Optional Equipment
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
7/09–Printed in U.S.A.
Standard Features
Standard kW Input & Amperage
CHP-10 (Reprint CHP-10 2/08)
Suggested
GPH@ Max. No. of kW No. of Modulating Amperage Draw
kW 100°F Btu/hr No. of Control Per Contactors Control Steps Single Phase Three Phase
Input Rise Equivalent Elements Steps Element 240/480V 240/480V 208V 240V 208V 240V 480V
12 49 40,944 1 1 12 2/1 - 58 50 33 29 14
15 62 51,180 1 1 15 2/1 - 72 63 42 36 18
18 74 61,416 1 1 18 2/1 - 87 75 50 44 22
30 123 102,360 2 1 15 2/1 - 144 125 83 72 36
36 148 122,832 2 1 18 4/2 4/2 174 150 100 87 44
45 185 153,540 3 1 15 3/2 3/2 216 188 125 108 54
54 221 184,248 3 1 18 6/2 3/2 260 225 150 130 65
60 246 204,720 4 2 15 12/6 4/3 289 250 167 144 72
72 295 245,664 4 2 18 8/4 4/4 - - 200 174 87
90 369 307,080 5 2 18 6/3 3/3 - - 250 217 109
108 443 368,496 6 2 18 12/4 4/4 - - 300 260 130
120 492 409,440 8 3 15 8/4 4/4 - - 333 289 144
135 554 460,620 9 3 15 9/6 4/4 - - 375 325 162
144 590 491,328 8 3 18 16/8 4/4 - - 400 347 174
162 664 552,744 9 3 18 18/6 8/6 - - 450 389 195
180 738 614,160 10 4 18 20/10 8/8 - - 500 434 217
216 886 736,992 12 4 18 24/8 8/8 - - 600 519 260
234 959 798,408 13 5 18 26/13 8/8 - - 650 563 282
252 1,033 859,824 14 5 18 28/14 8/8 - - 700 607 304
270 1,107 921,240 15 5 18 30/10 12/10 - - 750 649 325
288 1,181 982,656 16 6 18 32/16 12/12 - - 800 692 347
306 1,255 1,044,072 17 6 18 34/17 12/12 - - 850 736 368
324 1,328 1,105,488 18 6 18 36/12 12/12 - - 900 780 390
342 1,402 1,166,904 19 7 18 38/19 12/12 - - 950 822 412
360 1,476 1,228,320 20 7 18 40/20 12/12 - - 1,000 865 435
378 1,550 1,289,736 21 7 18 42/14 14/14 - - 1,050 909 455
396 1,624 1,351,152 22 8 18 44/22 15/16 - - 1,100 952 477
414 1,697 1,412,568 23 8 18 46/23 16/16 - - 1,150 995 498
432 1,771 1,473,984 24 8 18 48/16 16/16 - - 1,200 1,040 520
For KW above 432 or other voltages please consult factory
• Glass Lined Steel Tank
• Incoloy Heating Elements
• Internal Fusing (above 120 amps)
• Enamel Finished Galvanized Steel Jacket
• Magnesium Tank Saver Anodes
• Immersion Thermostat
• Manual Reset High Limit
• Full Length Hinged Doors with Key Lock
• Terminal Block Connections
• ASME Temperature and Pres sure Relief Valve
(Supplied but not installed)
• Low Water Cut-Off
• Pilot Lights
• Manual Limiting Switches
• Alarm Bell
• Shunt Trip Disconnect (Field Installed)
• Low or High Water Pressure Switch
• Lifting Lugs
• Time Clock (7 day or 24 hour)
• Channel Iron Skid Base (Except 150 & 200 gallon round)
• Approved for 180°F Temperature Operation
• ASME Construction and Na tion al Board Listed
• All models meet or exceed ASHRAE
energy efficiency standards
• 125 psi Working Pressure
• Handhole/Cleanout
• UL Listed (U.S. and Canada)
• Safety Drain Pan (Square Models)
• 3 Year Limited Tank Warranty
• Control Voltage On/Off Switch w/ Pilot Light
• BMS Enable/Disable Contacts
• Safety Door Interlock
• Temperature and Pressure Gauges
• Manway (250 Gallon and Larger Only)
• 150 psi or 160 psi Working Pressure
• Electronic Step Controller
• Seismic Attachment Points (250 Gallon and Larger Only)
(customer must provide seismic zone or city and state of install)