19
Building Management System control
To adjust the Building Management System control
parameters, click on the tab marked 4G BMS settings, see
FIG. 6-12.
Figure 6-12_BMS Settings
6 Power-fin Parameters (continued)
BMS setpoint at min voltage (4GC)
If parameter 4CB is set to 2, the control must know the
minimum setpoint temperature to use. This can be changed
by accessing parameter 4GA. The temperature range for this
parameter is 32°F (0°C) to 248°F (120°C). The default value
is 70°F (21°C).
BMS setpoint at max voltage (4GD)
If parameter 4CB is set to 2, the control must know the
maximum setpoint temperature to use. This can be changed
by accessing parameter 4GB. The temperature range for this
parameter is 32°F (0°C) to 248°F (120°C). The default value
is 180°F (82°C).
BMS voltage at low setpoint (4GA)
If parameter 4CB is set to 2, the control must know the voltage
corresponding to the minimum setpoint. This can be
adjusted by accessing parameter 4GC. The voltage range for
this parameter is 0Vdc to 10Vdc. The default value is 2Vdc.
BMS voltage at high setpoint (4GB)
If parameter 4CB is set to 2, the control must know the voltage
corresponding to the maximum setpoint. This can be
adjusted by accessing parameter 4GD. The voltage range for
this parameter is 0Vdc to 10Vdc. The default value is 10Vdc.
Min BMS voltage to start demand
If parameter 4GK is set to 1, the heat demand will be
generated by the voltage present on the 0 - 10Vdc input.
Parameter 4GE determines the voltage at which the SMART
SYSTEM control initiates a head demand. The range for this
parameter is 0Vdc to 10Vdc. The default value is 2Vdc.
Differential to stop BMS demand
If parameter 4GK is set to 1, the heat demand will be
generated by the voltage present on the 0 - 10Vdc input.
Parameter 4GF determines how far below the starting voltage
(parameter 4GE) the voltage must drop before the heat
demand ends. The range for this parameter is 0Vdc to 10Vdc.
The default value is 1Vdc.
BMS power at min voltage (4GI)
If parameter 4CB is set to 0, the control must know what
minimum power level to use. This can be changed by
accessing parameter 4GG. The range for this parameter is
20% to 100%. The default value is 20%.
BMS power at max voltage (4GJ)
If parameter 4CB is set to 0, the control must know the
maximum power level to use. This can be changed by
accessing parameter 4GH. The range for this parameter is
20% to 100%. The default value is 100%.
BMS voltage at min power (4GG)
If parameter 4CB is set to 0, the control must know the voltage
corresponding to the minimum power. This can be changed
by accessing parameter 4GI. The range for this parameter is
0Vdc to 10Vdc. The default value is 2Vdc.
BMS voltage at max power (4GH)
If parameter 4CB is set to 0, the control must know the voltage
corresponding to the maximum power. This can be changed
by accessing parameter 4GJ. The range for this parameter is
0Vdc to 10Vdc. The default value is 10Vdc.
BMS demand enable [1] voltage [0]
If parameter 4CA is set to 4 (BMS control), the heat demand
can be activated by either the voltage on the 0 - 10Vdc input,
or by closing the enable contacts (boiler) or tank thermostat
contacts (water heater). To choose the voltage input, set
parameter 4GK to 0. To choose the enable / tank thermostat
input, set parameter 4GK to 1. The default value is 0.
PC Program Instructions