Lochinvar INS7162, TST2313, INS7141, MP2 User Manual

The MP2is capable of controlling the supply water tempera­ture for up to nine ON / OFF stages based on outdoor tem­perature, control for the Domestic Hot Water (DHW) gener­ation, a set point requirement or optionally an external input signal (0 - 10 V (dc)). Alarge easy to read display provides current system temperatures and operating status (FIG. 1). The control has outputs for a primary pump and a combus­tion air damper or alarm. Based on the mode of operation selected, the control can operate different combinations of boiler stages and boiler pumps.
ADDITIONAL FUNCTIONS INCLUDE:
• Installer and Advanced Access Levels
• Primary Pump Output
• Individual Boiler Pump Outputs (in applicable modes)
• Pump Exercising
• Pump Purging (primary and boiler)
• Boiler Demand for Space Heating Loads
• DHW Demand for DHW Loads
• Set Point Demand for Set Point Loads
• Test Sequence to Ensure Proper Component Operation
• Setback Input for Energy Savings
• 0 - 10 V (dc) Input Signal
INSTALLATION INSTRUCTIONS
INS7162 Rev-
T
M
INTRODUCTION
FIG. 1
Modes 1 Up to 9 On/Off Boilers 2 Up to 4 On/Off Boilers & 4 Pumps 3 Up to 4 Lo/Hi Boilers 4 Up to 3 Lo/Hi Boilers & 3 Pumps 5 Up to 3 Three Stage Boilers 6 Up to 2 Three Stage Boilers & 2 Pumps 7 Up to 2 Four Stage Boilers 8 1 Four Stage Boiler & 1 Pump
This instruction manual is organized into four main sections:
1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4) Testing and Troubleshooting. The Sequence of Operation section has seven sub-sections. We recommend reading Section A: General Operation of the Sequence of Operation, as this contains important informa­tion on the overall operation of the control. Followed by the sub-sections that apply to your installation. The Control Settings section (starting at DIP Switch Settings) of this instruction manual describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
The control uses a Liquid Crystal Display (LCD) as the method of supplying information. The LCD is used in order to setup and monitor the operation of your system. The con­trol has four push buttons ( FIG. 2) for selecting and adjust­ing settings. As you program your control, record your set­tings in the ADJUST menu table which is found in the sec­ond half of this instruction manual.
MENU
All of the items displayed by the control are organized into two menus. These menus are listed on the top left hand side of the display (Menu Field). To select a menu, use the Menu button. By pressing and releasing the Menu button, the display switches between the two menus. Once a menu is selected, there will be a group of items that can be viewed within the menu, see Figure 2.
ITEM
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have reached the last available item in a menu, pressing and releasing the Item button will return the display to the first item in the selected menu. The items can be quickly scrolled through by holding the Item button and pressing the down arrow button. To rapidly scroll through the items in the reverse order, hold the Item button and press the up arrow button, see Figure 2.
ADJUST
To make an adjustment to a setting in the control, begin by selecting the ADJUST menu using the Menu button. Then select the desired item using the Item button. Finally, use the up arrow button, or down arrow button to make the adjustment. Additional information can be gained by observing the Status field of the LCD. The status field will indicate which of the control's outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected, see Figure 2.
TABLE OF CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Symbol Description . . . . . . . . . . . . . . . . . . . . . . . . .3
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . .4
Section A: General Operation . . . . . . . . . . .4
Section B: Staging . . . . . . . . . . . . . . . . . . . .6
Section C: Pump Operation . . . . . . . . . . . . .8
Section D: Boiler Reset . . . . . . . . . . . . . . . .9
Section E: DHW . . . . . . . . . . . . . . . . . . . . . .12
Section F: Set Point . . . . . . . . . . . . . . . . . . .14
Section G: External Input . . . . . . . . . . . . . . .15
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . .22
Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
View Menu . . . . . . . . . . . . . . . . . . . . . . . . . .24
Adjust Menu . . . . . . . . . . . . . . . . . . . . . . . . .25
Testing the Control . . . . . . . . . . . . . . . . . . . . . . . . .29
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Typical Boiler Installation . . . . . . . . . . . . . . . . . . . . .32
Typical DWH Priority Heating Package System . . .34
Notes Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
USER INTERFACE
2
DISPLAY
FIG. 2
SYMBOL DESCRIPTION
FIG. 3
3
Boiler Demand DHW / Setpoint Demand WWSD
External Input Signal Offset
The following defined terms and symbols are used through­out this manual to bring attention to the presence of hazards of various risk levels, or to bring attention to important infor­mation concerning the life of the product, see Figure 4 below.
SECTION A: GENERAL OPERATION
P
OWERING UP THE CONTROL
When the control is powered up, all segments in the LCD are turned on for two seconds. The control displays the control type number in the LCD for two seconds. Next, the software version is displayed for two seconds. Finally, the control enters the normal operating mode.
OPERATION
Boiler Reset (Stand Alone)
When a boiler demand signal from the heating system is present, the control operates the boiler(s) to maintain a sup­ply temperature based on the outdoor air temperature and Characterized Heating Curve settings, see Figure 5.
Domestic Hot Water
When a DHW demand signal from a DHW aquastat is pres­ent, the control operates the boiler(s) to maintain the supply water temperature at least as hot as the DHW XCHG set­ting. Refer to section E.
Set Point
When a set point demand signal from a set point system is present, the control operates the boiler(s) to maintain the supply water temperature at least as hot as the SETP set­ting. Refer to section F.
External Input 0 - 10 V (dc) or 2 - 10 V (dc)
When an external input signal is present, the control con­verts the signal to a target supply temperature. The control operates the boiler(s) to maintain the required supply water temperature.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the control has a set­back feature (FIG. 6). With setback, the supply water tem­perature in the system is reduced when the building is unoc­cupied. By reducing the supply water temperature, the air temperature in the space may be reduced even when ther­mostat(s) are not turned down. Any time the UnO Sw (5) and the Com - (1) are connected, the control operates in the UnOccupied mode. When in the UnOccupied mode, the UNOCC segment is displayed in the LCD. The control adjusts the supply water temperature based on the UNOCC settings made in the control. This feature has no effect when the control is used in the External Input mode.
DEFINITIONS
FIG. 4
SEQUENCE OF OPERATION
FIG. 5
4
COMBUSTION AIR OR ALARM CONTACT
Combustion Air (C. A.)
When the DIP switch is set to C. A., terminals 12 and 13 can be used as a switch to operate a combustion air damper. This contact closes prior to the first stage operating on the control. The amount of time that the contact closes prior to the first stage operating is set using the combustion delay setting. The combustion air contact remains closed for a minimum of 15 seconds after the last stage is turned off.
Alarm
When the DIP switch is set to Alarm, terminals 12 and 13 can be used as a switch to operate an alarm circuit. This contact closes whenever an error message is present on the control. When the alarm contact is activated, refer to the Error Messages section of this manual to determine the cause of the alarm. Once the fault has been fixed, the alarm can be cleared by pressing either the Menu, Item, up arrow or down arrow button.
Boiler Alarm
The control can monitor the boiler supply temperature and provide an alarm if the temperature does not increase with­in a certain amount of time. The amount of time can be set using the Boiler Alarm setting. This alarm can be used to determine if the boilers have failed to fire. To reset the alarm, press and hold the up and down arrow buttons for 5 seconds while in the VIEW menu.
ROTATION
The control's Equal Run Time Rotation function is fixed at 48 hours. The firing order of the boilers change whenever one boiler accumulates 48 hours more running time than any other boiler. After each rotation, the boiler with the least running hours is the first to fire and the boiler with the most running hours is the last to fire. This function ensures that all the boilers being rotated receive equal amounts of use. When the Rotate / Off DIP switch is set to the Off position, the firing sequence always begins with the lowest boiler to the highest boiler, see Figure 7 below.
Fixed Lead Rotation
In some applications, it may be desirable to have the first boiler fire first at all times while the firing sequence of the remaining boilers is changed using Equal Run Time Rotation. This rotation option is selected by setting the Fixed Lead / Off DIP switch to the Fixed Lead position.
First On / Last Off or First On / First Off
When using the Fixed Lead rotation option, a selection must be made between First On / Last Off and First On / First Off using the DIP switch. When First On / Last Off is selected, the lead boiler is always staged on first and staged off last. When First On / First Off is selected, the lead boiler is always staged on first and staged off first. This DIPswitch is only read by the control when the Fixed Lead / Off DIP switch is set to Fixed Lead.
Fixed Last
In some applications, it may be desirable to have the last boiler fire last at all times while the firing sequence of the remaining boilers is changed using Equal Run Time Rotation. This rotation option is selected by setting the Fixed Last / Off DIP switch to Fixed Last. With a fixed last rotation, the last boiler is the last to stage on and the first to stage off.
FIG. 6
5
FIG. 7
Resetting the Rotation Sequence
To reset the rotation sequence, set the Rotate / Off DIP switch to the Off setting for 5 seconds and then return the DIP switch to the Rotate setting.
RUNNING TIMES
The control displays the accumulated running time of each boiler in the VIEW menu. When using a multi-stage boiler, the running time that is displayed is the total number of run­ning hours of the Lo stage of the boiler.
Resetting the Running Times
To reset the running time for each boiler, select the appro­priate running time in the VIEW menu. Next, press the up and down arrow buttons simultaneously until CLR is dis­played.
EXERCISING
The control has a built-in exercising feature that is selected through the Exercise / Off DIP switch. To enable the exer­cising feature set the Exercise / Off DIP switch to Exercise. If exercising is enabled, the control ensures that each pump is operated at least once every 3 days. If a pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity. While the control is exercising, the Test LED flashes quickly.
RELOADING FACTORY DEFAULTS
To reload the factory defaults, power down the control for 10 seconds. Power up the control while simultaneously hold­ing the Menu and down arrow buttons. The control will now display the E01 error message. To clear this error message, follow the procedure in the Error Messages section of this manual.
BOILER MINIMUM
The boiler minimum is the lowest temperature that the con­trol is allowed to use as a boiler target temperature. During mild conditions, if the control calculates a boiler target tem­perature that is below the BOIL MIN setting, the boiler tar­get temperature is adjusted to at least the BOIL MIN setting. During this condition, if the boiler(s) is operating, the mini­mum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target tem­perature. Set the BOIL MIN setting to the boiler manufac­turer's recommended temperature.
BOILER MAXIMUM
The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the BOIL MAX setting, and the boil­er temperature is near the boiler maximum temperature, the maximum segment will be displayed in the LCD while either the boiler target temperature or the boiler supply tempera­ture is being viewed. At no time does the control operate the boiler(s) above 248°F (120°C).
SECTION B: STAGING OPERATION
S
ECTION B1: STAGING
Mode
The control is capable of staging single stage, two stage, three stage or four stage on / off heat sources. In certain modes of operation the control is capable of controlling the individual boiler pumps. The control has 8 modes of opera­tion based on the type of staging and pump operation that is desired. The following describes the modes of operation:
Mode 1: 9 Single Stage Boilers and a primary pump. Mode 2: 4 Single Stage Boilers with individual boiler pumps
and a primary pump.
Mode 3: 4 Lo/Hi boilers and a primary pump. Mode 4: 3 Lo/Hi boilers with individual boiler pumps and a
primary pump.
Mode 5: 3 Three Stage Boilers and a primary pump. Mode 6: 2 Three Stage Boilers with individual boiler pumps
and a primary pump.
Mode 7: 2 Four Stage Boilers and a primary pump. Mode 8: 1 Four Stage Boiler with a boiler pump and a pri-
mary pump.
6
FIG. 8
LO / HIORLO / LO
When using multi-stage boilers, a selection must be made regarding the staging order of the boiler(s). This adjustment is made in the ADJUST menu of the control.
Lo / Hi
If the Lo/Hi staging option is selected the control stages in sequence all of the stages in a single boiler. Once all of the stages are turned on, the control then stages in sequence all of the stages in the next boiler in the rotation sequence.
Lo / Lo
If the Lo/Lo staging option is selected, the control stages all of the Lo stage outputs in all of the boilers first. Once all of the boilers are operating on their Lo stages, the control then operates the second stage in each boiler in the same order.
STAGING
The control operates up to nine stages to supply the required temperature. After a stage is turned on in the firing sequence, the control waits for the minimum time delay. After the minimum time delay between stages has expired, the control examines the control error to determine when the next stage is to fire. The control error is determined using Proportional, Integral and Derivative (PID) logic.
Proportional compares the actual supply temperature to the boiler target temperature. The colder the supply water temperature, the sooner the next stage is turned on.
Integral compares the actual supply temperature to the boiler target temperature over a period of time.
Derivative compares how fast or slow the supply water temperature is changing. If the supply temperature is increasing slowly, the next stage is turned on sooner. If the supply temperature is increasing quickly, the next stage is turned on later, if at all.
FIRE DELAY
The Fire Delay is the time delay that occurs between the time that the control closes a stage contact to fire a stage and the burner fires for that stage. The fire delays for the first and third stages in a boiler are adjustable using the F DLY 1 and F DLY 2 settings. The fire delay for the sec­ond and the fourth stages is fixed at 10 seconds, see Figure 10 below.
Fire Delay 1
Fire Delay 1 is available in all modes of operation. Fire Delay 1 is the fire delay of the first stage of the boiler.
Fire Delay 2
Fire Delay 2 is only available in the modes of operation for Three and Four Stage Boilers. Fire Delay 2 is the fire delay of the third stage of the boiler.
FIG. 9
FIG. 10
7
STAGE DELAY
The stage delay is the minimum time delay between the fir­ing of stages. After this delay has expired the control can fire the next stage if it is required. This setting can be adjust­ed manually or set to an automatic setting. When the auto­matic setting is used, the control determines the best stage delay based on the operation of the system.
BOILER MASS
The BOIL MASS setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the application. The BOIL MASS setting also adjusts the minimum inter-stage delay time when operating with an automatic differential.
Lo (1)
The Lo setting is selected if the boiler(s) that is used has a low thermal mass. This means that the boiler(s) has a very small water content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite rapidly when fired. This is typical of many copper fin-tube boilers. The Lo MASS setting pro­vides the quickest staging on of boilers.
Med (2)
The Med setting is selected if the boiler(s) that is used has a medium thermal mass. This means that the boiler(s) either has a large water content and a low metal content or a low water content and a high metal content. This is typical of many modern residential cast iron boilers or steel tube boil­ers. The Med MASS setting stages on additional boilers at a slower rate than the Lo MASS setting.
Hi (3)
The Hi setting is selected if the boiler(s) that is used has a high thermal mass. This means that the boiler(s) has both a large water content and a large metal content. Aboiler that has a high thermal mass is relatively slow in coming up to temperature. This is typical of many commercial cast iron and steel tube boilers. The HI MASS setting stages on additional boilers at the slowest rate.
DIFFERENTIAL
An on / off heat source must be operated with a differential to prevent short cycling. With the control, either a fixed or an auto differential may be selected. The boiler differential is divided around the boiler target temperature. The first stage contact closes when the supply water temperature is ½ of the differential setting below the boiler target tempera­ture. Additional stages operate if the first stage is unable to bring the supply water temperature up to the boiler target temperature at a reasonable rate. As the supply tempera­ture reaches ½ of the differential above the boiler target temperature, stages are staged off.
Fixed Differential
If the user desires to have a fixed differential, this is set using the BOIL DIFF setting in the ADJUST menu (FIG. 11).
Auto Differential
If the Auto Differential is selected, the control automatically determines the best differential as the load changes. This reduces potential short cycling during light load conditions (FIG. 11).
SECTION C: PUMP OPERATION
SECTION C1: PUMP OPERATION PRIMARY PUMP OPERATION
The primary pump operates under the following conditions:
• The control receives a boiler demand and is not in warm weather shut down (WWSD).
• The control receives a DHW demand when DHW MODE is set to 3 or 4.
• The control receives a set point demand and set point MODE is set to 3.
Primary Pump Purge
After a demand is removed, the control continues to operate the primary pump for a period of time. The maximum length of time that the primary pump continues to run is adjustable using the Purge setting. The primary pump continues to run until either the purging time has elapsed or the boiler supply temperature drops more than a differential below the boiler minimum setting, see Figure 12.
8
FIG. 11
BOILER PUMP OPERATION
In certain modes of operation, the control can operate the individual boiler pumps on each boiler in addition to the pri­mary pump. The boiler pump turns on prior to the boiler fir­ing and continues to run after the boiler is turned off. The amount of time that the boiler pump turns on prior to the boiler firing is determined by the BOIL MASS setting. If a BOIL MASS of Lo is selected, the boiler pump turns on 15 seconds prior to the boiler. If a BOIL MASS of Medium is selected, the boiler pump turns on 22 seconds prior to the boiler. If a BOIL MASS of Hi is selected, the boiler pump turns on 30 seconds prior to the boiler. However, if the con­trol is operating based on a set point demand, the boiler pump turns on 5 seconds prior to the boiler, see Figure 13.
Boiler Pump Purge
The amount of time that the boiler pump continues to run after the boiler turns off is adjustable using the boiler pump purge setting (PURG Boil Pmp).
SECTION D: BOILER RESET OPERATION
S
ECTION D1: BOILER RESET (STAND ALONE)
BOILER DEMAND
When operating in the stand-alone mode, a boiler demand is required in order for the control to provide heat to the heating system. Aboiler demand is generated by applying a voltage between 24 and 230 V (ac) across the Boiler Demand and Common Demand terminals (6 and 7) (FIG. 14). Once voltage is applied, the Boiler Demand pointer is displayed in the LCD. If the control is not in WWSD, the control closes the primary pump contact. The control calculates a boiler target supply temperature based on the outdoor air temperature and the characterized heat­ing curve settings.
BOILER TARGET TEMPERATURE
The boiler target temperature is determined from the char­acterized heating curve settings and the outdoor air tem­perature. The control displays the temperature that it is cur­rently trying to maintain as the boiler supply temperature. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, "- - -" is displayed in the LCD.
CHARACTERIZED HEATING CURVE
The control varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since dif­ferent types of terminal units transfer heat to a space using different proportions of radiation, natural convection and forced convection, the supply water temperature must be controlled differently. Once a terminal unit is selected, the control varies the supply water temperature according to the
9
FIG. 12
FIG. 13
FIG. 14
BOILER INDOOR DESIGN TEMPERATURE
The indoor design temperature is the room temperature that was used in the original heat loss calculations for the build­ing. This setting establishes the beginning of the character­ized heating curve, see Figure 15 below.
OUTDOOR
DESIGN TEMPERATURE
The outdoor design temperature is the outdoor air tempera­ture that is the typical coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the boiler supply tempera­ture rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the boiler supply temperature rises rapidly as the outdoor temperature drops.
BOILER DESIGN TEMPERATURE
The design supply temperature is the supply water temper­ature required to heat the building when the outdoor air tem­perature is as cold as the outdoor design temperature.
W
ARM WEATHER SHUTDOWN
When the outdoor air temperature rises above the WWSD setting, the control turns on the WWSD pointer in the dis­play. When the control is in Warm Weather Shut Down, the boiler demand pointer is displayed if there is a boiler demand. However, the control does not operate the heating system to satisfy this demand. The control does respond to a DHW or set point demand and operates as described in sections E & F.
ROOM
The room is the desired room temperature for the building and provides a parallel shift of the heating curve. The room temperature desired by the occupants is often different from the design indoor temperature. If the room temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building. A ROOM setting is available for both the occupied (day) and unoccupied (night) periods.
TERMINAL UNITS
The control provides for a selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a termi­nal unit is selected, the control automatically loads the design supply temperature, maximum supply temperature, and minimum supply temperature (FIG. 16). The factory defaults are listed in Figure 16. These factory defaults can be changed to better match the installed system. If a facto­ry default has been changed, refer to section Ato reload the factory defaults.
FIG. 15
10
BOIL DSGN
BOIL IND
HIGH MASS RADIANT (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsumpour. This heating system has a large thermal mass and is slow acting (FIG. 17).
LOW MASS
RADIANT (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor, suspended in the joist sp ace, or sandwiched between the sub-floor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system (FIG. 17).
FANCOIL (3)
A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil and either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower, and is then delivered into the building space (FIG. 17).
FIN-TUBE CONVECTOR (4)
A convector terminal unit is made up of a heating element with fins on it. This type of terminal unit relies on the natu­ral convection of air across the heating element to deliver heated air into the space. The amount of natural convection to the space is dependant on the supply water temperature to the heating element and the room air temperature (FIG. 17).
RADIATOR (5)
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator provides heat to the room through radiant heat transfer and natural convection (FIG. 17).
BASEBOARD (6)
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the base of the wall. The pro­portion of heat transferred by radiation from a baseboard is greater than that from a fin-tube convector (FIG. 17).
BOOST
When the control changes from the UnOccupied mode to the Occupied mode, it enters into a boosting mode. In this mode, the supply water temperature to the system is raised above its normal values for a period of time to provide a faster recovery from the setback temperature of the build­ing. The maximum length of the boost is selected using the BST setting.
Typical settings for the boost function vary between 30 min­utes and two hours for buildings that have a fast responding heating system. For buildings that have a slow responding heating system, a setting between four hours and eight hours is typical. After a boost time is selected, the setback timer must be adjusted to come out of setback some time in advance of the desired occupied time. This time in advance is normally the same as the BST setting.
If the building is not up to temperature at the correct time, the BST setting should be lengthened and the setback timer should be adjusted accordingly. If the building is up to tem­perature before the required time, the BST setting should be shortened and the setback timer should be adjusted accord­ingly. If the system is operating near its design conditions or if the supply water temperature is being limited by set­tings made in the control, the time required to bring the building up to temperature may be longer than expected.
FIG. 16
11
FIG. 17
SECTION E: DOMESTIC HOT WATER OPERA­TION
S
ECTION E1: DOMESTIC HOT WATER (DHW)
DHW DEMAND
A DHW Demand is required for the control to provide heat to the DHW system. ADHW aquastat or set point control is used as a switch in the DHW demand circuit. Once the con­trol detects a DHW demand, the DHW Demand pointer turns on in the LCD and the control operates the boiler to provide a sufficient boiler supply water temperature to the DHW tank. The control operates the pumps as described below.
The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied across the Setp / DHW and Com Dem terminals (8 and 7).
BOILER TARGET DURING DHW GENERATION
The boiler target temperature is at least as hot as the DHW exchange setting (DHW XCHG). The DHW demand over­rides the boiler reset target temperature, except when the boiler reset target is higher than that of the DHW exchange setting.
DHW MODE & PRIORITY OPERATION
The control has five different settings available for DHW MODE. The required DHW MODE setting will depend on the piping arrangement of the DHW tank.
It is often desirable to have a priority for the DHW allowing for quick recovery of the DHW tank temperature. This is achieved by limiting or even stopping the flow of heat to the heating system when the DHW tank calls for heat see Figure 18.
DHW M
ODE OFF - NO DHW
DHW MODE 1 - DHW IN PARALLEL NO PRIORITY
When a DHW Demand is present, the Relay 9 / DHW con­tact (terminals 30 and 31) closes and the primary pump con­tact is opened. It is assumed that the DHW pump will
provide adequate flow through the heat exchanger and the boiler.
DHW MODE 2 - DHW IN PARALLEL NO PRIORITY
When a DHW Demand is present, the Relay 9 / DHW con­tact (terminals 30 and 31) closes with the DHW demand. The primary pump does not turn on, but may operate based on a Boiler Demand or External Input Signal. Refer to sec­tions E and G. It is assumed that the DHW pump will pro-
vide adequate flow through the heat exchanger and the boiler.
DHW M
ODE 3 - DHW IN PRIMARY / SECONDARY NO
PRIORITY
When a DHW Demand is present, the Relay 9 / DHW con­tact (terminals 30 and 31) is closed and the primary pump contact is closed. This mode can be used if a DHW tank
is piped in direct return and a DHW valve is installed.
12
FIG. 18
DHW MODE 4 - DHW IN PRIMARY / SECONDARY WITH PRIORITY
When a DHW Demand is present, the Relay 9 / DHW con­tact (terminals 30 and 31) is closed and the primary pump contact is closed. Priority can only be obtained using exter­nal wiring. During a priority override, the Relay 9 / DHW contact is opened until the heating system has recovered before returning to DHW operation, see Figure 19. This
mode can be used if a DHW tank is piped in direct return and a DHW valve is installed.
DHW PRIORITY OVERRIDE
The DHW Priority Override applies to DHW MODE 2 and 4. To prevent the building from cooling off too much or the pos­sibility of a potential freeze up during DHW priority, the con­trol limits the amount of time for DHW priority. The length of DHW priority time is determined using the Priority Override setting. Once the a llowed t ime for priority has elapsed, the control overrides the DHW priority and resumes space heating.
To provide external DHW priority in DHW Mode 4, the space heating zones must be interlocked with the Relay 9 / DHW contact, Figure 20. During DHW demands, the Relay 9 / DHW contact must remove any power to all space heating zone valves or zone pumps.
CONDITIONAL DHW PRIORITY
The Conditional DHW Priority Override applies to DHW MODE 2 and 4. If the boiler supply temperature is main­tained at or above the required temperature during DHW generation, this indicates that the boiler(s) has enough capacity for DHW and possibly heating as well. As long as the boiler supply temperature is maintained near its target and the heating and DHW targets are similar, DHW and heating occurs simultaneously.
DHW POST PURGE
After the DHW Demand is removed, the control performs a purge on the boiler(s). The control shuts off the boiler(s) and continues to operate either the DHW pump or the DHW valve and the system and boiler pump if applicable. This purges the residual heat from the boiler(s) into the DHW tank. The control continues this purge for a maximum of two minutes or until the boiler supply water temperature drops 20° F (11°C) below the boiler target temperature during the DHW operation. The control also stops the purge if the boil­er supply temperature is close to the current boiler target temperature.
DHW MIXING PURGE
After DHW operation, the boiler(s) is extremely hot. At the same time, the heating zones may have cooled off consid­erably after being off for a period of time. To avoid thermal­ly shocking the boiler(s) after DHW in parallel with priority (DHW MODE 2), the control shuts off the boiler(s), but con­tinues to operate the DHW while restarting the heating sys­tem. This allows some of the DHW return water to mix with the cool return water from the zones and temper the boiler return water (FIG. 21).
DHW DURING UNOCCUPIED
If the control receives a DHW Demand during an unoccu­pied period, the control can either continue operation of the DHW system as it would during the occupied period or the control can ignore a DHW Demand for the duration of the unoccupied period.
FIG. 19
FIG. 20
FIG. 21
13
NUMBER OF BOILERS USED FOR DHW GENERATION
The number of boilers used for DHW generation can be selected from one to the maximum number of boilers using the BOIL DHW setting. This applies when only a DHW Demand is present. If there are other demands present, the control does not limit the number of boilers operated.
SECTION E2: DHW WITH LOW TEMPERATURE BOILERS
If DHW is to be incorporated into a low temperature system such as a radiant heating system, a mixing device is often installed to isolate the high DHW supply temperature from the lower system temperature. If a mixing device is not installed, high temperature water could be supplied to the low temperature system while trying to satisfy the DHW demand. This may result in damage to the low temperature heating system. The control is capable of providing DHW in such a system while maximizing the chance that the tem­perature in the heating system does not exceed its allowed maximum setting.
To prevent high temperature water from being introduced into the heating system, the primary pump (Prim P1) must be turned off during a call for DHW. To do this, the control must be set to DHW MODE 2 or DHW MODE 4 and Boil MIN must be set to OFF, see Figure 22 below.
DHW MODE 2 OPERATION
On a call for DHW, the control provides DHW priority by shutting off the primary pump (Prim P1) for a period of time. This time is based on the DHW Priority Override setting. However, if the DHW Demand is not satisfied within the allotted time, the boiler(s) shuts off and the heat of the boiler is purged into the DHW tank.
Once the boiler supply temperature is sufficiently reduced, the Relay 9 / DHW contact shuts off. The heating system is turned on for a period of time to prevent the building from cooling off. After a period of heating, and if the DHW Demand is still present, the control shuts off the heating sys­tem and provides heat to the DHW tank once again.
For correct operation, close attention must be paid to the mechanical layout of the system. When the control turns off the primary pump (Prim P1), flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the maximum desired tempera­ture and can result in damage to the heating system.
DHW MODE 4 OPERATION
In DHW MODE 4, the space heating zones must be pre­vented from coming on during DHW demands using exter­nal wiring. This can be done using an external relay to remove power from zone pumps or zone valves while a DHW Demand is present. During a DHW Demand, the con­trol closes the primary pump (Prim P1) contact and the Relay 9 / DHW contact. Once the DHW Demand is removed, or during a DHW Priority Override, the Relay 9 / DHW contact is opened, and the external wiring should allow the space heating zones to operate.
There is no mixing purge available in DHW MODE 4. After DHW priority, the boiler supply water temperature may exceed the design water temperature of the space heating system and can result in damage to the heating system.
SECTION F: SET POINT OPERATION
SECTION F1: SET POINT
Set point operation is only available when DHW MODE is set to OFF.
SET POINT
The control can operate to satisfy the requirements of a set point load in addition to a space heating load. A set point load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to the set point load.
SET POINT DEMAND
A set point demand is required for the control to provide heat to the set point load. The control registers a set point demand when a voltage between 24 and 230 V (ac) is applied across the Setp / DHW and Com Dem terminals (8 and 7) (FIG. 23).
Once voltage is applied, the Set Point Demand pointer turns on in the LCD. The control operates the boiler(s) to main­tain at least the set point setting.
FIG. 22
FIG. 23
14
BOILER TARGET DURING SET POINT
The boiler target temperature during a set point demand is increased to at least the Set Point setting. This temperature is maintained as long as the control has a set point demand.
SET POINT MODE
SETP MODE 1 - Setpoint in Parallel
Whenever a set point demand is present, the boiler(s) is operated to maintain the set point target. The primary pump does not turn on, but may operate based on a Boiler Demand or an External Input Signal, see Figure 24.
It is assumed that the Set Point pump will provide ade­quate flow through the heat exchanger and the boiler.
SETP MODE 2 - Set Point in Parallel with Priority
Whenever a set point demand is present, the boiler(s) is operated to maintain the set point target and the primary pump (Prim P1) contact is opened.
It is assumed that the Set Point pump will provide ade­quate flow through the heat exchanger and the boiler.
SETP MODE 3 - Primary Pump during Set Point
Whenever a set point demand is present, the primary pump (Prim P1) is turned on and the boiler(s) is operated to main­tain the set point target.
SET POINT PRIORITY OVERRIDE
The set point has a Priority Override while in SETP MODE
2. In order to prevent the building from cooling off too much or the possibility of a potential freeze up during set point pri­ority, the control limits the amount of time for set point prior­ity. The length of Set Point priority is determined by the Priority Override setting. Once the allowed time for priority has elapsed, the control overrides the set point priority and
operates set point and heating simultaneously by turning on the primary pump (Prim P1).
CONDITIONAL SET POINT PRIORITY
If the boiler(s) supply temperature is maintained at or above the required temperature during set point generation, this indicates that the boiler(s) has enough capacity for set point and possibly heating as well. As long as the boiler target temperature is maintained and the heating and set point targets are similar, set point and heating occur at the same time.
SECTION G: EXTERNAL INPUT OPERATION
SECTION G1: EXTERNAL INPUT EXTERNAL I
NPUT
The control can accept an external DC signal in place of the outdoor sensor. The control converts the DC signal into the appropriate boiler target temperature between 50°F (10°C) and 210°F (99°C) based on the External Input Signal and Offset settings. To use the external input signal, the External Input / Stand Alone DIP switch must be set to External Input.
When operating in the external input mode, an external sig­nal is required in order for the control to provide heat to the heating system. An external signal is generated by apply­ing a voltage between 0 V (dc) and 10 V (dc) across the Out + and Com - terminals (4 and 1) (FIG. 25). Once voltage is applied, the External Input Signal pointer is displayed in the LCD and the control closes the primary pump contact. The control calculates a boiler target supply temperature based on the external input signal and the settings made in the control. The control then fires the boiler(s), if required, to maintain the target supply temperature. If the external sig­nal goes below the minimum voltage, the External Input Signal pointer is turned off in the display. The boiler target temperature is displayed as " - - - " to indicate that there is no longer a call for heating. The primary pump and boiler pumps operate as described in section C.
FIG. 24
FIG. 25
15
Do Not Apply Power
Do Not Apply Power
+
INPUT SIGNAL
The control can accept either a 0 - 10 V (dc) signal or a 2 ­10 V (dc) signal. The External Input Signal setting must be set to the proper setting based on the signal that is being sent to the control.
0 - 10 V (dc) or 0 - 20 mA
When the 0 - 10 V (dc) signal is selected, an input voltage of 1 V (dc) corresponds to a boiler target temperature of 50°F (10°C). An input volt age of 10 V (dc) corresponds to a boiler target temperature of 210°F (99°C). As the voltage varies between 1 V (dc) and 10 V (dc) the boiler target tem­perature varies linearly between 50°F (10°C) and 210°F (99°C). If a voltage below 0.5 V (dc) is received the boiler target temperature is displayed as " - - - " indicating that there is no longer a call for heating.
A 0 - 20 mA signal can be converted to a 0 - 10 V (dc) sig­nal by installing a 500 ohm resistor between the Out + and Com - terminals (4 and 1).
2 - 10 V (dc) or 4 - 20 mA
When the 2 - 10 V (dc) signal is selected, an input voltage of 2 V (dc) corresponds to a boiler target temperature of 50°F (10°C). An input volt age of 10 V (dc) corresponds to a boiler target temperature of 210°F (99°C). As the voltage varies between 2 V (dc) and 10 V (dc) the boiler target tem­perature varies linearly between 50°F (10°C) and 210°F (99°C). If a voltage below 1.5 V (dc) is received the boiler target temperature is displayed as " - - - " indicating that there is no longer a call for heating.
A 4 - 20 mA signal can be converted to a 2 - 10 V (dc) sig­nal by installing a 500 ohm resistor between the Out + and Com - terminals (4 and 1).
OFFSET
The Offset setting allows the boiler target temperature to be fine tuned to the external input signal. The control reads the external input signal and converts this to a boiler target tem­perature. The Offset setting is then added to the boiler tar­get temperature.
EXTERNAL INPUT SIGNAL CONVERSION TABLES
16
STEP ONE ----- GETTING READY
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your whole­saler or Lochinvar sales representative for assistance.
MP2includes: One Boiler Control MP2, One Outdoor Sensor TST2311, Two Temperature Sensors TST2313, Instruction Manuals INS7141 and INS7162
Note: Carefully read the details of the Sequence of Operation to ensure that you have chosen the proper con­trol for your application.
STEP TWO ---- ROUGH-IN WIRING
All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8" (22 mm) knockouts which accept common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections of the chamber with common volt­ages. Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should be installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
• All wires are to be stripped to a length of 3/8" (9 mm) to
ensure proper connection to the control.
• If an Outdoor Sensor TST2311 is used, install the sensor
according to the installation instructions in the INS7141 and run the wiring back to the control.
• Install the TST2311 sensor according to the installation
instructions in the Data Brochure D 070 and run the wiring back to the control.
• If a TST2311 sensor is used, install the sensor according
to the installation instructions in the Data Brochure D 070 and run the wiring back to the control.
• Run wire from other system components (pumps, boilers,
etc.) to the control.
• Run wires from the 115 V (ac) power to the control. Use a
clean power source with a 15 A circuit to ensure proper operation. Multi-strand 16 AWG wire is recommended for all 1 15 V (ac) wiring due to it s superior flexibility and ease of installation into the terminals.
STEP T
HREE ----- ELECTRICAL CONNECTIONS TO THE
CONTROL
General
The installer should test to confirm that no voltage is pres­ent at any of the wires. Push the control into the base and slide it down until it snaps firmly into place.
POWERED INPUT CONNECTIONS
115 V (ac) Power
Connect the 115 V (ac) power supply to the Power L and Power N terminals (10 and 9) (FIG. 26). This connection provides power to the microprocessor and display of the control. As well, this connection provides power to the Prim P1 terminal (11) from the Power L terminal (10).
Boiler Demand
To generate a boiler demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Boil Dem and Com Dem terminals (6 and 7) (FIG. 26).
DHW Demand
To generate a DHW Demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Setp / DHW and Com Dem terminals (8 and 7) (FIG. 26). If using DHW, the last boiler in MODE 1, 4 or 5 must be set to OFF and DHW MODE must also be set to 1 through 4.
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury . It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for uses as a primary limit control. Other con­trols that are intended and certified as safety limits must be placed into the control circuit. Do not open the con­trol. Refer to qualified personnel for servicing. Opening voids warranty and could result in damage to the equip­ment and possibly even personal injury.
INSTALLATION
17
Set Point Demand
To generate a setpoint demand, a voltage between 24 V (ac) and 230 V (ac) must be applied across the Setp / DHW and Com Dem terminals (8 and 7) (FIG. 26). The DHW MODE must be set to OFF.
External Input (0 - 10 V dc)
To generate an external input signal, a voltage between 0 and 10 V (dc) must be applied to the Com - and Out + ter­minals (1 and 4) (FIG. 27).
A 0 - 20 mA signal can be converted to a 0 - 10 V (dc) sig­nal by installing a 500 ohm resistor between the Com ­and Out + terminals (1 and 4) (FIG. 27).
A 4 - 20 mA signal can be converted to a 2 - 10 V (dc) sig­nal by installing a 500 ohm resistor between the Com ­and Out + terminals (1 and 4) (FIG. 27).
OUTPUT CONNECTIONS
Primary Pump Contact (Prim P1)
The Prim P1 output terminal (11) is a powered output. When the relay in the control closes, 115 V (ac) is provided to the Prim P1 terminal (11) from the Power L terminal (10). To operate the primary pump, connect one side of the pri­mary pump circuit to terminal 11 and the second side of the pump circuit to the neutral (N) side of the 115 V (ac) power supply, see Figure 28.
Combustion Air / Alarm Contact (C.A./Alarm)
The Combustion Air / Alarm Contact (C.A./Alarm) terminals (12 and 13) (FIG. 29) are an isolated output in the control. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break power to the combustion air damper or alarm. Since this is an isolated contact, it may switch a volt­age between 24 V (ac) and 230 V (ac).
Relay 1 to Relay 9
The Relay 1 to Relay 9 terminals (14 and 15 to 30 and 31) (FIG. 30) are isolated outputs in the control. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break power to a boiler stage or a boiler pump. Since this is an isolated contact, it may switch a voltage between 24 V (ac) and 230 V (ac).
FIG. 26
FIG. 27
FIG. 28
FIG. 29
18
10
9
Power
8
7
Setp/
Com
DHW
Dem
11
10
9
Prim
Power
L
P1
C.A./
Alarm
Do Not Apply Power
+
Do Not Apply Power
+
Relay 9 / DHW
If a DHW pump or DHW valve is connected to the Relay 9 / DHW contact (30 and 31) (FIG. 30), make sure the power to the pump or valve circuit is off and install a jumper between those terminals. When the DHW circuit is powered up, the DHW pump should turn on or the DHW valve should open completely . If the DHW pump or valve fails to operate, check the wiring between the terminals and the pump or valve and refer to any installation or troubleshooting information sup­plied with these devices. If the DHW pump or valve oper­ates correctly, disconnect the power and remove the jumper.
SENSOR AND UNPOWERED INPUT CONNECTIONS
Do not apply power to these terminals as this will dam­age the control.
Outdoor Sensor
If an outdoor sensor is used, connect the two wires from the Outdoor Sensor TST2311 to the Com - and Out + terminals (1 and 4) (FIG. 31). The outdoor sensor is used by the con­trol to measure the outdoor air temperature.
Boiler Supply Sensor
Connect the two wires from the TST2311 sensor to the Com
- and Boil Sup terminals (1 and 2) (FIG. 31). The boiler sup­ply sensor is used by the control to measure the boiler sup­ply water temperature.
Boiler Return Sensor
If a boiler return sensor is used, connect the two wires from the TST2311 sensor to the Com - and Boil Ret terminals (1 and 3) (FIG. 31). The boiler return sensor is used by the control to measure the boiler return water temperature.
UnOccupied Switch
If an external timer or switch is used, connect the two wires from the external switch to the Com - and UnO Sw terminals (1 and 5) (FIG. 32). When these two terminals are shorted together, the control registers an UnOccupied signal.
S
TEP FOUR ----- TESTING THE WIRING
GENERAL
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove the terminal block, pull straight down from the control.
The following tests are to be performed using standard test­ing practices and procedures and should only be carried out by properly trained and experienced persons.
FIG. 30
FIG. 31
19
FIG. 32
1
Com
Boil Sup
Boil Ret
Out
+
4
3
2
Com
1
Com
4
3
2
1
Boil
Sup
Boil Ret
Out
+
Boil
Sup
Boil
Ret
Out
+
4
3
2
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 ohm, is essential to properly test the wiring and sensors.
TEST THE SENSORS
In order to test the sensors, the actual temperature at each sensor location must be measured. A good quality digital thermometer with a surface temperature probe is recom­mended for ease of use and accuracy (FIG. 33). Where a digital thermometer is not available, a spare sensor can be strapped alongside the one to be tested and the readings compared. Test the sensors according to the instructions in INS7141.
TEST THE POWER SUPPLY
Make sure exposed wires and bare terminals are not in con­tact with other wires or grounded surfaces. Turn on the power and measure the voltage between the Power L and Power N terminals (10 and 9) (FIG. 34) using an AC volt­meter, the reading should be between 103.5 and
126.5 V (ac).
TEST THE POWERED INPUTS
Boiler Demand
If a boiler demand is used, measure the voltage between the Boil Dem and the Com Dem terminals (6 and 7) (FIG. 35). When the boiler demand device calls for heat, you should measure between 20 and 260 V (ac) at the ter­minals. When the boiler demand device is off, you should measure less than 5 V (ac).
DHW Demand
If a DHW demand is used, measure the voltage between the Setp / DHW and the Com Dem terminals (8 and 7) (FIG. 35). When the DHW demand device calls for heat, a voltage between 20 and 260 V (ac) should be measured at the terminals. When the DHW demand device is off, less than 5 V (ac) should be measured.
Set Point Demand
35). When the set point demand device calls for heat, you
should measure between 20 and 260 V (ac) at the termi­nals. When the set point demand device is off, you should measure less than 5 V (ac).
External Input
If an external input is used, measure the voltage between the Com - and the Out + terminals (1 and 4). When the external input device calls for heat, you should measure between 0 and 10 V (dc) at the terminals.
FIG. 33
c)
FIG. 34
20
FIG. 35
FIG. 36
10
V
9
Power
N
103.5 to 126.5 V (a
L
TEST THE OUTPUTS
Primary Pump (Prim P1)
If a primary pump is connected to the Prim P1 terminal (11), make sure that power to the terminal block is off and install a jumper between the Power L and Prim P1 terminals (10 and 11) (FIG. 37). When power is applied to the Power N and Power L terminals (9 and 10) (FIG. 37), the primary pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper.
Combustion Air or Alarm (C.A. / Alarm)
If a combustion air damper or an alarm is connected to the C.A. / Alarm terminals (12 and 13), make sure power to the damper or alarm circuit is off and install a jumper between terminals (12 and 13) (FIG. 38). When the circuit is powered up, the combustion air damper should open or the alarm should activate. If the damper or the alarm fails to operate, check the wiring between the terminals and the damper or the alarm and refer to any installation or troubleshooting information supplied with these devices. If the damper or the alarm operates properly, disconnect the power and remove the jumper.
Relay 1 to Relay 9
If a boiler stage is connected to the Relay 1 terminals (14 and 15) (FIG. 39), make sure power to the boiler circuit is off, and install a jumper between the terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does not turn on, refer to any installation or trou-
bleshooting information supplied with the boiler. (The boiler may have a flow switch that prevents firing until the primary pump (P1) or boiler pump is running.) If the boiler operates properly, disconnect the power and remove the jumper.
If a boiler pump is connected to the Relay 1 terminals (14 and 15) (FIG. 39), make sure that power to the terminal block is off and install a jumper between the terminals. When power is applied to the circuit, the boiler pump should start. If the pump does not turn on, check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper. Repeat the above procedure for Relay 2 to Relay 9.
Relay 9 / DHW
If a DHW pump or DHW valve is connected to the Relay 9 / DHW contact (30 and 31) (FIG. 40), make sure the power to the pump or valve circuit is off and install a jumper between those terminals. When the DHW circuit is powered up, the DHW pump should turn on or the DHW valve should open completely . If the DHW pump or valve fails to operate, check the wiring between the terminals and the pump or valve and refer to any installation or troubleshooting information sup­plied with these devices. If the DHW pump or valve oper­ates correctly, disconnect the power and remove the jumper.
21
L
FIG. 37
FIG. 38
FIG. 39
FIG. 40
11
0
1
9
Prim
Power
P1
L
N
N
14
1
Relay
15
1
14
1
Relay
15
1
C.A./
Alarm
CONNECTING THE CONTROL
Make sure all power to the devices and terminal blocks is off, and remove any remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control, and then pushing the terminal blocks into the headers. The terminal blocks should snap firmly into place, see Figure 41.
Install the supplied safety dividers between the unpowered sensor inputs and the powered or 115 V (ac) wiring cham­bers.
Apply power to the control. The operation of the control on power up is described in the Sequence of Operation section of this instruction manual.
CLEANING THE CONTROL
The control’s exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping the control. Do not use solvents or cleaning solutions.
GENERAL
The DIP switch settings on the control are very important and should be set to the appropriate settings prior to mak­ing any adjustments to the control through the User Interface. The DIP switch settings change the items that are available to be viewed and / or adjusted in the User Interface.
If a DIP switch is changed while the control is powered up, the control responds to the change in setting by returning the display to the VIEW menu, see Figure 42.
EXTERNAL INPUT / S TAND ALONE
The External Input / Stand Alone DIP switch selects whether a Lochinvar Outdoor Sensor TST2311 or an external 0 - 10 V (dc) input signal is to be connected to the Com - and the Out + terminals (1 and 4) (FIG. 43).
ADVANCED / INSTALLER
The Adv / Inst aller DIPswitch selects the access level of the control (FIG. 44). In the Installer access level, a limited number of items may be viewed and / or adjusted. In the Advanced access level, all items may be viewed and / or adjusted.
ALARM / COMBUSTION AIR
FIG. 41
22
DIP SWITCH SETTINGS
FIG. 42
FIG. 43
FIG. 44
TM
ROTATE / OFF
The Rotate / Off DIP switch selects whether or not the con­trol is to provide Equal Run Time Rotation of the boiler stages. If the switch is set to Rotate, the stages will be rotat­ed accordingly. If the switch is set to Off, the firing sequence is fixed starting with the lowest stage to the highest stage (FIG. 46).
FIXED LAST / OFF
The Fixed Last / Off DIP switch selects whether or not the last boiler is to be included in the rotation sequence. If the DIP switch is set to Fixed Last, the last boiler is always the last to fire (FIG. 47). This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate.
FIXED LEAD / OFF
The Fixed Lead / Off DIP switch selects whether or not the first boiler is to be included in the rotation sequence. If the DIP switch is set to Fixed Lead, the first boiler is always the first to fire (FIG. 48). This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate.
FIRST ON / LAST OFF OR FIRST ON / FIRST OFF
The First On / Last Off or First On / First Off DIP switch selects whether the first boiler is the first to stage on and the last to stage off or the first to stage on and the first to stage off. This DIP switch is only active when the Rotate / Off DIP switch is set to Rotate and the Fixed Lead / Off DIP switch is set to Fixed Lead (FIG. 49).
OFF / EXERCISE
The Off / Exercise DIP switch selects whether or not the control is to exercise the primary pump and boiler pumps (FIG. 50). If the DIP switch is set to Exercise, the pumps are operated for 10 seconds after every three days of inactivity.
23
FIG. 45
FIG. 46
FIG. 47
FIG. 48
FIG. 49
FIG. 50
24
5
6
25
A
7
A
8
A
9
1
26
This item is only available if the External Input /
Stand Alone DIP switch is set to Stand Alone.
Input Stand Alone DIP switch is set to Stand Alone.
This item is only available if the External Input / Stand Alone DIP switch is set to Stand Alone.
The item is only available if the External /
27
Boiler Minimum
Boiler Maximum
Fire Delay 1
Fire Delay 2
Combustion Air Damper Delay
Boil Mass
Stage Delay
Boiler Differential
Staging
lohi
DHW Mode
DHW Exchange Occupied
DHW Exchange Unoccupied
1 2 3
4
28
(This item is only available when DHW
MODE is set to OFF.)
x
m weather
(This item is only available if the External Input/ Stand Alone DIP switch is set to Stand Alone.)
time that the primary pump will continue to operate after the boiler demand has been removed.
The control has a built-in test routine that is used to test the main control functions. The control continually monitors the sensors and displays an error message whenever a fault is found. See the following pages for a list of the control’s error messages and possible causes. When the Test but- ton is pressed, the test light is turned on. The individual out­puts and relays are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds. During the test routine, if a demand from the system is pres-
ent, the test sequence may be paused by pressing the Test button. If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire test routine. If the test sequence is paused, the Test button can be pressed again to advance to the next step. This can also be used to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the Test button until the appropriate device and seg­ment in the display turn on.
Step 1 The primary pump is turned on and remains on for the entire test routine.
Step 2 If the Alarm / C.A. DIP switch is set to Alarm, the Alarm contact is turned on for 10 seconds and then shuts off. If the Alarm / C.A. DIP switch is set to C.A, the com­bustion Air Damper contact is turned on and remains on for the entire test routine.
Step 3 For each boiler that is set to Auto, the following test sequence is used.
• If the mode indicates that a boiler pump is used, the boiler pump is turned on and remains on.
• Next, the first stage of the boiler is turned on and remains on.
• If a second stage is present, the second stage is turned on and remains on.
• If a third stage is present, the third stage is turned on and remains on. If a fourth stage is
present, the fourth stage is turned on.
• After ten seconds, all stages and the boiler pump are turned off.
Step 4 If DHW MODE is set to 1 or 2 and the last boiler in modes 1, 4, and 5 are set to OFF, the primary pump is shut off and the DHW contact is closed.
Step 5 If DHW MODE is set to 3 or 4 and the last boiler in modes 1, 4, and 5 are set to OFF, the primary pump stays on and the DHW contact is closed.
Step 6 All contacts are turned off.
MAX HEAT
The control has a function called Max Heat, see Figure 52. In this mode, the control turns on and operates the system up to the maximum set temperatures as long as there is a demand for heat. The control continues to operate in this mode for up to 24 hours or until the Item, Menu or Test but­ton is pressed. This mode may be used for running all cir­culators during system start-up in order to purge air from the piping. To enable the Max Heat feature, use the following procedure.
1) Press and hold the Test button for more than 3 seconds.
At this point, the control flashes the MAX segment and dis­plays the word OFF.
2) Using the up or down arrow buttons, select the word On.
After 3 seconds, the control turns on all outputs. However, the max heat mode is still limited by the BOIL MAX setting.
3) To cancel the Max Heat mode, press the Item, Menu, or
Test button.
4) Once the Max Heat mode has either ended or is can-
celled, the control resumes normal operation.
FIG. 51
FIG. 52
29
TESTING THE CONTROL
The control was unable to read a piece of information stored in its memory (FIG. 53). Because of this, the control was required to reload the factory settings into all of the items in the ADJUST menu. The control will stop operation until all of the items in the ADJUST menu of the control have been checked by the user or installer.
Note: The Installer / Adv DIP Switch must be set to Adv in order to clear the error.
The control is no longer able to read the outdoor sensor due to a short circuit (FIG. 54). In this case the controlassumes an outdoor temperature of 32°F (0°C) and continues opera­tion. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button. This error message only occurs if the External Input / Stand Alone DIP switch is set to Stand Alone.
The control is no longer able to read the outdoor sensor due to an open circuit (FIG. 55). In this case the control assumes an outdoor temperature of 32°F (0°C) and contin­ues operation. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button. This error message only occurs if the External Input / Stand Alone DIP switch is set to Stand Alone.
The control is no longer able to read the boiler supply sen­sor due to a short circuit (FIG. 56). The control will not oper­ate the boiler(s) until the sensor is repaired. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the boiler supply sen­sor due to an open circuit (FIG. 57). The control will not operate the boiler(s) until the sensor is repaired. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
The control is no longer able to read the boiler return sen­sor due to a short circuit (FIG. 58). The control will continue to operate normally. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
FIG. 53
FIG. 54
FIG. 55
FIG. 56
FIG. 57
FIG. 58
30
ERROR MESSAGES
The control is no longer able to read the boiler return sen­sor due to an open circuit (FIG. 59). The control will contin­ue to operate normally. Locate and repair the problem as described in INS7141. To clear the error message from the control after the sensor has been repaired, press either the Menu or Item button.
If the boiler return sensor was deliberately removed from the control, remove power from the control and repower the control to clear the error message.
The control has detected no increase in the supply water temperature within the BOIL Alarm time setting. Check to see if the boilers are operating properly using the Test but­ton. To reset the alarm, press and hold the up and down arrow buttons for 5 seconds while in the VIEW menu.
MP2NINE STAGE BOILER & DHW / SET POINT
Control - Microprocessor PID control; This
is not a safety (limit) control.
Packaged Weight - - 3.3 lb. (1500 g), Enclosure A, blue
modified PPO plastic
Dimensions - 6-5/8" H x 7-9/16" W x 2-13/16" D
(170 x 193 x 72 mm)
Approvals - CSA C US, meets ICES & FCC
regulations for EMI/RFI
Ambient Conditions - Indoor use only, 30 to 120°F (0 to
50°C), <95% RH non-condensing
Power Supply - 115 V (ac) +
10% 50/60 Hz
600 Va
Relay Capacity - 230 V (ac) 5 A1/3 hp pilot duty
230 VA Demands - 20 to 260 V (ac) 2 VA Sensors Included - NTC thermistor, 10 k @ 77°F
(25°C +
0.2°C) B=3892
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromag­netic noise. Conversely , this Class B digit al apparatus com­plies with Part 15 of the FCC Rules and meets all require­ments of the Canadian Interference - Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is deter­mined by turning the control off and on, the user is encour­aged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connect­ed.
31
FIG. 59
FIG. 60
TECHNICAL DATA
FIG. 61
CAUTION
The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bush­ings and jumper wires.
Nine Stage Boiler & DHW / Setpoint
Do not apply power
21
3
4 5678910111213 141516
Com
BoilBoilOutUnO BoilCom SetpPrim Sup Ret Sw Dem Dem DH N + L P1 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 DHW
Signal wiring must be rated at least
17 181920 212223 242526 28272930 31
H2026B
32
TYPICAL BOILER INSTALLATION
33
TYPICAL BOILER INSTALLATION (CONTINUED)
34
TYPICAL DWH PRIORITY HEATING PACKAGE SYSTEM
MP2
Tekmar 150 Controller
35
NOTES
9/04 - Printed in U.S.A.
Loading...