with central ame control unit on).