Lochinvar’s Hot Water Generator Systems are ideal when
boiler capacity is sufficiently sized to cover potable hot
water demand and provide source water for hydronic
heating systems. Hot Water Generator Systems use steam
or boiler water as an energy source and can provide high
recovery rates, making them an economical water heating
system.
Availability
Hot Water Generator Systems are pre-engineered and
pre-assembled complete with all piping to meet your
specific application. And like every Lochinvar product, we
thoroughly test them to ensure proper performance from
the moment they’re installed.
Hot Water Generator Systems are available in horizontal or
vertical configurations in a wide array of gallon capacities.
Standard packages are available in tank sizes from 2001000 gallons with single wall copper tube bundle heating
units. Custom configurations, smaller and larger tank
and tube bundles, and optional control packages are also
available. Consult the factory for specifications.
Steam to Water
Tank Construction – Lochinvar tanks are available with
Glass or Cement lining.
ASME - All Lochinvar tanks are constructed in
accordance with ASME standards and certified for 125 psi
working pressure (standard) or 150 psi working pressure
(optional).
Cathodic Protection – All glass lined tanks are equipped
with magnesium anodes to provide protection against
corrosion.
Manway – A manway is provided as an option on
glass-lined tanks and is standard on cement lined tanks.
*Horizontal tanks with tube bundles 48” and longer require manway.
Tank Circulator Pump – All standard Hot Water
Generator systems are equipped with a circulator pump to
maximize the amount of hot water provided.
Five-Year Limited Tank Warranty – Provides warranty
protection against tank failure. (See warranty for details)
One-Year Limited Warranty – Tube Bundle, parts,
accessories and controls (See warranty for details)
Unit shown with optional control package.
Optional Control Packages
Steam to Water – Control packages include an isolation
valve, 2-way self-operated temperature regulator, inlet and
outlet wye strainers, a float and thermostatic steam trap
and all necessary piping.
Water to Water – Control packages include isolation
valves, 2-way self-operated temperature regulator, inlet
wye strainer and all necessary piping.
Optional Equipment
•
Manual Reset High Limit w/ Solenoid Valve
• Manway (See notes on manway)
• 150 psi Tank Working Pressure
• Temperature & Pressure Gauge
• Vacuum Breaker
Dimensions
Vertical Tanks Round Jacketed
Model Gallon Maximum Shipping
Number Capacity A C D E Coil Length Weight
NOTE: Manway required on tanks with tube bundles 48” and longer.
* Indicates Tank Lining – G=Glass C=Cement
Non-Jacketed Tanks
Maximum Minimum Maximum
Gallon Length** Diameter Coil Length Coil Length Coil Length Shipping
Model Capacity (Height) (Width) D E (Horizontal) (Horizontal) (Vertical) Weight
The Water to Water Generator System shall be a Lochinvar Model no. _____________ with ____________ tube bundle heating unit.
The hot water generator shall be constructed of a (vertical) (horizontal) storage tank. The storage tank shall be ________” diameter x
_______” (length) (height) with a ________ gallon capacity. The tube bundle heating unit will be single wall/double wall designed to
recover ____________ GPH with a temperature rise from ________°F to ________°F with _________°F as setpoint temperature when
supplied with ________°F boiler water. The interior of the storage tank shall be glass lined and fired to 1600°F to ensure a molecular
fusing of glass and steel and furnished with magnesium anode(s) to provide protection against corrosion. The storage tank shall be
constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National
Board of Boiler and Pressure Vessel Inspectors. The storage tank shall have a 125 psi (optional 150 psi) working pressure. The storage
tank shall be furnished with a factory installed heavy steel jacket finished with a baked acrylic enamel finish. The storage tank shall be
completely encased in a minimum of 2” thick, high density polyurethane foam insulation to meet the energy efficiency requirements of
the latest edition of the ASHRAE 90.1 Standard. The tank shall be supplied with a drain valve.
The tube bundle heating unit shall be constructed and stamped according to section VIII of ASME code. The tube bundles shall
be constructed of 3/4” O.D. 20 GA. deoxidized drawn copper tubing. A .75 amp @ 115 volt, 60 Hz, 1/25 HP integral circulator
pump with copper soldered recirculation line shall be provided. The heating units shall be installed in the tank by bolted connection to
the collar flange and tube bundle head.
Optional Tube Bundle Construction: LTW = Single Wall, LTWX = Double Wall
Optional Tube Bundle Material: Cupro-Nickel, Stainless Steel.
Optional Control Package: The Water to Water Generator shall be equipped with isolation valves, two-way self operated temperature
regulator, an inlet wye strainer and all necessary piping.
Optional Equipment: Manual Reset High Limit, Solenoid Valve, Manway, Temperature and Pressure Gauge, ASME Temperature
and Pressure Relief Valve.
Tank Lining Options: Cement tank lining designed to provide effective corrosion resistance against the chemicals and conditions
experienced in the storage of potable water at elevated temperatures.
Steam to Water Specification:
The Steam to Water Generator System shall be a Lochinvar Model no. _____________ with ____________ tube bundle heating
unit. The hot water generator shall be constructed of a (vertical) (horizontal) storage tank. The storage tank shall be ________”
diameter x _______” (length) (height) with a ________ gallon capacity. The tube bundle heating unit will be single wall/double
wall designed to recover ____________ GPH for a temperature rise from ________°F to ________°F with _________°F as setpoint
temperature when supplied with ________ psi steam to the temperature regulator. The interior of the storage tank shall be glass lined
and fired to 1600°F to ensure a molecular fusing of glass and steel and furnished with magnesium anode(s) to provide protection against
corrosion. The storage tank shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped
and registered with the National Board of Boiler and Pressure Vessel Inspectors. The storage tank shall have a 125 psi (optional 150
psi) working pressure. The storage tank shall be furnished with a factory installed heavy steel jacket finished with a baked acrylic
enamel finish. The storage tank shall be completely encased in a minimum of 2” thick, high density polyurethane foam insulation to
meet the energy efficiency requirements of the latest edition of the ASHRAE 90.1 Standard. The tank shall be supplied with a drain
valve.
The tube bundle heating unit shall be constructed and stamped according to section VIII of ASME code. The tube bundles shall be
constructed of 3/4” O.D. 20 GA. deoxidized drawn copper tubing. A .75 amp @ 115 volt, 60 Hz, 1/25 HP integral circulator pump
with copper soldered recirculation line shall be provided. The heating units shall be installed in the tank by bolted connection to the
collar flange and tube bundle head.
Optional Tube Bundle Construction: LTS = Single Wall, LTSX = Double Wall
Optional Tube Bundle Material: Cupro-Nickel, Stainless Steel.
Optional Control Package: The Steam to Water Generator shall be equipped with an isolation valve, two-way self operated
temperature regulator, an inlet and outlet wye strainer, a steam trap and all necessary piping.
Optional Equipment: Manual Reset High Limit, Solenoid Valve, Manway, Temperature and Pressure Gauge, ASME Temperature
and Pressure Relief Valve.
Tank Lining Options: Cement tank lining designed to provide effective corrosion resistance against the chemicals and conditions
experienced in the storage of potable water at elevated temperatures.