EFFICIENCY+
®
BOILER
Submittal Sheet
EBN-Sub-05
EFFICIENCY+® GAS BOILERS
JOB NAME ______________________________________________________________________
LOCATION ______________________________________________________________________
ARCH./ENGR.____________________________________________________________________
WHOLESALER __________________________________________________________________
MECH. CONTRACTOR ___________________________________________________________
MODEL NO. _____________________________________________________________________
TYPE GAS ______________________________________________________________________
Btu/hr INPUT_____________________________________________________________________
Btu/hr OUTPUT___________________________________________________________________
NOTES
Standard Features
• 84% AFUE
• Two Stage Firing
• Sealed Combustion Chamber
• Stainless Steel Burners
• Low NOx Operation Exceeds the most
Stringent Air Quality Requirements
• ASME Copper Finned Tube Heat Exchanger
• 160 PSI Working Pressure
• Gasketless Heat Exchanger Design
• Automatic Reset High Limit
• Loch-Heat Ceramic Tile Combustion Chamber
• Hot Surface Ignition
• ASME Pressure Relief Valve
• 24 Volt Control System
• Pump Relay
• 10 Year Limited Warranty
on Heat Exchanger
(See warranty for details)
Optional Equipment
Place an X in the box by all options that apply
Adjustable High Limit w/ Manual Reset
Alarm Bell
Cupro-Nickel Heat Exchanger
Flow Switch
Indoor/Outdoor Reset
Manual Reset Low Water Cut-Off w/test
MP2 Sequencer
Stack Frame
Pump Delay w/ Freeze Protection
Firing Control Systems
M9 Hot Surface Ignition with Electronic Supervision
(Standard)
M7 California Code
Efficiency+
®
Boiler Dimensions & Specifications
Efficiency+ Boiler Dimensions & Spec i fi ca tions
Input Heating Net
Model Max AFUE Capacity I=B=R Gas Vent Shipping
Number MBH % MBH MBH B D E G Conn. Size Weight
EBN150 150 83.2 129 112 19-3/4” 16” 7-1/4” 11-3/4” 3/4” 5” 245
EBN200 200 83.1 170 148 23-3/4” 20” 9-1/4” 11-3/4” 3/4” 5” 265
EBN250 250 83.2 218 190 27-1/2” 23-3/4” 11” 11-3/4” 3/4” 6” 290
EBN300 300 84.0 252 219 31-1/4” 27-1/2” 13” 11-3/4” 3/4” 6” 310
Notes: Change ‘N’ to ‘L’ to denote L.P. gas models Electrical Requirements: 120 VAC / 2 AMP Water connections are 1-1/2” NPT
Net ratings based on piping and pick-up allowance of 1.15 Performance data based on manufacturer test results.
Venting Options
Conventional
Efficiency+ DirectAire
Direct Vent Vertical
Direct Vent Horizontal
Outdoor
AMP DRAW DATA
150,000 thru 300,000 Btu Models
FIRING
CONTROLS
F-9
(Single Stage)
M-9
(Two Stage)
FAN
1.15
1.15
VALVE/
CON TROLS
3.97
4.15
MAXIMUM
TOTAL AMPS
@ 120 VAC
5.12
5.30
Horizontal Direct Vent Inlet and Outlet Cap
MODEL NO.
EB 150-200
EB 250-300
DIM “A”
9-1/8”
9-5/8”
DIM “B”
8-7/8”
9-3/8”
DIM “C”
7-1/8”
7-5/8”
PUMP
AMPS
100 150-300
2.1 5.8
2.1 5.8
DIM
“D”
7-3/8”
7-3/4”
DIM
“E”
4-3/8”
4-3/8”
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000