Lochinvar EFFICIENCY PLUS Designer's Manual

Page 1
DESIGNER’S GUIDE EFFICIENCY+
®
BOILER
150,000 – 300,000 BTU/HR
Page 2
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
The designer’s guide you are now holding has been designed to make it more convenient for you to select the perfect Lochinvar boiler for your projects and provide correct specifications for your teams.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope our manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built water heaters and boilers.
Sincerely,
Lochinvar Corporation
Lochinvar Corporation • 615-889-8900 / Fax: 615-547-1000
Page 3
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 1
Air Removal . . . . . . . . . . . . . . . . . . . . . .18
Boiler Operating Temperature Control . . . .19
Clearances . . . . . . . . . . . . . . . . . . . . . . . .3
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .3
Connection To Terminal Strip . . . . . . . . . .19
Contaminants . . . . . . . . . . . . . . . . . . . . . .5
Electrical Requirements (North America) . . 19
Gas Supply . . . . . . . . . . . . . . . . . . . . . .14
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low Water Temperature Systems . . . . . . . .17
Outdoor Installation . . . . . . . . . . . . . . . . .13
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .3
Primary/Secondary Piping . . . . . . . . . . . .15
Relief Valve Piping . . . . . . . . . . . . . . . . . .16
Remote Temperature Control . . . . . . . . . . .19
Special Design Applications . . . . . . . . . . .18
Three-Way Valves . . . . . . . . . . . . . . . . . .16
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Venting Options . . . . . . . . . . . . . . . . . . . .7
Water Flow Requirements . . . . . . . . . . . .15
Water Velocity Control . . . . . . . . . . . . . . .15
Figures & Tables Index
FIG. 1 Boiler Equipment & Control
Orientation . . . . . . . . . . . . . . . .3
FIG. 2-5 Combustion & Ventilation Air . . .4 FIG. 6 Barometric Damper
Installation . . . . . . . . . . . . . . . . .8
FIG. 7 Multiple Unit Barometric
Damper Installation . . . . . . . . . .8
FIG. 8 E+ Vent With
Sidewall Air Inlet . . . . . . . . . . . .9
FIG. 9 E+ Vent With
Vertical Air Inlet . . . . . . . . . . . .10
FIG. 10 Horizontal Direct Vent . . . . . . .11
FIG. 11 Horizontal Direct Vent Cap . . . .11
FIG. 12 Multiple Sidewall Vent Caps . . .12
FIG. 13 Vertical Direct Vent . . . . . . . . . .12
FIG. 14 Outdoor Venting . . . . . . . . . . .13
FIG. 15 Primary/Secondary
System Piping . . . . . . . . . . . . .16
FIG. 16 Low Temperature Bypass
System Piping . . . . . . . . . . . . .17
FIG. 17 Heating/Chilled
Water System . . . . . . . . . . . . .18
TABLE A. Clearances From
Combustible Construction . . . . . .3
TABLE B. Conventional Venting,
Vent Flue Size . . . . . . . . . . . . . .7
TABLE C. E+ Vent Sidewall
Air Kit Part Numbers . . . . . . . . .9
TABLE D. E+ Vent Horizontal
Air Kit Part Numbers . . . . . . . .11
TABLE E. Vertical Direct Vent Flue &
Air Inlet Sizes . . . . . . . . . . . . .13
TABLE F. Outdoor Vent Kit . . . . . . . . . . .13
TABLE G. Gas Supply Pipe Sizing . . . . . .14
TABLE H. Inlet Gas Pressure . . . . . . . . . .14
TABLE I. Minimum & Maximum
Boiler Flow Rates . . . . . . . . . . .15
TABLE J. Water Flow Requirements . . . . .15
TABLE K. Heat Exchanger Head-loss . . . .16
TABLE L. Amp Draw . . . . . . . . . . . . . . .19
Appendix A: Boiler Piping Diagrams
Primary/Secondary Boiler . . . . . . . . . . . .A1
Multiple Unit - Primary/Secondary . . . . . .A2
Low Temperature Bypass Piping . . . . . . . .A3
Table of Contents
Page 4
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These must be carefully followed in all cases. Authorities having jurisdiction must be consulted before installations are made. In the absence of such requirements, the installation must conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No.(CSD-1). All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where
required by the authority having jurisdiction, the installation must comply with the
Canadian Gas Association Code, CAN/CGA-B149.1 and/or B149.2
and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
Under no circumstances is the
manufacturer to be held responsible for
water damage in connection with this
unit or any of its components.
2 Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
L ochinv ar
Water Velocity
(
See Page 15 for minimum and
maximum flow rates.)
Piping Requirements and
Specialties
(
See Page 15 for piping
application requirements.)
System Water Temperature
(
See Page 17 for piping and
design recommendations.)
System and Boiler Control
(See Page 19 for boiler
operating and temperature
control.)
Air Elimination and
Expansion Tank Placement
(
See Page 18 for air removal
information.)
In designing
a hot water heating system,
pay special attention to:
1.
Page 5
The indoor unit must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.)
Units located in a residential garage must be installed so that all burners and burner ignition devices have a minimum clearance of 18” (46cm) above the floor. The unit must be located or protected so that it is not subject to physical damage by a moving vehicle.
The appliance must be installed on a level floor. A combustible wood floor may be used without additional bases or special floor buildup. Maintain required clearances from combustible surfaces.
The appliance must not be installed on carpet or other combustible material other than wood flooring.
SPECIAL LOCATION: OUTDOOR USE
Efficiency+ Models are approved for outdoor installations. Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See Outdoor Installation, in the venting section on page 13.
COMBUSTION AND VENTILATION
Provisions for combustion and ventilation air must be in accordance with Section
5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or in Canada, the latest edition of CGA Standard B149
2.
3.
4.
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 3
5.
(TABLE A)
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
RIGHT SIDE 1”
REAR 1”
LEFT SIDE 6” (24” suggested for service)
FRONT 3” (24” suggested for service)
Suitable for closet installation
TOP 3”
*Allow sufficient space for servicing pipe connections, pump
and other auxiliary equipment, as well as the appliance.
FLUE PRODUCTS
VENT
GAS
CONNECTION
SYSTEM RETURN
BURNER
INSPECTION
PORT
SYSTEM SUPPLY
BACK
AIR INLET
TERMINAL
STRIP
(INSIDE)
120V
ELECTRICAL
CONNECTION
DRAIN
LEFT SIDE
FRONT
EB150-300
(FIG. 1) BOILER EQUIPMENT &
CONTROL ORIENTATION
Page 6
4 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of
the local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation, when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two permanent openings: A. Combustion air opening with a
minimum free area of one square inch per 4000 Btu/hr input. This opening must be located within 12(30 cm) of the bottom of the enclosure. B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu/hr input. This opening must be located within 12(30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr.
If air is taken from another interior space, each of the two openings
specified above should have a net free area of one square inch for each 1000 Btu/hr of input, but not less than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening
must be sized based on a minimum free area of one square inch per 3000 Btu/hr. This opening must be located within 12 (30 cm) of the top of the enclosure.
L ochinv ar
(FIG. 4) COMBUSTION AIR FROM INTERIOR SPACE
(FIG. 3) COMBUSTION AIR THROUGH DUCTWORK
2.
3.
4.
(FIG. 5) COMBUSTION AIR FROM
OUTSIDE SINGLE OPENING
(FIG. 2) COMBUSTION AIR DIRECT FROM OUTSIDE
1.
EXAMPLE OF
SIZING FOR
COMBUSTION
& VENTILATION
AIR OPENINGS
(BOILER WITH
300,000 BTU/HR
INPUT):
When combustion and ventilated air is taken from directly outside the building (FIG. 2), divide the total BTU’s by 4,000. This yields 75 sq.in. of “Free Area” without restriction. 300,000 ÷ 4,000 = 75 sq.in. Since the air opening is 50% closed due to screens and louvers, the total opening MUST be multiplied by 2. 75 sq.in. x 2 = 150 sq.in. This project requires one Ventilation Air Opening with net “Area” of 75 square inches with louver dimensions of 12” x 15”= 168 sq.in. and one Combustion Air Opening with net “Area” of 75 square inches with louver dimensions of 12” x 15”= 168 sq in.
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
Page 7
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 5
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the boiler.
Burning chemical fumes results in the formation of corrosive acids which attack the boiler and cause improper combustion and premature failure of the boiler and vent.
These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment”, of the latest
edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local
building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly, using the proper vent table.
The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed Type “B” double wall vent (or equivalent) for conventional vent applications.
When utilizing direct vent capabilities connections must be made with AL29-4C stainless steel (or equivalent) vent material.
Material should be sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel
Gas Code.
The vent materials and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the manufacturer’s listing.
The vent connector and firestop shall provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in the existing building must be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code,
ANSI Z223.1.
CAUTION!
EXHAUST FANS:
Any fan or equipment
which exhausts air from
the equipment room may
deplete the combustion
air supply and/or cause
a down draft in the
venting system. If a fan
is used to supply
combustion air to
the equipment room, it
must be sized to make
sure that it does not
cause drafts which could
lead to nuisance
operational problems
with the boiler.
Page 8
6 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
The efficiency of this appliance allows its products of combustion to be vented through a smaller vent pipe when compared to units of the same Btu/hr capacity. For this reason, resizing common venting systems is recommended for proper operation.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables (FAN column) in the National Fuel Gas Code.
Failure to resize a common venting system could lead to the formation of condensate and premature deterioration of the vent material.
Flue gas condensate can freeze on exterior walls or on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition. Some discoloration to exterior building surfaces can be expected. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
Vent connectors serving appliances vented by natural draft must not be connected to any portion of a mechanical draft system operating under positive pressure.
Connection to a positive pressure stack may cause flue products to be discharged into the living space causing serious health injury.
Locate units as close as possible to a chimney or gas vent.
Vent Terminations
When locating the vent cap, consider the effects of snow, leaf dropping, etc., to ensure that no blockage occurs.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows that open and building openings must comply with the latest edition of the National Fuel Gas
Code, ANSI Z223.1.
The vent terminal must be vertical and exhaust outside the building at least 2 feet (0.6m) above the highest point of the roof within a 10 foot (3.0m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.9m) above the point of exit in the rooftop.
A vertical termination less than 10 feet (3.0m) from a parapet wall shall be a minimum of 2 feet (0.6m) higher than the parapet wall.
The vent cap shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m). The vent shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from or 1 foot (0.30m) above any door, window, or gravity air inlet to the building.
Do not terminate the vent in a window well, stairwell, alcove, courtyard, or other recessed area. The vent cannot terminate below grade.
L ochinv ar
IMPORTANT!
The vent cap should have a minimum clearance of 4 feet horizontally from electric meters, gas meters, regulators, air inlets and air relief equipment. Additionally, the vent cap should never be located above or below these items, unless a 4 foot horizontal distance is maintained.
NOTE:
The weight of the
venting system MUST
NOT rest on the boiler.
It should be properly
supported.
WARNING
Vent connectors serving
gas appliances, which
operate under a
negative vent pressure,
shall not be connected
into any portion of
mechanical draft
systems operating under
positive vent pressure.
Page 9
Masonry Chimney
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems.
Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. For this reason, exterior masonry chimneys are not generally recommended to vent high efficiency gas appliances.
An interior masonry chimney, which is not exposed to the outdoors below the roofline, may be used to vent high efficiency gas appliances based on the results of careful inspection, proper sizing and local code approval. If there is any doubt about the sizing or condition of a masonry chimney, it should be relined with a properly sized and approved chimney liner system.
An interior masonry chimney should be carefully inspected to determine its suitability for the venting of flue products.
A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breeching or clean out.
If there is any doubt about the condition of a masonry chimney, it should be relined.
Metallic liner systems (Type “B” double-wall, flexible, or rigid metallic liners) are recommended to line or reline an existing masonry chimney. Consult with local code officials to determine code requirements or the advisability of using a lined masonry chimney or relining of a masonry chimney.
VENTING OPTIONS
Conventional Venting - Negative Draft
Size vent material according to the “FAN” column of vent sizing tables in the latest edition of the National Fuel Gas Code. “FAN” applies to Category I fan assisted combustion appliances with natural draft. Utilize Category I type “B” vent material for all conventional venting applications.
A bell increaser is provided and installed directly on the boiler vent outlet. The bell increases the boiler vent size by 1 inch (25.4mm) in diameter. The vent connection is made directly to the bell increaser on the top of the unit. No additional draft diverter or barometric damper is required.
(TABLE B)
CONVENTIONAL VENTING, VENT CONNECTION SIZE
CONVENTIONAL
MODEL VENT FLUE SIZE
EB150 5
EB200 5
EB250 6
EB300 6”
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 7
Page 10
8 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
When each unit is installed with an individual vent, and the negative draft is higher than the specified range (0.02 to 0.05 inches of water column), a barometric damper will be necessary.
Multiple unit installations with combined venting require barometric dampers to regulate draft at each unit. The negative draft must be within the range of 0.02 to
0.05 inches of water column to ensure proper operation.
All draft readings are made while the unit is in stable operation (approximately 2 to 5 minutes).
For this type of installation, it is best to use a draft control for each boiler located on the riser between the vent outlet and the breeching - Location “A”. (Figure 7)
When this riser is too short to permit the installation of a control, locate a separate control for each boiler on the main breeching as illustrated in Location “B”. (Figure 7)
If, because of general crowding or other reasons, neither of these locations are possible, use a single large control in the breeching between the boiler nearest the chimney and the chimney, as shown in Location “C”. (Figure 7)
Conventional Venting with Direct Combustion Air Intake (E+Vent)
This vent system uses two pipes, one vertical pipe with a roof top termination for the flue products and one pipe for combustion air. The combustion air pipe may terminate horizontally with a sidewall air inlet or vertically with a roof top air inlet. All instructions for “Conventional Venting ­Negative Draft” apply to “Conventional Venting with Direct Combustion Air”. The flue may be combined with the vent from any other negative draft, Category I appliances. Utilize Category I type “B” vent material for venting flue products.
L ochinv ar
WATER HEATER/BOILER
BAROMETRIC DAMPER ON SINGLE UNIT INSTALLATION
Lined Chimney
WATER HEATER/BOILER
BAROMETRIC DAMPER ON SINGLE UNIT INSTALLATION
(FIG. 6) BAROMETRIC DAMPER INSTALLATION
(FIG. 7) MULTIPLE UNIT BAROMETRIC
DAMPER INSTALLATION
NOTE:
An unlined masonry
chimney should not be
used to vent flue
products from this high
efficiency appliance.
Page 11
The sidewall or vertical roof top E+Vent
combustion air supply system has specific vent material and installation requirements.
The air inlet pipe connects directly to the boiler to supply combustion air. In most installations, the combustion air inlet pipe will be a dedicated system with one air inlet pipe per boiler. Multiple air inlets may be combined if the guidelines in “Combined Air Inlet Points” are followed. The air inlet pipe will be connected to a combustion air inlet cap as specified in this section. Combustion air supplied from outdoors should be free of contaminants. The air inlet pipe(s) must be sealed. Select air inlet pipe material from the following specified materials:
• PVC, CPVC or ABS (4, 5or 6I.D.).
• Dryer vent (not recommended for roof top air inlet)
• Galvanized steel vent pipe with joints and seams sealed.
• Type “B” double wall vent with joints and seams sealed.
The total equivalent length of the sidewall or
vertical roof top E+Vent combustion air inlet pipe
shall not exceed a maximum of 50 equivalent feet (15.2m) in length. Subtract 5 feet (1.5m) for each elbow in the air intake system.
Sidewall Air Inlet
The sidewall air inlet cap is supplied in the E+ Sidewall Vent Kit. Each kit includes a sidewall combustion air inlet cap to supply air to a single boiler and instructions for proper installation. The part number for each kit is listed by unit size.
Locate units as close as possible to the sidewall where the combustion air supply system will be installed.
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in
the latest edition of the National Fuel Gas Code
and instructions in this guide.
The combustion air inlet cap must be placed at least one foot (0.3m) above ground level and above normal snow levels.
NOTE:
The use of double wall
vent material for the
combustion air inlet pipe
is recommended in cold
climates to prevent the
accumulation of
condensation on the
pipe exterior.
(FIG. 8) E+ VENT WITH SIDEWALL AIR INLET
(TABLE C)
E+ VENT SIDEWALL AIR KIT PART NUMBERS
MODE CONVENTIONAL VENT AIR SIDEWALL NUMBER FLUE SIZE* INLET PIPE** E+ VENT KIT
EB150 5
4
SVK 3020
EB200 5
4
SVK 3020
EB250 6
5
SVK 3021
EB300 6
5
SVK 3021
*Vent size with 1” increaser installed for conventional negative
draft venting.
Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 9
(FIG. 9) E+ VENT WITH VERTICAL AIR INLET
Page 12
10 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
Vertical Air Inlet
The air inlet cap for the vertical roof top air inlet is assembled from components purchased locally. The air inlet cap consist of two 90° ells installed at the point of termination for the air inlet pipe.
The point of termination for the combustion air inlet cap must be at least 2 feet (0.6m) below the point of flue gas termination (vent cap) if it is located within 10 ft. (3.0m) of the flue outlet.
The termination ell on the air inlet must be located a minimum of 12(0.3m) above the roof or above normal levels of snow accumulation. It must not be placed closer than 10 feet (3.0m) from an inside corner of an L-shaped structure.
Incorrect location of the air inlet cap can allow the discharge of flue products to be drawn into the combustion process of the boiler. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products.
Combined Air Inlet Points
The air inlet pipes from multiple boilers can be combined into a single common connection, if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
The air inlet point for multiple boiler air inlets shall be provided with an exterior opening which has a free area equal to or greater
than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors.
The total length of the combined air inlet pipe must not exceed a maximum of 50 equivalent feet(15.2m). Deduct the restriction in area provided by any screens, grills or louvers installed in the common air inlet point. Screens, grills, or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials used. The air inlet cap for the combined air supply from multiple boilers can be purchased or fabricated in the field.
Direct Venting
A direct vent boiler uses a two pipe system, one pipe for the flue products and one pipe for the combustion air supply.
The flue cannot be combined with any other
appliance vent or common vent from multiple boilers. The vent on a direct vent system will have a positive pressure in the flue, which requires all vent joints and seams to be sealed gas-tight. The flue from a direct vent system shall have a condensate drain with provisions to properly collect and dispose of any condensate that may occur in the venting system. Direct vent systems require Category IV vent material with AL29-4C approved stainless steel.
The air inlet pipe connects directly to the boiler to supply combustion air. The air inlet pipe must be sealed. Choose acceptable
L ochinv ar
EXAMPLE OF
COMBINED
AIR INLET
SIZING
Two 5” air inlet pipes
(19.6 in2area each) have
a total area of 39.2 in
2
requiring an 8” (50.3 in
2
area) common air inlet
pipe.
Page 13
combustion air pipe materials from those specified in this section. Approved material for air inlet pipes include: PVC, CPVC or ABS (3, 4, 5or 6I.D.), dryer vent, and galvanized steel vent pipe with joints and seams sealed.
The total equivalent length of the direct vent flue pipe or the air inlet pipe should not exceed a maximum of 50 equivalent feet (15.2m) in length for each pipe. Subtract 5 feet (1.5m) for each elbow in the vent pipe or air intake system.
Horizontal Direct Vent
Horizontal direct vent applications require a vent kit which will be supplied by Lochinvar to assure proper operation.
The part number for each kit is listed by unit size. Each kit includes a sidewall vent cap for flue products, a firestop, a combustion air inlet cap, and instructions for proper installation.
It is important to be careful in the placement of the horizontal direct vent caps. Combustion air supplied from outdoors should be free of contaminants.
To prevent recirculation of flue products into the combustion air inlet:
The combustion air inlet cap must not be installed above the flue outlet cap.
Maintain a minimum 3 foot (0.9m) radius clearance between the combustion air inlet cap and the flue outlet cap. Additional space may be required between caps where high winds may occur.
The combustion air inlet cap and vent cap for flue outlet must be located on the same sidewall and in the same pressure zone.
Do not place the combustion air inlet cap closer than 10 feet (3.0m) from an inside corner of an L-shaped structure.
Place the combustion air inlet cap at least one foot (0.3m) above ground level and above normal snow levels.
(FIG. 10) HORIZONTAL DIRECT VENT
(FIG. 11) HORIZONTAL DIRECT VENT CAP
(TABLE D)
HORIZONTAL DIRECT VENT KIT PART NUMBERS
MODEL FLUE AIR PART NUMBER PIPE SIZE INLET PIPE NUMBER
EB150 4” 4” HDK 3013
EB200 4” 4” HDK 3013
EB250 5” 5” HDK 3014
EB300 5” 5” HDK 3014
1.
NOTE:
The use of double wall
vent material for the
combustion air inlet
pipe is recommended in
cold climates to prevent
the accumulation of
condensation on the
pipe exterior.
2.
Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 11
3.
4.
5.
Page 14
Multiple Unit Applications (Horizontal Direct Vent)
The combustion air inlet caps for multiple unit installations must maintain the minimum 3 foot (0.9m) radius clearance below or horizontally from the closest flue outlet. Multiple flue outlet caps may be installed side by side, and multiple air inlet caps may be installed side by side, but the 3 foot (0.9m) radius minimum clearance between air inlet and flue outlet must be maintained.
All clearance and installation requirements in this section and the applicable portions of the general venting section must be maintained on multiple unit installations.
Vertical Direct Vent
Vertical direct vent applications do not require a vent kit to be supplied by Lochinvar. The vent cap and air inlet cap for vertical direct vent applications are fabricated or purchased in the field.
A vertical vent cap, as specified by the vent material manufacturer, is used to vent the flue products to the outdoors. The air inlet cap consists of two 90° ells installed at the point of termination for the air inlet pipe. The termination ell on the air inlet must be located a minimum of 12(15.2cm) above the roof or above normal levels of snow accumulation. The point of termination for the air inlet shall be 24(0.6m) lower than the point of flue gas termination, if it is located within 10 ft. (3.0m) of the flue outlet.
Incorrect installation and/or location of the air inlet cap can allow the discharge of flue products to be drawn into the combustion process on the boiler. This can result in incomplete combustion and potentially hazardous levels of carbon monoxide in the flue products.
L ochinv ar
12 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
(FIG. 13) VERTICAL DIRECT VENT
CAUTION!
Boilers which are shut
down or will not
operate may
experience freezing
due to convective air
flow in the air inlet
pipe connected to the
unit. Proper freeze
protection MUST be
provided.
(FIG. 12) MULTIPLE SIDEWALL VENT CAPS
AIR INLETS
AIR INLETS
3 feet
MIN.
3 feet
MIN.
FLUE OUTLETS
CAUTION!
Maintain a minimum 3 foot (0.9m) radius clearance between the combustion air inlet cap and the flue outlet cap.
(TABLE E) – VERTICAL DIRECT VENT,
FLUE AND AIR INLET SIZES.
MODEL DIRECT VENT AIR INLET
NUMBER FLUE SIZE PIPE
EB150 4” 4”
EB200 4” 4”
EB250 5” 5”
EB300 5” 5”
Page 15
Multiple Unit Applications (Vertical Direct Vent)
The combustion air inlet caps for multiple unit installations must maintain the minimum 2 foot (0.6m) clearance below the closest vertical flue outlet if within 10 feet (3.0m).
Multiple flue outlet caps may be installed side by side and multiple air inlet caps may be installed side by side, but the air inlet must always be at least 2 feet (0.6m) below the closest flue outlet if the outlet is within 10 feet (3.0m).
OUTDOOR INSTALLATION
Units are self venting and can be used outdoors when installed with the optional
Outdoor Vent Kit. This kit includes a one piece top cover which replaces the standard two piece cover, air inlet cap, exhaust cap, gas valve cover and junction box cover. The cap mounts directly to the top of the water heater and covers the flue outlet and combustion air inlet openings on the jacket. No additional vent piping is required. Maintain a minimum clearance of 3" (76mm) to combustible surfaces and a minimum of 3" (76 mm) clearance to the air inlet.
An outdoor unit should not be located so that high winds can deflect off of adjacent walls, buildings or shrubbery causing recirculation. Recirculation of flue products may cause operational problems, bad combustion or damage to controls. The unit should be located at least 3 feet (0.91m) from any wall or vertical surface to prevent adverse wind conditions from affecting performance. Multiple unit outdoor installations require 48" (1.22 m) clearance between each vent cap. The outdoor cap must be located 4 feet (1.22 m) below and 4 feet (1.22 m) horizontally from any window, door, walkway or gravity air intake.
The combustion air inlet of the outdoor cap must be located at least one foot (0.30 m) above grade and above normal snow levels. The water heater must be at least 10 feet (3.05 m) away from any forced air inlet and at least 3 feet (0.91 m) outside any overhang. Do not install in locations where rain from building runoff drains will spill onto the water heater. Lochinvar must furnish an outdoor vent kit in accordance with CSA international requirements. Each kit includes the flue outlet/combustion air inlet, gas valve cover, junction box cover and one piece unit top.
Freeze Protection- Outdoor Installation
A snow screen should be installed to prevent snow and ice accumulation around the appliance or its venting system. If for any reason the unit is to be shut off: (a.) Shut off water supply. (b.) Drain unit completely. (c.) Drain pump and piping. If freeze protection is not provided for the system, a low ambient temperature alarm or automatic drain system is recommended.
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 13
(FIG. 14) OUTDOOR VENTING
(TABLE F) –OUTDOOR VENT KITS
MODEL OUTDOOR
NUMBER VENT KIT
EB150 ODK3069 EB200 ODK3070 EB250 ODK3071 EB300 ODK3072
Page 16
14 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
GAS SUPPLY
Safe operation of unit requires properly sized gas supply piping (See TABLE G).
Gas pipe size may be larger than the heater connection.
An internal gas pressure regulator is required if upstream pressure exceeds 6 oz. (10.5" water column), an intermediate gas pressure regulator, of the lockup type,
must be installed.
Installation of a union is suggested for ease of service.
Install a manual main gas shutoff valve with test plug, outside of the appliance gas connection and before the gas valve, when local codes require.
A trap (drip leg) should be provided in the inlet of the gas connection to the unit.
High Altitude Applications
Atmospheric pressure decreases as the height above sea level increases. At any altitude above sea level, a cubic foot will contain less gas than a cubic foot at sea level. Thus, the
heating value of a cubic foot of fuel gas will decrease as height above sea level increases. Specific gravity of a gas with respect to sea level also decreases with altitude.
These changes in heating value and specific gravity tend to offset each other. However, as elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced in an appliance above 2000 feet. Ratings should be reduced at the rate of 4 percent for each 1000 feet above sea level.
WATER CONNECTIONS
Inlet and Outlet Water Connections
For ease of service, install unions on inlet and outlet of the boiler. The connection on the unit marked “Inlet” should be used for return water from the system. The connection on the header marked “Outlet” should be connected to the system supply. (See Boiler Piping diagrams, Appendix A).
L ochinv ar
NOTE:
Care should be
taken to measure
temperature rise
and maintain proper
water velocity in
the heat exchanger.
(TABLE H) – INLET GAS PRESSURE REQUIREMENTS
NATURAL GAS LPG
Max. Allowable 10.5” 13” (Inches-water column)
Min. Allowable 4.7” 8” (Inches-water column)
EXAMPLE OF
HIGH
ALTITUDE
APPLICATIONS
For example, if a unit’s
input is 200,000 Btu/hr
at sea level, the rated
input at 4000 feet of
elevation can be calculated
by derating input 4%
per 1000 feet above
sea level.
[Btu/hr Input]
[1.00 - (Elevation/ 1000’
x 0.04)] = Btu/hr Input
at specified elevation.
[200,000][1.00 -
(4000’/1000’ x 0.04)] =
Btu/hr Input 4000’
elevation.
[200,000][0.84] =
168,000 Btu/hr Input
at 4000’ elevation.
(TABLE G) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron
Pipe Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
3/4 369 256 205 174 155 141 128 121 113 106 95 86 79 74
1 697 477 384 328 292 267 246 256 210 200 179 164 149 138
1-1/4 1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
1-1/2 2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
2 4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
2-1/2 6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3 11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4 23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
1.
2.
3.
5.
4.
6.
Page 17
WATER VELOCITY CONTROL
IMPORTANT
To ensure proper velocity through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. (This
must be done on
initial installation and periodically rechecked). With the correct temperature rise across the heat exchanger (See TABLE J), you may be assured of the proper velocity in the tubes and long life and economical operation from the boiler.
WATER FLOW REQUIREMENTS AND SYSTEM PIPING
Lochinvar boilers are generally capable of operating within the design flow rates for the building heating system. To ensure the most efficient operation, a boiler needs adequate water flow. Pump sizing, pipe sizing, and piping
layout
must be taken into consideration for
proper system flow. (Table I) provides maximum and minimum
flow data for each model. (Table J) provides Gallons Per Minute and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. These two charts will provide assistance in system flow design.
Primary/Secondary Piping
Using a primary/secondary piping arrangement can solve many system flow complications.
This piping arrangement uses a dedicated pump to supply flow to the boiler. The pump is sized based on the required boiler flow rate, boiler head-loss and head-loss in the secondary system piping. A separate pump is used to provide the desired flow for the system.
Primary/Secondary piping allows the system and the boiler(s) to operate at their optimum flow rate. The system works best when the boiler(s) are supplied with pump control relays which are used to cycle the secondary pump(s). When piped correctly, the secondary pump helps to prevent flow through the boiler(s) when they are not firing. Use of primary/secondary system will eliminate the need for a system or boiler bypass. Figure 15 depicts one example of primary/secondary piping.
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 15
GPM
25.2
33.7
42.1
50.5
FT. HD
0.9
1.4
1.7
2.6
GPM
16.8
22.4
28
33.6
FT. HD
0.5
0.6
1.2
1.6
GPM
12.6
16.8
21
25.2
FT. HD
0.4
0.5
0.7
1.1
GPM
10.1
13.4
16.8
20.2
FT. HD
0.3
0.4
0.6
0.7
GPM
8.4
11.2
14
16.8
FT. HD
0.2
0.3
0.5
0.6
GPM
6.3
8.4
10.5
12.6
FT. HD
0.2
0.3
0.4
0.5
INPUT
150,000
200,000
250,000
300,000
OUTPUT
126,000
168,000
210,000
252,000
TEMPERATURE RISE 10°F ∆T 15°F ∆T 20°F ∆T 25°F ∆T 30°F ∆T 40°F ∆T
(TABLE J) – WATER FLOW REQUIREMENTS
(TABLE I) – MINIMUM & MAXIMUM
BOILER FLOW RATES
MODEL MINIMUM FLOW MAXIMUM FLOW NUMBER (GPM) (GPM)
EB 150 6 60
EB 200
8
60
EB 250 10 60
EB 300 12 60
*Min. flow based on 40°F temperature rise.
Page 18
16 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
L ochinv ar
Three Way Valves
The installation of a three-way valve in a hydronic heating application is not generally recommended, as most piping methods allow the three-way valve to vary flow through the boiler. This variable flow through the boiler is not recommended, as it alters heat transfer speed and places undue heat stresses on the heat exchanger surface. Additionally, low flow rates can result in overheating of the boiler water, which can cause short burner on cycles, system noise and in extreme cases, a knocking flash to steam. For these reasons, constant circulation is recommended to maintain proper operation while the boiler is firing.
Water Flow Switch
Due to the low water content (between 1 and 6 gallons) of the copper finned tube heat exchanger, a flow switch is available for use as a low water cutoff device on all models. The flow switch should be installed in the outlet piping of the boiler and wired into the ignition system. Per ASME CSD1 and in most localities, a flow switch is accepted as a low water cutoff for boilers requiring forced circulation. (See CSD1 CW-210, Part A) It is prudent to verify preference with the local code official.
A specially sealed flow switch and conduit are furnished for outdoor installations.
Low Water Cut-off
If this boiler is installed above radiation level, a low water cut-off device must be installed at the time of boiler installation (option available from factory).
Relief Valve Piping
This boiler is supplied with a pressure relief valve(s) sized in accordance with ASME Boiler
and Pressure Vessel Code, Section IV “Heating Boilers”.
Low Flow Systems
When the system flow rate is less than the minimum flow required for proper boiler operation, the Efficiency+ boiler should be installed with a primary/secondary piping system.
This will allow the installation of a secondary­circulating pump sized specifically to provide a higher flow rate through the boiler and the secondary loop piping to ensure proper operation. See “Primary/Secondary Piping” for installation and piping requirements.
IMPORTANT!
Operation of this boiler
on a low temperature
system requires special
piping to ensure correct
operation. Consult “Low
Water Temperature
System” section for
piping details.
(FIG. 15) PRIMARY/SECONDARY SYSTEM PIPING
HEATING SUPPLY
LOOP
*12” MAX
TO FLOOR
DRAIN
MAKE-UP WATER
LIT0476
HEATING RETURN LOOP
(TABLE K) – HEAT EXCHANGER
HEAD-LOSS CURVE
Page 19
High Flow Systems
When the flow rate of the system exceeds the maximum allowable flow rate through the boiler (Table I), boiler bypass piping should be installed.
The bypass will divert the required portion of the system flow to the boiler and bypass excess system flow. This will effectively reduce boiler flow to an acceptable rate and increase system flow. The bypass piping should be sized equal to the system piping. Figure 16 depicts the proper piping arrangement for the Boiler Bypass.
Low Water Temperature System
Any boiler system operating at a temperature of less than 140°F is considered a “low water temperature system” and must be piped with a low temperature bypass. There are a number of hydronic boiler applications that call for system water temperatures in the range of 60°F to 100°F. Typical applications are: Radiant heating systems; Water source heat pump systems; Greenhouse soil heating and irrigation systems; Process and manufacturing operations. These installations often incur problems resulting from boiler condensation, thermal stresses and poor overall system efficiency.
Copper tube boilers are particularly adaptable to these applications for several reasons:
A copper tube boiler is an instantaneous boiler, requiring virtually no heat-up time, and having no temperature “overshoot”. Result - High system efficiency.
The boiler’s unique construction prevents the transfer of heat exchanger thermal stresses to other boiler components, reducing wear and tear while increasing equipment life.
Its compact, simple design and low boiler mass permits a simple bypass arrangement which will allow the system to be operated at any temperature above 60°F (16°C).
A boiler operated with an inlet temperature of less than 140°F (60°C) must have a bypass to prevent problems with condensation.
A Low Temperature Bypass as shown in Figure 15 should be piped into the system at the time of installation. This piping is like a primary/ secondary boiler installation with a bypass in the secondary boiler piping. Inlet water temperatures below 140°F (60°C) can excessively cool the products of combustion resulting in condensation on the heat exchanger and in the flue. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to increase the boiler inlet temperature to at least 140°F (60°C). This will prevent the products of combustion from condensing in most installations. Size low temperature bypass piping equal to system piping, and use fully ported control valves.
1.
2.
3.
Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 17
(FIG. 16) LOW TEMPERATURE BYPASS SYSTEM PIPING
HEATING SUPPLY
LOOP
TO FLOOR
DRAIN
BYPASS
MAKE-UP WATER
HEATING RETURN LOOP
LIT0473
Page 20
SPECIAL DESIGN APPLICATIONS
Air Conditioning Re-Heat System
When used in connection with a refrigeration system, the boiler must be installed so the chilled medium is piped in parallel with the boiler and with appropriate valves to prevent the chilled medium from entering the boiler. The piping system of the hot water boiler (when connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation)
must
be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
The heating coil
must be vented at the high
point, and the hot water from the boiler
must
enter the coil at this point. Due to the fast heating capacity of the boiler, it is not necessary to provide a duct-stat to delay circulator operation. Also, omit thermal flow checks, as the boiler is cold when the heating thermostat is satisfied. This provides greater economy overall by maintaining standby heat.
AIR REMOVAL
An air separation device should be placed in the installation piping, on the suction side of the system pump, to eliminate trapped air in the system. Locate a system air vent at the highest point in the system. Additionally, a properly sized expansion tank may be required. Air charged, diaphragm type compression tanks are common. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper operation.
18 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
L ochinv ar
EXPANSION
TANK
LOW WATER
FLOW SWITCH
PUMP
B
A
C
IN
R
OUT
WATER SUPPLY
GAS
SUPPLY
DIAGRAM NOTES:
1. VALVES "D" AND "C" MAY BE MANUAL OR AUTOMATIC- TO SUIT.
2. PROVIDE DRAIN FOR RELIEF VALVE "R" TO SAFE PLACE.
3. CLOSE BOTH "A" AND "C" VALVES WHEN RUNNING CHILLER.
4. CLOSE BOTH "B" AND "D" VALVES WHEN RUNNING BOILER.
5. WATER SUPPLY VALVE REMAINS OPEN AT ALL TIMES.
D
E
HEATING &
COOLING
COIL
CHILLER
BOILER
(FIG. 17) HEATING/CHILLED WATER SYSTEM
Page 21
TEMPERATURE / PRESSURE GAUGE
This boiler is equipped with a dial type temperature/pressure gauge. This gauge is factory installed in the outlet side of the heat exchanger. The gauge has one scale for reading system pressure and a separate scale for water temperature in degrees Fahrenheit.
BOILER OPERATING TEMPERATURE CONTROL
In the absence of a remote temperature control, a dial operator controls the boiler operating temperature. The sensing element for the operator is placed in a bulb well, installed in the inlet side of the heat exchanger front header. Due to the location of the temperature sensor, the operator will generally require a lower temperature setpoint to achieve the desired discharge water temperature from the boiler. This sensing element location allows a boiler operating with a low to moderate flow rate to sustain longer burner “ON” cycles, based on high discharge water temperatures.
For example, a boiler operating with a 180°F discharge and a 20°F temperature rise would require approximately a 160°F to 165°F set point with the temperature sensor installed on the inlet side of the heat exchanger. The exact temperature set point is based on system requirements.
REMOTE TEMPERATURE CONTROL, CONNECTION TO TERMINAL STRIP
A remote temperature control may be connected to the boiler. The boiler is equipped with a terminal strip to allow easy connection. Connection to the terminal strip will allow the remote temperature control to make and break the 24 VAC boiler control circuit, turning the boiler on and off based on building and system demands.
ELECTRICAL REQUIREMENTS
(North America)
The appliance is wired for 120 volts. All wiring between the unit and field installed devices shall be made of type T wire [63°F (35°C) rise].
The pump must be wired to run continuously when unit is firing.
It is recommended that the boiler and pump be wired on separate circuits with properly sized breakers.
CAUTION!
For proper operation
the system should not
be operated at less
than 12 PSIG.
1.
2.
3.
(TABLE L) – AMP DRAW DATA
MODEL FAN CONTROLS APPRX. TOTAL
NUMBER AMPS @ 120 VAC
EB150-300 1.2 4.0 5.12
NOTE:
When the unit is
installed in Canada, it
must conform to the CAE
C22.1, Canadian
Electrical Code, Part 1
and/or local Electrical
Codes.
Lochinvar
DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 19
Page 22
20 Lochinvar DESIGNERS GUIDE EFFICIENCY + BOILER 615-889- 8900
EFFICIENCY+®BOILER
PIPING DIAGRAMS
Page 23
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 A1
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUT-OFF
UNION AIR SEPARATOR
LEGEND
PIPING DIAGRAM PRIMARY/SECONDARY BOILER PIPING
12” MAX*
HEATING RETURN LOOP
HEATING SUPPLY LOOP
*AS CLOSE AS PRACTICAL – 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
MAKE-UP WATER
TO FLOOR DRAIN
LIT0476
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 24
A2 Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE THREE WAY
VALVE
TEE ELBOW
EXPANSION
TANK
TANK FITTING SYSTEM PUMP FOUR WAY
UNION
UNION LOW WATER
CUT-OFF
AIR SEPARATOR
LEGEND
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
PIPING DIAGRAM MULTIPLE UNIT PRIMARY / SECONDARY PIPING
12” MAX*
FROM SYSTEM
RETURN
TO SYSTEM SUPPLY
MAKE-UP WATER
CAP EACH MANIFOLD
LIT0475
*AS CLOSE AS PRACTICAL– 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCEBETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
Page 25
Lochinvar DESIGNERS GUIDE EFFICIENCY+ BOILER 615-889-8900 A3
PIPING DIAGRAM LOW TEMPERATURE BOILER/BYPASS PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUT-OFF
UNION AIR SEPARATOR
LEGEND
MAKE-UP WATER
HEATINGRETURN LOOP
BYPASS
HEATING SUPPLY LOOP
PRIMARY - SECONDARY BOILER PIPING WITH BYPASS FOR LOW TEMPERATURE OPERATION
*AS CLOSE AS PRACTICAL– 12
OR 4 PIPE DIAMETERS MAXIMUM
DISTANCEBETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
TO FLOOR DRAIN
*12
MAX
LIT0473
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 26
28 Lochinvar DESIGNERS GUIDE EFFICIENCY + BOILER 615-889-8900
Notes
Page 27
Page 28
Lochinvar Corporation • 615-889-8900 / Fax 615-547-1000
www.Lochinvar.com
EB-DG-03 4.5M-2/05-Printed in U.S.A.
Loading...