Lochinvar VAL20000, INS7238, GKT2055, BLT2026 User Manual

LTV VALVE APPLICATION INSTRUCTIONS FOR
LOW TEMPERATURE PROTECTION
COPPER-FIN AND POWER-FIN MODELS
CB 495 - 2066 / CH 401 - 2071 AND PB 501 - 2000
INS7238 Rev C
Kit components:
VAL30000 - 1 1/2" VALVE
Models: CB 45 - 500
• INS7238 Instruction Sheet
VAL3048 - 2" VALVE
Models: CB 495 - 745 and CH 401 - 751
• VAL2123 2" LTV Valve
• INS7238 Instruction Sheet
VAL3047 - 2 1/2" VALVE
Models: CB 986 - 2066, CH 991 - 2071, and PB 501 - 2000
• VAL2124 2 1/2" LTV Valve
• BLT2118 Bolt (12)
• BLT2119 Nut (12)
• BLT2026 Flat Washer (24)
• BLT2120 Star Washer (12)
• GKT2055 Gasket (3)
• TFL2092 Flange (3)
• INS7238 Instruction Sheet
CAUTION
Pump and motor unit are designed to be supported by the inline piping only. Do not support in any other manner. When placing pump between flanges, tighten flange bolts evenly and do not tighten excessively.
Figure 2_ 2" Valve
Figure 3_ 2 1/2" Valve
Figure 1_ 1 1/2" Valve
C = SYSTEM RETURN WATER
B = FROM BOILER OUTLET
A = BLENDED WATER
B = FROM BOILER OUTLET
A = BLENDED WATER
C = SYSTEM RETURN WATER
B = FROM BOILER OUTLET
NOTE: A-B-C is noted on the valve to depict proper orientation.
C = SYSTEM RETURN WATER
A = BLENDED WATER
2 of 8
Typical piping applications:
Figure 4_Primary/Secondary Piping of a Single Boiler - 1 1/2" Valve
Figure 5_Primary /Secondary Piping of Multiple Boilers - 1 1/2" Valve for each boiler
INS7238 Rev C
A = BLENDED WATER
C = SYSTEM RETURN
B = FROM BOILER OUTLET
DETAIL
Note: Valve must be installed with proper port orientation.
Failure to observe port markings on the valve body prior to installing the valve could result in damage to the unit.
WATER
*Best practice for Indoor/Outdoor reset. **Best practice for set point operation.
DETAIL
*REMOTE
SENSOR
REQUIRED
MIN. 10 PIPE DIA.
**REMOTE
SENSOR
REQUIRED
NOT TO EXCEED 4 PIPE DIA.
OR A MAX. OF 12” APART
MIN. 10 PIPE DIA.
NOTES: 1) Unit(s) high limit must be set at max.
2) Inlet and outlet connections to the boiler are shown for reference only. Actual connections may vary from those represented here. Consult the Installation and Service Manual for actual locations.
3) Unit(s) pump should operate only during firing periods.
REMOTE SENSOR
REQUIRED
REMOTE SENSOR
REQUIRED
NOT TO EXCEED 4 PIPE DIA.
OR A MAX. OF 12” APART
MIN. 10 PIPE DIA.
REMOTE SEQUENCER
NOTES: 1) Unit(s) high limit must be set at max.
2) Inlet and outlet connections to the boiler are shown for reference only. Actual connections may vary from those represented here. Consult the Installation and Service Manual for actual locations.
3) Unit(s) pump should operate only during firing periods.
3 of 8
Typical piping applications (cont.):
Figure 6_Primary /Secondary Piping of a Single Boiler - 2" Valve
Figure 7_Primary/Secondary Piping of Multiple Boilers - 2" Valve for each boiler
INS7238 Rev C
A = BLENDED WATER
C = SYSTEM RETURN WATER
Note: Valve must be installed with proper port orientation. Failure to observe port markings on the valve body prior to installing the valve could result in damage to the unit.
NOT TO EXCEED 4 PIPE DIA.
OR A MAX. OF 12” APART
*Best practice for Indoor/Outdoor reset.
**Best practice for set point operation.
B = FROM BOILER OUTLET
DETAIL
DETAIL
NOTES: 1) Unit(s) high limit must be set at max.
2) Inlet and outlet connections to the boiler are shown for reference only. Actual connections may vary from those represented here. Consult the Installation and Service Manual for actual locations.
3) Unit(s) pump should operate only during firing periods.
NOT TO EXCEED 4 PIPE DIA.
OR A MAX. OF 12” APART
NOTES: 1) Unit(s) high limit must be set at max.
2) Inlet and outlet connections to the boiler are shown for reference only. Actual connections may vary from those represented here. Consult the Installation and Service Manual for actual locations.
3) Unit(s) pump should operate only during firing periods.