Lochinvar EFFICIENCY PLUS Designer's Manual

DESIGNER’S GUIDE EFFICIENCY+
®
BOILER
150,000 – 300,000 BTU/HR
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
The designer’s guide you are now holding has been designed to make it more convenient for you to select the perfect Lochinvar boiler for your projects and provide correct specifications for your teams.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope our manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built water heaters and boilers.
Sincerely,
Lochinvar Corporation
Lochinvar Corporation • 615-889-8900 / Fax: 615-547-1000
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 1
Air Removal . . . . . . . . . . . . . . . . . . . . . .18
Boiler Operating Temperature Control . . . .19
Clearances . . . . . . . . . . . . . . . . . . . . . . . .3
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .3
Connection To Terminal Strip . . . . . . . . . .19
Contaminants . . . . . . . . . . . . . . . . . . . . . .5
Electrical Requirements (North America) . . 19
Gas Supply . . . . . . . . . . . . . . . . . . . . . .14
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low Water Temperature Systems . . . . . . . .17
Outdoor Installation . . . . . . . . . . . . . . . . .13
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .3
Primary/Secondary Piping . . . . . . . . . . . .15
Relief Valve Piping . . . . . . . . . . . . . . . . . .16
Remote Temperature Control . . . . . . . . . . .19
Special Design Applications . . . . . . . . . . .18
Three-Way Valves . . . . . . . . . . . . . . . . . .16
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Venting Options . . . . . . . . . . . . . . . . . . . .7
Water Flow Requirements . . . . . . . . . . . .15
Water Velocity Control . . . . . . . . . . . . . . .15
Figures & Tables Index
FIG. 1 Boiler Equipment & Control
Orientation . . . . . . . . . . . . . . . .3
FIG. 2-5 Combustion & Ventilation Air . . .4 FIG. 6 Barometric Damper
Installation . . . . . . . . . . . . . . . . .8
FIG. 7 Multiple Unit Barometric
Damper Installation . . . . . . . . . .8
FIG. 8 E+ Vent With
Sidewall Air Inlet . . . . . . . . . . . .9
FIG. 9 E+ Vent With
Vertical Air Inlet . . . . . . . . . . . .10
FIG. 10 Horizontal Direct Vent . . . . . . .11
FIG. 11 Horizontal Direct Vent Cap . . . .11
FIG. 12 Multiple Sidewall Vent Caps . . .12
FIG. 13 Vertical Direct Vent . . . . . . . . . .12
FIG. 14 Outdoor Venting . . . . . . . . . . .13
FIG. 15 Primary/Secondary
System Piping . . . . . . . . . . . . .16
FIG. 16 Low Temperature Bypass
System Piping . . . . . . . . . . . . .17
FIG. 17 Heating/Chilled
Water System . . . . . . . . . . . . .18
TABLE A. Clearances From
Combustible Construction . . . . . .3
TABLE B. Conventional Venting,
Vent Flue Size . . . . . . . . . . . . . .7
TABLE C. E+ Vent Sidewall
Air Kit Part Numbers . . . . . . . . .9
TABLE D. E+ Vent Horizontal
Air Kit Part Numbers . . . . . . . .11
TABLE E. Vertical Direct Vent Flue &
Air Inlet Sizes . . . . . . . . . . . . .13
TABLE F. Outdoor Vent Kit . . . . . . . . . . .13
TABLE G. Gas Supply Pipe Sizing . . . . . .14
TABLE H. Inlet Gas Pressure . . . . . . . . . .14
TABLE I. Minimum & Maximum
Boiler Flow Rates . . . . . . . . . . .15
TABLE J. Water Flow Requirements . . . . .15
TABLE K. Heat Exchanger Head-loss . . . .16
TABLE L. Amp Draw . . . . . . . . . . . . . . .19
Appendix A: Boiler Piping Diagrams
Primary/Secondary Boiler . . . . . . . . . . . .A1
Multiple Unit - Primary/Secondary . . . . . .A2
Low Temperature Bypass Piping . . . . . . . .A3
Table of Contents
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These must be carefully followed in all cases. Authorities having jurisdiction must be consulted before installations are made. In the absence of such requirements, the installation must conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No.(CSD-1). All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where
required by the authority having jurisdiction, the installation must comply with the
Canadian Gas Association Code, CAN/CGA-B149.1 and/or B149.2
and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
Under no circumstances is the
manufacturer to be held responsible for
water damage in connection with this
unit or any of its components.
2 Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
L ochinv ar
Water Velocity
(
See Page 15 for minimum and
maximum flow rates.)
Piping Requirements and
Specialties
(
See Page 15 for piping
application requirements.)
System Water Temperature
(
See Page 17 for piping and
design recommendations.)
System and Boiler Control
(See Page 19 for boiler
operating and temperature
control.)
Air Elimination and
Expansion Tank Placement
(
See Page 18 for air removal
information.)
In designing
a hot water heating system,
pay special attention to:
1.
The indoor unit must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.)
Units located in a residential garage must be installed so that all burners and burner ignition devices have a minimum clearance of 18” (46cm) above the floor. The unit must be located or protected so that it is not subject to physical damage by a moving vehicle.
The appliance must be installed on a level floor. A combustible wood floor may be used without additional bases or special floor buildup. Maintain required clearances from combustible surfaces.
The appliance must not be installed on carpet or other combustible material other than wood flooring.
SPECIAL LOCATION: OUTDOOR USE
Efficiency+ Models are approved for outdoor installations. Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See Outdoor Installation, in the venting section on page 13.
COMBUSTION AND VENTILATION
Provisions for combustion and ventilation air must be in accordance with Section
5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or in Canada, the latest edition of CGA Standard B149
2.
3.
4.
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 3
5.
(TABLE A)
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
RIGHT SIDE 1”
REAR 1”
LEFT SIDE 6” (24” suggested for service)
FRONT 3” (24” suggested for service)
Suitable for closet installation
TOP 3”
*Allow sufficient space for servicing pipe connections, pump
and other auxiliary equipment, as well as the appliance.
FLUE PRODUCTS
VENT
GAS
CONNECTION
SYSTEM RETURN
BURNER
INSPECTION
PORT
SYSTEM SUPPLY
BACK
AIR INLET
TERMINAL
STRIP
(INSIDE)
120V
ELECTRICAL
CONNECTION
DRAIN
LEFT SIDE
FRONT
EB150-300
(FIG. 1) BOILER EQUIPMENT &
CONTROL ORIENTATION
4 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of
the local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation, when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two permanent openings: A. Combustion air opening with a
minimum free area of one square inch per 4000 Btu/hr input. This opening must be located within 12(30 cm) of the bottom of the enclosure. B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu/hr input. This opening must be located within 12(30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr.
If air is taken from another interior space, each of the two openings
specified above should have a net free area of one square inch for each 1000 Btu/hr of input, but not less than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening
must be sized based on a minimum free area of one square inch per 3000 Btu/hr. This opening must be located within 12 (30 cm) of the top of the enclosure.
L ochinv ar
(FIG. 4) COMBUSTION AIR FROM INTERIOR SPACE
(FIG. 3) COMBUSTION AIR THROUGH DUCTWORK
2.
3.
4.
(FIG. 5) COMBUSTION AIR FROM
OUTSIDE SINGLE OPENING
(FIG. 2) COMBUSTION AIR DIRECT FROM OUTSIDE
1.
EXAMPLE OF
SIZING FOR
COMBUSTION
& VENTILATION
AIR OPENINGS
(BOILER WITH
300,000 BTU/HR
INPUT):
When combustion and ventilated air is taken from directly outside the building (FIG. 2), divide the total BTU’s by 4,000. This yields 75 sq.in. of “Free Area” without restriction. 300,000 ÷ 4,000 = 75 sq.in. Since the air opening is 50% closed due to screens and louvers, the total opening MUST be multiplied by 2. 75 sq.in. x 2 = 150 sq.in. This project requires one Ventilation Air Opening with net “Area” of 75 square inches with louver dimensions of 12” x 15”= 168 sq.in. and one Combustion Air Opening with net “Area” of 75 square inches with louver dimensions of 12” x 15”= 168 sq in.
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 5
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the boiler.
Burning chemical fumes results in the formation of corrosive acids which attack the boiler and cause improper combustion and premature failure of the boiler and vent.
These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment”, of the latest
edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local
building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly, using the proper vent table.
The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed Type “B” double wall vent (or equivalent) for conventional vent applications.
When utilizing direct vent capabilities connections must be made with AL29-4C stainless steel (or equivalent) vent material.
Material should be sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel
Gas Code.
The vent materials and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the manufacturer’s listing.
The vent connector and firestop shall provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in the existing building must be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code,
ANSI Z223.1.
CAUTION!
EXHAUST FANS:
Any fan or equipment
which exhausts air from
the equipment room may
deplete the combustion
air supply and/or cause
a down draft in the
venting system. If a fan
is used to supply
combustion air to
the equipment room, it
must be sized to make
sure that it does not
cause drafts which could
lead to nuisance
operational problems
with the boiler.
6 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
The efficiency of this appliance allows its products of combustion to be vented through a smaller vent pipe when compared to units of the same Btu/hr capacity. For this reason, resizing common venting systems is recommended for proper operation.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables (FAN column) in the National Fuel Gas Code.
Failure to resize a common venting system could lead to the formation of condensate and premature deterioration of the vent material.
Flue gas condensate can freeze on exterior walls or on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition. Some discoloration to exterior building surfaces can be expected. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
Vent connectors serving appliances vented by natural draft must not be connected to any portion of a mechanical draft system operating under positive pressure.
Connection to a positive pressure stack may cause flue products to be discharged into the living space causing serious health injury.
Locate units as close as possible to a chimney or gas vent.
Vent Terminations
When locating the vent cap, consider the effects of snow, leaf dropping, etc., to ensure that no blockage occurs.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows that open and building openings must comply with the latest edition of the National Fuel Gas
Code, ANSI Z223.1.
The vent terminal must be vertical and exhaust outside the building at least 2 feet (0.6m) above the highest point of the roof within a 10 foot (3.0m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.9m) above the point of exit in the rooftop.
A vertical termination less than 10 feet (3.0m) from a parapet wall shall be a minimum of 2 feet (0.6m) higher than the parapet wall.
The vent cap shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m). The vent shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from or 1 foot (0.30m) above any door, window, or gravity air inlet to the building.
Do not terminate the vent in a window well, stairwell, alcove, courtyard, or other recessed area. The vent cannot terminate below grade.
L ochinv ar
IMPORTANT!
The vent cap should have a minimum clearance of 4 feet horizontally from electric meters, gas meters, regulators, air inlets and air relief equipment. Additionally, the vent cap should never be located above or below these items, unless a 4 foot horizontal distance is maintained.
NOTE:
The weight of the
venting system MUST
NOT rest on the boiler.
It should be properly
supported.
WARNING
Vent connectors serving
gas appliances, which
operate under a
negative vent pressure,
shall not be connected
into any portion of
mechanical draft
systems operating under
positive vent pressure.
Masonry Chimney
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems.
Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. For this reason, exterior masonry chimneys are not generally recommended to vent high efficiency gas appliances.
An interior masonry chimney, which is not exposed to the outdoors below the roofline, may be used to vent high efficiency gas appliances based on the results of careful inspection, proper sizing and local code approval. If there is any doubt about the sizing or condition of a masonry chimney, it should be relined with a properly sized and approved chimney liner system.
An interior masonry chimney should be carefully inspected to determine its suitability for the venting of flue products.
A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breeching or clean out.
If there is any doubt about the condition of a masonry chimney, it should be relined.
Metallic liner systems (Type “B” double-wall, flexible, or rigid metallic liners) are recommended to line or reline an existing masonry chimney. Consult with local code officials to determine code requirements or the advisability of using a lined masonry chimney or relining of a masonry chimney.
VENTING OPTIONS
Conventional Venting - Negative Draft
Size vent material according to the “FAN” column of vent sizing tables in the latest edition of the National Fuel Gas Code. “FAN” applies to Category I fan assisted combustion appliances with natural draft. Utilize Category I type “B” vent material for all conventional venting applications.
A bell increaser is provided and installed directly on the boiler vent outlet. The bell increases the boiler vent size by 1 inch (25.4mm) in diameter. The vent connection is made directly to the bell increaser on the top of the unit. No additional draft diverter or barometric damper is required.
(TABLE B)
CONVENTIONAL VENTING, VENT CONNECTION SIZE
CONVENTIONAL
MODEL VENT FLUE SIZE
EB150 5
EB200 5
EB250 6
EB300 6”
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 7
Loading...
+ 19 hidden pages