Lochinvar GAS HEATER FOR COMMERICAL POOL APPLICATIONS User Manual

INSTALLATION AND SERVICE MANUAL
Save this manual for future reference.
WWAARRNNIINNGG
: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
– This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WWAARRNNIINNGG
: Do not use this pool heater if any part has been under water. The possible damage to a flooded pool heater can be extensive and present numerous safety hazards. Any pool heater that has been under water must be replaced.
GAS HEATERS FOR COMMERCIAL
POOL APPLICATIONS
500,000 - 2,070,000 Btu/hr MODELS
Starting Serial #F0600187510
CPE-i&s-05
WWAARRNNIINNGG
: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials or loss of life. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier. This pool heater contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans.
Commercial Pool Heaters
2
TTaabbllee ooff CCoonntteennttss
General Product Information . . . . . . . . . . . . . . . . . . . . . . . . .3
Special Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Product Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Locating Pool Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Clearances from Combustible Construction . . . . . . . . . . . . .6
Base for Combustible Floors . . . . . . . . . . . . . . . . . . . . . . . . .6
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . . . . . .7
Combustion Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Combustion Air Options . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Exhaust Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Venting Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Vertical Vent Termination Clearances and Location . .10 Sidewall Vent Termination Clearances and Location . .11
Combustion Air Inlet Piping . . . . . . . . . . . . . . . . . . . . .12
Length of Air Inlet Piping . . . . . . . . . . . . . . . . . . . . . . .12
Sidewall Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Vertical Rooftop Air Inlet . . . . . . . . . . . . . . . . . . . . . . .13
Combined Air Inlet Points . . . . . . . . . . . . . . . . . . . . . .13
Vent System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Barometric Damper Location . . . . . . . . . . . . . . . . . . . .14
1. Conventional Negative Draft Venting . . . . . . . . . . .14
2. Vertical DirectAire
Venting . . . . . . . . . . . . . . . . . . .16
3. Sidewall Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4. Horizontal DirectAire
Venting . . . . . . . . . . . . . . . .20
5. Direct Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
6. Outdoor Installation Venting . . . . . . . . . . . . . . . . . . .25
Connecting to Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . .26
Gas Pressure Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Connecting Gas Piping to the Pool Heater . . . . . . . . . .27
Gas Train and Controls . . . . . . . . . . . . . . . . . . . . . . . . .27
Combination Gas Valves . . . . . . . . . . . . . . . . . . . . . . . .28
Venting of Combination Gas Valves . . . . . . . . . . . . . . .28
Checking Gas Supply Pressure . . . . . . . . . . . . . . . . . . .28
Gas Manifold Pressure Adjustment . . . . . . . . . . . . . . .30
Pool Heater Piping Installation . . . . . . . . . . . . . . . . . . . . . .31
Auxiliary Mixed Water Limit Control . . . . . . . . . . . . .31
Pumped Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Outdoor Operation - Outdoor 3-Way Valve Cover . . . .31
Manual Operation of the 3-Way Valve Actuator . . . . .32
TTaabbllee ooff CCoonntteennttss
Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Pump Purge Delay Option . . . . . . . . . . . . . . . . . . . . . .36
Service Indicator Option . . . . . . . . . . . . . . . . . . . . . . . .36
Connecting to Electrical Supply . . . . . . . . . . . . . . . . . . . . .36
3-Way Valve Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Terminal Strip Connection Options . . . . . . . . . . . . . . .37
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . .38
To Turn Off Gas To Pool Heater . . . . . . . . . . . . . . . . . .39
Pre-Start Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Starting the Filter System . . . . . . . . . . . . . . . . . . . . . . .39
Operating Temperature Control . . . . . . . . . . . . . . . . . .40
Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Error Messages -- Temperature Control . . . . . . . . . . . .41
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . .42
Operation and Diagnostic Lights . . . . . . . . . . . . . . . . . . . . .43
Water Chemistry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Pipe Size Requirements . . . . . . . . . . . . . . . . . . . . . . . .46
Circulating Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Minimum Pump Performance . . . . . . . . . . . . . . . . . . . .46
Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
High Water Temperature Limit Control . . . . . . . . . . . .47
Cleaning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .47
Heat Exchanger Cleaning . . . . . . . . . . . . . . . . . . . . . . .48
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . .48
Adjusting Differential Air Pressure . . . . . . . . . . . . . . . .49
Set-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Adjustment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . .50
Servicing Hot Surface Igniter and Ignition Module . . . . . .50
Ignition System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . .50
Energy Saving Recommendations . . . . . . . . . . . . . . . . . . . .51
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Wiring Box Connections . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Ladder Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Control Box Connections . . . . . . . . . . . . . . . . . . . . . . . . . .57
Appendix A_Unit Start Up Checklist . . . . . . . . . . . . . . . . .58
Appendix B_Adjust Menu Settings for Operating Modes .59 . . . `
GGEENNEERRAALL PPRROODDUUCCTT IINNFFOORRMMAATTIIOONN
Special Instructions
This manual supplies information for the installation, operation and servicing of this pool heater. Read and understand this manual completely before installing the pool heater.
Installation and service must be performed by a qualified service installer, service agency, or the gas supplier.
Unpacking
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the pool heater which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on the packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier.
Codes
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA-B149 Installation Code. All pool heater heat exchanger construction conforms to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV, Part HLW.
Warranty
Factory warranty (shipped with pool heater) does not apply to pool heaters installed or operated improperly. Improper installation or system design causes most operating problems.
1. Excessive water hardness causing a lime build up in the copper tube is not the fault of the equipment and is not covered under the appliance manufacturer’s warranty (see Water Chemistry, page 44).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the appliance manufacturer’s warranty.
3. Corrosion due to water chemistry imbalance is not the fault of the equipment and is not covered by the appliance manufacturer’s warranty (see Water Chemistry, page 44).
SSAAFFEETTYY IINNFFOORRMMAATTIIOONN
The information contained in this manual is intended for use by qualified professional installers, service technicians or gas suppliers. Consult your local expert for proper installation or service procedures.
IMPORTANT: Read this owner’s manual carefully and completely before trying to install, operate, or service this pool heater. Improper use of this pool heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon Monoxide poisoning
may lead to death!
IMPORTANT: Consult and follow local building and fire regulations and other safety codes that apply to this installation. Consult your local gas utility company to authorize and inspect all gas and flue connections.
WARNING: Should overheating occur or
the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the pool heater.
WARNING: To minimize the possibility of
serious personal injury, fire or damage to your pool heater, never violate the following safety rules.
1. Pool heaters are heat producing appliances. To avoid damage or injury, do not store materials against the pool heater or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the pool heater and vent-air intake components.
2. Never cover your pool heater, lean anything against it, store trash or debris near it, stand on it, or in any way block the flow of fresh air to your pool heater.
3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this pool heater, vent-air intake system or any location from which fumes could reach the pool heater or vent-air intake system.
4. This pool heater is only for use with the type of gas indicated on the rating plate.
5. If you smell gas shut off gas supply.
Installation and Service Manual
3
do not try to light any appliance
do not touch any electrical switch; do not use any phone in your building
immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
if you cannot reach your gas supplier, call the fire department
6. This appliance is a high efficiency pool heater which has been designed to operate scale-free and trouble free for many years. Particular attention should be directed to the following items.
Correct piping to the pool filter system with
specified pipe materials and size.
Electrical interconnection of the pool heater
controls, bypass pump and filter pump to ensure continuous circulation.
Proper venting.
Water chemistry.
7. Follow all clearances from combustibles contained in this manual.
8. Appliance surfaces become hot during operation. Be careful not to touch hot surfaces. Keep all adults, children, and animals away from an operating pool heater. Severe burns can occur.
9. This pool heater must have an adequate supply of fresh air during operation for proper gas combustion and venting.
10. Make sure all exhaust venting is properly installed and maintained. Improper venting of this pool heater could lead to increased levels of carbon monoxide.
11. Do not use this pool heater if any part has been under water. Immediately call a qualified service technician to replace the pool heater. The possible damage to a flooded pool heater can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
12. Do not alter this pool heater in any way. Any change to this pool heater or its controls can be dangerous.
Commercial Pool Heaters
4
PPRROODDUUCCTT IIDDEENNTTIIFFIICCAATTIIOONN
Installation and Service Manual
5
Figure 1B - Optional Vertical Piping Loop
Figure 1A - Standard Horizontal Piping Loop
INSTALLATION
This pool heater meets the safe lighting performance criteria with the gas manifold and control assembly provided, as specified in the ANSI Z21.10.3/CSA 4.3 standard for gas-fired water heaters.
LOCATING POOL HEATER
1. Maintain all clearances from combustible construction when locating pool heater. See Clearances from Combustible Construction, this page.
2. Locate the pool heater so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, install a suitable drain pan that is well­drained under the pool heater. The pan must not restrict combustion air flow. The pool heater manufacturer is not responsible for water damage in connection with this pool heater, or any of its components.
3. Install the indoor pool heaters so that the ignition system components are protected from any water while operating or during service.
4. You must install the pool heater on a level, non­combustible floor.
5. Do not install pool heater directly on carpet or other combustible material. A concrete-over-wood floor is not considered non-combustible. Maintain required clearances from combustible surfaces. If installing the pool heater in an area with a combustible floor, you must construct a special combustible floor base. See Base for Combustible Floors, this page.
6. For outdoor models, you must install an optional vent cap. Instructions for mounting the vent cap are included in the venting section. Do not install outdoor models directly on the ground. You must install the outdoor pool heater on a concrete, brick, block, or other non-combustible pad. Outdoor models have additional special location and clearance requirements. See Outdoor Installation Venting, page 25. A wind proof cabinet protects the pool heater from weather.
Clearances from Combustible Construction
Maintain minimum specified clearances for adequate operation. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the pool heater. See rating plate for specific service clearance requirements.
Right Side 3" (7.5 cm)
Rear 3" (7.5 cm) (3" min. from any surface)
Left Side 6" (15cm) (24" (0.61m) suggested for service)
Front Alcove* (30" (0.76m) suggested for service)
To p 3" (7.5cm)
Flue 1" (25.4mm)
Hot Water Pipes 1" (25.4mm)
*An Alcove is a closet without a door.
Note: No additional clearance is needed on the right side of the pool heater for the observation port. An observation port is located on both the right and left side of the pool heater.
Note: No additional clearances from combustibles are needed for use of the Direct Vent (DV) air inlet assembly.
Figure 2 – Clearances from Combustible Construction
Base for Combustible Floors
There are no manufactured combustible floor base kits available for 990,000 - 2,070,000 Btu models. See Table-A for floor base kits that are available.
If a manufactured combustible floor base kit is not used, you must construct a base for combustible floor installation. Install the pool heater over a base of hollow clay tiles or concrete blocks from 8" to 12" thick, extending at least 24" beyond the pool heater sides. Place tiles or blocks so that the holes line up horizontally to provide a clear passage through the tiles or blocks. Place a 1/2" fireproof millboard over the top of the tile or block base. Place a 20-gauge sheet metal cover over the fireproof millboard. Center the pool heater on the base. Also follow this procedure if electrical conduit runs through the floor beneath the pool heater. This base must meet all local fire and safety codes.
Commercial Pool Heaters
6
FREEZE PROTECTION
Although this pool heater is CSA design certified for outdoor installations - such installations are not recommended in areas where the pool heater will be operated in the winter months and the danger of freezing exists. Proper freeze protection must be provided for outdoor installations; pool heaters installed in unheated mechanical rooms or where temperatures may drop to the freezing point or lower. If freeze protection is not provided for the system, a low ambient temperature alarm is recommended for the mechanical room. Damage to the pool heater by freezing is non-warrantable.
1. Pump Operation - MOST IMPORTANT - This pool heater is designed for continuous operation of the filter system pump when the burners are firing. If the system pump does not run continuously, an additional pump must be installed to provide constant circulation through the pool heater. The constant flow of warm pool water can help prevent freezing.
2. Anytime the temperature measured at the sensor drops below 45°F, the temperature control turns on the pump to circulate the water, if the pump option is installed.
3. Location - Indoor pool heaters must be located in a room having a temperature safely above freezing [32°F(0°C)].
4. Outdoor Pool Heater Installation - Use extreme caution to prevent freezing. A snow screen should be installed to prevent snow and ice accumulation around the pool heater or its venting system.
5. Shut-Down and Draining - If for any reason, the pool heater is to be shut off, the following precautionary measures must be taken:
1. Shut off gas supply.
2. Shut off water supply.
3. Shut off electrical supply.
4. Drain the pool heater completely. Remove the
threaded drain plugs from the inlet and outlet sides of
the front header on the heat exchanger (see Figure 3).
Blow all water out of the heat exchanger. Leave
drains open until Spring.
5. Drain pump and piping.
Figure 3 – Draining Pool Heater
CAUTION: Under no circumstances should
the mechanical room ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the pool heater.
COMBUSTION AND VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
Provide properly-sized openings to the equipment room to assure adequate combustion air and proper ventilation when the pool heater is installed with conventional venting or sidewall venting.
Combustion Air Filter
This pool heater has a standard air filter located at the combustion air inlet. This filter helps ensure clean air is used for the combustion process. Check this filter every month and replace when it becomes dirty. The filter size on the 500,000
- 750,000 units is 12" x 12" x 1" (30.5cm x 30.5cm x 2.5cm) and 16" x 16" x 1 (40.6cm x 40.6cm x 2.5 cm) on the 990,000
- 2,070,000 units. You can find these commercially available filters at any home center or HVAC supply store.
Use filters rated for a maximum face velocity of 300 ft/min at a maximum pressure drop of 0.5" water column (w.c.) Pleated filters may be used provided they meet these specifications.
Installation and Service Manual
7
500,000 CFK3302 650,000 CFK3303 750,000 CFK3304
TABLE - A
COMBUSTIBLE FLOOR KITS
Input Btu/hr Kit Number
IINNSSTTAALLLLAATTIIOONN
Continued
CAUTION: Some pleated filters are too
restrictive and could cause air flow problems.
For convenience and flexibility, you can direct the combustion air inlet from either the back or right side of the pool heater. To arrange the combustion air inlet for side entry, follow the steps below.
1. Remove the metal panel from the pool heater’s side wall (see Figure 4).
2. Remove screws from the air filter/bracket assembly.
3. Move the filter/bracket assembly from the rear of the pool heater to the side opening (see Figure 5).
4. Attach the filter/bracket assembly to the pool heater’s side using the pre-drilled screw holes.
5. Attach the metal panel to the rear combustion air opening to seal it off.
Figure 4 – Metal Panel Covering Side Combustion Air Inlet
Figure 5 – Moving Air Filter/Bracket Assembly from Rear of Pool Heater to Side
Combustion Air Options
This pool heater has four combustion air options.
1. Outside Combustion Air, No Ducts
You can direct outside combustion air to this pool heater using either one or two permanent openings.
One Opening
The opening must have a minimum free area of one square inch per 3000 Btu input (7cm
2
per kW). You must locate this
opening within 12" (30cm) of the top of the enclosure.
Figure 6 – Outside Combustion Air - Single Opening
Two Openings
The combustion air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5cm
2
per kW). You must locate this opening within 12" (30cm) of the bottom of the enclosure.
The ventilation air opening must have a minimum free area of one square inch per 4000 Btu/hr input (5.5cm
2
per kW). You must locate this opening within 12" (30cm) of the top of the enclosure.
Commercial Pool Heaters
8
Figure 7 – Outside Combustion Air - Two Openings
2. Outside Combustion Air, Using Ducts
You can direct outside combustion air to this pool heater using two air ducts to deliver the air to the mechanical room. Each of the two openings must have a minimum free area of one square inch per 2000 Btu input (11cm
2
per kW).
Figure 8 – Outside Combustion Air Through Ducts
3. Outside Combustion Air, Using Direct Venting
With this option, you can connect combustion air vent piping directly to the pool heater. See the information under Direct Venting starting on page 21 for specific information regarding this option.
4. Combustion Air from Interior Space
You can direct combustion air to this pool heater using air from an adjoining interior space. You must provide two openings from the mechanical room to the adjoining room.
Each of the two openings must have a net free area of one square inch per 1000 Btu input (22cm
2
per kW), but not less
than 100 square inches (645cm2).
Figure 9 – Combustion Air from Interior Space
All dimensions are based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the mechanical room. Each opening must have a minimum net free area as specified in TABLE–C, page 12. Single openings shall be installed within 12" (30 cm) of the ceiling.
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the pool heater. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature pool heater failure.
Exhaust Fans
Any fan or equipment which exhausts air from the mechanical room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the mechanical room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the pool heater.
Vertical DirectAire™ and Horizontal DirectAire™ venting systems have specific requirements for combustion air ducts from the outside which are directly connected to the pool heater. See the requirements for combustion air duct in the venting section starting on page 12.
Installation and Service Manual
9
IINNSSTTAALLLLAATTIIOONN
Continued
VVEENNTTIINNGG
General Information
You must supply adequate combustion and ventilation air to this pool heater. You must provide minimum clearances for the vent terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment” of the above-mentioned standards.
IMPORTANT: Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also check for corrosion or deterioration. If you find any problems, correct them at once.
Venting Support
Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot (21mm/m) on all horizontal runs from the pool heater to the vertical flue run or to the vent terminal on sidewall venting installations.
Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the venting system must not rest on the pool heater. Provide adequate support of the venting system. Follow all local and applicable codes. Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.
Vertical Vent Termination Clearances and Location
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.
Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.
Figure 10 – Vent Termination from Peaked Roof - 10' or Less From Ridge
IMPORTANT: Vent terminations are not shown in Figures 10, 11, 12, and 13. Make sure all vertical vents are installed with vent terminations recommended by the vent manufacturer.
Figure 11 – Vent Termination from Peaked Roof More Than 10' From Ridge
Commercial Pool Heaters
10
Figure 12 – Vent Termination from Flat Roof 10' or Less from Parapet Wall
Figure 13 – Vent Termination from Flat Roof More Than 10' from Parapet Wall
Sidewall Vent Termination Clearances and Location
Locate the bottom of the vent terminal at least 12 inches (30cm) above grade and above normal snow levels. Locate the bottom of the vent terminal at least 7 feet (2.13m) above grade when located adjacent to public walkways. Do not terminate directly above a public walkway.
Do not terminate the venting system in a window well, stairwell, alcove, courtyard, or other recessed area. Do not terminate the venting system below grade.
Locate vent termination at least 3 feet (0.91m) from an inside corner of an L-shaped structure.
Provide a minimum clearance of 4 feet (1.2m) horizontally from electric meters, gas meters, regulators, and relief equipment. Never locate the vent cap above or below electric meters, gas meters, regulators, and relief equipment unless a 4 foot (1.2m) horizontal clearance is maintained.
Terminate the venting system at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
Terminate the venting system at least 4 feet (1.2m) below, 4 feet (1.2m) beside, or 1 foot (30cm) above any door, window, or gravity air inlet into any building.
Locate vent termination at least 8 feet (2.4m) horizontally from any combustion air intake located above the sidewall termination cap.
CAUTION: Pool heaters which are shut
down or will not operate may experience freezing due to convective air flow in the flue pipe, through the air inlet, or from negative pressure in the mechanical room. In cold climates, operate pump continuously to help prevent freezing of pool heater water. Provide proper freeze protection. See Freeze Protection, page 7.
TABLE–A
Input Flue Air Inlet
Btu/hr Size Size*
500,000 6" 6"
650,000 8" 8"
750,000 8" 8"
990,000 10" 10"
1,260,000 12" 12"
1,440,000 12" 12"
1,800,000 14" 12"
2,070,000 14" 12"
* Minimum diameter for air inlet pipe. Installer may increase diameter one pipe size for ease of installation, if needed. Refer to the National Fuel Gas Code (ANSI Z223.1) Vent Tables for additional guidance on vent sizing of fan
assisted appliances.
Installation and Service Manual
11
TABLE - B
Flue and Air Inlet Pipe Sizes
IINNSSTTAALLLLAATTIIOONN
Continued
Combustion Air Inlet Piping
WARNING: Locate and install the
combustion air inlet cap correctly. Failure to do so can allow the discharge of flue products to be drawn into the combustion process. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products. This will cause operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
The sidewall or vertical rooftop DirectAire™ combustion air supply system has specific vent material and installation requirements. The air inlet pipe connects directly to the pool heater to supply combustion air. In most installations, the combustion air inlet pipe will be a dedicated system with one air inlet pipe per pool heater. You can combine multiple air inlets if the guidelines in Combined Air Inlet Points, page 13 are followed. The air inlet pipe will be connected to a combustion air inlet cap as specified in this section.
For normal installations, this system uses a single-wall pipe to supply combustion air from outdoors directly to the pool heater.
Where overnight temperatures reach 40°F, use a Type-B double-wall vent pipe or an insulated single-wall pipe for combustion air. This will help prevent moisture in the cool incoming air from condensing and leaking from the inlet pipe.
Note: When the use of the DV box adapter in the following venting systems is not practical, contact the manufacturer for an “in-line” filter to address problems.
Length of Air Inlet Pipe
The installed length of air inlet pipe from the pool heater to the outside air inlet cap must not exceed 50 equivalent feet (15.2m). Upsizing air inlet pipe diameters is permitted to meet increased length requirements. Subtract 5 feet (1.5m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow.
Do not exceed the limits for the combustion air inlet piping lengths.
Sidewall Air Inlet
The sidewall air inlet cap is supplied in the Horizontal DirectAire™ Vent Kit. Order the kit from the appliance manufacturer. This sidewall cap supplies combustion air for a single pool heater only. See TABLE–D, page 17, for kit numbers.
Locate the pool heater as close as possible to the sidewall where you will install the combustion air supply system.
Commercial Pool Heaters
12
Combustion Air Source
Boiler Input Outside Air*/2 Openings Outside Air*/1 Opening Inside Air/2 Openings
500,000 125 in2(806 cm2) 167 in2(1077 cm2) 500 in2(3226 cm2)
650,000 163 in2(1052 cm2) 217 in2(1400 cm2) 650 in2(4194 cm2)
750,000 188 in2(1213 cm2) 250 in2(1613 cm2) 750 in2(4839 cm2)
990,000 248 in2(1,600cm2) 330 in2(2,129 cm2) 990 in2(6,388 cm2)
1,260,000 315 in2(2,032cm2) 420 in2(2,710 cm2) 1260 in2(8,130 cm2)
1,440,000 360 in
2
(2,323cm2) 480 in2(3,097 cm2) 1440 in2(9,291 cm2)
1,800,000 450 in2(2,903cm2) 600 in2(3,871 cm2) 1800 in2(11,614 cm2)
2,070,000 518 in2(3,342cm2) 690 in2(4,452 cm2) 2070 in2(13,356 cm2)
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the boiler only, additional gas fired units in the boiler room will require an increase in the net free area to supply adequate combustion air for all units. Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to CAN/CGA-B149 Installation Code. Check all local code requirements for combustion air.
TABLE-C
Minimum Recommended Combustion Air Supply to Mechanical Room
Figure 14 – Sidewall Combustion Air Inlet
Figure 15 – Air Inlet Cap for Sidewall Termination
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and/or CAN/CGA-B149 Installation Code and instructions in the Installation and Service Manual.
You must install the combustion air inlet cap at least one foot (0.30m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (powered vent cap) if it is located within 10 feet (3.05m) of the flue outlet from the powered vent cap. Make sure to properly install the air inlet cap assembly on the air inlet pipe.
You must install the combustion air inlet cap and the powered vent cap on the same wall and in the same pressure zone. Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Vertical Rooftop Air Inlet
Use the vertical air inlet terminations available from the pool heater manufacturer, recommended and/or supplied by the vent manufacturer, or use two 90° elbows as described on page 24.
Figure 16 – Roof Top Combustion Air Inlet
Clearances
You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.
If the air inlet cap is within a 10 foot (3.05m) radius of the flue outlet, the point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap).
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Combined Air Inlet Points
The air inlet pipes from multiple pool heaters can be combined to a single common connection if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
Example: Two 10" air inlet pipes (78.5 in
2
area each) have a
total area of 157 in
2
and will require a 15" (176.7 in2area)
common air inlet pipe.
The air inlet point for multiple pool heater air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected
Installation and Service Manual
13
IINNSSTTAALLLLAATTIIOONN
Continued
to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors. The total length of the combined air inlet pipe must not exceed a maximum of 50 (15.2m) equivalent feet. Subtract 5 feet (1.5m) for each 90° elbow in the air inlet pipe. You must deduct the restriction in the area provided by any screens, grills or louvers installed in the common air inlet point. These are common on the sidewall air inlet openings. Screens, grills or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials used.
Vent System Options
This pool heater has six venting options.
1. Conventional Negative Draft Venting
This option uses a vertical rooftop flue termination. Combustion air is supplied from the mechanical room.
2. Vertical DirectAire™ Venting
This option uses a vertical conventional vent for flue products. Combustion air is supplied by a pipe from the sidewall or rooftop. See page 16 for venting details.
3. Sidewall Venting
This option uses a powered vent assembly to exhaust the flue products out a sidewall vent termination. Combustion air is supplied from the mechanical room. See page 17 for venting details.
4. Horizontal DirectAire™ Venting
This option uses a powered vent assembly to exhaust the flue products out a sidewall. Combustion air is supplied by a pipe from the sidewall. See page 20 for venting details.
5. Direct Venting
This option uses a sealed AL29-4C flue and a separate combustion air pipe to the outdoors. This system terminates both the flue and combustion air inlet in the same pressure zone. The flue outlet and combustion air intake may terminate at either a sidewall (horizontal) or the rooftop (vertical). See page 21 for venting details.
6. Outdoor Installation Venting
This option uses the installation of a special air inlet/vent cap on top of the pool heater. See page 25 for venting details. All pool heaters are shipped from the factory equipped for conventional negative draft venting. All other optional vent systems require the installation of specific vent kits and venting materials. The following is a detailed explanation of the installation requirements for each venting system, components used and part numbers of vent kits for each model.
Barometric Damper Location
Any venting system option that requires a barometric damper must adhere to the following directions for optimum performance.
The preferred location for the barometric damper is in a tee or collar installed in the vertical pipe rising from the pool heater’s flue outlet. The barometric damper MUST NOT be installed in a bull head tee installed on the pool heater’s flue outlet. The
tee or collar containing the barometric damper should be approximately thr
ee feet vertically above the connection to
the pool heater’s flue outlet. This location ensures that any
positive velocity pressure from the pool heater’s internal combustion fan is dissipated and the flue products are rising due to buoyancy generated from the temperature of the flue products. Adjust weights on the damper to ensure that draft is maintained within the specified range.
1. Conventional Negative Draft Venting
IMPORTANT: Before installing the venting system, follow all venting clearances and requirements found in the Venting, General Information section, page 10.
Figure 17 – Conventional Negative Draft Vertical Venting with Combustion Air Louvers
This option uses Type-B doublewall flue outlet piping. The blower brings in combustion air. The buoyancy of the heated flue products cause them to rise up through the flue pipe. The flue outlet terminates at the rooftop.
Negative Draft
The negative draft in a conventional vent installation must be within the range of 0.02 to 0.08 inches w.c. to ensure proper operation. Make all draft readings while the pool heater is in stable operation (approximately 2 to 5 minutes).
Commercial Pool Heaters
14
Connect the flue vent directly to the flue outlet opening on the top of the pool heater. No additional draft diverter or barometric damper is needed on single unit installations with a dedicated stack and a negative draft within the specified range of 0.02 to 0.08 inches w.c. If the draft in a dedicated stack for a single pool heater installation exceeds the maximum specified draft, you must install a barometric damper to control draft. Multiple pool heater installations with combined venting or common venting with other Category I negative draft appliances require each pool heater to have a barometric damper installed to regulate draft within the proper range.
Do Not connect vent connectors serving appliances vented by natural draft (negative draft) to any portion of a mechanical draft system operating under positive pressure. Connecting to a positive pressure stack may cause flue products to be discharged into the living space causing serious health injury.
Flue Outlet Piping
With this venting option, you must use Type-B doublewall (or equivalent) vent materials. Vent materials must be listed by a nationally-recognized test agency for use as vent materials. Make the connections from the pool heater vent to the outside stack as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for doublewall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
Provide adequate clearance to combustibles for the vent connector and firestop.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings, and floors. Locate the pool heater as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° elbows, reductions and restrictions.
No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.02 to 0.08 inches w.c.
Common Venting Systems
You can combine the flue with the vent from any other negative draft, Category I appliance. Using common venting for multiple negative draft appliances requires you to install a barometric damper with each pool heater. This will regulate draft within the proper range. You must size the common vent and connectors from multiple pool heaters per the venting tables for Type-B doublewall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA-B149 Installation Code.
Common venting systems may be too large when an existing pool heater is removed.
At the time of removal of an existing pool heater, the following steps shall be followed with each pool heater remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting system are not in operation.
1. Seal any unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Make sure there is no blockage or restriction, leakage, corrosion and other unsafe conditions.
3. If possible, close all building doors and windows. Close all doors between the space in which the appliances remaining connected to the common venting system are located and other building spaces.
4. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
5. Close fireplace dampers.
6. Place in operation the unit being inspected. Follow the lighting instructions. Adjust thermostat so pool heater will operate continuously.
7. Test for spillage of flue gases at the draft hood/relief openings of all appliances connected to the venting system after five minutes of main burner operation.
8. After making sure that each appliance remaining connected to the common venting system properly vents when tested as above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions of use.
9. Correct any improper operation of the common venting system so that the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any portion of the common venting system, resize to approach the minimum size as determined using the appropriate tables of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment.
Masonry Chimney Installations
A masonry chimney must be properly sized for the installation of a high efficiency gas-fired pool heater. Venting of a high efficiency pool heater into a cold or oversized masonry chimney can result in operational and safety problems. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting
Installation and Service Manual
15
IINNSSTTAALLLLAATTIIOONN
Continued
problems. The temperature of the flue products from a high efficiency pool heater may not be able to sufficiently heat the masonry structure of the chimney to generate proper draft. This will result in condensing of flue products, damage to the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space. Carefully inspect all chimney systems before installation.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue products. A clay-tile-lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined with a properly-sized and approved chimney liner system. An unlined masonry chimney must not be used to vent flue products from this high­efficiency pool heater. An unlined chimney must be relined with an approved chimney liner system when a new pool heater is being attached to it. Metallic liner systems (Type-B doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Vertical Vent Termination Clearances and Location
Follow all vertical venting termination information for clearances and location under Vertical Vent Termination Clearances and Location, page 10.
2. Vertical DirectAire™ Venting
IMPORTANT: Before installing a venting system, follow all venting clearances and requirements found in the Venting, General Information section, page 10.
The Vertical DirectAire™ vent system is the same as the Conventional Negative Draft vent system, except it pulls combustion air from the outdoors through a sidewall or vertical air inlet. Follow all requirements in Conventional Negative Draft Venting, page 14.
The Vertical DirectAire™ vent system requires you to install two vent pipes directly to the pool heater; one vertical pipe with a rooftop termination for the flue products and one pipe for combustion air. For this venting option, you must purchase the DV box adapter. The DV box attaches to the air inlet of the pool heater. The pipe for combustion air attaches to the DV box.
You can terminate the combustion air pipe either horizontally with a sidewall air inlet or vertically with a rooftop air inlet. The installed length of air inlet pipe from the pool heater to the outside air inlet cap must not exceed 50 equivalent feet (15.2m).
Figure 18 – Vertical DirectAire Installation with Sidewall Combustion Air Inlet
Figure 19 – Air Inlet Cap for Sidewall Termination
Commercial Pool Heaters
16
Figure 20 – Vertical DirectAire Installation with Rooftop Combustion Air Inlet
Vent Kits
WARNING: Only use a sidewall air inlet cap
supplied by the appliance manufacturer or a rooftop air inlet cap supplied by the vent manufacturer. Using any other air inlet cap for single-unit installations or using a common air inlet cap for multiple units with insufficient free area and/or protections from wind and weather may result in operational problems and the spillage of flue products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
For single pool heater installations with sidewall air inlet, (see Figure 18) you must order the sidewall air inlet kit. The part number for each SVK kit is listed by input size in TABLE–D.
For single pool heater installations with rooftop air inlet (see Figure 20), you must order the rooftop air inlet kit The part number for each VDK kit is listed by input size in TABLE-D. Purchase the flue pipe, rooftop flue termination, and air inlet pipe locally.
There is no vent kit for combined air supply systems for multiple pool heaters. Make sure the air inlet cap is properly sized. You must purchase this cap locally.
Venting of Flue Products
For venting flue products vertically to the outdoors, follow all requirements in the installation instructions for conventional venting in this manual. Follow all clearance requirements in Vertical Vent Termination Clearances and Location, page 10.
A barometric damper is not required in the flue on Vertical DirectAire™ installations if the draft is within the negative
0.04 to 0.08 inches w.c. required for proper operation. If the
draft exceeds this range, install a barometric damper.
T–C
*
The SVK kits include a DV box adapter and sidewall air inlet cap. The VDK kits include a DV box adapter and a rooftop air inlet cap. See note on page 12 concerning DV box adapter.
3. Sidewall Venting
IMPORTANT: Before installing a venting system, follow all venting clearances and requirements found in the Venting, General Information section, page 10.
This option uses a powered vent assembly which pulls the flue products out of the stack. This fan generates a negative draft at the pool heater. Combustion air is drawn from the mechanical room (see Combustion and Ventilation Air, page 7).
Figure 21 – Sidewall Venting Installation with an Induced Draft Fan and Sidewall Vent Cap
Installation and Service Manual
17
Input Horizontal Vertical
Btu/hr Kit* Kit*
500,000 SVK3047 VDK3026
650,000 SVK3048 VDK3027
750,000 SVK3048 VDK3027
990,000 SVK3040 VDK3023
1,260,000 SVK3041 VDK3024
1,440,000 SVK3041 VDK3024
1,800,000 SVK3041 VDK3024
2,070,000 SVK3041 VDK3024
TABLE-D
DirectAire™ Kits
IINNSSTTAALLLLAATTIIOONN
Continued
Sidewall Fan
The sidewall fan can be mounted on the inside/outside (depending upon model) with a sidewall vent hood installed on the exterior wall. The sidewall fan and accessories are included in a venting kit provided by the appliance manufacturer. See TABLE–E for kit numbers.
The venting kit includes the sidewall fan, vent hood, tapered vent adapter, barometric damper, proving switch and all necessary relays to interlock with the heaters control system. The tapered vent adapter reduces the vent size at the inlet to the fan. There should be no reduction in vent diameter from the pool heater’s flue outlet to the sidewall fan. The barometric damper must be installed on the flue and adjusted to supply a negative draft within the range of 0.04 to 0.08 inches w.c. while the pool heater is operating.
Flue Outlet Piping
With this venting option, you must use Type-B doublewall (or equivalent) vent materials. Vent materials must be listed by a nationally-recognized test agency for use as vent materials. Make the connections from the pool heater vent to the sidewall fan/cap as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for doublewall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls.
The maximum installed length of sidewall vent pipe with
an induced draft fan must not exceed 100 feet (30.5m) on the 500,000 - 2,070,000 Btu/hr models. Note: Models 990,000 - 2,070,000 are not approved for sidewall venting without a fan. The maximum installed length of sidewall vent pipe without an induced draft fan must not exceed 50 feet (15.2m) on the 500,000 - 750,000 Btu/hr models. Subtract 5 feet (1.5m) for each 90° elbow. Subtract 2.5 feet (0.7m) for each 45° elbow.
Sidewall Venting Termination
The sidewall vent cap must be installed on an exterior sidewall. The sidewall fan/powered sidewall vent cap and accessories are included in a venting kit which is furnished by the pool heater manufacturer in accordance with CSA International requirements. This venting kit includes the powered sidewall fan/cap, proving switch and all necessary relays to interlock with the pool heater’s control system.
The sidewall fan/powered vent cap must be interlocked with the pool heater’s control system to start the fan on a call for heat and prove fan operation before the pool heater fires. Plug­in and terminal strip connections are provided on the pool heater for easy connection of the factory supplied vent kit and control package for the sidewall vent fan.
Sidewall Venting Without Fan
For 500,000 - 750,000 Btu/hr models approved for sidewall venting without an external power vent fan, you must install specific vent kits and venting materials. The following is a detailed explanation of Sidewall Venting Without an External Fan installation requirements.
Flue Outlet Piping
Venting Guidelines
If using this venting option, a sealed AL29-4C venting system for flue products is required on all models of this pool heater. This venting system operates with a positive pressure in the vent. The internal combustion air blowers generate this positive pressure which operates the combustion process and also exhausts the flue products from the building.
This vent system has specific vent material and installation requirements. Only use listed sealed AL29-4C vent system materials. Follow all installation requirements. See TABLE–B, page 11 for proper pipe size for your pool heater. A list of sealed AL29-4C flue pipe manufacturers is located on page 22.
Seal all vent joints and seams gas-tight.
Drain Tee Installation
A drain tee must be installed in the vent pipe to collect and dispose of any condensate that may occur in the vent system. The drain tee must be installed as the first fitting after the horizontal ell on the top of the unit (see Figures 22A and 22B). Plastic drain tubing, sized per the vent manufacturer’s instructions, shall be provided as a drain line from the tee. The drain tubing must have a trap provided by a 3" (7.6cm) diameter circular trap loop in the drain tubing. Prime the trap loop by pouring a small quantity of water into the drain hose before assembly to the vent. Secure the trap loop in position with nylon wire ties. Use caution not to collapse or restrict the condensate drain line with the nylon wire ties. The condensate drain must be routed to a suitable drain for disposal of condensate that may occur in the direct vent system. Refer to the condensate drain installation instructions as supplied by the manufacturer of the vent material.
Commercial Pool Heaters
18
Loading...
+ 42 hidden pages