This manual must only be used by
a qualified heating installer / service
technician. Read all instructions,
including this manual and the
Knight Boiler Service Manual,
before installing. Perform steps in
the order given. Failure to comply
could result in severe personal
injury, death, or substantial property
damage.
Revision Notes .................................................. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or
to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate
injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not
avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not
related to personal injury or property damage.
Page 3
Please read before proceeding
Installation & Operation Manual
WARNING
NOTICE
WARNING
WARNING
Installer – Read all instructions, including
this manual and the Knight Boiler Service
Manual, before installing. Perform steps
in the order given.
User – This manual is for use only
by a qualified heating installer/
service technician. Refer to the User’s
Information Manual for your reference.
Have this boiler serviced/inspected by
a qualified service technician, at least
annually.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
When calling or writing about the boiler
– Please have the boiler model and serial
number from the boiler rating plate.
Consider piping and installation when
determining boiler location.
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by
the consignee.
Factory warranty (shipped with unit) does
not apply to units improperly installed or
improperly operated.
Failure to adhere to the guidelines on this
page can result in severe personal injury,
death, or substantial property damage.
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
This appliance MUST NOT be installed in
any location where gasoline or flammable
vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a near by phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
• Installation and service must be
performed by a qualified installer,
service agency, or the gas supplier.
When servicing boiler –
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
• To avoid severe burns, allow boiler to cool before
performing maintenance.
Boiler operation –
• Do not block flow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut off,
do not turn off or disconnect electrical supply to
circulator. Instead, shut off the gas supply at a location
external to the appliance.
• Do not use this boiler if any part has been under water.
The possible damage to a flooded appliance can be
extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
Boiler water –
• Thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency
heat exchanger can be damaged by build-up or
corrosion due to sediment.
• Continual fresh make-up water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat
transfer, overheats the stainless steel heat exchanger,
and causes failure. Addition of oxygen carried in by
makeup water can cause internal corrosion in system
components. Leaks in boiler or piping must be repaired
at once to prevent makeup water.
CAUTION
CAUTION
Do not use petroleum-based cleaning or
sealing compounds in the boiler system.
Gaskets and seals in the system may be
damaged. This can result in substantial
property damage.
Do not use “homemade cures” or “boiler
patent medicines”. Serious damage to
the boiler, personnel, and/or property
may result.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are specifically
formulated for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used in hydronic
systems.
3
Page 4
The Knight Boiler - How it works...
Installation & Operation Manual
1. Stainless steel heat exchanger
Allows system water to flow through specially designed
coils for maximum heat transfer, while providing
protection against flue gas corrosion. The coils are
encased in a jacket that contains the combustion process.
2. Combustion chamber access cover
Allows access to the combustion side of the heat
exchanger coils.
3. Blower
The blower pulls in air and gas through the venturi (item
5). Air and gas mix inside the blower and are pushed into the
burner, where they burn inside the combustion chamber.
4. Gas valve
The gas valve senses the negative pressure created by the
blower, allowing gas to flow only if the gas valve is
powered and combustion air is flowing.
5. Venturi
The venturi controls air and gas flow into the burner.
6. Flue gas sensor (limit rated)
This sensor monitors the flue gas exit temperature. The control
module will modulate and shut down the boiler if flue gas
temperature gets too hot. This protects the flue pipe from
overheating.
7. Boiler outlet temperature sensor (housed with the
high limit sensor)
This sensor monitors boiler outlet water temperature (system
supply). If selected as the controlling sensor, the control
module adjusts boiler firing rate so the outlet temperature is
correct.
8. Boiler inlet temperature sensor
This sensor monitors return water temperature (system
return). If selected as the controlling sensor, the control
module adjusts the boiler firing rate so the inlet temperature is
correct.
9. Temperature and pressure gauge (field installed, not
shown)
Monitors the outlet temperature of the boiler as well as the
system water pressure.
10. Electronic LCD display
The electronic display consists of 4 buttons, a navigation dial
and a multiple line liquid crystal display.
11. Flue pipe adapter
Allows for the connection of the PVC vent pipe system to the
boiler.
12. Burner (not shown)
Made with metal fiber and stainless steel construction,
the burner uses pre-mixed air and gas and provides a
wide range of firing rates.
13. Water outlet (system supply)
NPT water connection that supplies hot water to the
system, either 1" or 1-1/4", depending on the
model.
14. Water inlet (system return)
NPT water connection that returns water from the
system to the heat exchanger, either 1" or 1-1/4",
depending on the model.
15. Gas connection pipe
Threaded pipe connection, either 1/2" or 3/4",
depending on the model. This pipe should be connected
to the incoming gas supply for the purpose of delivering
gas to the boiler.
4
16. SMART SYSTEM Control Module
The SMART SYSTEM Control responds to internal and
external signals and controls the blower, gas valve, and pumps
to meet the heating demand.
17. Manual air vent
Designed to remove trapped air from the heat exchanger
coils.
18. Air intake adapter
Allows for the connection of the PVC air intake pipe to
the boiler.
19. High voltage junction box
The junction box contains the connection points for the line
voltage power and all pumps.
20. Boiler drain port
Location from which the heat exchanger can be drained.
21. Low voltage connection board
The connection board is used to connect external low voltage
devices.
22. Low voltage wiring connections (knockouts)
Conduit connection points for the low voltage
connection board.
23. Condensate drain connection
Connects the condensate drain line to a 1/2" PVC union.
24. Access cover - front
Provides access to the gas train and the heat exchanger.
25. Ignition electrode
Provides direct spark for igniting the burner.
26. Flame inspection window
The quartz glass window provides a view of the burner
surface and flame.
27. Relief valve
Protects the heat exchanger from an over pressure condition.
The relief valve provided with the unit is set at 30 psi.
28. Flame sensor
Used by the control module to detect the presence of burner
flame.
29. Line voltage wiring connections (knockouts)
Conduit connection points for the high voltage junction box.
30. Top panel
Removable panel to gain access to the internal components.
31. Power switch
Turns 120 VAC ON/OFF to the boiler.
32. Leveling legs
Used to allow the heat exchanger to be leveled. This is needed
for the proper draining of the condensate from the combustion
chamber.
33. Air pressure switch
The air pressure switch detects blocked inlet conditions.
34. Transformer
The transformer provides 24V power to the integrated control.
35. High limit sensor (housed with the outlet
temperature sensor)
Device that monitors the outlet water temperature. If the
temperature exceeds its setting, the integrated control will
break the control circuit, shutting the boiler down.
36. Gas shutoff switch
An electrical switch designed to cut power to the gas valve to
prevent releasing any gas.
Used to detect excessive temperatures on the upper coil of the heat
exchanger.
Page 5
Installation & Operation Manual
The Knight Boiler - How it works... (continued)
Models 81 - 211
30
10
22
24
Front View - Models 81 - 211
33
10
29
31
11
6
Rear View - Models 81 - 211
19
21
18
15
8
14
27
13
20
32
23
Left Side (inside unit) - Models 81 - 211
28
12
25
4
5
36
7
35
2
26
Right Side (inside unit) - Models 81 - 211
16
34
3
1
17
5
Page 6
The Knight Boiler - How it works...
Model 286
15
Installation & Operation Manual
18
10
24
Front View - Model 286
33
37
Rear View - Model 286
34
Left Side (inside unit) - Model 286
6
4
Right Side (inside unit) - Model 286
Page 7
Ratings
Installation & Operation Manual
Knight Boiler
I=B=R Rating
Input
Model Number
Note: Change “N” to
“L” for L.P. gas models.
Min Max
KBN08116807263
KBN106211059482
KBN15130150135117
KBN21142210190165
KBN28657285260226
NOTICE
Maximum allowed working pressure is located on the rating plate.
Notes:
1. As an Energy Star Partner, Lochinvar has determined that
Knight boilers meet the Energy Star guidelines for energy
efficiency.
2. The ratings are based on standard test procedures prescribed
by the United States Department of Energy.
3. Net I=B=R ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.
4. Knight boilers require special gas venting. Use only
the vent materials and methods specified in the Knight
Installation and Operation Manual.
5. Standard Knight boilers are equipped to operate from sea
level to 4,500 feet only with no adjustments. The boiler
will de-rate by 4% for each 1,000 feet above sea level up to
4,500 feet.
6. High altitude Knight boilers are equipped to operate
from 3,000 to 12,000 feet only with no field adjustments.
The boiler will de-rate by 2% for each 1,000 feet above
3,000 feet. High altitude models are manufactured with
a different control module for altitude operation, but the
operation given in this manual remains the same as the
standard boilers. A high altitude label (as shown in FIG. A)
is also affixed to the unit.
7. Ratings have been confirmed by the Hydronics Institute,
Section of AHRI.
MBH
(Note 5)
Gross
Output
MBH
(Note 2,7)
Other Specifications
Air
Size
Vent
Size
(Note 4)
Net
I=B=R
Ratings
Water,
MBH
(Note 3,7)
Boiler
Water
Content
Gallons
0.61"1/2"3"3"
0.71"1/2"3"3"
1.31"1/2"3"3"
1.71"1/2"3"3"
2.41-1/4"3/4"4"4"
Water
Connections
Gas
Connections
8. Knight boilers comply with the requirements of CSD-1
Section CW-400 requirements as a temperature operation
control. The manual reset high limit provided with the
Knight is listed to UL353.
UNIT EQUIPPED FOR
HIGH ALTITUDE
3,000 FT. TO 12,000 FT.
Figure A High Altitude Label Location
7
Page 8
1 Determine boiler location
Installation & Operation Manual
Installation must comply with:
• Local, state, provincial, and national codes, laws,
regulations, and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1, when required.
• National Electrical Code.
• For Canada only: B149.1 Installation Code, CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
NOTICE
The Knight boiler gas manifold and
controls met safe lighting and other
performance criteria when the boiler
underwent tests specified in ANSI Z21.13
– latest edition.
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the
appliance. The pan must not restrict combustion air
flow. Under no circumstances is the manufacturer to be
held responsible for water damage in connection with
this appliance, or any of its components.
3. Check area around the boiler. Remove any combustible
materials, gasoline and other flammable liquids.
WARNING
4. The Knight boiler must be installed so that gas control
system components are protected from dripping or
spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check for
and correct system problems, such as:
• System leaks causing oxygen corrosion or heat exchanger
cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing system
and boiler to freeze and leak.
Failure to keep boiler area clear and free
of combustible materials, gasoline, and
other flammable liquids and vapors can
result in severe personal injury, death, or
substantial property damage.
8
WARNING
WARNING
This appliance is certified as an indoor
appliance. Do not install the appliance
outdoors or locate where the appliance will
be exposed to freezing temperatures or to
temperatures that exceed 100°F.
Failure to install the appliance indoors
could result in severe personal injury,
death, or substantial property damage.
This appliance requires a special venting
system. If using PVC the vent connection
to the appliance must be made with the
starter CPVC pipe section provided with
the appliance. The field provided vent
fittings must be cemented to the CPVC
pipe section. Use only the vent materials,
primer and cement specified in this manual
to make the vent connections. Failure to
follow this warning could result in fire,
personal injury, or death.
Closet and alcove installations
A closet is any room the boiler is installed in which is less
than 67 cubic feet for KBN081 and KBN106 models, 86 cubic
feet for KBN151 models, 107 cubic feet for KBN211 models,
and 120 cubic feet for KBN286 models.
An alcove is any room which meets the criteria for a closet
with the exception that it does not have a door.
Example: Room dimensions = 4 feet long, 3 feet wide, and
8 foot ceiling = 4 x 3 x 8 = 96 cubic feet. This would be
considered a closet for a Knight Boiler.
WARNING
For closet and alcove installations as
shown in FIG.’s 1-1 and 1-2, CPVC or
stainless steel vent material must be used
inside the structure. The ventilating air
openings shown in FIG.’s 1-1 and 1-2 are
required for this arrangement. Failure to
follow this warning could result in fire,
personal injury, or death.
Provide clearances:
Clearances from combustible materials
1. Hot water pipes—at least 1/4" (6 mm) from combustible
materials.
2. Vent pipe – at least 1" (25 mm) from combustible
materials.
3. See FIG.’s 1-1 and 1-2 on page 9 for other clearance
minimums.
Clearances for service access
1. See FIG.’s 1-1 and 1-2 on page 9 for recommended
service clearances. If you do not provide the minimum
clearances shown, it may not be possible to service the
boiler without removing it from the space.
For closet installations, CPVC or
stainless steel vent material MUST
BE used in a closet structure due to
elevated temperatures. Failure to
follow this warning could result in
1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES.
WARNING
13”
TOP
For alcove installations, CPVC or
stainless steel vent material MUST
BE used in an alcove structure
due to elevated temperatures.
Failure to follow this warning
could result in fire, personal
injury, or death.
12”
LEFT
14”
REAR
RECOMMENDED SERVICE CLEARANCES:
FRONT - 24”
TOP - 24”
LEFT SIDE - 24”
REAR - 24”
18”
FRONT
OPEN
FRONT
0”
RIGHT
9
Page 10
1 Determine boiler location
Installation & Operation Manual
Provide air openings to room:
Knight boiler alone in boiler room
1. No air ventilation openings into the boiler room are
needed when clearances around the Knight boiler are
at least equal to the SERVICE clearances shown in
FIG.’s 1-1 and 1-2. For spaces that do NOT supply this
clearance, provide two openings as shown in FIG. 1-1.
Each opening must provide one square inch free area per
1,000 Btu/hr of boiler input.
Knight boiler in same space with other gas or oilfired appliances
1. Follow the National Fuel Gas Code (U.S.) or CSA B149.1
(Canada) to size/verify size of the combustion/ventilation
air openings into the space.
WARNING
2. Size openings only on the basis of the other appliances in
the space. No additional air opening free area is needed
for the Knight boiler because it takes its combustion air
from outside (direct vent installation).
The space must be provided with
combustion/ventilation air openings
correctly sized for all other appliances
located in the same space as the Knight
boiler.
Do not install the boiler in an attic.
Failure to comply with the above warnings
could result in severe personal injury,
death, or substantial property damage.
Flooring and foundation
Flooring
The Knight boiler is approved for installation on combustible
flooring, but must never be installed on carpeting.
WARNING
If flooding is possible, elevate the boiler sufficiently to prevent
water from reaching the boiler.
Do not install the boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death, or
substantial property damage.
10
Residential garage installation
Precautions
Take the following precautions when installing the appliance
in a residential garage. If the appliance is located in a
residential garage, it should be installed in compliance with
the latest edition of the National Fuel Gas Code, ANSI Z223.1
and/or CAN/CGA-B149 Installation Code.
• Appliances located in residential garages and in
adjacent spaces that open to the garage and are not part
of the living space of a dwelling shall be installed so that
all burners and burner ignition devices are located not
less than 18 inches (46 cm) above the floor.
• The appliance shall be located or protected so that it is
not subject to physical damage by a moving vehicle.
Vent and air piping
The Knight boiler requires a special vent system, designed for
pressurized venting.
The boiler is to be used for either direct vent installation or
for installation using indoor combustion air. When room
air is considered, see Section 3, General Venting. Note
prevention of combustion air contamination below when
considering vent/air termination.
Vent and air must terminate near one another and may be
vented vertically through the roof or out a side wall, unless
otherwise specified. You may use any of the vent/air piping
methods covered in this manual. Do not attempt to install
the Knight boiler using any other means.
Be sure to locate the boiler such that the vent and air piping
can be routed through the building and properly terminated.
The vent/air piping lengths, routing and termination method
must all comply with the methods and limits given in this
manual.
Prevent combustion air contamination
Install air inlet piping for the Knight boiler as described in this
manual. Do not terminate vent/air in locations that can allow
contamination of combustion air. Refer to Table 1A, page
11 for products and areas which may cause contaminated
combustion air.
WARNING
You must pipe combustion air to the boiler
air intake. Ensure that the combustion air
will not contain any of the contaminants
in Table 1A, page 11. Contaminated
combustion air will damage the boiler,
resulting in possible severe personal
injury, death or substantial property
damage. Do not pipe combustion air near
a swimming pool, for example. Also,
avoid areas subject to exhaust fumes from
laundry facilities. These areas will always
contain contaminants.
Page 11
1 Determine boiler location (continued)
Installation & Operation Manual
When using an existing vent system to
install a new boiler:
WARNING
Check the following venting components before installing:
• Material - For materials listed for use with this appliance,
see Section 3 - General Venting, Table 3A. For stainless
steel venting, an adapter of the same manufacturer
(Table 3B) must be used at the flue collar connection.
• Size - To ensure proper pipe size is in place, see Table 3C.
Check to see that this size is used throughout the vent
system.
• Manufacturer - For a stainless steel application, you
must use only the listed manufacturers and their type
product listed in Table 3A for CAT IV positive pressure
venting with flue producing condensate.
• Supports - Non-combustible supports must be in place
allowing a minimum 1/4" rise per foot. The supports
should adequately prevent sagging and vertical slippage,
by distributing the vent system weight. For additional
information, consult the vent manufacturer’s
instructions for installation.
Failure to follow all instructions can result
in flue gas spillage and carbon monoxide
emissions, causing severe personal injury
or death.
Table 1A Corrosive Contaminants and Sources
Products to avoid:
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
Adhesives used to fasten building products and other
similar products
Areas likely to have contaminants
• Terminations - Carefully review Sections 3 through 5 to
ensure requirements for the location of the vent and air
terminations are met and orientation of these fit the
appropriate image from the Sidewall or Vertical
options listed in the General Venting Section. For
stainless steel vent, only use terminations listed in Table
3B for the manufacturer of the installed vent.
• Seal - With prior requirements met, the system should be
tested to the procedure listed in parts (c) through (f) of
the Removal of an Existing Boiler Section on page 12.
With stainless steel vent, seal and connect all pipe and
components as specified by the vent manufacturer used; with
PVC/CPVC vent, see the Installing Vent or Air Piping Section
on page 16.
WARNING
If any of these conditions are not met,
the existing system must be updated or
replaced for that concern. Failure to
follow all instructions can result in flue gas
spillage and carbon monoxide emissions,
causing severe personal injury or death.
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
11
Page 12
1 Determine boiler location
When removing a boiler from existing
common vent system:
Installation & Operation Manual
DANGER
WARNING
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected
to the common venting system placed in operation, while
the other appliances remaining connected to the common
venting system are not in operation.
a. Seal any unused openings in the common venting system.
b. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage
or restriction, leakage, corrosion, or other deficiencies,
which could cause an unsafe condition.
c. Test vent system – Insofar as is practical, close all building
doors and windows and all doors between the space
in which the appliances remaining connected to the
common venting system are located and other spaces of
the building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn on
any exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace dampers.
Do not install the Knight boiler into a
common vent with any other appliance.
This will cause flue gas spillage or appliance
malfunction, resulting in possible severe
personal injury, death, or substantial
property damage.
Failure to follow all instructions can result
in flue gas spillage and carbon monoxide
emissions, causing severe personal injury
or death.
g. Any improper operation of the common venting system
should be corrected so the installation conforms with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or
CAN/CSA B149.1, Natural Gas and Propane Installation
Code. When resizing any portion of the common venting
system, the common venting system should be resized
to approach the minimum size as determined using the
appropriate tables in Part 11 of the National Fuel Gas Code,
ANSI Z223.1/NFPA and/or CAN/CSA B149.1, Natural Gas
and Propane Installation Code.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.
e. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined herein, return
doors, windows, exhaust fans, fireplace dampers, and any
other gas-burning appliance to their previous conditions
of use.
12
Page 13
2 Prepare boiler
Remove boiler from wood pallet
1. After removing the outer shipping carton from the boiler,
remove the parts box.
2. Remove the front door to access the lag bolts in front of
the unit (FIG. 2-1).
3. To remove the boiler from the pallet (after removing the
front door):
a. Remove the two lag bolts from the wood pallet
inside the boiler (FIG. 2-1).
b. Detach the boiler from the lag bolts in the rear of the
unit, see FIG. 2-1.
NOTICE
Figure 2-1 Boiler Mounted on Shipping Pallet
Do not drop the boiler or bump the jacket
on the floor or pallet. Damage to the
boiler can result.
Installation & Operation Manual
5. After installation is complete, attach the propane conversion
label (in the conversion kit bag) next to the boiler rating
plate. Attach the LP caution label (in the conversion kit
bag) to the left side of the unit in the lower left corner.
6. Replace the top and front access covers.
Table 2A LP Conversion Table
LP Conversion Table
ModelLP Orifice Stamping
8180
106105
151150
211210 / W150
286285
WARNING
After converting to LP, check combustion
per the Start-up procedure in Section 10
of this manual. Failure to check and verify
combustion could result in severe personal
injury, death, or substantial property damage.
. 2
Gas conversions
WARNING
1. Remove the top and front access covers from the unit (no
tools required for removal).
2. Remove the three screws securing the gas valve to the
venturi (FIG. 2-2).
3. Locate the propane orifice disk from the conversion kit
bag. Verify that the stamping on the orifice disk matches
the boiler size (see Table 2A).
Place the orifice into the black rubber grommet in the
side of the gas valve and secure in the valve (FIG. 2-2).
4. Reposition the gas valve against the venturi and replace
the screws (FIG. 2-2) securing the valve to the venturi.
For a boiler already installed, you must
turn off gas supply, turn off power and
allow boiler to cool before proceeding.
You must also completely test the boiler
after conversion to verify performance
as described under Start-up, Section 10
of this manual. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
You must install a propane orifice to
operate the Knight boiler on propane gas.
Verify when installing that the orifice size
marking matches boiler size (Table 2A).
Figure 2-2 Installing Propane Orifice
Leveling the boiler
1. Set the boiler in place and check level.
a) Adjust legs if necessary to level boiler, see FIG. 2-3
below.
Figure 2-3 Leveling Legs on the Boiler
13
Page 14
3 Generalventing
Direct venting options - Sidewall Vent
Installation & Operation Manual
Figure 3-1 PVC/CPVC Two-Pipe Sidewall
Termination - See page 21 for more details
Figure 3-2 Stainless Steel Two-Pipe - See page 22
for more details
Figure 3-3 PVC/CPVC Concentric Sidewall
Termination - See page 25 for more details
14
Page 15
3 Generalventing (continued)
Direct venting options - Vertical Vent
Installation & Operation Manual
Figure 3-4 PVC/CPVC Two-Pipe
Vertical Termination - See page
28 for more details
Figure 3-5 Stainless Steel TwoPipe Vertical Termination - See
page 28 for more details
Figure 3-6 PVC/CPVC Concentric
Vertical Termination - See page 30
for more details
Direct venting options - Vertical Vent, Sidewall Air
Figure 3-7 PVC/CPVC Vertical Vent, Sidewall Air See page 20 for more details
NOTICE
Stainless steel vent/air design and terminations will vary slightly by manufacturer.
Figure 3-8 Stainless Steel Vertical Vent, Sidewall Air
- See page 20 for more details
15
Page 16
3 Generalventing
Install vent and combustion air piping
Installation & Operation Manual
DANGER
The Knight boiler must be vented and
supplied with combustion and ventilation
air as described in this section. Ensure the
vent and air piping and the combustion
air supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section 1
of this manual.
Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.
Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.
PVC/CPVC vent piping materials
WARNING
NOTICE
WARNING
NOTICE
WARNING
16
Use only the materials listed in Table
3A for vent pipe, and fittings. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
For closet and alcove installations, CPVC
or stainless steel material MUST BE used in
a closet/alcove structure. Failure to follow
this warning could result in fire, personal
injury, or death.
All PVC vent pipes must be glued, properly
supported, and the exhaust must be
pitched a minimum of a 1/4 inch per foot
back to the boiler (to allow drainage of
condensate).
This appliance requires a special venting
system. The vent connection to the
appliance must be made with the starter
CPVC pipe section provided with the
appliance if PVC/CPVC vent is to be used.
For stainless steel venting use an adapter
from Table 3B (page 19) that corresponds
with the intended vent manufacturer to
be used and discard the CPVC starter
piece. The field provided vent fittings must
be cemented to the CPVC pipe section
using an “All Purpose Cement” suitable for
PVC and CPVC pipe. Use only the vent
materials, primer, and cement specified in
this manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.
WARNING
Insulation should not be used on PVC
or CPVC venting materials. The use of
insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.
Requirements for installation in
Canada
1. Installations must be made with a vent pipe system
certified to ULC-S636.
IPEX is an approved vent manufacturer in Canada
supplying vent material listed to ULC-S636.
2. The first three (3) feet of plastic vent pipe from the
appliance flue outlet must be readily accessible for visual
inspection.
3. The components of the certified vent system must not be
interchanged with other vent systems or unlisted
pipe/fittings. For concentric vent installations, the inner
vent tube must be replaced with field supplied certified vent
material to comply with this requirement.
4. The 3" Concentric Vent Kit available from Lochinvar (see
Section 4 – Sidewall Termination – Optional Concentric Vent) and the 3" Concentric Vent Kit available from IPEX
are both approved for use on the Knight boiler. Both
kits are listed to the ULC-S636 standard for use in Canada.
CAUTION
Installing vent and air piping
NOTICE
1. Work from the boiler to vent or air termination. Do not
exceed the lengths given in this manual for the air or vent
piping.
2. Cut pipe to the required lengths and deburr the inside and
outside of the pipe ends.
3. Chamfer outside of each pipe end to ensure even cement
distribution when joining.
4. Clean all pipe ends and fittings using a clean dry rag.
(Moisture will retard curing and dirt or grease will prevent
adhesion.)
5. Dry fit vent or air piping to ensure proper fit up before
assembling any joint. The pipe should go a third to
two-thirds into the fitting to ensure proper sealing after
cement is applied.
Improper installation of PVC or CPVC
systems may result in injury or death.
Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.
Page 17
Installation & Operation Manual
3 Generalventing (continued)
6. Priming and Cementing:
a. Handle fittings and pipes carefully to prevent
contamination of surfaces.
b. Apply a liberal even coat of primer to the fitting
socket.
c. Apply a liberal even coat of primer to the pipe end to
approximately 1/2" beyond the socket depth.
d. Apply a second primer coat to the fitting socket.
e. While primer is still wet, apply an even coat of
approved cement to the pipe equal to the depth of
the fitting socket.
Table 3A Vent Pipe, and Fittings
All vent pipe materials and fittings must comply with the following:
*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure
no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method,
see manufacturer’s instructions.
f. While primer is still wet, apply an even coat of
approved cement to the fitting socket.
g. Apply a second coat of cement to the pipe.
h. While the cement is still wet, insert the pipe into the
fitting, if possible twist the pipe a 1/4 turn as you insert
it. NOTE: If voids are present, sufficient cement was not applied and joint could be defective.
i. Wipe excess cement from the joint removing ring or
beads as it will needlessly soften the pipe.
Standards for installation in:
United StatesCanada
CPVC and PVC venting must be ULC-S636
Certified. IPEX is an approved manufacturer
in Canada supplying vent material listed to
ULC-S636.
PVC/CPVC air intake/vent connections
1. Combustion Air Intake Connector (FIG.’s 3-9 and 3-10) - Used to provide combustion air directly to the unit from
outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines
listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.
2. Vent Connector (FIG.’s 3-9 and 3-10) - Used to provide a passageway for conveying combustion gases to the outside. A
transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code,
Section 305, Table 305.4 or as local codes dictate.
Figure 3-9 Near Boiler PVC/CPVC Venting Models
81 - 211
AIR
VENT
3” CPVC PIPE SUPPLIED WITH BOILER
MUST BE USED FOR VENT CONNECTION
NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN CLOSET
AND ALCOVE INSTALLATIONS.
Figure 3-10 Near Boiler PVC/CPVC Venting Model 286
4” CPVC PIPE SUPPLIED WITH BOILER
MUST BE USED FOR VENT CONNECTION
NOTE: CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN CLOSET
AND ALCOVE INSTALLATIONS.
17
Page 18
3 Generalventing
Installation & Operation Manual
Air inlet pipe materials:
The air inlet pipe(s) must be sealed. Choose acceptable
combustion air inlet pipe materials from the following list:
PVC, CPVC or ABS
Dryer Vent or Sealed Flexible Duct (not recommended
for rooftop air inlet)
Galvanized steel vent pipe with joints and seams sealed as
specified in this section.
Type “B” double-wall vent with joints and seams sealed as
specified in this section.
AL29-4C, stainless steel material to be sealed to
specification of its manufacturer.
*Plastic pipe may require an adapter (not provided) to
transition between the air inlet connection on the appliance
and the plastic air inlet pipe.
WARNING
NOTICE
Sealing of Type “B” double-wall vent material or galvanized
vent pipe material used for air inlet piping on a sidewall or
vertical rooftop Combustion Air Supply System:
a. Seal all joints and seams of the air inlet pipe using either
Aluminum Foil Duct Tape meeting UL Standard 723 or
181A-P or a high quality UL Listed silicone sealant such as
those manufactured by Dow Corning or General Electric.
b. Do not install seams of vent pipe on the bottom of
horizontal runs.
c. Secure all joints with a minimum of three sheet metal
screws or pop rivets. Apply Aluminum Foil Duct Tape or
silicone sealant to all screws or rivets installed in the vent
pipe.
d. Ensure that the air inlet pipes are properly supported.
Using vent or air intake materials other
than those specified, failure to properly
seal all seams and joints or failure to follow
vent pipe manufacturer’s instructions can
result in personal injury, death or property
damage. Mixing of venting materials will
void the warranty and certification of the
appliance.
The use of double-wall vent or insulated
material for the combustion air inlet pipe is
recommended in cold climates to prevent
the condensation of airborne moisture in
the incoming combustion air.
When a sidewall or vertical rooftop combustion air supply
system is disconnected for any reason, the air inlet pipe must
be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.
DANGER
Failure to properly seal all joints and seams
as required in the air inlet piping may
result in flue gas recirculation, spillage
of flue products and carbon monoxide
emissions causing severe personal injury
or death.
Stainless steel vent
This product has been approved for use with stainless steel
using the manufacturers listed in Table 3A.
WARNING
NOTICE
NOTICE
NOTICE
Use only the materials, vent systems, and
terminations listed in Table 3B. DO
NOT mix vent systems of different types
or manufacturers, unless listed in this
manual. Failure to comply could result
in severe personal injury, death, or
substantial property damage.
Installations must comply with applicable
national, state, and local codes. Stainless
steel vent systems must be listed as a
UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.
Installation of a stainless steel vent system
should adhere to the stainless steel vent
manufacturer’s installation instructions
supplied with the vent system.
The installer must use a specific vent starter
adapter at the flue collar connection,
supplied by the vent manufacturer to
adapt to its vent system. See Table 3B for
approved vent adapters. Discard CPVC
starter piece.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and
sealed with the pipe manufacturer’s recommended solvents
and standard commercial pipe cement for the material used.
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe
should use a silicone sealant to ensure a proper seal at the
appliance connection and the air inlet cap connection. Dryer
vent or flex duct should use a screw type clamp to seal the vent
to the appliance air inlet and the air inlet cap. Proper sealing
of the air inlet pipe ensures that combustion air will be free of
contaminants and supplied in proper volume.
18
Page 19
3 Generalventing (continued)
Installation & Operation Manual
Stainless steel air intake/vent connections
Figure 3-11 Near Boiler Stainless Steel Venting Model 286
1. Combustion Air Intake Connector (FIG. 3-11) - Used to
provide combustion air directly to the unit from
outdoors. A fitting is provided on the unit for final
connection. Combustion air piping must be supported
per guidelines listed in the National Mechanical Code,
Section 305, Table 305.4 or as local codes dictate.
2. Vent Connector (FIG. 3-11) - Used to provide a
passageway for conveying combustion gases to the
outside. A transition fitting is provided on the unit for
final connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.
Table 3B Approved Stainless Steel Terminations and Adapters
ProTechHeat FabZ Flex
FasNSealSaf-T VentZ-Vent
Model
81 - 211
Boiler
Adapter
300715
Flue
Termination
FSBS3
FSRC3(R.C)
Intake
Air
Termination
303889KB80210 9353BUREZ-1*
Boiler
Adapter
Intermediate
Adapter
Flue
Termination
9392
5300CI
3" S.S. ADAPTER
3" S.S. INTERMEDIATE
(FOR SAF-T VENT ONLY)
Intake
Air
Termination
9314TERM 2SVSLA03
Boiler
Adapter
Flue
Termination
2SVSTP03
2SVSRCX03
Intake Air
Termination
2SVSTEX0390
286
F303759
FSBS4
FSRC4(R.C.)
FSAIH04
303888
KB285600 9454BUREZ-1*
9492
5400CI
9414TERM 2SVSLA04
2SVSTP04
2SVSRCX04
2SVSTEX0490
* = This adapter must be used in addition to the boiler adapter for Saf-T vent pipe as shown in FIG. 3-11, unless approved vent
other than standard diameter is used. Consult a Heat Fab representative for questions.
The Knight boiler uses model specific combustion air intake
and vent piping sizes as detailed in Table 3C below.
Minimum / Maximum allowable combustion
air and vent piping lengths are as follows:
Combustion Air = 12 equivalent feet minimum / 100 equivalent
The appliance output rating will reduce by
up to 1.5% for each 25 feet of vent length.
19
Page 20
3 Generalventing
Table 3D Concentric Vent KitEquivalent Vent Lengths
ModelKit Number
81 - 211CVK30033 feet
286CVK30073 feet
Removing from existing vent
Equivalent Vent
Length
Installation & Operation Manual
• There will be a noticeable increase in the noise level
during normal operation from the inlet air opening.
• Using the room air kit makes the unit vulnerable to
combustion air contamination from within the
building. Please review Section 1, Prevent Combustion
Air Contamination, to ensure proper installation.
• Vent system and terminations must comply with the
standard venting instructions set forth in this manual.
Follow the instructions in Section 1, page 12 of this manual
when removing a boiler from an existing vent system.
Vent and air piping
Vent and air system:
NOTICE
You must also install air piping from outside to the boiler air
intake adapter. The resultant installation is direct vent (sealed
combustion).
You may use any of the vent/air piping methods covered in
this manual. Do not attempt to install the Knight boiler using
any other means.
WARNING
Vent, air piping and termination:
The Knight boiler vent and air piping can be installed through
the roof or through a sidewall. Follow the procedures in this
manual for the method chosen. Refer to the information
in this manual to determine acceptable vent and air piping
length.
Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
DO NOT mix components from different
systems. The vent system could fail,
causing leakage of flue products into the
living space. Use only approved stainless
steel, PVC or CPVC pipe and fittings. For
PVC/CPVC use with primer and cement
specifically designed for the material used.
Optional room air
NOTICE
Commercial applications utilizing the Knight boiler may
be installed with a single pipe carrying the flue products to
the outside while using combustion air from the equipment
room. In order to use the room air venting option the
following conditions and considerations must be followed.
• The unit MUST be installed with the appropriate
room air kit (Table 3E).
• The equipment room MUST be provided with
properly sized openings to assure adequate
combustion air. Please refer to instructions provided
with the room air kit.
20
Optional room air is intended for
commercial applications. Combustion
air piping to the outside is recommended
for residential applications.
WARNING
Table 3E Optional Room Air Kit
Model Kit Number
81 - 211KIT30052
286KIT30053
Air contamination
Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of flue gas spillage or
boiler water leakage into the building.
Please read the information given in Table 1A, page 11,
listing contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
combustion air and vent to another location, per this manual.
WARNING
WARNING
When utilizing the single pipe method,
provisions for combustion and ventilation
air must be in accordance with Air for
Combustion and Ventilation, of the latest
edition of the National Fuel Gas Code,
ANSI Z223.1, in Canada, the latest edition
of CGA Standard B149 Installation Code for
Gas Burning Appliances and Equipment, or
applicable provisions of the local building
codes.
If the boiler combustion air inlet is located in
a laundry room or pool facility, for example,
these areas will always contain hazardous
contaminants.
To prevent the potential of severe personal
injury or death, check for areas and products
listed in Table 1A, page 11 before installing
the boiler or air inlet piping.
If contaminants are found, you MUST:
• Remove contaminants permanently.
—OR—
• Relocate air inlet and vent terminations
to other areas.
Page 21
4 Sidewall directventing
Installation & Operation Manual
Vent/air termination – sidewall
WARNING
WARNING
WARNING
NOTICE
Determine location
Locate the vent/air terminations using the following guidelines:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page 19
of this manual.
2. You must consider the surroundings when terminating
the vent and air:
a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.
b. The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.
c. Prevailing winds could cause freezing of
condensate and water/ice buildup where flue
products impinge on building surfaces or plants.
d. Avoid possibility of accidental contact of flue
products with people or pets.
e. Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.
Follow instructions below when determining
vent location to avoid possibility of severe
personal injury, death, or substantial
property damage.
A gas vent extending through an exterior
wall shall not terminate adjacent to a wall
or below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
Do not connect any other appliance to the
vent pipe or multiple boilers to a common
vent pipe. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
Installation must comply with local
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S. installations
or CSA B149.1 for Canadian installations.
Figure 4-1A PVC/CPVC Sidewall Termination of Air
and Vent
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
POSSIBLE ORIENTATIONS
VENT / AIR
TERMINATION
GRADE OR
SNOW LINE
12"
MIN
TO
OVERHANG
12"
MIN
Table 4A Sidewall Vent Kits
ModelKit NumberVent Size
81 - 211KIT300453 inch vent
286KIT300464 inch vent
If using the alternate sidewall termination:
3. The air piping must terminate in a down-turned elbow
as shown in FIG. 4-1B. This arrangement avoids
recirculation of flue products into the combustion air
stream.
4. The vent piping must terminate in an elbow pointed
outward or away from the air inlet, as shown in FIG. 4-1B.
WARNING
Figure 4-1B Alternate PVC/CPVC Sidewall Termination
of Air and Vent w/Field Supplied Fittings
Do not exceed the maximum lengths of the
outside vent piping shown in FIG. 4-1B.
Excessive length exposed to the outside
could cause freezing of condensate in the
vent pipe, resulting in potential boiler
shutdown.
WARNING
Sidewall vent and air inlet terminations
must terminate in the same pressure zone.
f. Do not terminate above any door or window.
Condensate can freeze, causing ice formations.
g. Locate or guard vent to prevent condensate damage
to exterior finishes.
Figure 4-1D Alternate PVC/CPVC/SS Venting
Arrangement - Typical Stainless Steel Sidewall
Termination of Air and Vent w/Field Supplied Fittings,
Utilizing 90° Elbow Intake
COUPLING
12” MIN
15” MAX
BIRD SCREEN
12”
MIN
Installation & Operation Manual
5. Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,
pages 21 and 23. Also maintain the following:
a. Vent must terminate:
• At least 6 feet from adjacent walls.
• No closer than 12 inches below roof overhang.
• At least 7 feet above any public walkway.
• At least 3 feet above any forced air intake within
10 feet.
• No closer than 12 inches below or horizontally
from any door or window or any other gravity air
inlet.
b. Air inlet must terminate at least 12 inches above
grade or snow line; at least 12 inches below the vent
termination; and the vent pipe must not extend
more than 24 inches vertically outside the building
as shown in FIG. 4-1B.
c. Do not terminate closer than 4 feet horizontally
from any electric meter, gas meter, regulator, relief
valve, or other equipment. Never terminate above or
below any of these within 4 feet horizontally.
6. Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
BIRD SCREEN
GRADE OR
SNOW LINE
MODELS 80 - 285
12" MIN
12" MIN
15" MAX
Figure 4-1E Alternate SS Venting Arrangement Typical Stainless Steel Sidewall Termination of Air and
Vent w/Field Supplied Fittings, Utilizing FasNSeal’s
Hood Intake
TO BOILER
INTAKE AIR
CONNECTION
FROM BOILER
VENT PIPE
CONNECTION
BIRD SCREEN
12" (305 MM) MIN
15" (381 MM) MAX
Figure 4-2A Clearance to Gravity Air Inlets
12"
MIN.
VENT / AIR
TERMINATION
12"
MIN.
12"
MIN.
Figure 4-2B Alternate Clearance to Gravity Air Inlets w/
Field Supplied Fittings
12”
MIN.
12" (305 MM) MIN
GRADE OR
SNOW LINE
MODEL 285 WITH FASNSEAL ONLY
22
12”
MIN.
12”
MIN.
BIRD
SCREEN
(TYPICAL)
Page 23
4 Sidewall direct venting (continued)
Figure 4-3A Clearance to Forced Air Inlets
IF LESS
THAN 10’
VENT / AIR
TERMINATION
36"
MIN.
FORCED AIR
INLET
4. Assemble the vent cap to the vent plate (see FIG. 4-4A).
Insert the stainless steel screws into the vent cap screw
hole openings and securely attach the vent cap to the vent
plate.
5. Seal all wall cavities.
Figure 4-4A Sidewall Termination Assembly
Installation & Operation Manual
AIR PIPING
7' MIN. ABOVE ANY
PUBLIC WALKWAY
Figure 4-3B Alternate Clearance to Forced Air Inlets w/
Field Supplied Fittings
7’ MIN. ABOVE ANY
PUBLIC WALKWAY
Prepare wall penetrations
1. Use the factory supplied wall plate as a template to locate
the vent and air intake holes and mounting holes.
Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the
vent pipe outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors
into the wall.
2. Install the vent and air intake piping through the wall
into the vent plate openings. Seal all gaps between the
pipes and wall. Use RTV silicone sealant to seal the air
pipe. Use the cement/primer listed in Table 3A on page
17 to seal the vent pipe.
3. Mount and secure the vent plate to the wall using
stainless steel screws. Seal around the plate to the wall
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the vent
pipe outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole as shown in FIG. 4-4B.
3. Use a sidewall termination plate as a template for correct
location of hole centers.
4. Follow all local codes for isolation of vent pipe when
passing through floors or walls.
5. Seal exterior openings thoroughly with exterior caulk.
Figure 4-4B Alternate Sidewall Termination Assembly w/
Field Supplied Fittings
ELBOW
AIR PIPING
VENT PIPING
BIRD SCREEN
GALVANIZED
THIMBLE
SIDEWALL
TERMINATION PLATE
ELBOW
BIRD SCREEN
23
Page 24
4 Sidewall direct venting
Installation & Operation Manual
Termination and fittings
1. The air termination coupling must be oriented at least
12 inches above grade or snow line as shown in FIG. 4-1A,
page 21.
2. Maintain the required dimensions of the finished
termination piping as shown in FIG. 4-1A, page 21.
3. If using the alternate sidewall termination do not extend
exposed vent pipe outside of the building more than what
is shown in this document. Condensate could freeze and
block vent pipe.
4. PVC/CPVC terminations are designed to accommodate
any wall thickness of standard constructions per the
directions found in this manual.
5. Stainless steel terminations are designed to penetrate
walls with a thickness up to 9.25 inches of standard
construction.
Multiple vent/air terminations
1. When terminating multiple Knight boilers terminate
each vent/air connection as described in this manual
(FIG. 4-5A).
Figure 4-5A Multiple Vent Terminations (must also
comply with Figure 4-1A)
12" MIN. BETWEEN EDGE OF AIR
INLET AND ADJACENT VENT OUTLET
VENT
AIR
VENT / AIR
TERMINATION
Figure 4-5B Alternate Multiple Vent Terminations w/Field
Supplied Fittings (must also comply with Figure 4-1B)
WARNING
All vent pipes and air inlets must
terminate at the same height to avoid
possibility of severe personal injury,
death, or substantial property damage.
2. Place wall penetrations to obtain minimum clearance
of 12 inches between edge of air inlet and adjacent vent
outlet, as shown in FIG. 4-5A for U.S. installations. For
Canadian installations, provide clearances required by
CSA B149.1 Installation Code.
3. The air inlet of a Knight boiler is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent boiler vents.
24
Page 25
Installation & Operation Manual
4 Sidewall direct venting (continued)
Sidewall termination – optional concentric vent
Description and usage
Lochinvar offers optional concentric combustion air and vent
pipe termination kits (Factory Kit #CVK3003 for 3" diameter
- Models 81 - 211 and #CVK3007 for 4" diameter - Model
286). Both combustion air and vent pipes must attach to
the termination kit. The termination kits must terminate
outside the structure and must be installed as shown below
in FIG. 4-6.
The required combustion air and vent pipe materials are
listed in Table 3A, on page 17 of this manual.
Figure 4-6 Concentric Sidewall Termination
e. Do not terminate above any door or window.
Condensate can freeze, causing ice formations.
f. Locate or guard vent to prevent condensate damage
to exterior finishes.
4. Cut one (1) hole (5 inch diameter for #CVK3003
installations or 7 inch diameter for #CVK3007 installations)
into the structure to install the termination kit.
5. Partially assemble the concentric vent termination kit.
Clean and cement using the procedures found in these
instructions.
a. Cement the Y concentric fitting to the larger kit pipe
(FIG.’s 4-7 and 4-8).
b. Cement the rain cap to the smaller diameter kit pipe
(FIG.’s 4-7 and 4-8).
Sidewall termination installation
1. Determine the best location for the termination kit (see
FIG. 4-6).
2. The total length of piping for vent or air must not exceed
the limits given in the General Venting section on page 19
of this manual.
3. You must consider the surroundings when terminating
the vent and air:
a. Position the vent termination where vapors will not
damage nearby shrubs, plants or air conditioning
equipment or be objectionable.
b. The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.
c. Prevailing winds could cause freezing of condensate
and water/ice buildup where flue products impinge
on building surfaces or plants.
d. Avoid possibility of accidental contact of flue
products with people or pets.
Instead of cementing the smaller pipe
to the rain cap, a field-supplied stainless
steel screw may be used to secure the
two (2) components together when field
disassembly is desired for cleaning (see
FIG. 4-11).
WARNING
When using the alternate screw assembly
method, drill a clearance hole in the rain
cap and a pilot hole in the vent pipe for
the screw size being used. Failure to
drill adequate holes may cause cracking of
PVC components, allowing combustion
products to be recirculated. Failure to
follow this warning could result in personal
injury or death.
WARNING
Do not operate the appliance with the rain
cap removed or recirculation of combustion
products may occur. Water may also collect
inside the larger combustion air pipe and
flow to the burner enclosure. Failure to
follow this warning could result in product
damage or improper operation, personal
injury, or death.
Figure 4-11 Rain Cap to Vent Pipe Alternate Assembly
Figure 4-10 Concentric Vent Dimensional Drawing -
Model 286
"A"
"B" DIA.
"G"
3"
(76 MM)
"H" DIA.
"D"
"E"
"F"
"B" DIA. PVC
VENT / EXHAUST
"C" DIA.
6. Install the Y concentric fitting and pipe assembly through
the structure’s hole from an inside wall.
NOTICE
Do not allow insulation or other materials to
accumulate inside the pipe assembly when
installing through the hole.
7. Install the rain cap and small diameter pipe assembly into
the Y concentric fitting and large pipe assembly from an
outside wall. Ensure small diameter pipe is bottomed
and cemented in the Y concentric fitting for #CVK3003
installations and fastened tightly into the rubber adapter for
#CVK3007 installations.
8. Secure the assembly to the structure as shown in FIG. 4-12
using field-supplied metal strapping or equivalent support
material.
NOTICE
NOTICE
Ensure termination location clearance
dimensions are as shown in FIG. 4-6.
If assembly needs to be extended to allow
sidewall thickness requirement, the two (2)
pipes supplied in the kit may be replaced
by using the same diameter, field-supplied
SDR-26 PVC (D2241) pipe for CVK3003
and standard schedule 40 PVC for CVK3007.
Do not extend dimension D* more than 60
inches (see FIG.’s 4-9 and 4-10).
26
NOTICE
If assembly depth needs to be reduced,
dimension D can be as short as possible.
Page 27
Installation & Operation Manual
4 Sidewall direct venting (continued)
Sidewall termination – optional concentric vent
Figure 4-12 Concentric Vent Sidewall Attachment
Note: CVK3003 shown for illustration purposes.
CAUTION
9. Cement appliance combustion air and vent pipes to
the concentric vent termination assembly. See FIG.
4-12 for proper pipe attachment.
10. Operate the appliance one (1) heat cycle to ensure
combustion air and vent pipes are properly connected
to the concentric vent termination connections.
DO NOT use field-supplied couplings
to extend pipes. Airflow restriction
will occur and may cause intermittent
operation.
Multiventing sidewall terminations
When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see
FIG. 4-13). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 4-13. It is important that vent terminations be made as
shown to avoid recirculation of flue gases.
Figure 4-13 Concentric Vent and Combustion Air Termination
12"
MINIMUM
VENT
COMBUSTION
AIR
27
Page 28
5 Vertical direct venting
Vent/air termination – vertical
Installation & Operation Manual
WARNING
Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death
or substantial property damage.
WARNING
Do not connect any other appliance to the
vent pipe or multiple boilers to a common
vent pipe. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
NOTICE
Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
Determine location
Locate the vent/air terminations using the following
guidelines:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page
19 of this manual.
WARNING
Rooftop vent and air inlet terminations
must terminate in the same pressure
zone, unless vertical vent sidewall air is
set up as shown in the General Venting Vertical Vent, Sidewall Air Section.
Figure 5-1A PVC/CPVC Vertical Termination of Air and
Vent
ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” OF VENT
PIPE
BIRD SCREEN
(TYPICAL)
VENT
COUPLING
(FIELD SUPPLIED)
VENT OUTLET
12” MINIMUM
ABOVE AIR INLET
COMBUSTION
AIR
6” MINIMUM
ABOVE ROOF /
SNOW LINE
2. The vent must terminate at least 3 feet above the highest
place in which the vent penetrates the roof and at least
2 feet above any part of a building within 10 horizontal
feet.
3. The air piping must terminate in a down-turned 180°
return pipe no further than 2 feet from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.
4. The vent piping must terminate in an up-turned coupling
as shown in FIG. 5-1A. The top of the coupling must
be at least 1 foot above the air intake. When the vent
termination uses a rain cap as illustrated in FIG. 5-1B
maintain at least 36" (914 mm) above the air inlet. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than
2 feet (.6 m) apart and with the vent termination at least
1 foot above the air intake.
Figure 5-1B Stainless Steel Vertical Termination of Air
and Vent
ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” (610 MM)
OF VENT PIPE
BIRD SCREEN
(TYPICAL)
6" (152 MM) MINIMUM
ABOVE ROOF /
SNOW LINE
VENT OUTLET
36” (914 MM) MINIMUM
ABOVE AIR INLET
VENT
COM,BUSTION
AIR
5. Locate terminations so they are not likely to be damaged
by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.
28
Page 29
5 Vertical direct venting (continued)
Vent/air termination – vertical
Installation & Operation Manual
Prepare roof penetrations
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole with at least a 1/2 inch clearance around the
vent pipe outer diameter:
• 4½ inch hole for 3 inch vent pipe
• 5½ inch hole for 4 inch vent pipe
b. Insert a galvanized metal thimble in the vent pipe
hole.
3. Space the air and vent holes to provide the minimum
spacing shown in FIG. 5-1A, page 28.
4. Follow all local codes for isolation of vent pipe when
passing through floors, ceilings, and roofs.
5. Provide flashing and sealing boots sized for the vent pipe
and air pipe.
Termination and fittings
Multiple vent/air terminations
1. When terminating multiple Knight boilers, terminate
each vent/air connection as described in this manual
(FIG. 5-2).
WARNING
2. Place roof penetrations to obtain minimum clearance of
12 inches between edge of air intake elbow and adjacent
vent pipe of another boiler for U.S. installations (see
FIG. 5-2). For Canadian installations, provide clearances
required by CSA B149.1 Installation Code.
3. The air inlet of a Knight boiler is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent boiler vents.
Figure 5-2 Vertical Terminations with Multiple Boilers
Terminate all vent pipes at the same height
and all air pipes at the same height to
avoid possibility of severe personal injury,
death, or substantial property damage.
1. Prepare the vent termination coupling and the air
termination elbow (FIG. 5-1A) by inserting bird screens.
Bird screens should be obtained locally.
2. The air piping must terminate in a down-turned 180°
return bend as shown in FIG. 5-1A. Locate the air
inlet pipe no further than 2 feet from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.
3. The vent piping must terminate in an up-turned coupling
as shown in FIG. 5-1A. The top of the coupling must
be at least 1 foot above the air intake. When the vent
termination uses a rain cap as illustrated in FIG. 5-1B
maintain at least 36" (914 mm) above the air inlet. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than
2 feet apart and with the vent termination at least 1 foot
above the air intake.
4. Maintain the required dimensions of the finished
termination piping as shown in FIG. 5-1A.
5. Do not extend exposed vent pipe outside of building
more than shown in this document. Condensate could
freeze and block vent pipe.
Figure 5-3 Alternate Vertical Terminations with Multiple
Boilers
29
Page 30
Installation & Operation Manual
5 Vertical direct venting
Vertical termination – optional concentric vent
Description and usage
Lochinvar offers an optional concentric combustion air and
vent pipe termination kit. Both combustion air and vent
pipes must attach to the termination kit. The termination kit
must terminate outside the structure and must be installed as
shown in FIG. 5-4.
Field supplied pipe and fittings are required to complete the
installation.
The required combustion vent pipe and fittings are listed in
Table 3A, on page 17 of this manual.
Vertical termination installation
1. See Section 5, Vertical Direct Venting - Determine
Location (where applicable).
Figure 5-4 Concentric Vertical Termination
2. Cut one (1) hole (5 inch diameter for #CVK3003
installations or 7 inch diameter for #CVK3007
installations) into the structure to install the termination
kit.
3. Partially assemble the concentric vent termination kit.
Clean and cement following the cleaning procedures in
these instructions.
a. Cement the Y concentric fitting to the larger
diameter kit pipe (see FIG.’s 4-7 and 4-8, page 25).
b. Cement rain cap to the smaller diameter kit pipe (see
FIG.’s 4-7 and 4-8, page 25).
NOTICE
WARNING
Instead of cementing the smaller pipe
to the rain cap, a field supplied stainless
steel screw may be used to secure the
two (2) components together when field
disassembly is desired for cleaning (see
FIG. 4-11, page 26).
When using the alternate screw assembly
method, drill a clearance hole in the rain
cap and a pilot hole in the vent pipe for
the screw size being used. Failure to drill
adequate holes may cause cracking of
PVC components, allowing combustion
products to be recirculated. Failure
to follow this warning could result in
personal injury or death.
Figure 5-5 Do Not Install U-Bend to Rain Cap
30
Page 31
Installation & Operation Manual
5 Vertical direct venting (continued)
Vertical termination – optional concentric vent
WARNING
Do not operate the appliance with
the rain cap removed or recirculation
of combustion products may occur.
Water may also collect inside the larger
combustion air pipe and flow to the
burner enclosure. Failure to follow this
warning could result in product damage
or improper operation, personal injury,
or death.
4. Install the Y concentric fitting pipe assembly up through
the structure’s hole and field supplied roof boot/flashing.
NOTICE
Do not allow insulation or other materials
to accumulate inside the pipe assembly
when installing through the hole.
5. Secure the assembly to the roof structure as shown
below in FIG. 5-6 using field supplied metal strapping or
equivalent support material.
Figure 5-6 Concentric Vent Roof Installation
Note: CVK3003 shown for illustration purposes.
CAUTION
DO NOT use field-supplied couplings
to extend pipes. Airflow restriction will
occur.
6. Install the rain cap and the small diameter pipe
assembly into the roof penetration assembly. Ensure
the small diameter pipe is cemented and bottomed in
the Y concentric fitting for #CVK3003 installations and
fastened tightly into the rubber adapter for #CVK3007
installations.
7. Cement the appliance combustion air and vent pipes to
the concentric vent termination assembly. See FIG. 5-6
for proper pipe attachment.
8. Operate the appliance through one (1) heat cycle to ensure
combustion air and vent pipes are properly connected to
the concentric vent termination connections.
Multiventing vertical terminations
When two (2) or more direct vent appliances are vented
near each other, each appliance must be individually vented
(see FIG. 5-7). NEVER common vent or breach vent this
appliance. When two (2) or more direct vent appliances
are vented near each other, two (2) vent terminations may
be installed as shown in FIG. 5-7. It is important that vent
terminations be made as shown to avoid recirculation of flue
gases.
NOTICE
NOTICE
Ensure termination height is above the
roof surface or anticipated snow level
(12 inches in U.S.A. or 18 inches in
Canada) as shown in FIG. 5-4, page 30.
If assembly is too short to meet height
requirement, the two (2) pipes supplied
in the kit may be replaced by using the
same diameter, field supplied SDR26 PVC (D2241) pipe for CVK3003
and standard schedule 40 PVC for
CVK3007. Do not extend dimension
D* more than 60 inches (see FIG.’s 4-9
and 4-10, page 26).
Figure 5-7 Concentric Vent and Combustion Air Vertical
Termination
12”
MINIMUM
COMBUSTION
AIR (TYPICAL)
12” (18” FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24” ABOVE ROOF.
31
Page 32
5 Vertical direct venting
A
A
Alternate vertical concentric venting
Installation & Operation Manual
This appliance may be installed with a concentric vent
arrangement where the vent pipe is routed through an
existing unused venting system; or by using the existing
unused venting system as a chase for vent and combustion
air routing.
Concentric Venting Arrangement
The venting is to be vertical through the roof. The annular
space between the O.D. of the vent pipe and the I.D. of the
existing unused venting system is utilized for the combustion
air source.
The minimum size of the existing vent system required to
achieve enough annular space for combustion air can be
found in Table 5A below.
The upper and lower termination as well as any other unsealed
joints in the existing vent system must be sealed to ensure that
all combustion air is drawn from under the vent cap as shown
in FIG.’s 5-8 and 5-9.
Approved venting materials must be used as specified in
Table 3A on page 17.
Follow all vent / air termination and clearance requirements
per this section to the appropriate example. Installation must
comply with local requirements and with the National Fuel
Gas Code.
The maximum allowable equivalent vent and air intake
lengths for this venting arrangement are to be determined
from the General Venting Section.
If an existing unused venting system is converted for use
with this method of concentric venting, the installer must
ensure that the existing venting system is clean and free from
particulate contamination that will harm this appliance and
cause increased nuisance calls or maintenance. See Table 1A
on page 11 for a list of corrosive contaminants and sources.
Two example scenarios of a concentric venting arrangement
are shown for illustrative purposes in FIG.’s 5-8 and 5-9.
Follow all existing termination and clearance requirements
and allowable pipe lengths. Use only approved venting
materials listed in the General Venting Section of this manual.
The Knight is designed to function in a closed loop pressurized
system not less than 12 psi. A temperature and pressure
gauge is included to monitor system pressure and outlet
temperature and should be located on the boiler outlet.
It is important to note that the boiler has a minimal
amount of pressure drop and must be figured in when
sizing the circulators. Each boiler installation must have
an air elimination device, which will remove air from
the system. Install the boiler so the gas ignition system
components are protected from water (dripping, spraying,
etc.) during appliance operation for basic service of circulator
replacement, valves, and others.
Observe a minimum of 1/4 inch (6 mm) clearance around all
un-insulated hot water pipes when openings around the
pipes are not protected by non-combustible materials.
Low water cutoff device
On a boiler installed above radiation level, some states and
local codes require a low water cutoff device at the time of
installation.
Chilled water system
If the boiler supplies hot water to heating coils in air handler
units, flow control valves or other devices must be installed to
prevent gravity circulation of heater water in the coils during
the cooling cycle. A chilled water medium must be piped in
parallel with the heater.
Freeze protection
Freeze protection for new or existing systems must use glycol
that is specially formulated for this purpose. This includes
inhibitors, which prevent the glycol from attacking the
metallic system components. Make certain to check that
the system fluid is correct for the glycol concentration and
inhibitor level. The system should be tested at least once
a year and as recommended by the producer of the glycol
solution. Allowance should be made for the expansion of the
glycol solution in the system piping.
WARNING
Use only inhibited propylene glycol
solutions, which are specifically formulated
for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used
in hydronic systems.
General piping information
3. Install purge and balance valve or shutoff valve and drain
on system return to purge air out of each zone.
4. Install a backflow preventer on the cold feed make-up water
line.
5. Install a pressure reducing valve on the cold feed makeup water line, (15 psi nominal). Check temperature and
pressure gauge (shipped separately), which should read a
minimum pressure of 12 psi.
6. Install a circulator as shown on the piping diagrams in this
section. Make sure the circulator is properly sized for the
system and friction loss.
7. Install an expansion tank on the system supply. Consult the
tank manufacturer’s instruction for specific information
relating to tank installation. Size the expansion tank for the
required system volume and capacity.
8. Install an air elimination device on the system supply.
9. Install a drain valve at the lowest point of the system.
Note: The boiler cannot be drained completely of water
without purging the unit with an air pressure of 15 psi.
10. This appliance is supplied with a relief valve sized in
accordance with ASME Boiler and Pressure Vessel Code,
Section IV (“Heating Boilers”). Pipe the discharge of the
safety relief valve to prevent injury in the event of pressure
relief. Pipe the discharge to a drain. Provide piping that is
the same size as the safety relief valve outlet. Never block
the outlet of the safety relief valve.
WARNING
*See the piping illustrations included in this section, FIG.’s 6-4
thru 6-10 for suggested guidelines in piping the Knight boiler
with either zone valves or circulator pumps.
NOTICE
CAUTION
The relief valve, tee and any necessary fittings
are shipped in the install kit with the boiler
and are to be field installed (FIG. 6-1).
*Please note that these illustrations are
meant to show system piping concept only,
the installer is responsible for all equipment
and detailing required by local codes.
The Knight boiler is capable of servicing
multiple temperature loop systems. It is the
responsibility of the installer to protect the
loops with lower temperature requirements
from higher temperatures that may be
required by other loops.
Basic steps are listed in this section along with illustrations on
the following pages (FIG.’s 6-4 thru 6-10), which will guide
you through the installation of the Knight boiler (reference
FIG.’s 6-2A and 6-2B).
1. Connect the system return marked “Inlet”.
2. Connect the system supply marked “Outlet”.
34
Page 35
6 Hydronic piping (continued)
Installation & Operation Manual
Relief valve and temperature and
pressure gauge installation
Basic steps are listed below to guide you through the
installation of the relief valve and the temperature and
pressure (T & P) gauge provided with the unit.
1. Install the tee with the 3/4 inch fitting positioned
vertically and on the top as shown in FIG. 6-1.
2. Install the relief valve into the 3/4 inch fitting of the tee
installed in Step 1 (FIG. 6-1).
3. Install a field provided close nipple and tee with the
fitting positioned vertically on the top on the
downstream side of the relief valve (see FIG. 6-1).
4. Install the temperature and pressure gauge provided with
the unit into the top fitting of the tee (a bushing may be
necessary) installed in Step 3 (FIG. 6-1).
Figure 6-1 Relief Valve / T & P Installation
Knight boilers are capable of controlling a variable
speed boiler circulator. Variable speed circulators
MUST be sized to meet the specified minimum flow
requirements listed in FIG. 6-3 on page 37 at full
speed.
3. Domestic hot water circulating pump:
Field supplied. The pump MUST be sized to meet
the specified minimum flow requirements listed in
FIG. 6-3. Consult the indirect water heater operating
guide to determine flow characteristics for the selected
product used.
4. Boiler isolation valves:
Field supplied. Full port ball valves are required.
Failure to use full port ball valves could result in a
restricted flow rate through the boiler.
5. Check valves:
Field supplied. Check valves are recommended for
installation as shown in FIG.’s 6-4 thru 6-10. Failure to
install check valves could result in a reverse flow
condition during pump(s) off cycle.
6. Domestic indirect hot water isolation valves:
Field supplied. Full port ball valves are required. Failure
to use full port ball valves could result in a restricted flow
rate through the boiler.
RELIEF VALVE
TEMPERATURE &
PRESSURE GAUGE
TEE W/FITTING ON TOP
(FIELD PROVIDED)
CLOSE NIPPLE
(FIELD PROVIDED)
TEE WITH 3/4” FITTING ON TOP
CLOSE NIPPLE
Near boiler piping components
1. Boiler system piping:
Boiler system piping MUST be sized per the pipe
requirements listed in Table 6A. Reducing the pipe size
can restrict the flow rate through the boiler, causing
inadvertent high limit shutdowns and poor system
performance. Flow rates are based on 20 feet of piping,
4 - 90° elbows, and 2 - fully ported ball valves.
2. Boiler system pump:
A Grundfos UPS26-99F pump will be provided by the
factory (for standard altitude models) as the boiler
circulation pump based on 20 feet of piping, 4 - 90°
elbows, and 2 - fully ported ball valves.
7. Anti-scald mixing valve:
Field supplied. An anti-scald mixing valve is
recommended when storing domestic hot water above
115°F.
8. Unions:
Field supplied. Recommended for unit serviceability.
9. Temperature and pressure gauge:
Factory supplied. The temperature and pressure gauge is
shipped loose. It is the responsibility of the contractor to
install the temperature and pressure gauge on the boiler
water outlet.
10. Pressure relief valve:
Factory supplied. The pressure relief valve is sized to
ASME specifications.
11. Boiler purge valve:
Field supplied. The boiler purge valve is used to
remove entrapped air from the heat exchanger during
start-up.
12. System temperature sensor:
Lochinvar supplies a system temperature sensor.
The sensor is to be installed in the heating loop
downstream from the boiler hot water piping and
heating loop junction. Typically the sensor will be
located far enough downstream to sense system diluted
water temperature.
35
Page 36
6 Hydronic piping
Installation & Operation Manual
13. Indirect water heaters:
The Knight boiler may be piped to an indirect water
heater to heat domestic hot water with the space heat
transfer medium. As depicted on pages 39 through 45
there are two options when utilizing an indirect water
heater.
A. The space heating piping will branch off to flow the
space heat transfer medium through a single wall
heat exchanger coil inside the indirect water heater.
B. The indirect water heater is connected to the system
supply piping. A pump controlled by the Knight
boiler’s control will regulate the flow of water
through the indirect water heater. The indirect water
heater’s temperature will be regulated by the Knight
boiler’s control.
The Knight boiler is pre-configured to control the
operation of the DHW pump with Domestic Hot Water
Prioritization programming. The DHW programming is
designed to control and balance the space heating
demand by switching between DHW and space heating.
Lochinvar offers the Squire which is a series of indirect
water heaters. The Squire features a stainless steel vessel
with a single wall stainless steel heat exchanger.
Near boiler piping connections
CAUTION
It is up to the installer to ensure the
minimum system flow is not less than the
minimum boiler flow at any time.
WARNING
The National Standard Plumbing Code, the
National Plumbing Code of Canada and the
Uniform Plumbing Code limit the pressure
of the heat transfer fluid to less than the
minimum working pressure of the potable
water system up to 30 psi maximum. Also,
the heat transfer fluid must be water or
other non-toxic fluid having a toxicity of
Class 1, as listed in Clinical Toxicology of
th
Commercial Products, 5
Edition.
14. Y-Strainer:
Field supplied. A Y-strainer or equivalent multipurpose
strainer is recommended at the inlet of the heat exchanger
to remove system particles from older hydronic systems and
protect newer systems.
Circulator sizing
The Knight boiler heat exchanger does have a pressure drop,
which must be considered in your system design. Refer to the
graph in FIG. 6-3 for pressure drop through the Knight boiler
heat exchanger.
Figure 6-2A Near Boiler Piping w/Y-Strainer
T
S
Y
S
M
O
R
F
Y-S T R AI N ER
(RECOMMENDED)
TO FLOOR
DRAIN
DOMESTIC HOT
WATER PUMP
AIR SEPARATOR
SYSTEM
M
E
T
S
Y
S
O
T
SYSTEM SENSOR
PUMP
BOILER
PUMP
DRAIN
(TYPICAL)
T
M
E
O
M
O
R
F
INDIRECT
DOMESTIC
HOT WATER
TAN K
Figure 6-2B Near Boiler Piping w/Low Loss Header
AIR VENT VALVE
LOW LOSS HEADER
(TYPICAL)
Y-S T R AI N ER
(RECOMMENDED)
BOLIER PUMP
SYSTEM SENSOR
AIR SEPARATOR
DRAIN
(TYPICAL)
DRAIN VALVE
M
O
R
F
O
T
FILL VALVE
INDIRECT
DOMESTIC
HOT WATER
M
E
T
S
Y
S
O
T
S
M
O
R
F
EXPANSION TANK
M
E
T
S
Y
36
TO FLOOR
DRAIN
Page 37
Installation & Operation Manual
0
5
10
15
20
25
3 4 5 6 7 8 9 10111213141516171819202122232425
81
106
151
211
286
6 Hydronic piping (continued)
Figure 6-3 Pressure Drop vs. Flow
Pressure Drop vs. Flow (Includes Secondary Piping)
Pressure Drop (Feet of Head)
Flow Rate (GPM)
Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
*The minimum temperature rise is derived from the chart in FIG. 6-3 with the firing rate and pump speed at 100% as shown in
the table above.
The shaded regions of pump coverage are only available for applications with 230V (60 Hz) supply voltage, all others are
to be 115V. (A field supplied relay is required to connect the 230V pump listed in the shaded area in Table 6B to the boiler
high voltage terminal strip.)
Grundfos
UP26-96 FC/VS
TACO
0013 IFC VS
Wilo
Stratos 1.25 3 x 30
Variable speed pump setup
Before operation, ensure the following:
- Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control
- Pump is set for external signal control (if applicable)
- Pump is set for linear output (if applicable)
- If pump does not come equipped with a 0 - 10 Vdc input option, an optional module
will be required from the vendor
NOTICE
NOTICE
Pump sizing and flow requirements are
based on 20 feet of piping, 4 - 90°
elbows, and 2 - fully ported ball valves.
It is required that near boiler piping
systems utilize the Primary/Secondary
configuration shown in FIG. 6-10 only.
The use of other near boiler piping
configurations could result in improper
building and system flow rates leading to
inadvertent boiler high limit shutdowns
and poor system performance.
38
Page 39
6 Hydronic piping (continued)
Figure 6-4 Single Boiler - Single Temperature Zoned with Circulators
ZONE #1
Installation & Operation Manual
PRESSURE
REDUCING VALVE
BACKFLOW
PREVENTER
MAKE UP WATER
AIR SEPARATOR
BALL VALVE
(TYPICAL)
DRAIN POINT
(TYPICAL)
PRESSURE
GAUGE
SYSTEM SUPPLY
SENSOR
(WHEN USED)
ZONE #2 ZONE #3
EXPANSION
TANK
MAY SUBSTITUTE LOW LOSS HEADER
Y-STRAINER
(RECOMMENDED)
BOILER
CIRCULATOR
DOMESTIC
HOT WATER
CIRCULATOR
ZONE #4
ANTI-SCALD
MIXING VALVE
FLOW CHECK
VALVE
(TYPICAL)
ZONE CIRCULATORS
(TYPICAL)
HOT
WATER
OUT
COLD
WATER
IN
TEMPERATURE /
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
UNION
(TYPICAL)
PRESSURE
GAUGE
DRAIN
BOILER
INDIRECT
DHW TANK
39
Page 40
Installation & Operation Manual
R
6 Hydronic piping
Figure 6-5 Multiple Boilers - Single Temperature Zoned with Circulators
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
40
Page 41
6 Hydronic piping (continued)
Figure 6-6 Single Boiler - Multiple Temperatures
Installation & Operation Manual
MAKE
UP
WATER
BACKFLOW
PREVENTER
AIR SEPARATOR
BALL VALVE
(TYPICAL)
DRAIN POINT
(TYPICAL)
PRESSURE
REDUCING VALVE
PRESSURE
GAUGE
EXPANSION
TEMPERATURE
LOOP #1
SYSTEM
SUPPLY
SENSOR
TANK
MAY SUBSTITUTE
LOW LOSS HEADER
NOT TO EXCEED 4 PIPE DIA
OR MAX. OF 12" APART
Y-STRAINER
(RECOMMENDED)
BOILER
CIRCULATOR
FLOW CHECK
VALVE
TEMPERATURE
LOOP #2
TEMPERATURE
LOOP #3
DOMESTIC
HOT WATER
CIRCULATOR
MIXING VALVES
(TYPICAL)
HOT
WATER
OUT
ANTI-SCALD
MIXING VALVE
COLD
WATER
IN
CAUTION
NOTICE
Mixing valves are required for the protection of low temperature loops.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
Mixing valves are required for the protection of low temperature loops.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
42
BOILER
INDIRECT
DHW TANK
Page 43
Installation & Operation Manual
6 Hydronic piping (continued)
Figure 6-8 Single Boiler - Multiple Temperatures with DHW Piped as a Zone
MAKE
UP
WATER
BACKFLOW
PREVENTER
AIR SEPARATOR
BALL VALVE
(TYPICAL)
DRAIN POINT
(TYPICAL)
PRESSURE
REDUCING VALVE
PRESSURE
GAUGE
EXPANSION
MAY SUBSTITUTE
LOW LOSS HEADER
TEMPERATURE
LOOP #1
SYSTEM
SUPPLY
SENSOR
TANK
NOT TO EXCEED 4 PIPE DIA
OR MAX. OF 12" APART
Y-STRAINER
(RECOMMENDED)
BOILER
CIRCULATOR
TEMPERATURE
LOOP #2
TEMPERATURE
LOOP #3
MIXING VALVES
(TYPICAL)
DOMESTIC
HOT WATER
CIRCULATOR
FLOW CHECK
VALVE
HOT
WATER
OUT
ANTI-SCALD
MIXING VALVE
COLD
WATER
IN
TEMPERATURE /
CAUTION
NOTICE
NOTICE
Mixing valves are required for the protection of low temperature loops.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
Please note that the installer is responsible for ensuring DHW prioritization when piped as a zone.
UNION
(TYPICAL)
PRESSURE
GAUGE
DRAIN
BOILER
INDIRECT
DHW TANK
43
Page 44
6 Hydronic piping
Figure 6-9 Multiple Boilers - Single Temperature Zoned with Valves
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
45
Page 46
7 Gas connections
Installation & Operation Manual
Connecting gas supply piping
1. Remove the top access panel and refer to FIG.’s 7-1 and
7-2 to pipe gas to the boiler.
a. Install ground joint union for servicing, when
required.
b. Install a manual shutoff valve in the gas supply
piping outside boiler jacket when required by local
codes or utility requirements.
c. In Canada – When using manual main shutoff
valves, it must be identified by the installer.
2. Install sediment trap / drip leg.
Figure 7-1 Gas Supply Piping - Models 81 - 211
UNION
GAS SUPPLY
DRIP
LEG
MANUAL
SHUTOFF
VALVE
3. Support piping with hangers, not by the boiler or its
accessories.
WARNING
The gas valve and blower will not support
the weight of the piping. Do not attempt
to support the weight of the piping with
the boiler or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
4. Purge all air from the gas supply piping.
5. Before placing the boiler in operation, check the boiler
and its gas connection for leaks.
a. The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
c. The appliance and its gas connection must be leak
tested before placing it in operation.
WARNING
Do not check for gas leaks with an open
flame – use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
Figure 7-2 Gas Supply Piping - Model 286
SEDIMENT TRAP / DRIP LEG
46
6. Use pipe sealing compound compatible with propane
gases. Apply sparingly only to male threads of the pipe
joints so that pipe dope does not block gas flow.
WARNING
Failure to apply pipe sealing compound as
detailed in this manual can result in severe
personal injury, death, or substantial
property damage.
WARNING
Knight boilers are typically shipped ready
to fire on natural gas. Check boiler rating
plate to determine which fuel the boiler
is set for. If set to natural gas, it may be
converted to LP by installing an orifice
(see page 13). In order to operate on LP
gas, an orifice MUST BE installed. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
Page 47
7 Gas connections (continued)
Installation & Operation Manual
WARNING
Figure 7-3 Inlet Pipe with Backup Wrench
Use two wrenches when tightening gas
piping at boiler (FIG. 7-3), using one
wrench to prevent the boiler gas line
connection from turning. Failure to
support the boiler gas connection pipe to
prevent it from turning could damage gas
line components.
Natural gas:
Pipe sizing for natural gas
1. Refer to Table 7A for pipe length and diameter. Based on
rated boiler input (divide by 1,000 to obtain cubic feet per
hour).
a. Table 7A is only for natural gas with specific gravity
0.60 inches, with a pressure drop through the gas
piping of 0.5 inches w.c.
b. For additional gas pipe sizing information, refer to
ANSI Z223.1 (or B149.1 for Canadian installations).
Natural gas supply pressure requirements
1. Pressure required at the gas valve inlet pressure port:
• Maximum 14 inches w.c. with no flow (lockup) or
with boiler on.
• Minimum 4 inches w.c. with gas flowing (verify during
boiler startup).
2. Install 100% lockup gas pressure regulator in supply line if
inlet pressure can exceed 14 inches w.c. at any time. Adjust
lockup regulator for 14 inches w.c. maximum.
NOTICE
Maximum inlet gas pressure must not
exceed the value specified. Minimum
value listed is for the purposes of input
adjustment.
Propane Gas:
WARNING
Pipe sizing for propane gas
1. Contact gas supplier to size pipes, tanks, and 100% lockup
gas pressure regulator.
Propane Supply Pressure Requirements
1. Adjust propane supply regulator provided by the gas
supplier for 14 inches w.c. maximum pressure.
2. Pressure required at gas valve inlet pressure port:
• Maximum 14 inches w.c. with no flow (lockup) or with
boiler on.
• Minimum 8 inches w.c. with gas flowing (verify during
boiler startup).
Knight boilers are typically shipped ready to
fire on natural gas. Check boiler rating plate
to determine which fuel the boiler is set for.
If set to natural gas, it may be converted
to LP by installing an orifice (see page 13).
In order to operate on LP gas, an orifice
MUST BE installed. Failure to comply
could result in severe personal injury, death,
or substantial property damage.
WARNING
Ensure that the high gas pressure regulator
is at least 6 - 10 feet upstream of the
appliance.
47
Page 48
7 Gas connections
Table 7A Natural Gas Pipe Size Chart
Installation & Operation Manual
Nominal
Iron Pipe
Size (Inches)
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
WARNING
10
1751209782N/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
369
697
1400
2150
4100
6460
11200
23500
20
256
477
974
1500
2820
4460
7900
16100
30
205
384
789
1210
2260
3610
6400
13100
11100
Knight boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine which
fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page 13).
In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe personal
injury, death, or substantial property damage.
Check inlet gas supply
NOTICE
WARNING
The gas piping must be sized for the proper flow and length
of pipe, to avoid excessive pressure drop. Both the gas meter
and the gas regulator must be properly sized for the total gas
load.
If you experience a pressure drop greater than 1 inch w.c.,
the meter, regulator, or gas line is undersized or in need of
service. Perform the steps below when checking inlet gas
supply:
1. Turn the main power switch to the “OFF” position.
2. Shut off gas supply at the manual gas valve in the gas
piping to the appliance.
48
CSA or UL listed flexible gas connections
are acceptable, but you must exercise
caution to ensure that the line has adequate
capacity to allow your boiler to fire at full
rate. Consult with local codes for proper
installation or service procedures.
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane, requiring no field adjustment.
Attempting to alter or measure the gas
valve outlet pressure could result in
damage to the valve, causing potential
severe personal injury, death, or substantial
property damage.
Single Unit
Natural Gas Pipe Capacity Chart
Length of Pipe in Straight Feet for 1/2 PSI
40
174
328
677
1020
1950
3100
5400
50
155
292
595
923
1720
2720
4870
10000
60
141
267
543
830
1560
2460
4410
9000
70
128
246
502
769
1440
2310
4000
8300
80
121
236
472
707
1330
2100
3800
7690
90
113
210
441
666
1250
2000
3540
7380
100
106
200
410
636
1180
1900
3330
6870
3. Loosen the set screw one (1) full turn from inside the
pressure tap on top of the gas valve. Place the tubing of
the manometer over the tap once the set screw is
loosened as shown in FIG. 7-4.
4. Slowly turn on the gas supply at the field installed
manual gas valve.
5. Turn the power switch to the “ON” position.
6. Adjust the temperature set point on the control panel of
the SMART SYSTEM control module to call for heat.
7. Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the control panel.
8. Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.
9. If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.
10. If the gas pressure is out of range, contact the gas utility,
gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.
11. Turn the power switch to the “OFF” position.
12. Shut off the gas supply at the manual gas valve in the gas
piping to the appliance.
13. Remove the manometer from the pressure tap on top of
the gas valve. Re-tighten the set screw inside the pressure
tap.
125
95
179
369
564
1100
1700
3000
6150
150
86
164
333
513
974
1540
2720
5640
175
79
149
308
472
871
1400
2500
5130
200
74
138
287
441
820
1300
2340
4720
Page 49
7 Gas connections (continued)
Installation & Operation Manual
WARNING
14. Turn on the gas supply at the manual gas valve.
15. Turn the power switch to the “ON” position.
16. Adjust the temperature set point on the control panel of
the SMART SYSTEM control module to the desired
water temperature so the appliance will call for heat.
17. Check burner performance by cycling the system while
you observe burner response. The burner should ignite
promptly. Flame pattern should be stable. Turn system
off and allow burner to cool, then cycle burner again to
ensure proper ignition and flame characteristics.
Figure 7-4 Inlet Gas Supply Check
LOOSEN THE SET SCREW ONE (1) FULL TURN
AND PLACE THE MANOMETER TUBING OVER
THE PRESSURE TAP.
When re-tightening the set screw, be sure
to tighten securely to prevent gas leaks.
Do not check for gas leaks with an open
flame -- use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
DETAIL
Gas Pressure
The gas pressure must remain between 4 inches w.c. (natural),
8 inches w.c. (LP) minimum and 14 inches w.c. (natural and
LP) maximum during stand-by (static) mode and while in
operating (dynamic) mode. If an in-line regulator is used, it
must be a minimum of 10 feet from the Knight boiler. It is
very important that the gas line is properly purged by the gas
supplier or utility company. Failure to properly purge the
lines or improper line sizing, will result in ignition failure.
The problem is especially noticeable in NEW LP installations
and also in empty tank situations. This can also occur when
a utility company shuts off service to an area to provide
maintenance to their lines.
Gas valve replacement
The gas valve MUST NOT be replaced with a conventional
gas valve under any circumstances. As an additional safety
feature, this gas valve has a flanged connection to the venturi
and blower.
WARNING
WARNING
Failure to follow all precautions could
result in fire, explosion, or death!
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane, requiring no field adjustment.
Attempting to alter or measure the gas
valve outlet pressure could result in
damage to the valve, causing potential
severe personal injury, death, or substantial
property damage.
49
Page 50
8 Field wiring
Installation & Operation Manual
WARNING
NOTICE
CAUTION
Figure 8-1 Line Voltage Field Wiring Connections
ELECTRICAL SHOCK HAZARD – For
your safety, turn off electrical power
supply before making any electrical
connections to avoid possible electric
shock hazard. Failure to do so can cause
severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler
must be replaced, use only type 105°C
wire or equivalent.
Boiler must be electrically grounded as
required by National Electrical Code
ANSI/NFPA 70 – latest edition.
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation.
Installation must comply with:
1. National Electrical Code and any other national, state,
provincial, or local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,
and any local codes.
Line voltage connections
1. Connect 120 vac power wiring to the line voltage terminal
strip in the junction box, as shown in FIG. 8-1.
2. Provide and install a fused disconnect or service switch
(15 amp recommended) as required by the code (see
FIG. 8-1).
3. The boiler pump is shipped loose. Wire the boiler pump
as shown in FIG. 8-1.
4. When connecting a domestic hot water (DHW) pump,
connect the wiring to the line voltage terminal strip as
shown in FIG. 8-1.
5. To activate a system pump, wire as shown in FIG. 8-1.
If the motor is larger than 1/8 hp or 1.8 amps, you must
isolate with a relay.
Low voltage connections
1. Route all low voltage wires through the knockouts in the
rear of the boiler, as shown in FIG. 8-2.
2. Connect low voltage wiring to low voltage connection
board as shown in FIG. 8-3 on page 53 of this manual and
the boiler wiring diagram.
Figure 8-2 Routing Field Wiring
LOW VOLTAGE
CONNECTION BOARD
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE WIRING KNOCKOUTS
50
Page 51
8 Field wiring (continued)
Installation & Operation Manual
Thermostat
1. Connect the room thermostats or end switches (isolated
contact only) to room thermostat 1, 2, or 3, as shown in
FIG. 8-3.
2. Install the thermostat on the inside wall away from
influences of drafts, hot or cold water pipes, lighting
fixtures, television, sunlight, or fireplaces.
3. Thermostat anticipator (if applicable):
a. If connected directly to boiler, set for 0.1 amps.
b. If connected to relays or other devices, set to match
total electrical power requirements of connected
devices. See device manufacturers’ specifications
and thermostat instructions for details.
Outdoor temperature sensor
1. Mount the sensor on an exterior wall, shielded from
direct sunlight or flow of heat or cooling from other
sources.
2. Route sensor wires through a knockout at the rear of the
boiler (see FIG. 8-2).
3. Connect outdoor temperature sensor (FIG. 8-3) to the
outdoor sensor terminals on the connection board to
enable outdoor reset operation of the Knight boiler. If
fixed temperature operation is required, do not install
outdoor sensor.
DHW thermostat
Connect storage indirect water heater (DHW) thermostat
(FIG. 8-3) to the DHW thermostat terminals on the
connection board. If a tank sensor is connected (see DHW
Tank Sensor below) the tank thermostat is ignored.
3. If the TST20015 is not compatible with the indirect tank,
a tank thermostat can be used to control the boiler. The
tank thermostat should be installed per the manufacturers
instructions and wired to the DHW Thermostat terminals
on the Low Voltage Connection Board.
Louver relay
If louvers need to operate when the boiler fires, they can be
controlled by this output. Connect these terminals to a 24 vac
relay coil, which is wired to operate the louvers (FIG. 8-3).
Louver proving switch
When the operation of the louvers needs to be verified before
the boiler fires, remove the jumper wire from these terminals
and connect them to the normally open contacts on its proving
switch (FIG. 8-3).
High gas pressure switch
If a switch is provided to detect excessive gas pressure, remove
the jumper wire from the terminals on the connection board,
and then connect them to its normally closed contacts (FIG.
8-3).
Low gas pressure switch
1. If a switch is provided to detect low gas pressure, remove the
jumper wire from the terminals on the connection board
and connect them to its normally open contacts (FIG. 8-3).
2. If both a high and low gas pressure switch is used, connect
their respective contacts in series, and connect them to the
terminals on the connection board (FIG. 8-3).
DHW tank sensor
1. By installing a tank sensor, the SMART SYSTEM control
can perform the tank thermostat function. The SMART
SYSTEM control automatically detects the presence of
this sensor and generates a DHW call for heat when
the tank temperature drops 6°F (3°C) below the tank
set point and finishes the call for heat when the tank
temperature reaches the tank set point.
2. The tank sensor included with the Lochinvar Squire
Indirect DHW tank (TST20015) is the only sensor
suitable for use with the SMART SYSTEM control.
Connect the sensor leads to the Tank Sensor terminals on
the Low Voltage Connection Board (FIG. 8-3). Consult
the tank manufacturer for application and performance
when used with any other indirect tank.
WARNING
Failure to use the correct sensor may result
in the tank temperature being either above
or below the set point. Failure to consult
the manufacturer of the indirect tank,
when the Squire is not used, may result in
decreased performance or the risk of scald
injury.
Variable speed system pump
If a variable speed pump is used in the primary loop, and
a 0-10V signal is available from the pump speed control,
this signal can be used by the SMART SYSTEM control to
anticipate changes in the building heat load. By connecting this
0 - 10V signal to the 0 - 10V SYS PUMP IN terminals, the boiler
(or cascade) can modulate up and down as the primary flow
increases and decreases.
Boiler pump speed output
This 0 - 10V output is available to control the speed of a variable
speed boiler pump. The SMART SYSTEM control will vary the
speed of this pump in order to maintain a minimum T across
the heat exchanger, as well as prevent high limit lockouts when
the flow in the primary loop is extremely low. Connect this
output to the 0 - 10V input on the boiler pump speed control.
Rate output
This output provides a 0 - 10V signal that is proportional to the
firing rate of the boiler. This may be used by a BMS system to
monitor the actual rate of the boiler.
51
Page 52
8 Field wiring
Installation & Operation Manual
ModBus
When the optional ModBus interface module is installed, the
RS-485 ModBus cable is connected to these terminals. Use
shielded, 2-wire twisted pair cable. If desired, the shield can
be connected to ground by installing a jumper wire between
terminals 1 and 3 on connector X5 on the optional ModBus
interface module.
Flow switch
1. A flow switch is used to guarantee flow through the
boiler before allowing it to fire. The flow switch must be
installed at the boiler outlet.
2. Remove the jumper wire from these terminals, and
connect these terminals to the normally open contacts on
the flow switch (FIG. 8-3).
System supply sensor
1. By installing the system supply sensor into the supply
of the primary loop, the temperature of the primary
supply can be controlled. The SMART SYSTEM control
automatically detects the presence of this sensor, and
controls the boiler firing rate to maintain the system supply
temperature to the set point (if the outlet sensor control
is currently selected). If it is desired to control the system
return temperature, then program the SMART SYSTEM
control to use the inlet sensor as the controlling sensor.
See the Knight Boiler Service Manual for instructions
on how to use the inlet sensor as the controlling sensor.
When the inlet sensor is programmed as the controlling
sensor, it is vital that the SYSTEM SUPPLY sensor be
installed. DO NOT INSTALL THE SYSTEM SUPPLY
SENSOR INTO THE SYSTEM RETURN.
2. The TST2032 sensor provided with the boiler must be
used for the system sensor.
3. Connect these terminals to the system supply sensor
(FIG. 8-3).
Boiler management system
1. An external control may be connected to control either
the firing rate or the set point of the boiler. If the external
control uses a set of contacts to enable the boiler, connect
the contacts to the Room Thermostat 1 terminals.
Otherwise, the SMART SYSTEM control will be enabled
by the 0-10V signal.
2. Make sure the ground terminal is connected to the
ground output terminal of the external control, and the
0 - 10 vdc terminal is connected to the 0 - 10 vdc terminal
of the external control.
Runtime contacts
The SMART SYSTEM control closes a set of dry contacts
whenever the burner is running. This is typically used by
Building Management Systems to verify that the boiler is
responding to a call for heat.
Alarm contacts
The SMART SYSTEM control closes another set of contacts
whenever the boiler is locked out or the power is turned off.
This can be used to turn on an alarm, or signal a Building
Management System that the boiler is down.
Wiring of the cascade
When wiring the boilers for Cascade operation, select one
boiler as the Leader boiler. The remaining boilers will be
designated as Members. See page 60 “Configuration of the
Cascade” for a detailed explanation of this procedure.
Connect the system supply sensor and outdoor air sensor (if
used) to the Leader boiler. For the Cascade system to work
properly the system supply sensor must be installed. The
location of the system supply sensor should be downstream
of the boiler connections in the main system loop (FIG.’s 6-4,
6-6, and 6-8). The system supply sensor should be wired to
the Low Voltage Connection Board at the terminals marked
for the system sensor (see FIG. 8-3). The Leader control will
use the water temperature at the system supply sensor to
control the operation of the Cascade.
If outdoor air reset is desired, the outdoor air sensor should be
wired to the Low Voltage Connection Board at the terminals
marked for the outdoor air sensor (FIG. 8-3). If the outdoor
air sensor is connected, the Leader control will calculate the
water temperature set point based on the programmed reset
curve parameters. If the outdoor air sensor is not connected,
the Leader control will maintain the fixed water temperature
set point that is programmed into the control.
If a Thermostat, Zone Control enable output, or Building
Management System enable output is available, it should
be wired to the Low Voltage Connection Board on the
Leader boiler at the terminals marked for one of the Room
Thermostats 1-3 (FIG. 8-3). If the boilers are to run
continuously, connect a jumper wire between the R and W
terminals for the Thermostat input. This will initiate a call for
heat on the Cascade.
Communication between the Leader boiler and the Member
boilers is accomplished by using shielded, 2-wire twisted pair
communication cable. Connect one of the twisted pair wires
to Cascade terminal A on each of the Low Voltage Connection
boards, and the other wire of the twisted pair to Cascade
terminal B on each of the Low Voltage Connection Boards.
Connect the shield wires to one of the shield terminals on
the Low Voltage Connection Boards (FIG. 8-3). If more than
two boilers are on the Cascade, daisy chain the wiring from
the Cascade terminals on the second boiler to the Cascade
terminals on the third boiler, then from the third to the forth,
and so on. The connections between boilers can be made in
any order, regardless of the addresses of the boilers. Try to
keep each cable as short as possible.
52
Page 53
8 Field wiring (continued)
Figure 8-3 Low Voltage Field Wiring Connections
SYSTEM SUPPLY SENSOR
OUTDOOR SENSOR
TANK SENSOR
TO
NEXT
BOILER
A
B
Installation & Operation Manual
NOTE:
CONNECTION BOARD SPLIT FOR
ILLUSTRATION PURPOSES
A
FROM
B
BOILER
PREVIOUS
SHIELD
SHIELD
LOW WATER
CUTOFF
SPEED
CONTROL
SYSTEM PUMP
BOILER
PUMP
B
A
SYSTEM
BUILDING
MANAGEMENT
NEEDED
WIRE AS
NO
COM
LOUVER
LOUVER RELAY
PROVING SWITCH
FLOW SWITCH
TANK THERMO STAT
ROOM THERMOSTAT 2
ROOM THERMOSTAT 3
ROOM THERMOSTAT 1
53
Page 54
9 Condensate disposal
Installation & Operation Manual
Condensate drain
1. This boiler is a high efficiency appliance that produces
condensate.
2. The side of the boiler has a 1/2 inch PVC union for
connection of a 1/2 inch PVC pipe (FIG. 9-1).
3. Slope condensate tubing down and away from the
boiler into a drain or condensate neutralizing filter.
Condensate from the Knight boiler will be slightly acidic
(typically with a pH from 3 to 5). Install a neutralizing
filter if required by local codes.
A Neutralizer Kit (FIG. 9-1) is available from the factory
(Kit 3087).
4. Install the 1/2 inch PVC tee assembly (shipped with the
unit) as shown in FIG. 9-1.
5. Leave the top of the 1/2 inch tee OPEN. This is needed as
a vacuum break.
6. Do not expose condensate line to freezing temperatures.
7. Use only plastic tubing or piping as a condensate drain
line (FIG. 9-1).
NOTICE
NOTICE
8. A condensate removal pump is required if the boiler is
below the drain. When installing a condensate pump,
select one approved for use with condensing boilers and
furnaces. The pump should have an overflow switch to
prevent property damage from condensate spillage. The
switch should be wired in series with the blocked drain
switch inside the boiler (see FIG. 10-1 on page 56).
Use materials approved by the authority
having jurisdiction. In the absence of
other authority, PVC and CPVC pipe
must comply with ASTM D1785 or D2845.
Cement and primer must comply with
ASME D2564 or F493. For Canada use
CSA or ULC certified PVC or CPVC pipe,
fittings, and cement.
To allow for proper drainage on large
horizontal runs, a second line vent may
be required and tubing size may need to
increase to 1 inch.
The condensate line must remain
unobstructed, allowing free flow of
condensate. If condensate is allowed to
freeze in the line or if the line is obstructed
in any other manner, condensate can exit
from the boiler tee, resulting in potential
water damage to property.
Figure 9-1 Condensate Disposal
1/2" PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
1/2" PVC UNION
(FACTORY SUPPLIED)
NEUTRALIZER KIT
FLOOR DRAIN OR
DRAIN PAN
54
Page 55
10 Start-up
Installation & Operation Manual
Check/control water chemistry
CAUTION
Hardness less than 7 grains
1. Consult local water treatment companies for hard water
areas (above 7 grains hardness).
Chlorine concentration less than 200 ppm
1. Do not fill boiler or operate with water containing
chlorine in excess of 200 ppm.
2. Filling with chlorinated fresh water should be acceptable
since drinking water chlorine levels are much lower.
3. Do not use the boiler to directly heat swimming pool or
spa water.
Test/replace freeze protection fluid
1. For systems using freeze protection fluids, follow fluid
manufacturer’s instructions.
2. Freeze protection fluid must be replaced periodically due
to degradation of inhibitors over time. Follow all fluid
manufacturer’s instructions.
Do not use petroleum-based cleaning or
sealing compounds in the boiler system.
Damage to elastomer seals and gaskets
in the system could occur, resulting in
substantial property damage.
Freeze protection (when used)
1. Determine freeze protection fluid quantity using
system water content, following fluid manufacturer’s
instructions. Boiler water content is listed on page 7.
Remember to include expansion tank water content.
2. Local codes may require a backflow preventer or actual
disconnect from city water supply.
3. When using freeze protection fluid with automatic fill,
install a water meter to monitor water makeup. Freeze
protection fluid may leak before the water begins to
leak, causing concentration to drop, reducing the freeze
protection level.
4. The freeze protection set points may be lowered when
freeze protection fluid is used (see the Knight Service
Manual).
Fill and test water system
1. Fill system only after ensuring the water meets the
requirements of this manual.
2. Close manual and automatic air vents and boiler drain
valve.
3. Fill to correct system pressure. Correct pressure will vary
with each application.
a. The minimum cold water fill pressure for a
residential system is 12 psi.
b. Pressure will rise when boiler is turned on and
system water temperature increases.
4. At initial fill and during boiler startup and testing, check
system thoroughly for any leaks. Repair all leaks before
proceeding further.
WARNING
Eliminate all system leaks. Continual
fresh makeup water will reduce boiler life.
Minerals can build up in the heat exchanger,
reducing heat transfer, overheating the heat
exchanger, and causing heat exchanger
failure.
Purge air from water system
1. Purge air from system:
a. Connect a hose to the purge valve (see purge/drain
valves, in piping diagrams on pages 39 through 45).
Route the hose to an area where water can drain and
be seen.
b. Close the boiler or system isolation valve between
the purge valve and fill connection to the system.
c. Close zone isolation valves.
d. Open quick-fill valve on cold water makeup line.
e. Open purge valve.
f. One zone at a time, open the isolation valves. Allow
water to run through the zone, pushing out the air.
Run until no noticeable air flow is present. Close the
zone isolation valves and proceed with the next zone.
Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve and
remove the hose. Open all isolation valves. Watch
that system pressure rises to correct cold-fill
pressure.
h. After the system has operated for a while, eliminate
any residual air by using the manual air vents located
throughout the system.
i. If purge valves are not installed in the system, open
the manual air vents in the system one at a time,
beginning with the lowest floor. Close the vent when
water squirts out. Repeat with remaining vents.
2. Open automatic air vent (diaphragm-type or bladder-type
expansion tank systems only) one turn.
3. Open other vents:
a. Starting on the lowest floor, open air vents one at a
time until water squirts out.
b. Repeat with remaining vents.
4. Refill to correct pressure.
55
Page 56
10 Start-up
Installation & Operation Manual
Check for gas leaks
WARNING
WARNING
Figure 10-1 Condensate Trap
Before starting the boiler, and during
initial operation, smell near the floor and
around the boiler for gas odorant or any
unusual odor. Remove the top access
panel and smell the interior of the boiler
enclosure. Do not proceed with startup
if there is any indication of a gas leak.
Use an approved leak detection solution.
Repair any leaks at once.
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve is
factory set for the correct outlet pressure.
This setting is suitable for natural gas and
propane, requiring no field adjustment.
Attempting to alter or measure the gas
valve outlet pressure could result in
damage to the valve, causing potential
severe personal injury, death, or
substantial property damage.
RETAINING
SCREW
2” PVC CAP WITH
BLOCKED DRAIN SWITCH
WARNING
Propane boilers only – Your propane
supplier mixes an odorant with the propane
to make its presence detectable. In some
instances, the odorant can fade, and the
gas may no longer have an odor. Before
startup (and periodically thereafter), have
the propane supplier verify the correct
odorant level in the gas.
Check thermostat circuit(s)
1. Disconnect the two external wires connected to each of
the room thermostat terminals on the connection board.
2. Connect a voltmeter across these two incoming wires.
Close each thermostat, zone valve, and relay in the
external circuit one at a time and check the voltmeter
reading across the incoming wires.
3. There should NEVER be a voltage reading.
4. If a voltage does occur under any condition, check and
correct the external wiring. (This is a common problem
when using 3-wire zone valves.)
5. Once the external thermostat circuit wiring is checked and
corrected if necessary, reconnect the external thermostat
circuit wires to the connection board.
Inspect/fill condensate system
CONDENSATE FROM
HEAT EXCHANGER
TO FLOOR
DRAIN
PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
Inspect/check condensate lines and fittings
1. Inspect the condensate drain line, condensate PVC
fittings and condensate trap.
Fill condensate trap with water
1. Remove the PVC cap retaining screw from the PVC cap
(FIG. 10-1).
2. Remove the 2 inch PVC cap with the switch located at the
top of the trap (FIG. 10-1).
3. Fill with fresh water until the water begins to pour out of
the drain.
4. Replace the cap. Press the cap onto the trap until the cap
makes contact with the drain.
5. Replace the retaining screw.
WARNING
The condensate trap (FIG. 10-1) must be
filled with water during all times of boiler
operation to avoid flue gas emission from
the condensate drain line. Failure to fill
the trap could result in severe personal
injury or death.
56
Page 57
10 Start-up (continued)
Final checks before starting the boiler
Installation & Operation Manual
Check vent piping and air piping
Read the Knight Boiler Service Manual to familiarize
yourself with SMART SYSTEM control module
operation. Read this manual, page 58 for proper steps to
start boiler.
Verify the boiler and system are full of water and all
system components are correctly set for operation.
Verify the preparation procedures of Section 10, pages 55
and 56 have been completed.
Fill the vent condensate trap with water (removing the
retaining screw in order to remove the 2 inch PVC cap
with the switch located at the top of the trap). Replace
the cap. Press the cap onto the trap until the cap makes
contact with the drain. Replace the retaining screw.
Verify electrical connections are correct and securely
attached.
Inspect vent piping and air piping for signs of deterioration
from corrosion, physical damage or sagging. Verify air
piping and vent piping are intact and correctly installed
per this manual.
Start the boiler
1. Read and follow the Operating instructions in FIG. 10-2,
page 58.
If boiler does not start correctly
1. Check for loose connections, blown fuse or service switch
off?
2. Is boiler water temperature above 200°F?
3. Is thermostat set below room temperature?
4. Is gas turned on at meter or boiler?
5. Is incoming gas pressure less than 4 inches w.c.?
If none of the above corrects the problem, refer to the
Troubleshooting Section of the Knight Boiler Service Manual.
1. Check for gastight seal at every connection, seam of air
piping, and vent piping.
WARNING
Check gas piping
1. Check around the boiler for gas odor following the
procedure on page 46 of this manual (connecting gas supply
piping).
WARNING
Propane boilers – verify conversion
1. Verify propane conversion has been completed per the
Propane Conversion instructions.
WARNING
WARNING
Venting system must be sealed gastight
to prevent flue gas spillage and carbon
monoxide emissions, which will result in
severe personal injury or death.
If you discover evidence of any gas leak,
shut down the boiler at once. Find the
leak source with a bubble test and repair
immediately. Do not start the boiler again
until corrected. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
DO NOT adjust or attempt to measure
gas valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane, requiring no field adjustment.
Attempting to alter or measure the gas valve
outlet pressure could result in damage to
the valve, causing potential severe personal
injury, death, or substantial property
damage.
Knight boilers are typically shipped ready
to fire on natural gas. Check boiler rating
plate to determine which fuel the boiler is set
for. If set to natural gas, it may be converted
to LP by installing an orifice (see page 13).
In order to operate on LP gas, an orifice
MUST BE installed. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
Check flame and combustion
Check system and boiler
Check water piping
1. Check system piping for leaks. If found, shut down
the boiler and repair immediately. (See WARNINGS
on pages 55 and 56 (startup) regarding failure to repair
leaks.)
2. Vent any remaining air from the system using manual
vents. Air in the system will interfere with circulation
and cause heat distribution problems and noise.
1. Turn the main power off to the boiler by placing the “On/
Off” switch in the OFF position.
2. Remove the flue temperature sensor from the flue pipe
connection. NOTE: Combustion measurements will be
made at this point.
3. Turn the main power on to the boiler by placing the “On/
Off” switch in the ON position.
57
Page 58
10 Start-up
Figure 10-2 Operating Instructions
Installation & Operation Manual
58
Page 59
Installation & Operation Manual
10 Start-up (continued)
Check flame and combustion (continued)Set space heating operation
NOTICE
4. Place the boiler into the active position by pressing the
RIGHT SELECT [ON] key (FIG. 11-1, page 67).
5. Locate the pinhole button below the RESET button on
the display board (FIG. 11-1). Insert a thin wire (such as
a paper clip) into the hole and press the button once and
hold for 5 seconds to place the boiler into Service Mode.
In Service Mode the boiler will fire at ignition speed and
will then modulate up to full fire.
6. Insert the probe from a combustion analyzer into the hole
left by the removal of the flue temperature sensor.
7. Once the boiler has modulated up to full fire, measure
the combustion. The values should be in the range listed
in Table 10A below. The CO levels should be less than
150 ppm for a properly installed unit.
If the combustion is not within the specified range,
reference the Troubleshooting Section of the Knight
Boiler Service Manual for possible causes and corrective
actions.
Table 10A Flue Products Chart
Natural GasPropane
CO
2
8.0% - 10%3.0% - 6.5%9.0% - 11% 4.1% - 6.9%
8. Once the combustion analysis is complete, test the safety
shutoff device by turning the manual shutoff switch to
the OFF position and ensuring that the boiler shuts
down and registers an alarm. Turn the manual shutoff
switch to the ON position, reset the control, and return
to Service Mode.
9. Turn the main power off to the boiler and replace the flue
temperature sensor into the flue pipe connection.
10. Place the boiler back into normal operation.
WARNING
Please note that the brackets ([]) denote
screen status.
O
2
You must replace the flue gas temperature
sensor to prevent flue gas spillage into
the room. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
CO
2
O
2
Determine controlling sensor
For space heating systems, the temperature control can be
based on one of three sensors; the inlet, outlet, or system
supply sensor. The SMART SYSTEM control is programmed
at the factory to control the temperature of the outlet
sensor. The control will automatically switch to the system
supply sensor once it is connected. If it is desired to base
the temperature control on the inlet sensor, the appropriate
parameter must be changed in the control. See the Knight
Boiler Service Manual for a detailed explanation of this
procedure.
Verify space heat circulator mode
The Space Heating Mode controls both the system (primary)
pump (if connected), and the boiler (secondary) pump.
When the SMART SYSTEM control receives a space heating
call for heat, it turns on the system pump. If the boiler is not
heating an indirect DHW (Domestic Hot Water) tank, and
the set point is not met, it also turns on the boiler pump.
After the space heating call for heat ends, the system pump
continues to run for a short period of time. The system
pump can be programmed to run continuously, except
during outdoor shutdown. If the boiler pump was running,
it continues to run for a short period of time as well. These
pump delays are factory set to 30 seconds. If different delays
are desired, the appropriate parameters in the control must
be changed. See the Knight Boiler Service Manual for a
detailed explanation of this procedure.
Adjust set point temperature
NOTICE
The NAVIGATION dial may be used during normal
operation to adjust the space heating and tank set point
temperatures.
1. From the Status Screen press the NAVIGATION dial.
2. Turn the NAVIGATION dial counterclockwise to select
the appropriate set point.
3. Press the NAVIGATION dial to adjust the temperature.
4. Once the desired temperature is displayed, press the
RIGHT SELECT [SAVE] key.
5. If necessary repeat Steps 3 and 4 to make adjustments to
additional set points.
6. Press the RIGHT SELECT [HOME[ key to upload the
changes.
7. If the RIGHT SELECT [SAVE] key is not pressed, the
new settings will be discarded.
Please note that the brackets ([]) denote
screen status.
59
Page 60
10 Start-up
Set domestic hot water (DHW) operation
Installation & Operation Manual
Verify DHW mode
There are two (2) modes of operation for DHW. In Normal
Mode, when a DHW demand begins, the control will start
the DHW pump, turn off the boiler pump (if running), and
modulate to bring the outlet temperature to the DHW boiler
set point. The maximum firing rate may be limited in this
mode if desired.
In Zone Mode it is assumed that the indirect DHW tank is
piped as a zone on the primary loop. When a DHW demand
begins, the control will turn on the DHW pump output, and
raise the system temperature set point to the DHW boiler set
point (if higher). The system pump and the boiler pump will
be turned on. In this mode, any low temperature zones (such
as radiant heating) may need additional controls to limit the
water temperature sent to those zones.
Set DHW target temperature
When in the DHW Mode, the control will modulate to
maintain the boiler outlet temperature or system supply
temperature to a set point. This set point is set at the factory
to 180°F. If a different set point is desired, the appropriate
parameter in the control must be changed. See the Knight
Boiler Service Manual for a detailed explanation of this
procedure.
Set maximum DHW fan speed
If the rated input of the indirect tank is less than the
maximum output of the boiler, change the maximum DHW
fan speed setting to limit the boiler output accordingly, see
the Knight Boiler Service Manual for a detailed explanation
of this procedure.
Set clock
NOTICE
The SMART SYSTEM control has a built-in clock that it
uses for its night setback feature and for logging events. This
clock must be set when the boiler is installed, and anytime
the boiler has been powered off for more than 4 hours. Use
the following procedure to set the clock:
1. Press and hold the LEFT SELECT [MENU] key for at
least 5 seconds.
2. The display changes to read [PASSWORD],
with four (4) zeros below it.
3. Press the RIGHT SELECT [SAVE] key.
4. The display will then show a menu with the time and
date and temperature unit.
5. Press the NAVIGATION dial twice.
6. Turn the NAVIGATION dial to adjust the hours. Press
the NAVIGATION dial.
7. Turn the NAVIGATION dial to adjust the minutes. Press
the NAVIGATION dial.
Please note that the brackets ([]) denote
screen status.
60
8. Turn the NAVIGATION dial to adjust the month. Press the
NAVIGATION dial.
9. Turn the NAVIGATION dial to adjust the date. Press the
NAVIGATION dial.
10. Turn the NAVIGATION dial to adjust the year. Press the
RIGHT SELECT [SAVE] key.
11. Press the RIGHT SELECT [HOME] key.
NOTICE
Configuration of the cascade
NOTICE
When installed in a Cascade system, the individual controls
must be programmed for cascade operation. This is
accomplished by accessing the control parameters.
Press the [MENU] key for at least five (5) seconds. Input
the Installer code as described in the Knight Boiler Service
Manual. Once the control parameters have been accessed,
use the NAVIGATION dial to select the Control Mode
parameters. Press the NAVIGATION dial to access these
parameters.
Rotate the NAVIGATION dial to select the parameter
“Cascade Address”. Press the NAVIGATION dial to access
this parameter. Each appliance in the Cascade system must
be programmed with its own address. The boiler designated
as the Leader will have an address of 0. The remaining boilers
in the Cascade will be Members and have addresses from 1
- 7. Rotate the NAVIGATION dial to select the appropriate
address. Press the RIGHT SELECT [SAVE] key. If installing
the boilers in an existing system, the new boilers should
be programmed as the Leader and/or the higher number
addresses.
Press the RIGHT SELECT [HOME] key to upload the address
into the control. Repeat this procedure for all boilers in the
Cascade, designating the Leader control and the Member
controls.
The internal clock does not adjust for
Daylight Savings Time and therefore, will
require a manual adjustment.
Please note that the brackets ([]) denote
screen status.
Page 61
11 Operating information
Installation & Operation Manual
General
How the boiler operates
The Knight boiler uses an advanced stainless steel heat
exchanger and electronic control module that allows fully
condensing operation. The blower pulls in air and pushes
flue products out of the boiler through the heat exchanger
and flue piping. The control module regulates blower speed
to control the boiler firing rate. The gas valve senses the
amount of air flowing into the boiler and allows only the right
amount of gas to flow.
How the control module operates
The SMART SYSTEM control module receives inputs
from boiler sensors and external devices. The control
module activates and controls the blower and gas valve to
regulate heat input and switches the boiler, Domestic Hot
Water (DHW), and system pumps on and off as needed.
The user programs the module to meet system needs by
adjusting control parameters. These parameters set operating
temperatures and boiler operating modes. Boiler operation
can be based on boiler outlet water temperature, boiler inlet
water temperature, system temperature, a 0-10V signal or
Modbus, depending on the parameter settings.
Control inputs and outputs
Room thermostat
There are three (3) thermostat connections available on this
control. These inputs tell the boiler to provide water for space
heating. Each thermostat connection has its own set point
and outdoor air reset curve. When multiple thermostats have
a call for heat the control will give priority to the demand with
the highest set point.
Example: Assume that both Room Thermostat 1 and Room
Thermostat 2 have a call for heat. RoomThermostat 1 has
a set point of 110°F. Room Thermostat 2 has a set point of
140°F. The boiler will regulate the system temperature to
140°F until Room Thermostat 2 has been satisfied. Once
Room Thermostat 2 has been satisified the boiler will provide
110°F water to the system.
CAUTION
0 - 10V input (set point or power)
The Knight boiler can be controlled by a Building Management
System (BMS) using a 0 - 10 vdc signal. The control can be
configured by the installer to use this signal to either control
set point or firing rate.
The Knight boiler can also be programmed to accept a call for
heat from a 0 - 10V signal, reference the Knight Boiler Service
Manual for a detailed explanation of this procedure.
When multiple temperature loops are
used, thermostatic mixing valves are
required for the protection of any low
temperature loops.
DHW priority
The SMART SYSTEM control allows the connection of a DHW
thermostat or tank sensor to the low voltage connection board.
When a tank sensor is connected, the DHW thermostat input
is ignored.
DHW / space heating (SH) cycling
If a DHW call for heat is received while a space heating call
is in progress and the DHW is in Normal Mode, the control
will start the DHW pump and shut the boiler pump off. The
system pump will remain on. If the space heating call is still
active while the DHW call is in operation, the control will wait
for 30 minutes (time adjustable by installer) then it will switch
back to the space heating demand. There is a timer to switch
from space heating to DHW and a timer to switch from DHW
to space heating. The control will switch back and forth until
one of the heat demands end.
Programmable controlling sensor
The control module is programmed to use the outlet sensor
as the control sensor by default. If a system supply sensor
is connected, the control automatically uses it as the control
sensor. The control sensor can be changed by the installer to
the inlet sensor. If the inlet sensor is chosen as the controlling
sensor, it is recommended that the system supply sensor be
installed in the system supply in order to provide the best
control of the inlet temperature.
Anti-cycling
After the burner turns off, the control will delay the next burner
cycle for a set time period (time is adjustable by the installer).
The time delay will be bypassed if the inlet water temperature
drops too far during the delay.
Boiler and system pump control
The boiler pump will run whenever the burner is firing, unless
the DHW is programmed for Normal Mode and the boiler is
heating the DHW tank. The boiler pump will run during Freeze
Protection Mode as well. It will continue to run for a short time
after the burner turns off or the Freeze Protection Mode ends.
The system pump will run whenever there is a space heating call
for heat, a DHW call for heat when the DHW is programmed
for Zone Mode, or the boiler goes into Freeze Protection Mode.
It will continue to run for a short time after the end of the heat
demand or the Freeze Protection Mode. The system pump can
be programmed to run continuously if desired, except during
outdoor shutdown.
Temperature control
Modulation
The Knight boiler is capable of modulating its firing rate from
a minimum of 20% to a maximum of 100%. The firing rate is
dictated by the call for heat (i.e., space heating or domestic hot
water), the heating load, ramp delay (if enabled), and various
other temperature limitations.
61
Page 62
11 Operating information
Installation & Operation Manual
Ramp delay
For systems with lower flow, the SMART SYSTEM can limit
the firing rate (when enabled) when a space heating call for
heat starts, or when switching from a DHW call for heat to a
space heating call for heat. There are six (6) limits that can be
programmed, as well as six (6) time intervals corresponding
to each limit. The sixth limit will also limit the firing rate for
the rest of the call for heat.
Gradient limiting
If during operation of the boiler the outlet water temperature
is rising too quickly, the control will reduce the firing rate to
its lowest setting.
Outdoor air reset
With the outdoor air sensor connected, the control module
will calculate the set points of the three (3) space heating
demands based on the programmed reset curves. The
installer can change the slope of the reset curves by several
adjustable parameters. The user can limit the maximum set
point for the system using the space heating set points.
Boost function
Protection features
Outlet temperature, flue temperature, and
temperature rise limiting
The outlet temperature is monitored by the boiler outlet
temperature sensor. When the outlet temperature exceeds
185°F, the unit will reduce the fan speed. If the outlet water
temperature exceeds 195°F the control will shut the unit
down until it cools off.
The control module monitors the flue temperature by a
sensor located in the flue exhaust. If the flue temperature
exceeds 215°F the control will reduce the maximum fan
speed. If the flue temperature exceeds 240°F the control will
shut the unit down. The unit will restart automatically once
the flue temperature drops 25°F and the minimum off time
has expired.
The control monitors the temperature difference between
the inlet and the outlet sensor. If this difference exceeds
55°F the control will reduce the maximum fan speed. If
the temperature difference exceeds 60°F the control will
shut the unit down. The unit will restart automatically once
the temperature difference has dropped below 55°F and the
minimum off time has expired.
If outdoor air reset is active, and any space heating demand
has been active continuously for a set period of time (time
adjustable by installer) and there has been no DHW demands,
the control will increase the set point of that demand
by a fixed number of degrees (adjustable by installer).
This process will continue until the space heating demand
ends, the set point reaches the programmed set point or a
maximum of 20 increases has occurred. Once the system
heat demand is satisfied, the set point will revert to the value
determined by the reset curve.
Night setback
The controller may be programmed to reduce the space
heating and DHW set points during certain times each week.
Seven different start and stop times may be programmed
for the space heating setback and seven start and stop times
for the DHW setback. Any night setback event scheduled
within the next seven (7) days can be temporarily bypassed
if desired.
Flame current support
To prevent nuisance shutdowns when the boiler is firing at
minimum rates, the control will increase the firing rate when
the flame signal drops too low.
62
Freeze protection
DO NOT install the boiler in a room likely to freeze.
The following integral feature of the SMART SYSTEM
control module provides some protection for the boiler only
-- not for the system.
• The SMART SYSTEM control module provides
freeze-up protection as follows when the boiler
water temperature drops below 45°F:
• Below 45°F, the boiler and system pumps operate
constantly.
• Below 37°F, the boiler turns on.
• Boiler and pumps turn off if boiler water
temperature rises above 45°F.
• Lower temperatures may be programmed for
systems with anti-freeze solutions.
NOTICE
CAUTION
When system return temperatures
are maintained below the dew point,
condensation will form on the inside of
the boiler jacket causing some internal
sheet metal components to rust.
This feature of the SMART SYSTEM
control module does not eliminate the
possibility of freezing. The installation
must still use recognized design,
installation and maintenance practice to
prevent freeze potential for the boiler and
system.
Page 63
11 Operating information (continued)
Monitor external limits
Connections are provided on the connection board for
external limits such as flow switch, low water cutoff, gas
pressure switches, and a louver proving switch. The SMART
SYSTEM will shut off the burner and inhibit relighting
whenever any of these external limits open.
Run-time and alarm outputs
The boiler provides dry contacts for indicating when the
boiler is running, and when it is unable to operate.
Run-time and cycle counting
The control uses two timers to monitor the total hours of
burner operation. One timer monitors the time the boiler is
firing in the Space Heating Mode. The other timer monitors
the time the boiler is firing in the DHW Mode.
The control uses two (2) ignition counters to monitor the
amount of boiler cycles. The first counter counts all ignitions
of the control. The second counter counts only ignition
attempts that have failed.
Service reminder
The control can be programmed for service reminder
notification. This notification will become active when either
a set time frame has expired, or a set amount of running
hours or cycles has expired (all adjustable by the installer).
The display will show a Maintenance Required screen. The
service reminder notification can be reset or disabled by the
installer.
The time dependent feature has been disabled by the
manufacturer. To enable this feature change parameter K1 to
the desired time range, reference the Knight Service Manual
for details regarding parameters.
Error logging
The control will hold in memory the last 10 lockouts as
well as the last 10 blockings. The date and time of the
occurrence will be recorded as well. Only the 10 most current
occurrences of each will be held in memory.
Boiler temperature regulation
Operating temperature (target)
The SMART SYSTEM control module senses water
temperature and regulates boiler firing and firing rate to
achieve a target temperature. The target temperature can be
set between 32°F and 190°F.
• Target temperature is fixed when the outdoor sensor
is not installed.
• Target temperature is calculated as described below
under “Outdoor Reset Operation” and “Target
Temperature Boost” when the outdoor sensor is
connected.
Installation & Operation Manual
High limit operations
The Knight boiler is equipped with adjustable automatic reset
and manual reset high limits. The automatic reset high limit
has a maximum set point of 200°F and the manual reset high
limit has a maximum set point of 210°F.
When the outlet temperature exceeds 200°F, the automatic
high limit action occurs. The boiler shuts down until the outlet
water temperature cools below 190°F, and a 60 second timer
has expired. If the outlet temperature continues to increase, the
manual reset high limit action will occur at 210°F.
High limit test procedure
NOTICE
1. Turn ON the main power to the boiler by placing the
ON/OFF switch in the ON position.
2. If boiler status reads [SHUTDOWN] place the boiler into
the active position by pressing the RIGHT SELECT [ON]
key.
3. Locate the pinhole (SERVICE button) below the RESET
button on the display board. Insert a thin wire (such as a
paper clip) into the hole and press the button once, hold
for five (5) seconds to place the boiler into Service Mode.
In Service Mode the boiler will fire at ignition speed and
will then modulate up to full fire.
4. From the Status Screen, press the NAVIGATION dial to
access the Set Points Screen.
5. Press the LEFT SELECT [LIMITS] key.
6. Select the manual reset high limit (MRHL) by pressing the
NAVIGATION dial.
7. Decrease the set point of the MRHL below the outlet
temperature by turning the NAVIGATION dial
counterclockwise.
8. Press the RIGHT SELECT [SAVE] key.
9. Press the RIGHT SELECT [HOME] key.
10. The new parameters will upload to the control and the
MRHL will function causing boiler shutdown and
[LOCKOUT] to be displayed.
11. Press the RESET button to clear the lockout.
12. Repeat Steps 4, 5 and 6.
13. Set the MRHL to the appropriate set point by turning the
NAVIGATION dial clockwise.
14. Repeat Steps 8 and 9.
Low water cutoff protection
1. The SMART SYSTEM control module uses temperature
sensing of both supply and return areas of the heat
exchanger. If the flow rate is too low or the outlet
temperature too high, the control module modulates and
shuts the boiler down. This ensures boiler shutdown in the
event of low water or low flow conditions.
2. Some codes and jurisdiction may accept these integral
features of the control in lieu of requiring an additional
limit control or low water cutoff. Consult local jurisdiction
to determine. A low water cutoff is available from the
factory (WTR20009).
Please note that the brackets ([]) denote
screen status.
63
Page 64
11 Operating information
Installation & Operation Manual
Outdoor reset operation, if used
Target temperature with outdoor reset
This feature improves the system’s efficiency as the outdoor
temperature warms up.
See the Knight Boiler Service Manual to change the settings.
Reset curve
The reset curve looks at outdoor air temperature and adjusts
the set point.
Cascade
When multiple boilers are installed, they can be wired together
in a cascade sequence. A maximum of eight boilers can be
controlled from a single control. In this application one boiler
would be designated as the Leader control and all others would
be designated as Member controls. If installing the boilers in
an existing system, the new boilers should be programmed as
the Leader and/or the higher number addresses. The Leader
control can be programmed to use Lead/Lag or Efficiency
Optimization control methods.
Once the Leader boiler receives a call for heat from a room
thermostat, BMS, or Modbus, the control will determine what
the set point will be. If outdoor air reset is desired, connect
the outdoor air sensor to the terminals on the Low Voltage
Connection Board on the Leader boiler. The set point will be
calculated based on the programmed reset curve parameters.
See the Knight Boiler Service Manual to program the reset
curve. If outdoor air reset is not desired, do not connect the
outdoor air sensor. A fixed temperature set point can be
programmed into the control. See page 59 of this manual to
program the set point.
If the water temperature at the system supply sensor is less than
the set point + the turn-off offset - the off-on differential, then
the control will initiate a call for heat on the Cascade (see the
Knight Boiler Service Manual for an explanation of the offset
and differential). The Leader will energize the lead boiler on the
Cascade. For a new startup this will be the Leader boiler.
Sequence of the cascade
To equalize the run time of all boilers on the Cascade, the
firing sequence will automatically be changed at set intervals.
The sequence will be changed once every 24 hours. The
switching on/off sequence will be as follows:
DAYSWITCHING ON SEQUENCE
Day 1L-M1-M2-M3-M4-M5-M6-M7
Day 1 + 1 hourM1-M2-M3-M4-M5-M6-M7-L
Day 1 + 2 hoursM2-M3-M4-M5-M6-M7-L-M1
If a boiler is used to heat an indirect DHW tank, or locks out,
it will automatically be given the lowest priority for the rest
of that 24 hour period.
DHW, Night Setback, and Ramp Delay operation
with cascade
For Normal Mode DHW operation any boiler(s) in the
Cascade can be selected to provide heat for a DHW call.
Select a boiler to be designated as the DHW boiler. Connect
the DHW thermostat or sensor to the terminals on the Low
Voltage Connection Board marked for the corresponding
device. When the boiler receives a DHW call, the Leader
control will take that boiler out of the Cascade sequence. If
another boiler is available, the Leader will start it up to take
its place.
The DHW boiler will adjust its set point to the programmed
DHW set point and will adjust its firing rate to maintain this.
Once the DHW call has been satisfied, the Leader control will
place that boiler back into the Cascade sequence.
Switching of the boiler between DHW operation and SH
operation when there is a call for both does not occur in
Cascade Mode.
When DHW is programmed for Zone Mode, connect the
DHW thermostat or tank sensor to the Leader boiler. When
a DHW call is received, the Leader will modulate the entire
Cascade to bring the system supply temperature up to the
DHW boiler set point.
64
Night Setback operation of the boilers within the Cascade is
available. Programming of the Night Setback will be done
through the Leader boiler. Refer to the Knight Boiler Service
Manual for information regarding Night Setback.
Ramp Delay operation of the boilers as described in the
Knight Boiler Service Manual is available when the boilers are
part of a Cascade system.
Page 65
11 Operating information (continued)
Sequence of operation
OPERATIONDISPLAY
1. Upon a call for heat, the gas pressure switch(es) must be closed.
2. Once the gas pressure switch(es) are closed, the control turns
on the appropriate pumps (system and boiler pumps for space
heating, DHW pump for DHW). The flow switch and/or LWCO
must close.
Installation & Operation Manual
3. The control turns on power to the louver relay. The louver
proving switch, air pressure switch, and blocked drain switch
must close.
4. The control starts a 15 second prepurge cycle by initiating the
blower.
5. The control starts a 4 second trial for ignition by firing the spark
electrode and opening the gas valve.
6. If flame is not detected within 1 second after the sparking ends,
the control will perform a 10 second post-purge, then start
another prepurge cycle and try to light the burner again. The
control will perform a total of 4 attempts before locking out.
7. If flame is detected, it holds the firing rate steady for 5 seconds
to let the flame stabilize, then it begins to modulate the firing rate
based on a set point or some other command (such as a 0-10V
BMS signal).
65
Page 66
11 Operating information
Sequence of operation (continued)
OPERATIONDISPLAY
8. If the space heating call for heat is active, and the tank thermostat
or sensor starts a DHW call for heat, the boiler will switch to the
DHW mode. If programmed for normal DHW operation (not as a
zone), the DHW pump will turn on first, then the boiler pump will
turn off 2 seconds later. This will divert the boiler’s outlet water
from the heating system and send it to the tank coil instead. The
control will then modulate to maintain the outlet temperature to
the DHW boiler set point.
9. If the boiler is not part of a Cascade, and both the space heating
and DHW calls for heat remain active long enough, the boiler will
switch back and forth between the two heating modes until one of
them is satisfied.
Installation & Operation Manual
10. Once both calls for heat are satisfied, the control will turn off the
burner. The blower will continue to run during a 10 second
postpurge.
11. Any pumps that are running will continue to run for their respective
pump delay times before turning off, unless programmed to
remain on continuously. A 60 second anti-cycle period will start,
which will delay any new call for heat until it times out.
12. In Standby, ready to start a new cycle.
66
Page 67
Installation & Operation Manual
11 Operating information (continued)
Knight boiler control module
Use the control panel (FIG. 11-1) to set temperatures, operating conditions, and monitor boiler operation.
Figure 11-1 Control Panel
NAVIGATION DIAL
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the
NAVIGATION dial (in the center):
MENU = Left SELECT Key
SETPOINTS = NAVIGATION Dial - Pressing Down
SHDN = Right SELECT Key
67
Page 68
11 Operating information
Access modes
User
The user can adjust space heating and tank target temperatures
by pressing the NAVIGATION dial when “SETPOINTS” is
flashing at the bottom of the display. The date and time, and the
temperature units can also be changed (see page 60).
Installer
Most parameters are available only to the installer, accessible
by entering the installer password, see the Knight Boiler Service
Manual.
Saving parameters (reference the Parameter Table in the
Knight Boiler Service Manual)
Installation & Operation Manual
NOTICE
To save parameters and exit programming:
Press the RIGHT SELECT [SAVE] key and then press the RIGHT
SELECT [HOME] key.
To enter a parameter and continue programming:
Press the RIGHT SELECT [SAVE] key 1 time to return to the
parameter listings; press again to return to the menu listings.
Remember to press the RIGHT SELECT [HOME] key when
finished programming in order to save the changes made.
See the Knight Boiler Service Manual for a detailed description of
parameters and access modes.
Please note that the brackets ([]) denote
screen status.
68
Page 69
11 Operating information (continued)
Figure 11-2 Status Display Screen
Installation & Operation Manual
A
(BOILER
STATUS)
C
(OPERATIONAL
INFORMATION)
D
(LEFT SELECT
KEY)
E
(NAVIGATION DIAL)
Status Display Screens
SectionDisplayDescription
STANDBY
START The unit has begun a burn cycle and is checking all safety circuits.
PREPURGEThe unit has initiated a 10 second purge period on a call for heat.
The unit has not received a call for heat from a remote thermostat nor
has it received a call for heat from a DHW thermostat.
B
(CALL FOR
HEAT)
F
(RIGHT SELECT KEY)
A
(Boiler Status
Bar)
B
(Call for Heat
Indicators)
IGNITIONThe unit has begun a 4 second spark period to ignite the main burner.
The unit has fired and is running at the displayed percentage.
POSTPURGE
SHUTDOWNThe unit has been placed in the OFF position.
BLOCKED
%
The call for heat has been satisfied and the unit runs the fan for an
additional 10 seconds to clear the combustion chamber and vent
system of residual flue products.
The controlled temperature has exceeded its set point and its offset.
The unit has detected a condition that has temporarily interrupted
the current call for heat.
Room Thermostat 1 has a call for heat.
Room Thermostat 2 has a call for heat.
Room Thermostat 3 has a call for heat.
The tank thermostat or sensor has a call for heat.
Indicates which room thermostat demand shows priority.
The unit is being controlled by a 0 - 10V BMS signal.
The member unit is supplying heat while in Cascade Mode.
69
Page 70
11 Operating information
Status Display Screens (cont’d)
SectionDisplayDescription
SYSTEM:The temperature read by the system supply sensor (if connected).
TANK: The temperature read by the tank sensor (if connected).
OUTDOOR:The temperature read by the outdoor sensor (if connected).
INLET TEMP:The temperature read at the inlet to the heat exchanger.
OUTLET TEMP:The temperature read at the outlet of the heat exchanger.
Installation & Operation Manual
C
(Operational
Information)
DELTA T:
FLUE TEMP:The temperature read by the flue sensor.
FLAME CURRENT:The current measured by the flame sense circuit.
FAN SPEED:The speed of the combustion blower.
BOILER PUMP:The status of the boiler pump output.
SYSTEM PUMP:The status of the system pump output.
DHW PUMP:The status of the DHW pump output.
BMS VOLTAGE:The voltage received from a BMS system.
BLR PUMP OUTPUT:The speed signal sent to a variable speed boiler pump in percent.
SYS PUMP INPUT:The speed signal received from a variable speed system pump control.
RATE OUTPUT:A 0 - 10V signal indicating the firing rate of the boiler.
SH RUN HOURS:The total hours of operation in the Space Heating Mode.
SH CYCLES:The total burner cycles in the Space Heating Mode.
The temperature difference between the inlet and the outlet of the
heat exchanger.
DHW RUN HOURS:The total hours of operation in the DHW Mode.
DHW CYCLES:The total burner cycles in the DHW Mode.
LAST 10 FAULTS NO:*The last 10 lockouts.
MENU
EXITPress the LEFT SELECT key to exit the current screen or setting.
D
YES
(LEFT SELECT
key function)
70
LIMITS
HOME
Press and hold the LEFT SELECT key for 5 seconds to enter the Menu
Screen.
Press the LEFT SELECT key to confirm that the boiler needs to
shutdown.
Press the LEFT SELECT key to enter the screen that allows you to
adjust the limit settings.
Press the LEFT SELECT key to return to the Status Screen and upload
parameter changes.
Page 71
11 Operating information (continued)
Status Display Screens (cont’d)
SectionDisplayDescription
Turning the NAVIGATION dial will select the next or previous Status
Screen.
Pressing the NAVIGATION dial will show the next fault, NSB (Night
Setback) trigger, or ramp delay setting.
Installation & Operation Manual
E
(NAVIGATION
Dial Function)
F
(RIGHT SELECT
key function)
Pressing the NAVIGATION dial will select the setting indicated by
the cursor.
Pressing the NAVIGATION dial will display the Set Points Screen.
Turning the NAVIGATION dial will move the cursor up or down.
Turning the NAVIGATION dial will increase or decrease the current
setting.
SHDNPress the RIGHT SELECT key to turn the boiler OFF.
ONPress the RIGHT SELECT key to turn the boiler ON.
NOPress the RIGHT SELECT key to cancel the shutdown operation.
SAVEPress the RIGHT SELECT key to save the current change.
HOME
Press the RIGHT SELECT key to return to the Status Screen and
upload parameter changes.
71
Page 72
12 Maintenance
Maintenance and annual startup
Table 12A Service and Maintenance Schedules
Installation & Operation Manual
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if
necessary;
• Clean condensate trap and fill with fresh
water
• Check for leaks (water, gas, flue,
condensate)
• Verify flue and air lines in good condition
and sealed tight
• Check system water pressure/system
piping/expansion tank
• Check control settings
• Check ignition and flame sense
electrodes (sand off any deposits; clean
and reposition)
• Check wiring and connections
ANNUAL START-UP
• Perform start-up checkout and
performance verification per Section 10
of this manual.
• Flame inspection (stable, uniform)
Owner maintenance
(see the Knight User’s Information Manual for
instructions)
• Check boiler area
• Check pressure / temperature
Daily
Monthly
Periodically
gauge
• Check vent piping
• Check air piping
• Check air and vent termination
screens
• Check relief valve
• Check condensate drain system
• Check air vents
• Test low water cutoff (if used)
• Flame signal (at least 10 microamps at
high fire)
• Clean the heat exchanger if flue
temperature is more than 54°F above
return water temperature.
If combustion or performance
indicate need:
• Clean heat exchanger
• Remove and clean burner using
compressed air only
• Clean the blower wheel
72
Every
6 months
End
of season
months
• Reset button (low water cutoff)
• Check boiler piping (gas and
water) for leaks
• Operate relief valve
• Shut boiler down (unless boiler
used for domestic hot water)
Page 73
12 Maintenance (continued)
Installation & Operation Manual
Flue vent system and air piping
1. Visually inspect the entire flue gas venting system and air
piping for blockage, deterioration or leakage. Repair any
joints that show signs of leakage. Verify that air inlet pipe
is connected and properly sealed.
2. Verify that boiler vent discharge and air intake are clean
and free of obstructions.
WARNING
Failure to inspect for the above conditions
and have them repaired can result in
severe personal injury or death.
Check water system
1. Verify all system components are correctly installed and
operational.
2. Check the cold fill pressure for the system. Verify it is
correct (must be a minimum of 12 psi).
3. Watch the system pressure as the boiler heats up (during
testing) to ensure pressure does not rise too high.
Excessive pressure rise indicates expansion tank sizing or
performance problem.
4. Inspect automatic air vents and air separators. Remove
air vent caps and briefly press push valve to flush vent.
Replace caps. Make sure vents do not leak. Replace any
leaking vents.
Check expansion tank
1. Expansion tanks provide space for water to move in
and out as the heating system water expands due to
temperature increase or contracts as the water cools.
Tanks may be open, closed or diaphragm or bladder
type. See Section 6 - Hydronic Piping for suggested best
location of expansion tanks and air eliminators.
WARNING
WARNING
Safety relief valves should be re-inspected
AT LEAST ONCE EVERY THREE YEARS,
by a licensed plumbing contractor or
authorized inspection agency, to ensure
that the product has not been affected by
corrosive water conditions and to ensure
that the valve and discharge line have not
been altered or tampered with illegally.
Certain naturally occurring conditions
may corrode the valve or its components
over time, rendering the valve inoperative.
Such conditions are not detectable unless
the valve and its components are physically
removed and inspected. This inspection
must only be conducted by a plumbing
contractor or authorized inspection
agency – not by the owner. Failure to
re-inspect the boiler relief valve as directed
could result in unsafe pressure buildup,
which can result in severe personal injury,
death, or substantial property damage.
Following installation, the valve lever
must be operated AT LEAST ONCE
A YEAR to ensure that waterways are
clear. Certain naturally occurring
mineral deposits may adhere to the valve,
rendering it inoperative. When manually
operating the lever, water will discharge
and precautions must be taken to avoid
contact with hot water and to avoid water
damage. Before operating lever, check
to see that a discharge line is connected
to this valve directing the flow of hot
water from the valve to a proper place of
disposal. Otherwise severe personal injury
may result. If no water flows, valve is
inoperative. Shut down the boiler until a
new relief valve has been installed.
Check boiler relief valve
1. Inspect the relief valve and lift the lever to verify flow.
Before operating any relief valve, ensure that it is piped
with its discharge in a safe area to avoid severe scald
potential. Read Section 6 - Hydronic Piping before
proceeding further.
2. After following the above warning directions, if the relief
valve weeps or will not seat properly, replace the relief
valve. Ensure that the reason for relief valve weeping is
the valve and not over-pressurization of the system due
to expansion tank waterlogging or undersizing.
73
Page 74
12 Maintenance
Installation & Operation Manual
WARNING
Follow the service and maintenance procedures given throughout this manual and in component literature
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler
or system. Failure to follow the directions in this manual and component literature could result in severe
personal injury, death, or substantial property damage.
WARNING
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance
and care of the boiler designated in Table 12A and explained on the following pages must be performed to
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could
result in equipment failure.
WARNING
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,
causing severe personal injury or death.
Address reported problems
1. Inspect any problems reported by the owner and correct
before proceeding.
Inspect boiler area
1. Verify that boiler area is free of any combustible materials,
gasoline and other flammable vapors and liquids.
2. Verify that air intake area is free of any of the contaminants
listed in Section 1 of this manual. If any of these are
present in the boiler intake air vicinity, they must be
removed. If they cannot be removed, reinstall the air and
vent lines per this manual and the Knight Boiler Service
Manual.
Figure 12-1 Condensate Trap
RETAINING
SCREW
2” PVC CAP WITH
BLOCKED DRAIN SWITCH
PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
Inspect boiler interior
1. Remove the front access cover and inspect the interior of
the boiler.
2. Vacuum any sediment from inside the boiler and
components. Remove any obstructions.
Clean condensate trap
1. Inspect the condensate drain line, condensate PVC
fittings, and condensate trap.
2. Remove the PVC cap retaining screw from the PVC cap
(FIG. 12-1).
3. Remove the 2 inch PVC cap with the switch located at the
top of the trap (FIG. 12-1).
4. Remove any sediment in the trap.
5. Fill with fresh water until the water begins to pour out of
the drain.
6. Replace the cap. Press the cap onto the trap until the cap
makes contact with the drain.
7. Replace the retaining screw.
CONDENSATE FROM
HEAT EXCHANGER
WARNING
The condensate trap must be filled with
water during all times of boiler operation
TO FLOOR
DRAIN
to avoid flue gas emission from the
condensate drain line. Failure to fill the
trap could result in severe personal injury
or death.
Check all piping for leaks
WARNING
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems
found.
3. Check gas line using the procedure found in Section 7
- Gas Connections.
Eliminate all system or boiler leaks.
Continual fresh makeup water will
reduce boiler life. Minerals can build
up in sections, reducing heat transfer,
overheating heat exchanger, and causing
heat exchanger failure. Leaking water may
also cause severe property damage.
74
Page 75
12 Maintenance (continued)
Installation & Operation Manual
Inspect ignition and flame sense
electrodes
1. Remove the ignition and flame sense electrodes from the
boiler heat exchanger access cover.
2. Remove any deposits accumulated on the ignition/flame
sense electrode using sandpaper. If the electrodes cannot
be cleaned satisfactorily, replace with new ones.
3. Replace ignition/flame sense electrode, making sure
gasket is in good condition and correctly positioned.
Check ignition ground wiring
1. Inspect boiler ground wire from the heat exchanger
access cover to ground terminal strip.
2. Verify all wiring is in good condition and securely
attached.
3. Check ground continuity of wiring using continuity
meter.
Check burner flame
1. Inspect flame through observation window.
2. If the flame is unsatisfactory at either high fire or low fire,
turn off boiler and allow boiler to cool down. Remove the
burner and clean it thoroughly using a vacuum cleaner or
compressed air. Do not use compressed air to clean burner
if performed inside a building.
3. Remove the burner, reference FIG. 12-2 below.
4. When replacing the burner, ensure gasket is in good
condition and positioned correctly (FIG. 12-2).
Figure 12-2 Burner Assembly
4. Replace ground wires if ground continuity is not
satisfactory.
Check all boiler wiring
1. Inspect all boiler wiring, making sure wires are in good
condition and securely attached.
Check control settings
1. Set the SMART SYSTEM control module display to
Parameter Mode and check all settings. See Section
1 of Knight Boiler Service Manual. Adjust settings if
necessary. See Section 1 of the Knight Boiler Service
Manual for adjustment procedures.
2. Check settings of external limit controls (if any) and
adjust if necessary.
Perform start-up and checks
1. Start boiler and perform checks and tests specified in
Section 10 - Start-up.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
Check flame signal
1. At high fire the flame signal shown on the display should be
at least 10 microamps.
2. A lower flame signal may indicate a fouled or damaged
flame sense electrode. If cleaning the flame sense electrode
does not improve, ground wiring is in good condition, and
ground continuity is satisfactory, replace the flame sense
electrode.
3. See Section 3 - Troubleshooting of the Knight Boiler
Service Manual for other procedures to deal with low flame
signal.
75
Page 76
12 Maintenance
Installation & Operation Manual
Review with owner
1. Review the Knight Boiler User’s Information Manual
with the owner.
2. Emphasize the need to perform the maintenance schedule
specified in the Knight Boiler User’s Information Manual
(and in this manual as well).
3. Remind the owner of the need to call a licensed contractor
should the boiler or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown
procedure and to schedule an annual start-up at the
beginning of the next heating season.
Cleaning boiler heat exchanger
For recommended materials; including brush, appropriate
extension(s), refractory cover, and detailed instructions see
Table 12B - Heat Exchanger Cleaning Kits.
1. Shut down boiler:
• Follow the “To Turn Off Gas to Appliance” instructions
for the boiler in Section 10 - Startup.
• Do not drain the boiler unless it will be exposed to
freezing temperatures. If using freeze prevention fluid
in system, do not drain.
2. Allow time for the boiler to cool to room temperature if
it has been firing.
3. Remove the nuts securing the heat exchanger access
cover to the heat exchanger and set aside.
4. Remove the heat exchanger access cover, burner, and
gas/air arm assembly.
11. Close isolation valves on piping to isolate boiler from
system. Attach a hose to the boiler drain and flush boiler
thoroughly with clean water by using purging valves to
allow water to flow through the water make-up line to the
boiler.
12. Perform start-up and check-out procedures in the Check
Flame and Combustion - Section 10 - Startup on pages 57
and 59 of this manual.
13. Replace the access cover and restore boiler to operation.
Table 12B Heat Exchanger Cleaning Kits
Model
81
-
106
151
-
286
CAUTION
Kit
Number
KIT30062
KIT30063
* Do NOT use a metal brush. Only use
the kit provided brush or an equivalent
Part
Number
CTN20005Rear Refractory Cover
MSC20083* Nylon 4" Wheel Brush*
MSC20085 1/4" x 12” Drill Extension
CTN20005Rear Refractory Cover
MSC20083* Nylon 4" Wheel Brush*
MSC200843mm Allen Wrench
MSC20086 1/4" x 24" Drill Extension
Component
Description
replacement nylon brush.
Figure 12-3 Rope Gasket - Heat Exchanger Door
WARNING
The boiler contains ceramic fiber
materials. Use care when handling these
materials per instructions in the Service
Manual. Failure to comply could result in
severe personal injury.
5. Remove the condensate hose from the heat exchanger
end. Connect a field supplied 3/4" diameter hose to
a drain pan. Using field supplied means, cover the
refractory in the back of the combustion chamber of the
heat exchanger.
6. Use a vacuum cleaner to remove any accumulation on the
boiler heating surfaces. Do not use any solvent.
7. Brush the heat exchanger while dry using a nylon bristle
brush. Caution: DO NOT use a metal brush. Re-vacuum
the heat exchanger.
8. Finish cleaning using a clean cloth dampened with warm
water. Rinse out debris with a low pressure water supply.
9. Allow the heat exchanger to thoroughly dry.
10. Remove the field supplied rear refractory cover from the
back of the combustion chamber of the heat exchanger
and reassemble.
76
ROPE GASKET
CAUTION: IF GASKET IS DAMAGED
DO NOT REUSE, THE HEAT EXCHANGER DOOR
MUST BE REPLACED.
NOTICE
Rope gasket is intended for sealing combustion
(FIG. 12-3). If damaged DO NOT reuse, the
heat exchanger door must be replaced. Consult
factory for replacement heat exchanger door
(kit WTR3080).
Oiled bearing circulators
1. The circulator shipped with the Knight boiler is waterlubricated. No oiling is required.
2. Check other circulators in the system. Oil any circulators
requiring oil, following circulator manufacturer’s
instructions. Over-oiling will damage the circulator.
3. Replace the boiler front access cover.
Page 77
13 Diagrams
Figure 13-1 Ladder Diagram
120VAC
TERMINAL STRIP
120V SUPPLY "L"
ON / OFF
KB ONLY
SWITCH
PC INTERFACE
ALARM
BELL
SWITCH
SILENCING
CONTACTS
RUN-TIME
CONTACTS
SYSTEM
SENSOR
OUTDOOR
SENSOR
TANK
SENSOR
SHIELD
A
CASCADE
B
SHIELD
BMS
+
IN
-
+
SYS PUMP
IN
-
+
BLR PUMP
OUT
-
+
RATE
OUT
-
SHIELD
A
MODBUS
B
SHIELD
1
2
6
13
ALARM
X4-3
CN5-5
X1-6
S6
S5
S4
0-10V
0-10V
0-10V
0-10V
X5-9
3.5A
KB 801 ONLY
CN7-1
CN7-3
CONNECTION
INTEGRATED CONTROL
F2
3.15A
F1
5A
F3
.8A
120 VAC
24 VAC
LWCO
CONNECTION BOARD
S2
INLET
SENSOR
S1a
OPERATING
SENSOR
S1b
HIGH LIMIT
SENSOR
FLUE
SENSOR
FLUE
SENSOR
BOARD
1
2
3
4
21
22
23
24
26
27
29
30
31
32
33
34
35
36
37
38
39
40
41
CN8-1
42
CN8-2 X6-2
43
CN8-3 X6-3
44
JUNCTION BOX
SYSTEM PUMP
RELAY
BOILER PUMP
RELAY
DHW PUMP
RELAY
24V DC
SUPPLY
CN7-4
CN7-2
RIBBON CABLE
S3a
S3b
CN5-1
CN5-8
CN6
CN6
CN6
CN3-9
CN3-6
CN6
CN6
CN6
CN6
CN6
CN6
CN6
CN6
CN6
CN6
Installation & Operation Manual
GROUND
NEUTRAL
TERMINAL STRIP
120V SUPPLY "N"
12
9
5
6
7
8
BLOCKED
DRAIN SWITCH
BLOWER
3
CN5-14 X4-8
CN5-10
CN5-7
CN5-13
CN5-6
CN5-12
CN5-11
CN5-3
CN5-4 X4-4
X5-2
X5-10
X5-11
X2-2
X2-1
1
2
4
5
TR2
X1-7
FLAME ROD
INTEGRATED
X4-12
X4-1
X4-9
X4-2
X4-10
X4-11
X4-5
GAS VALVE
X5-7
X5-16
X5-8
X5-15
BOX DEPICTS
OPTIONAL ITEMS
LOW VOLTAGE
120 VAC
HIGH VOLTAGE
LADDER DIAGRAM
CONTROL
RELAY
LBL20148 REV C
SYSTEM
PUMP
BOILER
PUMP
DHW
PUMP
CONNECTION BOARD
FLOW
SWITCH
HEAT/LOOP
1
DEMAND
HEAT/LOOP
2
DEMAND
HEAT/LOOP
3
DEMAND
TANK
THERMOSTAT
HIGH GAS
PRESSURE
SWITCH
LOUVER
RELAY COIL
24VAC
LOUVER
PROVING SWITCH
GND
SYSTEM
PUMP "N"
GND
BOILER
PUMP "N"
GND
DHW
PUMP "N"
TERMINAL
STRIP
12
20
18
16
14
SYSTEM
X1-1
PUMP "L"
X1-2
BOILER
PUMP "L"
X1-4
DHW
PUMP "L"
X1-3
TERMINAL
STRIP
X5-1
11
19
17
15
13
LOW GAS
PRESSURE
SWITCH
10
INTEGRATED
CONTROL
X7
KB 286 ONLY
X5-6
X5-4
X5-12
X5-5
X5-13
X5-14
X4-7
X4-14
CN5-2
X4-6
CN5-9
X4-13
X6
X6
X6
X4-9
X4-6
X6
X6
X6
X6
X6
X6
X6
X6
X6
X6
M
O
X4-1
X9-2
X6-1
D
X4-2
X9-1
B
U
X4-3
X9-3
S
O-TEMP HEX SW
AIR PRESSURE
SWITCH
GAS VALVE
BLOWER
SPARK
ROD
CAUTION HIGH VOLTAGE SPARK LEAD
NOTES:
1. Where possible, switches are shown without utilities (gas, water or
electricit y) connected to th e unit. As such, actual swi tch states may
vary from those shown on diagrams depending upon whether utilities
are connected or a fault condition i s present.
2. See wiring diagram for additional notes.
77
Page 78
13 Diagrams
Figure 13-2 Wiring Diagram
Installation & Operation Manual
LOW VOLTAGE
120 VAC
HIGH VOLTAGE
CONNECTION BOARD
ALARM
CONTACT S
RUN-TIME
CONTACT S
24 VAC LOUVER
RELAY COIL
BELL JUMPER
ALARM BELL
SILENCING SWITCH
Notes:
1. All wiring must be installed in accordance with:
2. If any original equipment wire as supplied with
minimum of 105°C. Exceptions: Replacement high vo ltage spark lead and ribbon cables must be purchase
or ribbon cables can lead to operational problems w
3. Actual connector block locations may vary from t
diagrams to troubleshoot unit.
LOUVER
PROVING SWIT CH
GAS PRESSURE
SWITCH
FLOW
SWITCH
TANK
THERMOSTAT
HEAT/LOOP
DEMAND
HEAT/LOOP
DEMAND
HEAT/LOOP
DEMAND
SYSTEM
SENSOR
OUTDOOR
SENSOR
TANK
SENSOR
SHIELD
A
CASCADE
GROUNDING
SHIELD
BMS
SYS PUMP
BLR PUMP
OUT
RATE
OUT
MODBUS
OPTION
LOW
WATER
CUT-OFF
SHIELD
JUMPER
B
IN
IN
SHIELD
SHIELD
+
-
+
-
+
-
+
-
A
B
1
2
3
0-10V
0-10V
0-10V
0-10V
24 VAC
COM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
CN5-1
CN5-8
CN5-2
CN5-9
CN5-3
CN5-10
CN5-11
CN5-4
CN5-5
CN5-14
CN5-12
CN5-6
CN5-13
CN5-7
CN6
33
34
35
36
37
38
39
40
41
42
43
44
CN7-1
CN7-2
CN7-3
CN7-4
MODBUS BOARD
X5-1
X5-2
local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada.
the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a
hich could result in non-repairable damage to the integrated controller or other components.
hose shown on diagrams. Refer to actual components
MTR-01
CN8-1
CN8-2
CN8-3
BL
R
G
X6-3
X6-2
X6-1
X6-4
X4-1
X4-2
X4-3
X4-4
X1-1
X1-2
X1-3
X-7
X4-7
BK
BK
X4-14
BK
X4-6
BK
X4-13
BK
X4-5
BK
X4-12
BK
X4-11
BK
X4-4
BK
X4-3
BK
X4-8
BK
X4-10
BK
X4-2
BK
X4-9
BK
X4-1
X6
O
X9-1
GY
X9-2
X9-3
G
X9-4
BK
W
G
BOX DEPICTS
OPTIONAL ITEMS
BOX DEPICTS
DUAL SENSOR
SINGLE HOUSING
INTEGR ATED
CONTROL
X1-3
OR
KB ONLY
ON/OFF
SWITC H
R W
1
W
W
W
G
2
3
TRANSFORMER
X1-4
X1-2
X1-6
X1-5
X1-8
X1-1
BR
PR
BK
W
G
R
BLOWER
1 2
5
3 4
R
X5-7
T
X5-16
W
X5-8
BK
X5-15
Y
X5-9
X5-1
BL
O
X5-2
BLOCKED DRAIN SWITCH
P
X5-10
X5-11
X5-4
X5-12
X5-6
X5-5
X5-13
X5-14
X2-2
X2-1
X1-7
TR2
O/BK
R/BK
GY
P/BK
W/BK
PR
Y
BK
Y
W/R
AIR PRESSURE SWITCH
-T
OPERATING SENSOR S1a
-T
HIGH LIMIT SENSOR S1b
-T
INLET SENSOR S2
-T
FLUE SENSOR S3a
-T
FLUE SENSOR S3b
GAS VALVE
@24VAC
FLAME SENSOR
SPARK
ROD
HIGH VOLTAGE SPARK LEADCAUTION
d from t he factory. Use of a non-approv ed spark le
for proper connector block locations when using
JUNCTION
BOX
L
N
L
N
L
N
L
N
KB 286 ONLY
O-TEMP HEX SW
G
ad
BOX DEPICTS
OPTIONAL
ITEMS
G
G
G
L
120V
GND
SUPPLY
N
WIRING DIAGRAM
LBL20127 REV C
DHW
PUMP
BOILER
PUMP
SYSTEM
PUMP
78
Page 79
Notes
Installation & Operation Manual
79
Page 80
Revision Notes: Revision A (ECO C05747) initial release. Reflects the
new model numbers for the Knight upgrade.
Revision B (ECO #C06188) reflects updates made to the ladder and
wiring diagrams (ECO #C06158).
Revision C (ECO #C06234) reflects changes made to the Service
Reminder feature.
Revision D (ECO #C07981) reflects the layout in InDesign, edits made
to Section 11 - Operating Information, ECR04077 - combustible water
pipes change from 1" to a 1/4", changes made to the vent pipe chart on
page 17, ECR03743 - 20° rise notice on page 37, addition of O-temp
switch.
KBII-I-O Rev D
05/11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.