Lochinvar CWN090, CWN135, CWN180, CWN199, CWN225 Installation Manual

...
Page 1
CFA-I-S_100160907_2000001336_Rev H
Installation & Service Manual
Models: 90,000 - 500,000 Btu/hr
WARNING:
This manual supplies information for the installation, operation, and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
Page 2
Contents
HAZARD DEFINITIONS .................................................... 2
PLEASE READ BEFORE PROCEEDING ..................... 3-4
RATINGS ........................................................................ 5-6
THE COPPER-FIN -- HOW IT WORKS ............................... 7-9
1. DETERMINE UNIT LOCATION
Location of Unit ................................................................ 10
Clearances from Combustible Construction .....................10
Combustion and Ventilation Air .................................. 11-13
2. VENTING
A Conventional Negative Draft Venting System ......... 14-15
Vertical Vent Termination Clearances ............................. 16
Masonry Chimney Installation .......................................... 17
Inspection of a Masonry Chimney .............................. 17
Automatic Vent Damper ................................................... 20
3. GAS CONNECTIONS
Gas Supply ....................................................................... 21
Gas Pressure Test ........................................................... 21
Gas Connection ............................................................... 21
Gas Piping ........................................................................ 22
Gas Manifold Pressure Adjustment Procedure ................ 23
Checking Gas Supply Pressure ....................................... 24
Combination Gas Valves .................................................. 25
4. HYDRONIC PIPING
Relief Valve ...................................................................... 26
Water Flow Switch (if equipped) ...................................... 26
Low Water Cutoff (if equipped) ........................................ 27
Typical Heating Boiler Installations ............................. 27-28
Piping of the Boiler System .............................................. 28
Water Connections Heating Boilers Only ......................... 29
Circulator Pump Requirements ........................................ 29
Circulator Pump Specifications ...................................... 29
Circulator Pump Operation (Heating Boilers Only) ........ 29
Primary/Secondary Boiler Piping ..................................... 30
Low Temperature Bypass Requirements ......................... 31
Three Way Valves ............................................................ 31
Boiler Flow Rates ............................................................. 31
Figure 4-4_Prim. / Sec. Piping of a Single Boiler ....... 32
Figure 4-5_Prim. / Sec. Piping w/Low Temp. Bypass 33
Figure 4-6_Multiple Boilers Zoned w/Circulators ........ 34
5. ELECTRICAL CONNECTIONS
Boiler Operating Temperature Control ............................. 35
Room Thermostat or Remote Thermostat Connection .... 35
Power Venter Connection to Terminal Strip .................... 35
Pump Wiring for a Heating Boiler .................................... 36
Temperature Adjustment .................................................. 36
Temperature Control Settings .......................................... 37
Maximum Set Point Determination .................................. 37
Outdoor Air Reset Option ................................................. 38
Additional Temperature Controls ................................ 40-41
Blocked Vent and Flame Roll-Out / Flame Interlock Switch . 41
6. STARTUP
Initial Startup .................................................................... 42
Lighting Instructions for Standing Pilot Models (F1) ... 42-44
Safety Shutoff Test for Standing Pilot Ignition System .... 44
Lighting Instructions for Spark Ignition Pilot Models (F9/M9) 45-46
Safety Shutoff Test for Spark Ignition Pilot System ............ 46
Intermittent Pilot Spark Ignition System (F9/M9) ................. 46
Freeze Protection ........................................................................... 46
Water Treatment ....................................................................... 47-49
7. DOMESTIC WATER HEATERS
Water Velocity Control ..................................................... 50
Required Temperature Rise ............................................. 50
Water Chemistry............................................................... 51
Softened Water Systems ................................................. 51
Pump Operation ............................................................... 51
Figure 7-1_Single Water Heater Piping w/Single Tank ... 52 Figure 7-2_Single Water Heater Piping w/Multiple Tanks 53 Figure 7-3_Multiple Water Heater Piping w/Single Tank . 54
Remote Sensor Installation .............................................. 55
Heat Exchanger ............................................................... 55
Thermostat Settings .................................................... 55-56
Optional Relief Valve ........................................................ 57
Thermal Expansion .......................................................... 57
Cathodic Protection .......................................................... 57
8. MAINTENANCE
Maintenance and Annual Startup ................................ 58-64
9. TROUBLESHOOTING ............................................ 65-66
10. DIAGRAMS ............................................................67-70
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Page 3
Please read before proceeding
Installation & Service Manual
NOTICE
WARNING
This is a gas appliance and should be installed by a licensed electrician and/or certified gas supplier. Service must be performed by a qualified service installer, service agency or the gas supplier.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
What to do if you smell gas –
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or additional information, consult a qualified installer, service agency or the gas supplier.
Checking equipment –
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliances which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on the packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier.
Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Owner warning –
NOTE: Retain this manual for future reference.
The information contained in this manual is intended for use by qualified professional installers, service technicians, or gas suppliers. Consult your local expert for proper installation
or service procedures.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Warranty –
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
1. Excessive water hardness causing a lime/scale build-up in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements).
IMPORTANT
Your conventionally vented gas appliance must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting.
WARNING
Consult and follow all local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult your local gas utility company to authorize and inspect all gas and flue connections.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
33
Page 4
Installation & Service Manual
Please read before proceeding
WARNING
To minimize the possibility of serious personal injury, fire, or damage to your appliance, never violate the following safety rules:
1. Boilers and water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your appliance.
3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this appliance, vent-air intake system or any location from which fumes could reach the appliance or vent-air intake system.
Codes –
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or local codes.
This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided as specified in the ANSI standards for gas-fired appliances, ANSI Z21.13 and ANSI Z21.10.3.
Boiler water –
Thoroughly flush the system to remove debris. Use an approved pre-commissioning cleaner (see Start-Up Section), without the boiler connected, to clean the system and remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
NOTE: Cleaners are designed for either new systems or pre-existing systems. Choose accordingly.
Prevention of freezing –
Heat exchangers and headers damaged by freezing are not covered by warranty.
See Section 6, Start-Up - Freeze Protection for more information.
4
Page 5
Ratings
Copper-Fin
AHRI Rating
Installation & Service Manual
Other Specifications
Model Number
Note: Change
“N” to “L” for
L.P. gas models
CBN315 158 315 258 224 CBN360 180 360 295 257 CBN399 200 399 328 285 CBN500 250 500 410 357
NOTICE
Maximum allowed working pressure is located on the rating plate.
Input MBH
(Note 4)
MIN MAX
Gross
Output
MBH
(Note 1)
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
Net
AHRI
Ratings
Water,
MBH
(Note 2)
Boiler
Water Content Gallons
1.2
1.2
1.3
1.4 2" 1" 10"
Water
Connections
2" 3/4" 8" 2" 1" 9" 2" 1" 10"
Gas
Connections
HIGH ALTITUDE
UNIT EQUIPPED FOR
UP TO 2000 FT.
Vent Size
(Note 3)
3. Copper-fins require special gas venting. Use only the vent materials and methods specified in the Installation and Service Manual.
4. The Copper-fin is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation.
5. Ratings have been confirmed by AHRI.
Figure A High Altitude Label Location
5
Page 6
Ratings
Installation & Service Manual
HLW
LOW LEAD CONTENT
Copper-fin Specifications
Model Number
Note: Change “N” to
“L” for L.P. gas models
CWN090 90 1.0 2" 1/2" 5" CWN135 135 1.0 2" 1/2" 6" CWN180 180 1.1 2" 3/4" 7" CWN199 199 1.1 2" 3/4" 7" CWN225 225 1.1 2" 3/4" 7" CWN270 270 1.1 2" 3/4" 8" CWN315 CWN360 CWN399
CWN500
Input MBH
315 1.2 2" 3/4" 8" 360 1.2 2" 1" 9" 399 1.3 2" 1" 10"
500 1.4 2" 1" 10"
Water
Content Gallons
Water Connections Gas Connections
Vent Size
(Note 1)
NOTICE
Maximum allowed working pressure is located on the rating plate.
Notes:
1. Copper-fins require special gas venting. Use only the vent materials and methods specified in the Installation and Service Manual.
2. The Copper-fin is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation.
UNIT EQUIPPED FOR
HIGH ALTITUDE
UP TO 2000 FT.
Figure B High Altitude Label Location
6
Page 7
Installation & Service Manual
The Copper-fin - How it works...
1. Control panel cover
The control panel cover provides access to the thermostat, ignition module, and transformer.
2. Drain port (not shown)
Location from which the heat exchanger can be drained.
3. Flue outlet
The flue outlet allows the connection of the vent pipe to the unit.
4. Gas connection pipe
The gas pipe connection on this appliance should be connected to the incoming gas supply for the purpose of delivering gas to the appliance.
5. Gas valve
The gas valve allows the proper amount of gas to pass into the burner for combustion.
6. Heat exchanger
The heat exchanger allows system water to flow through specially designed tubes for maximum heat transfer. The glass lined headers and copper finned tubing are encased in a jacket that contains the combustion process.
7. High limit sensor
Device that monitors the outlet water temperature to ensure safe operation. If the temperature exceeds its setting , it will break
the control circuit, shutting the appliance down.
8. Ignition module (F9 and M9 models only)
The ignition module responds to a call for heat signal to provide burner operation .
9. Junction box
The junction box contains the connection points for the line voltage power and the pump.
10. Relief valve
The relief valve is a safety device that ensures the maximum pressure of the appliance is not exceeded. Water heaters are supplied with a temperature and pressure relief valve.
15. Water inlet
The water inlet is a 2" pipe connection that receives water from the system and delivers it to the heat exchanger.
16. Water outlet
The water outlet is a 2" pipe connection that supplies water to the system .
17. Burner (not shown) The burner is a cylindrical stainless steel tube used to regulate
burner flame.
18. Pilot (not shown)
( F9 and M9 models only)
The pilot is a spark ignition device is used to light a pilot flame
which in turn is used to light the main burners.
( F1 models only)
The pilot uses a standing flame to light the main burner.
19. Sight Glass (not shown)
The sight glass provides a view of the burner surface, burner flame, and the pilot flame.
20. Temperature and pressure gauge (CB models only)
The temperature and pressure gauge monitors the outlet temperature of the boiler as well as the system water pressure.
21. Pump (shipped with CW models only)
The pump ensures adequate flow to operate the unit.
22. Pump relay
The pump relay energizes the pump on a call for heat.
23. Temperature sensor
This sensor monitors inlet water temperature. If selected as the controlling sensor, the appliance will maintain the setpoint at this sensor.
11. Terminal strip
The boiler is equipped with a terminal strip on the left side of the control panel to allow easy connection to contact points on the unit.
12. Thermostat The thermostat monitors the water temperature via a temperature
sensor and will initiate a call for heat when the water temperature drops below the setpoint plus the differential on the thermostat.
13. Temperature gauge (CW models only)
The temperature gauge monitors the inlet temperature of the water heater as well as the outlet temperature.
14. Transformer The transformer reduces 120 VAC supply voltage to 24 VAC for the
control circuit.
7
Page 8
Installation & Service Manual
The Copper-fin - How it works...
10
16
21
15
5
Models CWN270 Front View
3
3
1
1
10
16
9
11
21
5
15
9
11
Model CWN399 Front View
7
13
23
4
Model CWN270 (inside unit)
22
14
6
6
8
12
13
8
12
7
23
4
14
22
Model CWN399 (inside unit)
8
Page 9
Installation & Service Manual
The Copper-fin - How it works... (continued)
20
10
16
15
5
Model CBN399 Front View
11
3
1
9
6
20
10
16
15
5
Model CBN500 Front View
3
1
9
11
6
7
23
4
Models CBN399 (inside unit)
22
14
12
8
8
12
7
14
23
22
4
Model CBN500 (inside unit)
9
Page 10
1 Determine unit location
Location of unit
1. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
2. The appliance must be installed indoors where it is
protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition
system components are protected from water (dripping, spraying, rain, etc.,) during appliance operation and service (circulator replacement, control replacement, etc.,).
Installation & Service Manual
14 " TOP
6" REAR
24"
FRONT
24" LEFT
6"
RIGHT
4. Appliances located in a residential garage and in adjacent
spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18” (46cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.
5. DO NOT install this appliance in any location where
gasoline or flammable vapors are likely to be present.
6. All units have been approved for alcove installation (an
ALCOVE is a closet enclosure without a front door).
7. The appliance must not be installed on carpet.
8. All units have been approved for use on combustible
surfaces.
9. Allow sufficient space for servicing pipe connections,
pump and other auxiliary equipment, as well as the appliance.
NOTICE
Clearances from combustible construction are noted on the appliance rating plate.
Figure 1-1_Alcove installation, 90,000 - 180,000 Btu/hr
29" TOP
6" RIGHT
6"
REAR
24"
FRONT
24" LEFT
10
Figure 1-2_Alcove Installation , 225,000 - 500,000 Btu/hr
Page 11
Installation & Service Manual
1 Determine unit location (continued)
Combustion and ventilation air requirements for conventionally vented appliances
Provisions for combustion and ventilation air must be in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The room where the appliance is installed MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.
Figure 1-4_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the room where the appliance is installed, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11cm2 per kW) (see FIG. 1-4).
Figure 1-3_Combustion Air Direct from Outside
1. If air is taken directly from outside the building with no duct, provide two permanent openings (see FIG. 1-3):
(a) Combustion air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). This opening must be located within 12" (30 cm) of the floor.
(b) Ventilation air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm located within 12" (30 cm) of the ceiling.
2
per kW). This opening must be
Figure 1-5_Combustion Air from Interior Space
3. If air is taken from another interior space that is adequately ventilated, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/ hr (22cm2 per kW) of input, but not less than 100 square inches (645cm2) (see FIG. 1-5).
11
Page 12
1 Determine unit location
Installation & Service Manual
Figure 1-6_Combustion Air from Outside Single Opening
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-6).
Combustion air require ments are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to National Standard CAN B149.1. Check all local code re quire ments for combustion air.
All dimensions are based on net free area in square inch es. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are pro vid ed, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the room where the appliance is installed. Each opening must have a net free area as specified in Table 1B (on page 13). Single openings shall be located with in 12" (30 cm) of the ceiling.
CAUTION
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as freon, tricholorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure.
The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the equipment room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.
Under no circumstances should the room where the appliance is installed ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the appliance.
12
Page 13
Installation & Service Manual
1 Determine unit location (continued)
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
Input
Btu/hr
90,000
135,000
180,000
199,999
225,000
270,000
315,000
360,000
399,999
500,000
*Outside Air from
2 Openings Directly from
Outdoors
Top
Opening, in
23
(148 cm2)
34
(220 cm2)
45
(291 cm2)
50
(323 cm2)
57
2
(368 cm
(439 cm
(510 cm
(581 cm2)
(646 cm2)
(807 cm2)
68
79
90
100
125
)
2
)
2
)
Bottom
2
Opening, in
(148 cm2)
(220 cm2)
(291 cm2)
(323 cm2)
(368 cm2)
(439 cm2)
(510 cm2)
(581 cm2)
(646 cm2)
(807 cm2)
23
34
45
50
57
68
79
90
100
125
*Outside Air from 1 Opening Directly from Outdoors, in
2
30
(194 cm2)
45
(291 cm2)
60
(388 cm2)
67
(433 cm2)
75
(484 cm2)
90
(581 cm2)
105
(678 cm2)
120
(775 cm2)
134
(865 cm2)
167
(1,078 cm2)
*Outside Air from
2 Ducts Delivered from
Outdoors
2
Top
Opening, in
(291 cm2)
(439 cm2)
(581 cm2)
(646 cm2)
(730 cm2)
(871 cm2)
(1,020 cm2)
(1,162 cm2)
(1,291 cm2)
(1,613 cm2)
2
45
68
90
100
113
135
158
180
200
250
Bottom
Opening, in
45
(291 cm2)
68
(439 cm2)
90
(581 cm2)
100
(646 cm2)
113
(730 cm2)
135
(871 cm2)
158
(1,020 cm2)
180
(1,162 cm2)
200
(1,291 cm2)
250
(1,613 cm2)
**Inside Air from
2 Ducts Delivered from
Interior Space
Top
2
Opening, in
(646 cm2)
(871 cm2)
(1,162 cm2)
(1,291 cm2)
(1,452 cm2)
(1,742 cm2)
(2,033 cm2)
(2,323 cm2)
(2,581 cm2)
(3,226 cm2)
100
135
180
200
225
270
315
360
400
500
2
Bottom
Opening, in
100
(646 cm2)
135
(871 cm2)
180
(1,162 cm2)
200
(1,291 cm2)
225
(1,452 cm2)
270
(1,742 cm2)
315
(2,033 cm2)
360
(2,323 cm2)
400
(2,581 cm2)
500
(3,226 cm2)
2
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.
* “Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).
Vent installations for connection to gas vents or chimneys must be in accordance with “Vent ing of Equipment,” of the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1, in Canada, the latest edi tion of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable pro vi sions of the local building codes.
Adequate combustion and ventilation air must be sup plied to the room where the appliance is installed in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Ap pli anc es and Equipment, or applicable pro vi sions of the local building codes.
13
Page 14
2 Venting
The distance of the vent terminal from adjacent build ings, windows that open and building open ings MUST comply with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 In stal la tion Code for Gas Burn ing Appliances and Equipment.
Vent connection is made directly to the top of the ap pli ance. This appliance is designed with a built-in draft diverter. No additional external draft hood is re quired. The connection from the appliance vent to the common vent or chimney must be made as direct as possible.
A Conventional Negative Draft Venting System
The negative draft in a conventional vent in stal la tion must be within the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. All draft read ings are made while the appliance is in stable op er a tion (approximately 2 to 5 minutes).
Multiple appliance installations with combined vent ing or common venting with other negative draft ap pli anc es require that each appliance must have draft with in the proper range. If the draft mea sured above the appliance’s built-in draft diverter ex ceeds the specified range in a dedicated chimney for a single appliance installation or in combined venting with other negative draft appliances, a baro met ric damper must be
in stalled to control draft.
Installation & Service Manual
Figure 2-1_Conventional Negative Draft Vertical Venting
TABLE - 2A
VENT PIPE SIZES
Input Btu/hr Flue Size
90,000 5"
135,000 6"
180,000 7"
199,999 7"
225,000 7"
270,000 8"
315,000 8"
360,000 9"
399,999 10"
500,000 10"
14
On a conventionally vented, negative draft ap pli ance, the connection from the vent to the chimney or vent termination on the outside of the building MUST be made with listed Type “B” double wall (or equivalent) vent connectors and must be direct as possible with no reduction in diameter. To properly size all double wall vent connectors and stacks, use the venting tables in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment. The Type “B” vent and accessories, such as firestop spacers, thim bles, caps, etc., MUST be installed in accordance with the manufacturer’s list ing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any vent materials used must be listed by a na tion al ly recognized test agency for use as vent ma te ri al.
Page 15
2 Venting (continued)
Locate appliance as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° el bows, reductions and restrictions. Horizontal por tions of the venting system shall be supported to prevent sagging. Horizontal runs must slope up wards not less than 1/4 inch per foot (21 mm/m) from the appliance to the vent terminal. Follow manufacturer’s instructions.
Do not use an existing chimney as a raceway for a flue pipe if another appliance or fireplace is vented through the chimney. A water heater shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
The weight of the venting system must not rest on the appliance. Adequate support of the venting sys tem must be provided in compliance with local codes and other applicable codes. All connections should be secured with rustproof sheet metal screws.
Vent connectors serving appliances vented by nat u ral draft shall not be connected to any portion of a me chan i cal draft system operating under positive pres sure. Connection to a positive pressure chim ney may cause flue products to be discharged into the living space causing serious health injury.
Common venting systems may be too large when an existing appliance is removed. At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining con nect ed to the common venting system are not in operation.
Installation & Service Manual
(e) Test for spillage at the draft hood/relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning ap pli anc es to their previous conditions of use.
(g) Any improper operation of the common venting
system should be corrected so that the installation conforms to the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any por tion of the common venting system, the common venting system should be resized to ap proach the min i mum size as determined using the appropriate tables in Part 11 in the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Stan dard B149 Installation Code for Gas Burning Appliances and Equipment.
(a) Seal any unused opening in the common venting
system.
(b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer ex haust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
15
Page 16
2 Venting
Y
Vertical Vent Termination Clearances
10' OR LESS
CHIMNEY
Installation & Service Manual
10' OR LESS
10' OR LESS
2' MIN
RIDGE
3' MIN
Figure 2-2_Vent Termination from Peaked Roof 10' or Less from Ridge
MORE THAN 10'
10'
2' MIN
RIDGE
CHIMNE
3' MIN
2' MIN
CHIMMEY
WALL OR PARAPET
2' MIN
3' MIN
CHIMMEY
Figure 2-4_Vent Termination from Flat Roof 10' or Less from Parapet Wall
10' OR MORE
3'
NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN DISTANCE FROM WALLS OR PARAPETS IS MORE THAN 10'.
Figure 2-3_Vent Termination from Peaked Roof More than 10' from Ridge
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the high est point of the roof within a 10 foot (3.05m) radius of the termination. The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical terminal less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
The vent cap should have a minimum clearance of 4 feet (1.22m) horizontally from and in no case above or below, unless a 4 foot (1.22m) horizontal distance is maintained from electric meters, gas meters, reg u la tors and relief equipment.
The venting system shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
The venting system shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building.
Do not terminate the vent in a window well, stair well, alcove, courtyard or other recessed area.
16
WALL OR PARAPET
CHIMNEY
Figure 2-5_Vent Termination from Flat Roof More Than 10' from Parapet Wall
The vent can not terminate below grade. The bot tom of the vent terminal shall be located at least 12 inches (30cm) above grade.
To avoid a blocked vent condition, keep the vent cap clear of snow, ice, leaves, debris, etc.
Flue gases will form a white plume in winter. Plume could obstruct window view.
Flue gas condensate can freeze on exterior sur fac es or on the vent cap. Frozen condensate on the vent cap can result in a blocked vent condition. Flue gas condensate can cause discoloration of exterior build ing surfaces. Adjacent brick or masonry sur fac es should be protected with a rust resistant sheet metal plate.
NOTICE
Examine the venting system at least once a year. Check all joints and vent pipe con nec tions for tightness. Also check for corrosion or de te ri o ra tion. Immediately correct any problems ob served in the venting system.
Page 17
2 Venting (continued)
Installation & Service Manual
Masonry Chimney Installation
A masonry chimney must be properly sized for the installation of a gas fired appliance. Venting of an appliance into a cold or oversized masonry chimney can result in op er a tion al and safety problems. Exterior masonry chim neys, with one or more sides exposed to cold out door tem per a tures, are more likely to have venting problems. The temperature of the flue gases from an appliance may not be able to suf fi cient ly heat the ma son ry structure of the chim ney to generate proper draft. This will result in condensing of flue gases, damage the masonry flue/tile, insufficient draft and possible spill age of flue gases into an occupied living space. Care ful ly in spect all chimney systems before installation. If there is any doubt about the sizing or condition of a masonry chimney, it must be relined with a prop er ly sized and approved chimney liner system.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue gas es. A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of con den sate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined. An unlined masonry chimney must not be used to vent flue gases from this appliance. An unlined chimney must be relined with an approved chimney liner system when a new appliance is be ing attached to it. Metallic liner systems (Type “B” double wall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Sidewall Venting
This appliance is NOT approved for sidewall venting with the negative draft venting system as shipped from the factory. An induced draft fan MUST be used if the installation requires that the flue gases be vented out a sidewall. A properly sized and in stalled induced draft fan may also be used to vent the flue gases ver ti cal ly if required by job site conditions. The induced draft fan must be listed by a nationally recognized test agency, be properly sized and installed per the rec om men da tions of the in duced draft fan manufacturer and meet local code requirements. Use care to ensure that the me chan i cal ly supplied draft does not exceed the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. If draft exceeds the spec i fied range, the fan must be adjusted or the installation of a baro met ric damper in the flue may be required to prop er ly control draft.
An induced draft fan MUST be interlocked into the appliance’s control circuit to start when the appliance calls for heat. The in duced draft fan MUST also be equipped with a prov ing switch, properly interlocked into the ap pli ance’s con trol circuit to prove fan operation before the main burn ers are allowed to fire. A vertical or sidewall vent termination for an induced draft fan MUST be in stalled per the recommendations of the fan manufacturer and provide proper clearances from any combustion or ventilation openings, win dows, doors or other open ings into the building. All induced draft fan in stal­la tions must comply with local code requirements. See FIG. 2-7 for minimum sidewall venting clearances.
Fan Assisted Venting
A Power Venter kit is available on models 90,000 - 135,000 Btu/hr, water heaters only.
TABLE 2B - VENT MATERIALS
Kit
Number
100157734
Minimum Vent Length = 12 Equivalent Feet *
Maximum Vent Length = 25 Equivalent Feet * *
CAUTION
NOTE: In Canada, CPVC and PVC vent pipe,  ttings and cement/primer must be ULC-S636 certi ed.
WARNING
Figure 2-6_CW135 with Fan Assisted Venting
Input
Btu / hr
90,000 CPVC Rated
135,000 CPVC Rated
(ALL UNITS)
(ALL UNITS)
*Equivalent Feet: 90° Elbow = 5 Feet
45° Elbow = 3 Feet
DO NOT use Radel or cellular (foam) core PVC or CPVC pipe.
DO NOT insulate PVC or CPVC venting materials. Use of insulation will cuase increased vent wall temperatures, which could result in vent pipe failure.
Material
17
Page 18
2 Venting
Figure 2-7 Other than Direct Vent Terminal Clearances
Installation & Service Manual
Table 2C Other than Direct Vent Terminal Clearances
Canadian Installations¹ US Installations²
A =
B =
C =
D =
E = Clearance to unventilated soffit
F = Clearance to outside corner
G = Clearance to inside corner
H =
Clearance above grade, veranda, porch,
deck, or balcony
Clearance to window or door that may
be opened
Clearance to permanently closed
window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 ft (61 cm) from
the center line of the terminal.
Clearance to each side of center line
extended above meter / regulator
assembly
6 in (15 cm) for appliances < 10,000 Btuh
(3 kW), 12 in (30 cm) for appliances >
10,000 Btuh (3 kW) and < 100,000 Btuh
(30 kW), 36 in (91 cm) for appliances >
12 in (30 cm) 12 in (30 cm)
4 ft (1.2 m) below or to side of opening; 1 ft
(300 mm) above opening
100,000 Btuh (30 kW)
**
**
**
**
**
**
18
Page 19
Installation & Service Manual
2 Venting (continued)
Table 2C Other than Direct Vent Terminal Clearances (continued)
I =
J =
K =
L =
M =
Clearance to service regulator vent
outlet
Clearance to nonmechanical air supply
inlet to building or the combustion air
inlet to any other appliance
Clearance to a mechanical air supply
inlet
Clearance above paved sidewalk or
paved driveway located on public
property
Clearance under veranda, porch, deck,
or balcony
Above a regulator within 3 ft (91 cm) horizontally of the vertical center line of the regulator vent outlet to a maximum vertical
distance of 15 ft (4.5 m)
6 in (15 cm) for appliances < 10,000 Btuh
(3kW), 12 in (30 cm) for appliances >
10,000 Btuh (3 kW) and < 100,000 Btuh
(30 kW), 36 in (91 cm) for appliances >
100,000 Btuh (30 kW)
6 ft (1.83 m) 3 ft (91 cm) above if within 10 ft (3 m)
7 ft (2.13 m)† 7 ft (2.13 m)
12 in (30 cm)‡ *
4 ft (1.2 m) below or to side of opening; 1 ft
(300 mm) above opening
*
horizontally
* Clearance in accordance with local installation codes and the requirements of the gas supplier.
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings
and serves both dwellings.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath he  oor.
NOTES:
1) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
2) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
19
Page 20
2 Venting
Installation & Service Manual
Automatic Vent Damper
This heating boiler is design certified for use with the automatic vent damper (FIG. 2-8) part number printed on the boiler’s rating plate. A vent damper is optional on heating boilers above 360,000 Btu/hr. Automatic vent dampers are not required or fur nished on potable water heaters. Water heaters with inputs of 360,000 Btu/hr and less may be ordered with the vent damp er as an option. A vent damper is a useful tool for saving energy when installed inside the living space where air can cir cu late freely around the appliance. The vent damper will not save as much, if any, energy if it is installed in locations such as:
- Unheated garage
- Attic
- Crawlspace
- Mechanical room that is vented outdoors
For installation and maintenance on the vent damper, refer to the instructions supplied with the vent damper.
Larger input heating boilers and water heaters will have a jumper plug installed in the ter mi nal block to allow operation without a damper. Remove the jumper plug from the terminal block to connect an optional vent damper wire harness (water heater shown in FIG. 2-9). The jumper plug MUST be in place if an optional vent damper is not used on water heaters and larger input heating boilers.
Figure 2-8_CB with Vent Damper and Vent Damper Terminal Block
VENT DAMPER
TERMINAL
BLOCK
Figure 2-9_CW with Vent Damper
VENT DAMPER
WARNING
DANGER
The damper position indicator must be in a visible lo ca tion with access for service following in stal la tion. The damper must be in an open position when appliance main burners are operating.
The part number for the automatic vent damper required on this heating boiler is printed on the rating plate. Vent damper regulations are design certified per the latest edition of ANSI Z21.66.
Do not install the vent damper within 6" (152 mm) of combustible materials.
Install the vent damper to service only the single ap pli ance for which it is intended. If improperly installed, a hazardous condition such as an ex plo sion or carbon monoxide poisoning could result.
WARNING
CAUTION
The vent damper must be installed directly on the flue outlet located on the top of the draft hood (see FIG. 2-8). Do not alter the wire har ness sup plied with the vent damper. Follow the instructions supplied with the vent damper.
An appliance which is shut down or will not operate may experience freezing due to con vec tive air flow down the flue pipe connected to the unit. Proper freeze protection must be pro vid ed, see Freeze Pro tec tion in the Startup Section of this manual.
20
Page 21
3 Gas connections
Gas Supply
Installation & Service Manual
Gas Pressure Test
Verify that the appliance is supplied with the type gas spec i fied on the rating plate. This appliance is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation. Field conversions for operation at high altitude must be performed by certified per son nel only. The appliance will be marked to indicate suitability for high al ti tude operation.
GAS SUPPLY PRESSURE: Measured at the inlet pres­sure tap located upstream of the combination gas valve(s) see FIG.’s 3-5 and 3-6, page 25.
TABLE - 3A
GAS SUPPLY PRESSURE
Natural Gas LP Gas
Max. (Inches Water Column)
Min. (Inches Water Column) *4.5 11
Min. (Inches Water Column) **5.0 11
*Models 90,000 - 360,000 Btu/hr Only
**Models 399,999 - 500,000 Btu/hr Only
Maximum inlet gas pressure must not exceed the val ue specified. Minimum value listed is for the purposes of input adjustment.
MANIFOLD PRESSURE: Measured at the pres sure tap on the downstream side of the com bi na tion gas valve(s) (see FIG.’s 3-5 and 3-6, page 25). The gas regulator settings for single stage and two stage operation are factory set to supply proper manifold pressure for normal operation. To check manifold pressure, see Manifold Ad just ment Procedure. Do not increase manifold pressure beyond spec i fied pressure settings shown below in Table 3B.
14 14
1. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5kPa).
2. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5kPa).
3. The appliance and its gas connection must be leak-tested before placing it in operation.
Gas Connection
1. Safe operation of the appliance requires properly sized gas supply piping.
2. Gas pipe size may be larger than appliance gas connection.
3. Installation of a union is suggested for ease of service, see FIG. 3-1 on page 22.
4. Install a manual main gas shutoff valve, outside of the appliance gas connection and before the gas valve or manifold connection, when local codes require.
5. A trap (drip leg) MUST be provided by the installer in
the inlet of the gas connection to the appliance, see FIG. 3-1 on page 22.
6. The combination gas valve has an integral vent lim it ing device and does not require venting to atmosphere, outside the building.
7. Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.
TABLE - 3C
FITTINGS TO EQUIVALENT STRAIGHT PIPE
Diameter Pipe (inches)
TABLE - 3B
MANIFOLD PRESSURE
Input Gas
Btu/hr
90,000 - 180,000 3.5" 10" 0.9" 2.5"
199,999 2.9" 7.5" 0.9" 2.5"
215,000 - 399,999 3.5" 10" 0.9" 2.5"
500,000 3.5"
Single and Two-Stage Two Stage
Full or High Fire Settings Low Fire Settings
Natural Gas LP Gas Natural Gas LP Gas
10"
(two valves)
N/A N/A
3/4 1 1 1/4 1 1/2 2 3 4 5
Equivalent Length of Straight Pipe (feet)
22345101420
TABLE - 3D
GAS CONNECTIONS
Btu/hr
INPUT
90,000 - 135,000 1/2"
180,000 - 315,000 3/4"
360,000 - 500,000 1
Pipe Size
21
Page 22
3 Gas connections
Capacity of Schedule 40 Metallic Pipe in Cubic Feet of Natural Gas Per Hour
(based on .60 specific gravity, 0.30" w.c. pressure drop)
Pipe
Size
(Inches)
1/2 131 90 72 62 55 N/A N/A N/A N/A N/A N/A N/A N/A N/A
3/4 273 188 151 129 114 104 95 89 83 79 70 63 58 N/A
1 514 353 284 243 215 195 179 167 157 148 131 119 109 102
1 1/4 1,060 726 583 499 442 400 368 343 322 304 269 244 224 209 1 1/2 1,580 1,090 873 747 662 600 552 514 482 455 403 366 336 313
2 3,050 2,090 1,680 1,440 1,280 1,160 1,060 989 928 877 777 704 648 602
2 1/2 4,860 3,340 2,680 2,290 2,030 1,840 1,690 1,580 1,480 1,400 1,240 1,120 1,030 960
3 8,580 5,900 4,740 4,050 3,590 3,260 3,000 2,790 2,610 2,470 2,190 1,980 1,820 1,700
4 17,500 12,000 9,660 8,270 7,330 6,640 6,110 5,680 5,330 5,040 4,460 4,050 3,720 3,460
10 20 30 40 50 60 70 80 90 100 125 150 175 200
Installation & Service Manual
TABLE - 3E
Length of Pipe in Straight Feet
Gas Piping
GAS VALVE
GAS SHUTOFF
TRAP ( DRIP LEG )
Figure 3-1_Gas Line Connection
All gas connections must be made with pipe joint com pound resistant to the action of liquefied pe tro leum and natural gas. All piping must comply with local codes. Tubing installations must com ply with ap proved standards and practices. Reference FIG. 3-1 for a typical installation.
Install Piping to Control
1. The gas line should be a separate line direct from the meter unless the existing gas line is of sufficient capacity. Verify pipe size with your gas sup pli er.
UNION
2. Use new, properly threaded black iron pipe free from chips. If tubing is used, make sure the ends are cut squared, deburred and clean. All tubing bends must be smooth and without deformation. Avoid flexible gas connections. Internal diameter of flexible lines may not provide proper volume of gas.
3. Run pipe or tubing to the gas valve or manifold inlet. If tubing is used, obtain a tube to pipe coupling to connect the tubing to the gas valve or man i fold inlet.
4. DO NOT OVER TIGHTEN. Over tightening may result in damage to the gas valves. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas valve.
5. Apply a moderate amount of good quality pipe compound (DO NOT use Teflon tape) to pipe only, leaving two end threads bare.
6. Remove seal over gas valve or manifold inlet.
7. Connect pipe to gas valve or manifold inlet. Use wrench to square ends of the gas valve (FIG. 3-2).
8. For L.P. gas, consult your L.P. gas supplier for expert installation.
22
Page 23
3 Gas connections (continued)
WHEN FLANGE
IS USED
WHEN FLANGE
APPLY WRENCH TO FLANGE ONLY
Figure 3-2_Wrench
IMPORTANT
Upon completion of any piping con nec tions to the gas system, leak test all gas con nec tions with a soap solution while system is un der pressure. Immediately repair any leaks found in the gas train or related components. Do Not op er ate an appliance with a leak in the gas train, valves or related piping.
Gas Manifold Pressure Adjustment Procedure
PRESSURE REGULATOR
INLET
PRESSURE
TAP
(UNDER SCREW CAP)
IS NOT USED
APPLY WRENCH FROM
BOTTOM OF GAS CONTROL
TO EITHER SHADED AREA
ADJUSTMENT
OUTLET
PRESSURE TAP
Installation & Service Manual
2. Turn gas valve control knob to “PILOT” po si tion on standing pilot models. Ensure that the stand ing pilot remains on. If the pilot goes out, follow the “Lighting Instructions” in Section 6 - Startup for standing pi lot models to light the pilot. Turn gas valve control knob to “OFF” po si tion on spark ignition models.
3. Remove the 1/8" hex plug located on the out let side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. See FIG. 3-3. Minimum range of scale should be up to 5" w.c. for Natural gas mod els and 10" w.c. for L.P. gas models.
4. The 500,000 Btu/hr model will have two gas valves with a pressure regulator on each valve. Repeat the following adjustment pro ce dure to set the manifold pressure on each gas valve.
5. Remove the pressure regulator adjustment cap screw on the gas valve. See FIG. 3-3 for location.
6. Turn the power “ON” at the main dis con nect switch.
7. Turn gas valve control knob to “ON” po si tion.
8. Set the thermostat(s) to call for heat.
9. Observe gas regulator pressure when all burn ers are firing. See Table 3B, Manifold Pressure (page 21) for proper regulator pressure settings.
10. If adjustment is necessary, turn regulator ad just ment screw clockwise to raise regulator gas pres sure, counterclockwise to lower gas pres sure, to proper setting.
Note: Adjustment fitting is plas tic and may require
slightly greater turning force than a metal fitting.
11. Turn the power “OFF” at the main dis con nect switch.
PILOT OUTLET
GAS CONTROL KNOB
RED RESET BUTTON
MANOMETER
UNION
GAS VALVE
Figure 3-3_Manifold Pressure Adjustment
1. Turn the power “OFF” at the main dis con nect switch.
NOTICE
Do not increase regulator pres sure beyond specified pressure setting.
12. Turn gas valve control knob to “PILOT” po si tion on standing pilot models. Turn gas valve control knob to “OFF” position on spark ignition models.
13. Remove fitting from the gas valve and re place the 1/8” hex plug that was previously removed and tighten.
14. Repeat the adjustment procedure for the sec ond gas valve on the 500,000 Btu/hr model.
15. Turn the gas valve control knob(s) to “ON” position.
16. Turn the power “ON” at the main dis con nect switch. The appliance is now ready to op er ate.
If manifold pressure can not be properly adjusted, use the procedure on page 24 to check gas supply pressure with a manometer connected to the inlet pressure tap on the gas control.
23
Page 24
3 Gas connections
Installation & Service Manual
Checking Gas Supply Pressure
MANOMETER
GAS SUPPLY PRESSURE
GAS VALVE
UNION
Figure 3-4_Gas Supply Pressure
1. Turn the power “OFF” at the main dis con nect switch.
2. Turn gas valve control knob(s) to the “OFF” position.
3. The 500,000 Btu/hr model will have two gas valves. Turn the gas valve control knob on each valve to the “OFF” position.
4. Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. gas, shut off gas supply at the tank.
5. Remove the 1/8" hex plug, located on the “inlet” side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. On two gas valve models, remove the hex plug from the gas valve closest to the gas sup ply connection. Range of scale should be 14" w.c. or greater to check inlet pressure. See FIG.’s 3-3 and 3-4 for location.
6. Turn on gas supply at the manual valve, turn on L.P. gas at tank if required.
7. Turn the power “ON” at the main dis con nect switch.
8. Turn gas valve control knob to “PILOT” po si tion on standing pilot models. Follow the “Lighting Instructions” in Section 6 - Startup for standing pilot models to light the pilot . Turn gas valve control knob to the “ON” po si tion when the pilot is established. Turn gas valve control knob(s) to the “ON” position on spark ig ni tion models.
9. Set the thermostat(s) to call for heat.
10. Observe the gas supply pressure with all burn ers firing. Ensure inlet pressure is within specified range. Check gas supply pressure with all other gas fired appliances in operation to en sure prop er gas volume during periods of peak gas usage.
11. If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agen cy to determine necessary steps to provide prop er gas pressure to the appliance.
12. If the gas supply pressure is within the spec i fied range, proceed with the following steps to return the appliance to service.
13. Turn the power “OFF” at the main dis con nect switch.
14. Turn gas valve control knob to “PILOT” po si tion on standing pilot models. Turn gas valve control knob(s) to “OFF” position on spark ig ni tion mod els.
15. Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. Gas, shut off gas supply at the tank.
16. Remove the manometer and related fittings from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve.
17. Turn on gas supply at the manual valve, turn on L.P. Gas at tank if required.
18. Turn the power “ON” at the main dis con nect switch.
19. Turn the gas valve control knob(s) to the “ON” position. If the pilot is not burning, follow the “Light ing Instructions” in Section 6 - Startup for standing pilot models to light the pilot. Spark ignition models will au to mat i cal ly light the pilot on a call for heat.
20. Set the thermostat to call for heat. The appliance is now ready to operate.
IMPORTANT
Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see the “Main te nance Section
-Normal Flame Pattern”. Turn system off and allow burners
to cool, then cycle burners again to en sure proper ignition and flame characteristics.
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
24
Page 25
3 Gas connections (continued)
A
A
Combination Gas Valves
PRESSURE REGULATOR
DJUSTMENT (UNDER CAP SCREW)
INLET PRESSURE TAP
RED RESET BUTTON
Figure 3-5_F1 Gas Valve, standing pilot
GAS CONTROL KNOB
Installation & Service Manual
OUTLET PRESSURE TAP
PILOT OUTLET
Each unit has a combination gas valve(s) to control the gas supply to the burners. The 500,000 Btu/hr model has two combination gas valves to supply gas to the burners. The com bi na tion valve con sists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open po si tion at all times when the appliance is in service. Each gas valve has pres sure taps located on the inlet and outlet sides. Manifold pressure is adjusted using the regulator located on the valve. The manifold pres sure is pre set at the factory and adjustment is not usu al ly re quired. If the manifold pressure is to be ad just ed, follow the “Gas Manifold Pressure Ad just ment Pro ce dure”, page 23 for proper adjustment.
PRESSURE REGULATOR
DJUSTMENT (UNDER CAP SCREW )
INLET PRESSURE TAP
GAS CONTROL KNOB
WIRING TERMI NALS
Figure 3-6_F9 Gas Valve, spark ignition
OUTLET PRESSURE TAP
PILOT OUTLET
Venting of Combination Gas Valves
The combination gas valve regulator used on all mod els is equipped with an integral vent limiting orifice. The vent limiter ensures that the volume of gas emitted from the valve does not exceed the maximum safe leak age rate allowed by agency re quire ments. Com bi na tion gas valve/regulators equipped with integral vent limiters are not re quired to have vent or relief lines piped to the outdoors. A dust cap is provided at the vent termination point on the valve to prevent block age of the vent limiter by foreign material. The com bi na tion gas valve regulator with an integral vent limiter complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the manufacturer with out the in stal la tion of additional vent lines.
Two Stage Burner Control System
The 315,000 through 399,999 Btu/hr boiler models (M9) will be equipped with a two stage gas valve to control high/low burner op er a tion. The 500,000 Btu/hr boiler mod el achieves two stage burner firing by staging the operation of the two combination gas valves.
25
Page 26
4 Hydronic piping
Installation & Service Manual
Relief Valve
RELIEF VALVE
Figure 4-1_Relief Valve - CBN315-500
This appliance is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Ves sel Code, Section IV (“Heating Boilers”). The re lief valve(s) is mounted directly into the heat ex chang er inside the header (see FIG.’s 4-1 and 4-2). To pre vent water damage, the dis charge from the relief valve shall be piped to a suit able floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION
Avoid contact with hot discharge water.
Water Flow Switch (if equipped)
FLOW SWITCH
Figure 4-2_Water Flow Switch - CBN315-500
A water flow switch is available as a factory sup plied option on all heating boilers and water heaters (see section 7). The flow switch should be wired between terminals X and B. Remove the jumper between the X and B terminals on the terminal strip. This wiring connection installs the flow switch in the 24 VAC safety cir cuit to prove water flow before main burner ig ni tion. A flow switch installed with the fac to ry sup plied minimum adjustment setting requires a spe cif ic minimum flow to make the switch and start burner operation. The flow rate required is a function of the diameter of pipe and tee used for installation. Ensure that the pump installed on the boiler will supply adequate flow to make the flow switch con tacts and operate the appliance.
26
Page 27
4 Hydronic piping (continued)
A water flow switch meets most code re quire ments for a low-water cut off device on boil ers requiring forced cir cu la tion for operation.
Low Water Cutoff (if equipped)
A hot water boiler installed above radiation level must be provided with a low water cutoff device either as part of the unit or installed at the time the boiler is installed. An electronic low water cutoff is available as a kit on all units. Low water cutoffs should be in spect ed every six months, including flushing of float types.
Installation & Service Manual
Typical Heating Boiler Installations
General Plumbing Rules
1. Check all local codes.
2. For serviceability of the boiler, always install unions.
3. Always pipe pressure relief valves to an open drain.
4. Locate system air vents at the highest point of the system.
5. Expansion tank must be installed near the boil er and on the suction side of the pump.
TABLE - 4A
MINIMUM REQUIRED FLOW
FOR HEATING BOILER
Input Btu/hr GPM Flow
315,000 13
360,000 14.9
399,999 16.5
500,000 20.7
NOTICE
Minimum flow is based on a 40°F temper a ture rise across the boiler. Minimum flow may not prove a flow switch installed in the boiler piping. Use care when operating a boiler at or near the min i mum recommended flow because conditions unique to the installation (system pressure, operation of multiple zone valves, glycol, variations in flow, etc.,) may result in overheating of the boiler water caus ing noise or nuisance operation of safety limit con trols. Typical heat ing boiler applications will op er ate with a 20°F to 30°F temperature rise across the boiler.
6. Support all water piping.
Placing the Boiler in Operation
Filling the System: All air must be purged from the system for proper operation. An air scoop and air vent must be located close to the boiler outlet and there should be a minimum distance between the cold water feed and the system purge valve.
1. Close all drain cocks and air vents.
2. Open the makeup water valve and slowly fill the system.
3. If a makeup water pump is employed, ad just the pressure to provide a minimum of 12 psi at the highest point in the system. If a pressure regulator is also installed in the line, it should be adjusted to the same pressure.
4. Close all valves. Purge one circuit at a time as follows:
A. Open one circuit drain valve and let the water drain
for at least five minutes. Ensure that there are no air bubbles visible in the wa ter stream before closing the drain valve.
B. Repeat this procedure for each circuit.
5. Open all valves after all circuits have been purged. Make sure there are no system leaks.
NOTICE
6. Run the system circulating pump for a min i mum of 30
minutes with the boiler turned off.
Do not use petroleum based stop leak products. All system leaks must be repaired. The constant addition of make-up water can cause damage to the boiler heat exchanger due to scale accumulation. Scale reduces flow and heat transfer, causing overheating of the heat exchanger.
7. Open all strainers in the system and check for debris.
8. Recheck all air vents as described in step 4, General
Plumbing Rules.
27
Page 28
4 Hydronic piping
Installation & Service Manual
9. Inspect the liquid level in the expansion tank. The system must be full and under normal operating pressure to ensure proper water level in the expansion tank. Ensure that diaphragm type ex pan sion tanks are properly charged and not water logged.
10. Start the boiler according to the Section 6 - “Start-Up Instructions” in this manual. Operate the system, including the pump, boiler and radiation units, for one hour.
11. Recheck the water level in the expansion tank. If it exceeds half the tank volume, open the tank to reduce the water level. Recheck pres sure charge on diaphragm type tanks.
12. Shut down the entire system and vent all ra di a tion units and high points in the system.
13. Close the water makeup valve and check the strainer and pressure reducing valve for sediment or debris. Reopen the water makeup valve.
14. Verify system pressure with the boiler pres sure gauge before beginning regular operation.
15. Within three days of start-up, recheck and bleed all air vents and the expansion tank using these instructions.
Piping of the Boiler System
The drawings in this section (see FIG’s 4-4 through 4-6) show typical heating boil er piping installations. Before beginning the in stal la tion, consult local codes for specific plumb ing re quire ments. The installation should provide unions and valves at the inlet and outlet of the boil er so it can be isolated for service. The boiler cir cu lat ing pump, air sep a ra tor, expansion tank and oth er components required for proper installation must be purchased locally. An air separation device must be supplied in the in stal la tion piping to eliminate trapped air in the system. Lo cate a system air vent at the highest point in the sys tem. The system must also have a properly sized expansion tank installed. Typically, an air charged di a phragm-type expansion tank is used. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper op er a tion. A water meter to monitor makeup water is recommended. Makeup water volume should not exceed 5% of total system per year. Install a Y-strainer or equivalent multi-purpose strainer just before the boiler pump at the inlet of the heat exchanger. This item is used to remove system debris from older hydronic systems and to protect newer systems.
CAUTION
This boiler system should not be operated at less than 12 PSIG (83 kPa) (Non-metallic system piping must have an oxygen barrier to be considered a closed loop).
TABLE - 4B
SYSTEM TEMPERATURE RISE CHART
Based on Boiler Output in Btu/hr
Btu/hr
Input Output GPM Ft/hd GPM Ft/hd GPM Ft/hd
315,000 258,300 26.0 4.1 17.3 2.2 13.0 1.3
360,000 295,200 29.7 5.4 19.8 2.5 14.9 1.5
399,999 327,180 -- -- 22.0 3.6 16.5 2.0
500,000 410,000 -- -- 27.6 6.6 20.7 3.5
20°F T 30°F T 40°F T
28
Page 29
4 Hydronic piping (continued)
3
3
Installation & Service Manual
Hot water pip ing must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and con trac tion. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the relief valve section on page 26 of this manual.
CAUTION
A leak in a boiler system will cause the system to intake fresh water constantly, which will cause the tubes to accumulate a lime/scale build up. This will cause a NON-WARRANTABLE FAILURE.
Water Connections Heating Boilers Only
All water heaters and heating boilers with inputs of 315,000 ­500,000 Btu/hr have 2" NPT.
CAUTION
Field installed reducing bushings may de crease flow re sult ing in boiler noise or flashing to steam.
Circulator Pump Requirements
This is a low mass, high efficiency hot water boil er which must have adequate flow for quiet, efficient op er a tion. The boiler circulating pump must be pur chased locally. The boiler circulator pump must operate con tin u ous ly while the boiler is firing. Pump selection is critical to achieve proper op er­a tion. A pump should be selected to achieve proper system design water temperature rise. A heat ex chang er pressure drop chart (Table 4C) is provided to assist in proper pump selection. Also provided is a System Temperature Rise Chart (Table 4B). This table provides GPM and boiler head-loss at various temperature rises for each boiler based on Btu/ hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing. Example: The boiler inlet tem per a ture is 160°F and the boiler outlet temperature is 180°F, this means that there is a 20°F tem per a ture rise across the boiler.
3. Cast iron circulators may be used for closed loop systems.
4. A properly sized expansion tank must be in stalled near the boiler and located on the suction side of the pump.
TABLE - 4C
HEAT EXCHANGER PRESSURE DROP CHART
7
7
6
6
5
5
4
4
FT/HD
FT/HD
3
3
2
1
0
0 5 10 15 20 25
Gallons per Minute
CB 399
CB
399
Circulator Pump Operation (Heating Boilers
Only)
Boilers are equipped with a relay for controlling the circulation pump for the hot water loop. The relay turns ON and OFF in response to the “W” input from the wall thermostat or zone control.
The field installed boiler pump MUST NOT exceed 1 h.p. For continuous pump operation, wire the system pump to the 120V supply. The pump should be connected at the junction box as shown in FIG. 4-3.
120V
SUPPLY
CB
CB
315
315
CB 500
CB
500
CB 360
CB
30 35
360
Circulator Pump Specifications
1. Maximum operating pressure for the pump must exceed system operating pressure.
2. Maximum water temperature should not ex ceed nameplate rating.
Figure 4-3_Boiler Wiring - Circulation Pump to Junction Box
TO
UNIT
TO
CIRCULATION
29
Page 30
4 Hydronic piping
Installation & Service Manual
PUMP INSTALLATION AND MAIN TE NANCE: The boiler circulating pump must be purchased lo cal ly. For installation and maintenance information on the circulator pump, refer to the pump man u fac tur ers in struc tion package included with the pump.
Primary/Secondary Boiler Piping
Heating boilers with inputs of 315,000 - 500,000 Btu/hr or larg er installed on multiple zone systems are rec om mend ed to be installed with a primary/sec ond ary piping sys tem as shown in FIG. 4-4. A primary/secondary piping system uses a dedicated pump to supply flow to the boiler only. This pump is sized based on de sired boiler flow rate, heat exchanger head loss and head loss in the sec ond ary system piping only. The secondary pump, in stalled in the boiler piping, ensures a constant wa ter flow rate to the boiler for proper operation. Boiler installation with a primary/secondary piping sys tem can prevent noise problems caused by low sys tem water flows. A primary/secondary piping system is recommended on any boiler where low water flow conditions may present an operational problem.
A primary/secondary piping system is ideal for sys tems filled with a propylene glycol and water mix ture. A glycol and water mixture is more dense than water only and may result in a lower boiler flow rate. A lower boiler flow may cause noise on operation or short cycling of the burners. A larger secondary pump may be used on a primary/sec ond ary system to pro vide an increased boiler flow rate. A glycol and water system may require from 10 to 20% more flow to compensate for the in creased density of the glycol and its effect on the heat transfer process in the boiler. The exact in crease in flow that may be required is based on the type and percentage of glycol added to the boiler system. Consult the manufacturer of the glycol for additional recommendations when using a gly col and water fill for your boiler system.
The installer must ensure that the boiler has ad e quate flow without excessive temperature rise. The tem per a ture rise on a multiple zone system should be made when only the zone with the longest length and/or high est head loss is open. Low system flow can result in overheating of the boiler water which can cause short burner on cycles, system noise and in extreme cases, a knocking flash to steam. Sys tem noise may also indicate an oversized boiler.
CAUTION
NOTICE
At no time should the system pressure be less than 12 PSIG (83 kPa) (Non-metallic system piping must have an oxygen barrier to be considered a closed loop).
A boiler operated with an inlet temperature of less than 140°F (60°C) must have a low temperature bypass to prevent problems with condensation. A 1 1/2" LTV Valve Kit may be used. Follow the piping diagram in FIG. 4-5 to complete installation.
30
Page 31
4 Hydronic piping (continued)
Installation & Service Manual
Low Temperature Bypass Requirements
This piping is like a primary/secondary boiler installation with a bypass in the secondary boil er piping. Inlet water temperatures below 140°F (60°C) can excessively cool the prod ucts of combustion re sult ing in condensation on the heat exchanger and in the flue. Condensation can cause operational prob lems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system and related components. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to in crease the boiler inlet temperature above 140°F (60°C). This should prevent the prod ucts of com bus tion from condensing in most in stal la tions.
The bypass should be fully sized with a bal anc ing valve to allow for proper adjustment. A valve must also be provided on the boiler discharge, after the by pass. Closing this discharge valve forces water through the bypass. Start boiler adjustment with the bypass valve in the full open position and the boiler discharge valve half open. A small amount of the high er temperature boiler discharge water is mixed with the system water to maintain the de sired lower system tem per a ture. A remote low tem per a ture range operator is recommended to control the boiler operation for temperatures lower than 100°F. This remote op er a tor should be wired across the R and W terminals (see Room Ther mo stat Connection and Terminal Strip Instructions in Section 5 of this manual).
Three Way Valves
Boiler Flow Rates
TABLE - 4D
MAXIMUM FLOW FOR HEATING BOILER
The maximum flow rate through the boiler with a copper
heat exchanger must not exceed the following:
Model Maximum Flow
90,000 - 500,000 30 GPM 38 GPM
The heat exchanger is generally capable of op er at ing within the flow rates of a residential heating system. Should the flow rate exceed the maximum allowable flow rate through the boiler 30 GPM) an external bypass must be installed. The bypass should be fully sized with a balancing valve to al low for proper ad just­ment of flow. Flow rate can be determined by measuring the temperature rise through the boiler.
The basic guide for minimum flow in this boiler is based on a 40°F temperature rise in most in stal la tions. Low er flow and a higher temperature rise is acceptable if the boiler system is specifically de signed for the char ac ter is tics of a higher tem­per a ture rise. A system not specifically designed for a higher temperature rise may experience over heat ing of the boiler water. This can cause short burn er on cycles, system noise and in ex treme cases, a knocking flash to steam. These con di tions can lead to operational problems and non-war rant able fail ures of the boiler. High temperature rise systems must be designed by a qualified engineer.
Maximum Flow for
CuNi Heat Exchanger
The installation of a three way valve on this boiler is not generally recommended because most piping meth ods allow the three way valve to vary flow to the boil er. This boiler is a low mass, high ef fi cien cy unit which requires a constant water flow rate for proper op er a tion.
Low flow rates can re sult in overheating of the boiler water which can cause short burner on cycles, system noise and in extreme cases, a knocking flash to steam. These conditions can cause operational prob lems and non-warrantable failures of the boiler. If a three way valve must be installed, please pipe in a primary/secondary system. Based on boiler sizing and system flow requirements, this piping may still result in boiler short cycling.
31
Page 32
4 Hydronic piping
Primary / Secondary Piping
Figure 4-4_Primary / Secondary Piping of a Single Boiler
Installation & Service Manual
AIR SEPARATOR
DRAIN POINT
(TYPICAL)
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
(WHEN USED)
M
E
T
S
Y
S
O
T
MAKE UP W ATER
WATER METER
PRESSURE REDUCING
LOW LOSS HEADER
BACK FLOW PREVENTER
MAY SUBSTITUTE
VALVE
PRESSURE GAUGE
EXPANSION TANK
VALVE (TYPICAL)
BOILER CIRCULATOR
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART
Y-STRAI NER
FLOW CHECK
S
SY
M
O
R
F
BALL VALVE (TYPICAL)
DIR #2000548410 00
M
E
T
PRESSURE RELIEF VALVE
TEMPERATURE / PRESSURE
FLOW SWITCH
DRAIN
BOILER
UNION (TYPICAL)
NOTICE
32
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Page 33
Installation & Service Manual
4 Hydronic piping (continued)
Primary / Secondary Piping
Figure 4-5_Single Boiler - Primary / Secondary with Low Temperature Bypass
AIR SEPARATOR
DRAIN POINT
(TYPICAL)
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
(WHEN USED)
M
E
T
S
Y
S
O
T
MAKE UP W ATER
WATER METER
PRESSURE REDUCING
BACK FLOW PREVENTER
MAY SUBSTITUTE
LOW LOSS HEADER
VALVE
PRESSURE GAUGE
EXPANSION TANK
VALVE (TYPICAL)
BOILER CIRCULATOR
FLOW CHECK
M
E
T
S
SY
M
O
R
F
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART
BALL VALVE (TYPICAL)
LOW TEMPERATURE BYPASS
PRESSURE RELIEF
VALVE
Y-STRAINER
FLOW SWITCH
DRAIN
TEMPERATURE / PRESSURE
GAUGE
BOILER
NOTICE
UNION (TYPI
DIR #2000548419 00
CAL)
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
33
Page 34
4 Hydronic piping
Primary / Secondary Piping
Figure 4-6_Multiple Boilers Zoned with Circulators
TEMPERATURE
LOOP 3
TEMPERATURE
LOOP 2
TEMPERATURE
LOOP 1
Installation & Service Manual
M
E
T
S
Y
S
O
T
M
E
T
S
Y
S
M
O
R
F
MAKE UP WATER
WATER METER
BACK FLOW PREVENTER
PRESSURE
PRESSURE
REDUCING
VALVE
NOTICE
AIR SEPARATOR
GAUGE
E
XPANSION
TA
NK
I
NDI
RECT
TANK
ANTI-SCALD
MIXING VALVE
HOT
WATER OUT
COLD WATER IN
DH
SUBSTITUTE LOW
LOSS HEADER
W
SYSTEM SUPPLY
( WHEN USED )
DRAIN POINT
MAY
DRAIN
SENSOR
(TYPICAL)
PRESSURE RELIEF VALVE
FLOW VA
LVE
CHECK
NOT EXCEED 12" APART
BALL
VALVE
(TYPICAL)
B
O
I
LER
DRAI ( TYPICAL )
CIRCULATO
N
U
NION (TYPI
DO
MESTIC
HOT WATER
CIRCULATOR
R
BOILER
CAL)
1
DIR #2000548422 00
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
Y-STRAINER (TYPICAL)
FLOW CHECK VALVE (TYPICAL)
BOILER 2
TEMPERATURE / PRESSURE ( TYPICAL)
PRESSURE RELIEF VALVE (TYPICAL)
GAUGE
34
Page 35
5 Electrical connections
Installation & Service Manual
This appliance is wired for 120 VAC service. The appliance, when installed, must be electrically ground ed in accordance with the requirements of the authority having jurisdiction or in the absence of such re quire ments, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. When the unit is in stalled in Canada, it must conform to the CSA C22.1, Ca na di an Electrical Code, Part 1 and/or local Electrical Codes.
1. All wiring between the appliance and field in stalled devices shall be made with type T wire [63° F(35° C) rise].
2. Line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.
3. The pump must run continuously when the appliance is being fired.
4. To avoid serious damage, DO NOT en er gize the appliance until the system is full of water. Serious damage may result.
5. Provide the unit with proper overload protection.
Remove the jumper between the R and W terminals on the terminal strip. Refer to the chart in this section (Table 5A) to determine maximum allowable length and wire gauge recommended to connect the switching con tacts of the room thermostat to the R and W terminals on the terminal strip. Connection to the terminal strip will allow the room thermostat to make and break the 24 VAC boiler control circuit turning the boiler on and off based on the room ambient temperature require ments. Set the boiler operating temperature control as described in this section.
B
DETAIL
A
6. Install a wall thermostat on the inside wall. DO NOT install the thermostat in an area affected by drafts, sunlight, light fixtures, hot or cold water pipes or near a fireplace. See “Terminal Strip Con nec tion of a Room Thermostat” (this page), for prop er wiring con nec tion.
Boiler Operating Temperature Control
The operating temperature control is located in the control panel, behind the control panel front ac cess door. The sensing element for the operator is placed in a bulbwell installed in the heat exchanger. Carefully observe the inlet water temperature on the initial boiler on cycles. The exact temperature set point is based on your system’s requirements. Turn the con trol set point dial to the desired operating water tem per a ture. Observe the boiler discharge tem per a ture after each set point adjustment to ensure prop er operation.
Room Thermostat or Remote Thermostat Connection to Terminal Strip
A room thermostat or remote temperature control may be connected to the boiler. The room ther mo stat should be installed on an inside wall, away from the influences of drafts, hot or cold water pipes, lighting fixtures, televisions, sun rays or fire plac es. Follow the manufacturers instructions supplied with the ther mo stat for proper installation and ad just ment. The boiler is equipped with a terminal strip on the left side of the control panel to allow easy connection (FIG. 5-1).
Figure 5-1_Terminal Strip Connections
TABLE - 5A
TERMINAL STRIP WIRING
Wire Gauge
Allowable Length
12 GA 100 ft.
14 GA 75 ft.
16 GA 50 ft.
18 GA 30 ft.
Power Venter Connection to Terminal Strip
A terminal connection strip is provided for ease of connection for Power Venting Systems, see FIG. 5-1, inset A.
A field supplied powered venter or powered louver/damper may be connected to the boiler via a terminal strip located on the left side of the unit, see FIG. 5-1, inset B.
A 24 VAC relay can be powered from this location when a call for heat has been established. A proving switch can be interlocked back to the appliance to ensure its operation before the appliance is allowed to fire.
Reference the wiring diagrams on pages 65 through 68 of this manual.
Maximum
35
Page 36
5 Electrical connections
Pump Wiring for a Heating Boiler
Installation & Service Manual
The heating boiler circulating pump must be pur chased locally. The max i mum load for the pump switched by the internal pump relay must not exceed 1 HP. The current draw for a field installed 120 VAC pump MUST be add ed to the boiler’s current draw to de ter mine the minimum wire size for 120 volt service.
TABLE - 5B
AMP DRAW DATA FOR
STANDARD FIRING CODES
Maximum
Firing Control
Model
CB315 .5
M9
CB360 .5 CB399 .5
CB500 .5
CW90 1.5
CW135 1.5
*F1
CW180 1.5 CW199 1.5 CW225 1.5 CW270 1.5
CW315 1.5
*F9
CW360 1.5 CW399 1.5 CW500 1.5
* 1.0 AMPs added for “PM” water heaters
Total AMPs /
120VAC
TEMPERATURE
CONTROL
IGNITION
MODULE
PUMP
RELAY
MANUAL RESET HIGH LIMIT (IF EQUIPPED)
TRANSFORMER
Figure 5-3_Intermittent Pilot System 500,000 Btu/hr Control Panel
Temperature Adjustment
Operating Temperature Control
NOTICE
WARNING
The temperature controller is pre-set at the factory with test settings. You may need to adjust the settings to meet your specific needs.
Return water temperatures must not be less than 140°F. If lower return water temperatures are required, follow the instructions for Low Temperature
Bypass Requirements or Three-Way Valves, see page 31.
IGNITION MODULE
TEMPERATURE CONTROL
PUMP RELAY
MANUAL RESET HIGH LIMIT (IF EQUIPPED)
TRANSFORMER
INTERMITTENT PILOT SYSTEM M9 CONTROL PANEL
Figure 5-2_Control Panel Assembly 90-135,000 BTU/hr
36
Page 37
Installation & Service Manual
5 Electrical connections (continued)
Locating Temperature Control
Remove the control panel door on the front of the unit in order to locate and access the temperature control.
Temperature Control Settings
Remove the control panel door on the front of the unit unless your unit is specified as a boiler only with an outdoor air reset option. If your unit is a boiler only with an outdoor air reset option, there are additional controls for this option. They are explained under Outdoor Air Reset Option, page 39.
The three setting knobs on the temperature control are for Set point, Differential, and High-Fire Offset (see FIG. 5-4).
NOTICE
Set Point
The Set Point knob specifies the target inlet (or system sensor, if used) water temperature in degrees, Fahrenheit. After the water temperature reaches the set point, the temperature control shuts off the burners.
Differential
The Differential specifies the number of degrees below the set point that the control will allow the water temperature to drop before it brings the unit back on again.
High-Fire Offset
The temperature control operates a two-stage firing system. The two stages are High-Fire and Low-Fire. High-Fire operates all burners at full rate while Low-Fire operates the burners at approximately one-half rate.
Anytime that OJ1 is the only jumper cut, a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 190°F.
Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.
Figure 5-4_Temperature Control
Maximum Set Point Determination
The maximum set point for the control is factory set. Boilers can be set to 240°F max., water heaters are set to 190°F max., and specialty state and local codes to 200°F.
These maximum set points are established by cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller. The maximum set point is determined as shown
below in Table 5C.
TABLE - 5C
MAXIMUM SET POINT DETERMINATION
OJ1 OJ2
Connected Connected 240°F
Cut Connected 190°F
Connected Cut 200°F
Cut Cut 160°F
MAX.
SET POINT
The High-Fire Offset knob specifies the number of degrees below set point that the High-Fire stage shuts down. At that point, the unit will continue to operate at the Low-Fire stage until the set point is reached.
The High-Fire Offset knob has settings between 0°F and 20°F. If set at 0°F, the High-Fire Offset is disabled and the unit will operate the High-Fire stage until the set point is reached and the temperature control shuts the unit off.
If the High Fire Offset knob is set to 0 or 1, the delay will be 10 seconds; if set to 2 or above the delay will be 120 seconds.
Boiler Application
Standard boiler units are equipped with one inlet water temperature sensor. An optional sensor is also provided for use as a remote system sensor. Boilers with the outdoor air reset option also have an outside air temperature sensor.
Water Heater Application
Water heater units are shipped with an inlet water temperature sensor and a multi-purpose temperature sensor to be used as a tank sensor. The inlet water temperature sensor is factory installed on all water heaters.
37
Page 38
5 Electrical connections
Installation & Service Manual
Temperature Control Sensors
This is a two-stage temperature control (M9/F9) that controls the burner ignition and pump functions. This temperature controller can measure up to three different sensor inputs, depending upon how the unit is set up. They are as follows:
1. Inlet Water Temperature Sensor
2. Multi-Purpose Temperature Sensor
3. Outside Air Temperature Sensor
Inlet Water Temperature Sensor
This sensor measures the inlet water temperature coming into the unit.
The inlet water temperature sensor is placed into the inlet bulbwell on the boiler. This sensor is installed by the factory.
Multi-Purpose Temperature Sensor
Depending upon how your unit is set up, this sensor can be used as a system sensor in a boiler system or a tank sensor for water heater applications. Connect this sensor to the two blue wires in the upper left-hand corner of the control panel.
Outdoor Air Temperature Sensor
The outside air temperature sensor will only be used for boiler systems. The outside air sensor is optional. This sensor allows you to tie boiler operation to the outdoor air temperature. As outside temperatures drop, the control will increase the temperature setting of the boiler. As outdoor temperatures rise, the control will decrease the temperature to the selected set point of the boiler. You can set the control to shut the boiler off when a desired outdoor air temperature level is reached.
You must purchase the sensor from the appliance manufacturer. The sensor comes with a housing that helps protect the sensor from the elements. Mount the air sensor housing outdoors, under the eve of the roof. Make sure the housing is out of direct sunlight. This will ensure that the sensor will accurately read the true outdoor temperature. Connect the outdoor air temperature sensor to the terminal block on the outdoor air reset board. For more information on wiring the sensor, see Wiring of Remote Sensors, this page.
Installation of Remote Sensors
Make sure to insert the sensor all the way into the bulbwell, leaving no air pocket between the front surface of the sensor and the back of the bulbwell. Air pockets are thermally non-conductive and will cause sensors to read inaccurately.
Tank Sensor
Water heaters are provided with an extra temperature sensor that MUST be field installed. The sensor is shipped loose in the I & O packet. This remote mounted sensor will be the primary temperature sensor which will inform the appliance’s built-in thermostat control. For domestic water heating, the sensor MUST be installed into a bulbwell on the storage tank. This is required to maintain the desired temperature in the tank and reduce cycling of the heater.
In both applications be sure to insert the sensor all the way into the bulbwell, leaving no air pockets between the front surface of the sensor and the back of the bulbwell. Air pockets are thermally non-conductive and will cause sensors to read inaccurately.
Wiring of Remote Sensors
To wire remote sensors, follow the guidelines below. Take care to correctly wire sensors to the unit. Erratic temperature readings can be caused by poor wiring practices. Twist the wires between the unit and the remote sensor. Turn wires at least three or four turns per linear foot of wiring. This provides protection against some types of electrical interferences.
1. Do not route temperature sensor wiring with building power wiring.
2. Do not locate temperature sensor wiring next to control contactors.
3. Do not locate temperature sensor wiring near electric motors.
4. Do not locate temperature sensor wiring near welding equipment.
5. Make sure good mechanical connections are made to the sensor, any interconnecting wiring and the controller.
6. Do not mount sensor with leadwire end pointing up in an area where condensation can occur.
7. Use shielded wiring to connect the sensor to the control when the possibility of an electrically noisy environment exists. Shielded cable is recommended on all cable runs of more than 25 feet in length.
NOTICE
Ground the cable shield at the connection to the boiler temperature control only. Do not ground the shielded cable at the sensor end.
System Sensor
The system sensor must be installed when piping the boiler in Primary - Secondary fashion when using the Pump Delay option.
38
To maintain temperature accuracy, sensor wires should be 18 AWG two conductor (18/2). Use shielded wire if required.
Page 39
Installation & Service Manual
5 Electrical connections (continued)
Installation of a Remote Sensor (Boiler Application)
1. Turn OFF the main electrical power and the main manual gas shutoff to the appliance.
2. Remove the side access panel from the appliance to gain access to the thermostat.
3. Locate the sensor in the kit. Determine the location of the remote sensor and measure the amount of wire needed to connect the sensor to the thermostat. See Wiring of Remote Sensors on page 38 for guidelines.
4. Use twisted pair wire, minimum 18 gauge or larger. See Table 5A, page 35 regarding distance versus wire gauge. Ensure all wire insulation is trimmed to reveal at least 3/8" of exposed wire.
5. Connect the measured wire to the sensor wire using wire caps (see FIG. 5-5). Install .250 x .032 insulated female quick connect terminals to the end of the wires. Feed the wires through the access hole located on the back of the unit and secure the connectors to the thermostat connections (Sys/Tank) CN5 and CN6 located in the upper right-hand of the thermostat.
6. Turn on the electrical power and the main manual gas shutoff to the appliance.
7. Replace the side access panel.
8. Fire the appliance and resume operation.
Installation of a Tank Sensor (Water Heater Application)
1. Turn OFF the main electrical power and the main manual gas shutoff to the appliance.
2. Remove the side access panel from the appliance to gain access to the wire harness.
3. Locate the two blue wires with a tag notating the remote thermostat sensor. Feed the blue wires through the access hole located on the back of the unit.
NOTE: It will be necessary to add additional wire to
reach from the appliance to the remote water source. Use twisted pair wire, minimum 18 gauge or larger. See Table 5A, page 35 regarding distance versus wire gauge. Ensure all wire insulation is trimmed to reveal at least 3/8" of exposed wire.
4. Connect the wires to the sensor wire using wire caps.
5. Turn on the electrical power and the main manual gas shutoff to the appliance.
6. Replace the side access panel.
7. Fire the appliance and resume operation.
Figure 5-5_Installation of Remote Sensors
Outdoor Air Reset Option
For boilers ordered with the Outdoor Air Reset option, there is an additional control (FIG. 5-6). There are three setting knobs for Shutdown, Outdoor Air Max., and Ratio. There is also a switch to turn the outdoor air shutdown feature On or Off. An O.A. Sensor is also included.
Figure 5-6_Optional Outdoor Air Reset Control
ACCESS HOLE
CONNECT THE MEASURED WIRE TO THE SENSOR WIRE
(c)2002 L.C.
CN7
CN8
CN1
140
120
D4
W1
160
OFF
SETPOINT
55
50
45
VR3
SHUTDOWN
55
50
45
VR1
40
O.A. MAX.
240
60
65
7040
60
65
70
200
7
220
6
DIFFERENTIAL
CN1
O.A. SENSOR
ON
ENABLE
SW1
DISABLE
O.A. SHUTDOWN
0.9
0.8
0.7
0.6
0.5 RATIO
9
8
VR2
5
TST2314
11
1.0
VR2
15
12
1.1
13 14
1.2
1.3
1.4
1.5
W1 W2
5
R16
R15
(F-)0
HIGH-FIRE
OFFSET
CN2
R6
W3
10
VR3
CN3
OJ1
CN4
OJ2
CN5
R4
C7
C9 C10
CN6
J4
R8
CN9
15
20
39
Page 40
5 Electrical connections
Shutdown
The Shutdown knob specifies the outdoor air lockout temperature at which the control would prevent the unit from operating.
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum outdoor air temperature specified by this knob setting. When the outdoor air temperature is above the specified setting, the unit will not function in the O.A. Reset Mode, but will continue to run at the selected set point temperature.
Note that the set point knob will now indicate the “minimum” boiler temperature. Target temperature is determined by the ratio and outdoor air temperature below the O.A. Max setting.
Ratio
The Ratio knob allows control over the reset ratio to be used during Outdoor Air Reset. The allowable ratios are as low as
0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5° for every 1.0° drop in outdoor air temperature up to the maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5° for every 1.0° drop in outdoor air temperature up to the maximum set point temperature.
If the outdoor design and boiler design temperatures are known, the Ratio setting can be calculated using the following formula:
Ratio = (boiler design temperature - operator set point)
(O.A. Max. setting - outdoor design temperature)
Note that the reset set point cannot exceed the maximum set point of the boiler thermostat.
These settings are illustrated graphically in FIG. 5-7.
Installation & Service Manual
Figure 5-7_Outdoor Air Control Example Chart
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns the outdoor air shutdown feature On and Off. Disabling the Outdoor Air Shutdown feature allows the unit to operate regardless of the outdoor air temperature. This is needed for indirect domestic hot water systems for example.
Additional Temperature Controls
High Water Temperature Limit Con trol
The appliance is supplied with a fixed setting, auto-reset high water temperature limit control. The setting of this control limits max i mum discharge water tem per a ture. If water temperature exceeds the setting, the limit will break the con trol circuit and shut down the appliance. The limit control will only be reset after the water tem per a ture has cooled well below the setting of the limit. The auto-reset high water temperature limit control is mount ed in the outlet side of the front header.
40
Page 41
Installation & Service Manual
5 Electrical connections (continued)
Manual Reset High Water Temperature Limit Control (Standard Fixed Settings on Boilers and Water
Heaters with Optional Adjustable Settings)
Water heaters are supplied with a fixed setting, manual reset high water temperature limit control. This manual reset temperature limit control has a fixed limit setting of 230°F (110°C). If water tem per a ture ex ceeds this setting, the limit will break the control circuit and shut down the unit. The limit control can only be reset after the water tem per a ture has cooled well below the setting of the lim it. Reset of the limit con trol is accomplished by push ing the Red Reset But ton (Manual Reset High Limit) (see FIG.’s 5-2 and 5-3 on page 36) located on the front side of the control panel. A label on the control panel indicates the exact lo ca tion of the manual reset high water temperature limit control.
Blocked Vent and Flame Roll-Out / Flame Interlock Switch
BLOCKED VENT SWITCH INVERTED TO SHOW RESET UNDERNEATH
Figure 5-9_Flame Roll-Out / Flame Interlock Switch Location
All units are equipped with manual reset blocked vent and flame roll-out / flame interlock switches. These temperature switches are located in the controls compartment and in the relief opening of the boiler’s built-in draft hood. Each switch has a red reset button. In the event the system has actuated to shut off the main burner gas supply, wait for the boiler to cool, then press the red reset to return the boiler to operation. Op er a tion of a blocked vent and/or flame roll-out / interlock switch usually indicates a problem with the venting system, obstruction of the heat ex chang er flue gas passageway and/or a combustion air supply prob lem. The cause for operation of the blocked vent and/or flame roll-out / interlock switch must be determined and corrected. If the boiler cannot be restored to normal operation, contact a qualified ser vice in stall er, service agency or the gas supplier.
LOWER FRONT JACKET PANEL
HEX FILLER BRACKET
UPPER FRONT JACKET PANEL
FLAME ROLL-OUT SWITCH / INTERLOCK SWITCH
DETAIL
DRAFT HOOD
Figure 5-8_Blocked Vent Switch Location
FRONT OF UNIT
41
Page 42
6 Start-up
Initial Start-up
Follow the Lighting Instructions on the label applied to the appliance.
A. On water heaters and boilers with the system pump
delay option, the operating temperature control will energize the pump relay which energizes the pump on a call for heat. The operating temperature control will de-energize the pump relay approximately 30 seconds after the call for heat ends. If either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
On boilers, the pump will operate whenever the “W”
terminal is energized.
Installation & Service Manual
7. Check carefully for gas leaks.
8. Read the appliance’s safety warnings, light ing instructions and check out procedure carefully, be fore firing the system.
Lighting Instructions for Standing Pilot Models (F1) Models (F1) Models 90,000 through 270,000 Btu/hr Input
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
If you do not follow these in struc tions exactly, a fire or explosion may result causing prop er ty damage, personal injury or loss of life.
B. Location - The appliance should be located within
a room having a temperature safely above freezing [32°F(0°C)].
C. Shutdown and Draining - If, for any rea son, the
appliance is shut off, the following pre cau tion ary measures must be taken:
1. Shut off gas supply,
2. Shut off water supply.
3. Shut off electrical supply.
4. Drain the heat exchanger completely. Re move one 3/8" NPT plug or bulbwell from the inlet side and one from the outlet side of the front head er of the heat exchanger.
5. Drain the pump. Remove the 3/4" plug in the bypass loop.
Pre-start Checklist
1. Inspect the burners to be sure they are prop er ly aligned.
2. Inspect the pilot gas line, thermocouple leads, ignition
leads and wire connections to the gas valve to be sure none were damaged during shipment.
3. Check to ensure that gas connections have been made
properly and the gas line is purged of air.
A. This appliance has a pilot which must be ig nited
by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE OPERATING, smell around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a near by
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not turn by hand, don’t try to repair it, call a qualified ser vice technician. Force or attempted repair may result in a fire or explosion.
4. Check to ensure that water connections are tight and the
appliance and piping system have been properly filled.
5. Ensure that discharge from the relief valve has been piped
to a floor drain.
6. Verify that properly sized combustion and ven ti la tion air
openings are provided and not obstructed in any way.
42
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance. The pos si ble damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Page 43
6 Start-up (continued)
Installation & Service Manual
Lighting Instructions
1. STOP! Read the safety information (page 42).
2. Remove the control panel door.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
5. Turn the gas control knob on the gas valve clockwise to the “OFF” position.
Figure 6-1_Gas Valve 90,000 - 270,000 Btu/hr Models
F-1 GAS VALVE
90,000 -270,000 BTU MODELS
TOP
Figure 6-2_Pilot Location
Pilot Location
Main Burner
TOP OF FLAME SPREADER TO BE FLUSH WITH TOP OF BURNER
9. Turn the control knob on the gas valve coun ter clock­wise to the “PILOT” position.
Figure 6-3_Lighting Wand
FLOW
SIDE
OUTLET
6. Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the“What To Do If You Smell Gas” section in the safety information on page 42. If you do not smell gas go on to the next step.
7. Remove the lower panel door to gain access to the pilot.
8. Find the pilot - Follow the metal tube from the gas valve to the pilot. The pilot is located on the right side of the burner approximately centered in the burner tray.
NOTICE
USE A FIELD SUPPLIED LIGHTER OR THE FACTORY SUPPLIED LIGHTING WAND TO LIGHT THE STANDING PILOT
The information package shipped with the appliance contains a wire lighting wand. The loop end of the wand will hold a match. The wand extends your reach to the pilot and makes lighting the pilot easier (see FIG. 6-3).
43
Page 44
6 Start-up
Installation & Service Manual
10. Use the loop end of the wire lighting wand, shipped with the instruction pack age, to hold the match and reach the pi lot. An access slot is provided in the lower front jacket panel, beside the burner, to insert the lighting wand and match to the pilot. Lift the pilot cover (FIG. 6-3) to access the pilot. Push down and hold in the red button on the gas valve. This should start gas flow to the pilot. Con tin ue to hold the red button in for about one (1) minute after the pilot is lit. Release the button and it will pop back up. The pilot should remain lit. If the pilot goes out, repeat steps 5 through 10.
If the red button does not pop up when re leased, stop
and immediately call your gas supplier.
If the pilot will not stay lit after sev er al tries, turn the gas
control to “OFF” and call your service technician or gas supplier.
11. Turn the gas control knob on the gas valve counterclockwise to the “ON” position.
12. Turn on all electric power to the appliance.
13. Re-install the lower panel door.
14. Set the thermostat to the desired setting.
15. Re-install the control panel door.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
3. Turn the gas control knob on the gas valve clockwise to the “OFF” position. Do not force.
WARNING
Should overheating occur or the gas fail to shut off, turn off the external manual gas valve to the appliance.
Safety Shutoff Test For Standing Pilot Ignition System
PILOT WITH THERMOCOUPLE
Figure 6-4_Pilot with Thermocouple and Spark Ignition
1. With the main burners on and firing, un screw the thermocouple connection from the gas valve (FIG. 6-4) and remove from the fitting.
2. The main gas valve should extinguish the burn ers immediately after removal of the thermocouple.
3. If burners do not extinguish, immediately fol low steps in “To Turn Off Gas To Appliance”.
4. Immediately call a qualified serviceman or in stall er to repair an ignition system that fails to op er ate properly and shut down the burners.
5. After successful completion of test, turn the control knob on the gas valve clockwise to the “OFF” position. Do not force.
6. Carefully reconnect the thermocouple to the gas valve.
PILOT WITH SPARK IGNITION
44
7. Follow the Lighting Instructions to relight the pilot and establish normal operation.
Page 45
6 Start-up (continued)
Installation & Service Manual
Lighting Instructions for Spark Ignition Pilot Models (F9/M9) Models 90,000 through 500,000 Btu/hr Input
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING, smell around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a nearby
phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to turn the gas control knob.
Never use tools. If the knob will not turn by hand, don’t try to repair it, call a qualified ser vice technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance. The pos si ble damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Operating Instructions
1. STOP! Read the safety information first.
2. Remove the control panel door.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
5. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
6a. 90,000 - 135,000 and 399,999 - 500,000 Btu/hr models,
rotate the gas control knob on the gas valve clockwise to the “OFF” position.
6b. 180,000 - 360,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position.
7. Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the “What To Do If You Smell Gas” section in the safety information, this page. If you do not smell gas go on to the next step.
8a. 90,000 - 135,000 and 399,999 - 500,000 Btu/hr
models, rotate the gas control knob on the gas valve counterclockwise to the “ON” position.
8b. 180,000 - 360,000 Btu/hr models, rotate the gas control
knob on the gas valve counterclockwise to the line on the collar around the knob. Al low the knob to “pop” up, and continue rotation to the “ON” position.
9. Turn on all electric power to the appliance.
10. Set the thermostat to the desired setting.
11. Re-install the control panel door.
12. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
45
Page 46
6 Start-up
Installation & Service Manual
To Turn Off Gas to Appliance
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
3a. 90,000 - 135,000 and 399,999 - 500,000 Btu/hr models,
rotate the gas control knob on the gas valve clockwise to the “OFF” position. Do not force.
3b. 180,000 - 360,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position. Do not force.
WARNING
Should overheating occur or the gas fail to shut off, turn off the external manual gas valve to the appliance.
Safety Shutoff Test for Spark Ignition Pilot System
1. Turn “OFF” gas supply to the appliance.
2. Turn thermostat to highest setting.
3. Turn electric power “ON”.
4. Pump relay pulls in to start pump.
5. The ignition will begin sparking at the pilot.
6. The ignition module will lock out after the trial for ignition period.
7. Immediately call a qualified serviceman or in stall er to repair an ignition system that fails to lock out and properly shut down burner operation.
8. After successful completion of the test, re ad just the thermostat to normal setting.
9. Turn “ON” gas supply.
10. Turn power “OFF” then “ON” to reset ignition module.
11. If ignition system fails to operate properly, re pair work must be performed by a qualified serviceman or installer.
Intermittent Pilot Spark Ignition System (F9/M9)
The ignition module is not repairable. Any mod i fi ca tion or repairs will invalidate the warranty and may create hazardous conditions that result in prop er ty damage, personal injury, fire, explosion and/or toxic gases. A faulty ignition module must be re placed with a new module.
Freeze Protection
1. For water heaters and boilers that utilize the pump delay option, if either the inlet sensor or the optional multi­purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
2. Location - Heating boilers and water heaters must be located in a room having a temperature safely above freezing [32°F(0°C)].
3. Caution - A room where the appliance is installed and operating under a negative pressure may experience a downdraft in the flue of an appliance which is not firing. The cold outside air pulled down the flue may freeze a heat exchanger. This condition must be cor rect ed to provide adequate freeze protection.
4. Freeze protection for a heating boiler or hot water supply boiler using an indirect coil can be provided by using hydronic system antifreeze. Follow the manufacturers instructions. DO NOT use un di lut ed or automotive type antifreeze.
5. A snow screen should be installed to pre vent snow and ice accumulation around the appliance vent ing system in cold climates.
6. Shut-down and Draining - If for any rea son, the appliance is to be shut off, the following precautionary measures must be taken:
(a) Shut off gas supply.
(b) Shut off water supply.
(c) Shut off electrical supply.
(d) Drain the unit completely. Remove one threaded plug
or bulbwell from the inlet side of the front header and one from the outlet side of the front header on the heat exchanger. Blow all wa ter out of the heat exchanger.
46
(e) Drain pump and piping.
Page 47
6 Start-up (continued)
Installation & Service Manual
Pre-Commissioning Cleaning
1. Prior to fill and start-up, flush the entire heating system.
2. Clean the entire heating system with an approved pre­commissioning cleaner (comparable to Sentinel X300 or Fernox F3) in accordance with the manufacturer’s recommendation to remove debris and prolong the life of the heat exchanger.
3. Clean all water filtering devices in the system.
4. Flush the cleaning solution out of the entire system and refill.
Fill water
Check/control fill water chemistry
IMPORTANT
The manufacturer recommends the following for properly filling your boiler with the appropriate water chemistry for closed loop boilers. Good fill water quality will help extend the life of the appliance by reducing the effects of lime scale buildup and corrosion in closed loop systems.
Hardness between 5 and 15 grains per gallon
1. Consult local water treatment companies for hard water areas (above 15 grains per gallon hardness).
2. Hardness levels that are above 15 grains/gallon can lead to lime scale buildup throughout the boiler system. If the fill water is below 5 grains/gallons, usually due to use of a water softener, it is recommended to mix in some potable water at the inlet to increase the hardness of the water to above 5 grains/gallons.
pH between 6.5 and 8.5
1. pH levels below 6.5 can cause an increase in the rate of corrosion. pH of 8.5 or higher can potentially cause lime scale buildup.
Total Dissolved Solids (TDS) less than 350 ppm
1. Total dissolved solids are all minerals, salts, metals, and charged particles that are dissolved in water.
2. The greater the amounts of TDS present, the higher the corrosion potential due to increased conductivity in the water.
Chlorine concentration less than 150 ppm
1. Do not fill boiler or operate with water containing chlorine in excess of 150 ppm.
2. Filling with fresh drinking water should be acceptable.
3. Do not use the boiler to directly heat swimming pool or spa water.
Conduct water quality testing prior to installing the appliance. Various solutions are available to adjust water quality.
Boiler water
CAUTION
Table 6A Boiler Water Chemistry
Speci cation Range
Dissolved Solids < 2000 ppm
• Monitoring pH, chlorides, TDS, and hardness levels can prolong the life of the appliance by reducing lime scale buildup, corrosion, and erosion. Check for leaks to ensure that fresh water is not entering the system.
Continual fresh makeup water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure.
The addition of oxygen carried in by makeup water can cause internal corrosion in system components.
Leaks in the boiler or piping must be repaired at once to prevent excessive makeup water. For this purpose, it is recommended to install a water meter to easily check the amount of makeup water entering the system. Makeup water volume should not exceed 5% of the total system volume per year. NOTE: When makeup water is added, make sure the chemical additives are added to maintain the correct level.
• An approved multi-metal corrosion inhibitor (comparable to Sentinel X100 or Fernox F1) is recommended at the correct concentration and in the manner recommended by the manufacturer.
Do not use petroleum based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
DO NOT use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel, and/or property may result.
BOILER WATER CHEMISTRY
pH Level 6.5 to 9.5
Chloride < 150 ppm
Freeze protection for a heating boiler system (if required)
WARNING
Ethylene glycol is toxic, DO NOT use as your freeze protection. Ethylene glycol has a sweet aroma which children and pets could mistake as food and ingest; leading to death.
47
Page 48
6 Start-up
1. Use glycol only if needed for freeze protection.
Installation & Service Manual
Fill and test water system
2. Propylene glycol is the recommended freeze protection.
3. Make sure to flush the boiler system before adding glycol.
4. Determine the freeze protection fluid quantity using system water content, following the fluid manufacturer's instructions. Boiler water content is listed on page 6. Remember to include expansion tank water content.
5. Local codes may require a backflow preventer or actual disconnect from city water supply.
6. When using freeze protection fluid with automatic fill, it is suggested to install a water meter to monitor water makeup. Freeze protection fluid may leak before the water begins to leak, causing the concentration to drop, which reduces the freeze protection level.
7. The freeze protection set points may be lowered when freeze protection fluid is used (see the Copper-Fin Service Manual).
8. Consult the glycol manufacturer for details on the suggested mix of glycol and water for the desired freeze protection level and the de-rate effect it will have on the boiler output.
Test / replace freeze protection fluid
1. For systems using freeze protection fluids, follow the fluid manufacturer's instructions.
2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time.
3. It is recommended to test the glycol concentration annually and adjust within the desired set points.
Oxygen prevention
CAUTION
Dissolved oxygen can have a negative effect on the boiler system. Oxygen can cause iron oxide to generate iron deposits. Oxygen may also increase the rate of corrosion on non-stainless steel parts of the system. A low pH level combined with oxygen further enhances its corrosive effects. After boiler installation, check for air leaks in the following areas:
• Suction gasket
Pump
• Air valve
• O-ring gaskets
Precautions include installing a water meter to evaluate the fresh water volume entering the system (should be no more than 5% system volume). Additional volumes of fresh water could indicate that a leak is present.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.
1. Fill system only after ensuring the water meets the requirements of this manual.
2. Close automatic and manual air vents and boiler drain valve.
3. Fill to correct system pressure. Correct pressure will vary with each application.
a. The minimum cold water fill pressure for a system is
12 psi.
b. Pressure will rise when the boiler is turned ON and
system water temperature increases.
4. At initial fill and during boiler startup and testing, check the system thoroughly for any leaks. Repair all leaks before proceeding further.
Purge air from water system
1. Purge air from system:
a. Connect a hose to the purge valve (see purge/drain
valve in the piping diagrams on pages 32 through 34). Route the hose to an area where water can drain and be seen.
b. Close the boiler or system isolation valve between the
purge valve and fill connection to the system.
c. Close zone isolation valves. d. Open the quick-fill valve on the cold water makeup
line.
e. Open purge valve. f. Open the isolation valves one zone at a time. Allow
water to run through the zone, pushing out the air. Run until no noticeable air flow is present. Close the zone isolation valves and proceed with the next zone. Follow this procedure until all zones are purged.
g. Close the quick-fill water valve and purge valve and
remove the hose. Open all isolation valves. Watch that system pressure rises to correct cold-fill pressure.
h. After the system has operated for a while, eliminate
any residual air by using the manual air vents located throughout the system.
i. If purge valves are not installed in the system, open the
manual air vents in the system one at a time, beginning with the lowest floor. Close the vent when water squirts out. Repeat with remaining vents.
2. Open the automatic air vent (diaphragm-type or bladder type expansion tank systems only) one turn.
3. Open other vents:
a. Starting on the lowest floor, open air vents one at a
time until water squirts out.
b. Repeat with remaining vents.
4. Refill to correct pressure.
48
Page 49
6 Start-up (continued)
Check for gas leaks
Installation & Service Manual
WARNING
WARNING
WARNING
Before starting the boiler, and during initial operation, smell near the floor and around the boiler for gas odorant or any unusual odor. Remove the top access panel and smell the interior of the boiler enclosure. Do not proceed with startup if there is any indication of a gas leak. Use an approved leak detection solution. Repair any leaks at once.
Propane boilers only – Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
DO NOT adjust gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.
49
Page 50
7 Domestic water heaters
Installation & Service Manual
Domestic Water Heaters 90,000 ­500,000 Btu/hr Models
This section applies only to those units used to sup ply direct fired domestic hot water and installed with a storage tank(s). The use of a properly sized pump and the control of water velocity, as ex plained in the Water Velocity Control section,
are important for correct operation of your hot water heater.
This section contains specific instructions for those units used to supply domestic hot water. All warn ings, cau tions, notes and instructions in the gen er al installation and service sections apply to these instructions. Water heat ers are designed for installation with a storage tank. The use of a properly sized pump and the control of water velocity, as ex plained below, is important for correct operation of your water heater.
Water Velocity Control
IMPORTANT - To ensure proper velocity through the heat exchanger, it is necessary to regulate the tem per a ture rise across the heat exchanger from inlet to outlet. This must be done on initial in stal la tion and periodically rechecked. With the correct temperature rise across the heat exchanger, you may be assured of the proper velocity in the tubes. This will yield long life and economical operation from your water heater. Excessive lime build-up in the tube is a result of too little velocity in the tubes. Excessive pit ting or erosion in the tube is caused by too much ve loc i ty through the tubes. Care should be taken to measure tem per a ture rise and maintain a velocity as follows:
1. The pump must run continuously when the burners are firing.
2. With the pump running and the water heat er off, the inlet and outlet ther mom e ters should read the same temperatures. If they do not, an adjustment must be made to your final calculation.
3. Turn the water heater on and allow time for the temperature to stabilize. Record the difference between the inlet and outlet temperatures. This difference will be the “tem per a ture rise.”
4. Compare the temperature rise on the heater with the required temperature rise in Table 7A. Should adjustment be needed, proceed as fol lows:
If the temperature rise is too high, the water ve loc i ty is too low. Check the following:
1. Check for restrictions in the outlet of the wa ter heater.
2. Be sure all valves are open between the water heater and the tank.
3. Check the pump to be sure it is running prop er ly and that the pump motor is running in the proper direction.
50
4. Be sure the circulation pipes between the wa ter heater and storage tank are not less than 2" diameter for a single unit installation.
5. Common manifold piping for multiple unit in stal la tions will require larger minimum pipe siz es to tank tappings to ensure proper flow. See Table 7B on page 49.
6. Multiple unit installations may also require a larger circulating pump to achieve the specified flow against the increased head loss of multiple unit com mon manifold piping.
If the temperature rise is too low, the water ve loc i ty is too high. Adjust as follows:
1. Slowly throttle the valve on the outlet side of the water heater until the temperature rise is steady at the required tem per a ture rise as noted in Table 7A.
2. Sustained high water velocity and low tem per a ture rise may result in pitting or erosion of the copper tubes in the heat exchanger. This is a non-warrantable failure. Temperature rise must be properly adjusted to achieve the specified flow rate.
TABLE - 4D
MAXIMUM FLOW FOR HEATING BOILER
The maximum flow rate through the boiler with a copper
heat exchanger must not exceed the following:
Model Maximum Flow
90,000 - 500,000 30 GPM 38 GPM
Maximum Flow for
CuNi Heat Exchanger
Required Temperature Rise
Temperature rise is based on the hardness of the potable water to be heated. The temperature rise specified is for water with a hardness of 5 to 20 grains per gallon. The total dissolved solids shall not exceed 350 ppm.
TABLE - 7A
REQUIRED TEMPERATURE RISE
Btu/hr
INPUT
90,000 30 5
135,000 30 7
180,000 30 10
199,999 30 11
225,000 30 12
270,000 30 15 315,000 30 17 360,000 30 20 399,999 30 22 500,000 30 28
Flow Rate
GPM
Temperature Rise °F
Page 51
Installation & Service Manual
7 Domestic water heaters (continued)
Water Chemistry
The required temperature rise and the standard pump sizing are based on the heating of potable water with chemistry within the specified limits. Caution should be used when heating water softened to less than 5 grains per gallon. Many commercial water softeners reduce hardness to 0 grains which may result in long term problems in the system. Softened water will usually have a lower pH which can be aggressive and corrosive causing non-warrantable damage to the heater, pump, and associated piping.
Corrosion due to water chemistry generally shows up first in the hot water system because heated water increases the rate of corrosive chemical reactions. As water is heated it becomes less soluble. The dissolved minerals and solids will precipitate and collect as scale if water velocity is not properly controlled. Follow the temperature rise requirements for unsoftened water. Consult the manufacturer when heating potable water with hardness or total dissolved solids exceeding these specifications. Heating of high hardness and/or high total dissolved solids water may require a larger circulating pump, an optional cupro-nickel heat exchanger and a revised temperature rise specification based on the water chemistry of the water to be heated.
Softened Water Systems
Decreasing the flow rate will reduce the erosion process, however the heat exchanger should be monitored to ensure the scale/liming process is not made worse. The unit should be placed on a comprehensive inspection schedule until optimum flow rates can be established. Problematic water areas may require heat exchanger inspection every two weeks. The total scale accumulation should never exceed the thickness of a piece of paper. Should scale accumulation exceed this thickness the flow rate will need to be increased. The tubes should not have a bright shiny copper look. This would indicate that the erosion process has begun and the flow rate will need to be decreased. Once the proper flow rates have been established the inspection intervals can be increased to every 30 days, once a quarter, or to a bi-annual inspection. This procedure should ensure proper operation of the unit as long as the water quality stays consistent.
TABLE - 7B
COMMON WATER MANIFOLD SIZE FOR
MULTIPLE HOT WATER SUPPLY BOILER
INSTALLATIONS
Pipe sizing chart provides minimum pipe size for common manifold piping and tank tappings to ensure adequate flow.
Number of Units Common Manifold Size (Min.)
12"
22"
3 2 1/2"
43"
5 3 1/2"
6 3 1/2"
Pump Operation
1. The water heater/hot water supply boiler must be connected to a properly sized pump that circulates water between the heater and storage tank.
2. A standard water heater is furnished with a 1/6 HP, 120 VAC, 3.6 AMP circulating pump to be mounted on the units in let water connection. This pump is sized based on installation of a single storage tank and heat er in close proximity. If the number of fit tings and straight pipe exceeds the quantities shown in this sec tion, a larger pump will be required.
3. The pump must run continuously when the burners are firing.
4. Lubricate the pump to the manufacturers rec om men da tions. Pump damage due to inadequate lu bri ca tion is non­warrantable.
5. Pump is sized to heater input and water hard ness. Care should be taken to size the pump correctly. See “Water Chemistry”, this page.
The standard pump selection is based on the fol low ing pipe and
fittings from the unit to the stor age tank:
6 - 90° elbows 2 - ball valves 2 - unions 1 - cold water tee
Plus the following length of straight pipe based on the heater size: 90,000 through 360,000 Btu/hr Models Not more than 45 feet of straight pipe
399,999 through 500,000 Btu/hr Models Not more than 25 feet of straight pipe
For every elbow and tee in excess of those shown above, DEDUCT 5 FEET from maximum allowable straight pipe in heater to tank circulating loop.
51
Page 52
7 Domestic water heaters
Figure 7-1_Single water heater_single tank
Installation & Service Manual
COLD WATER
SUPPLY
THERMOMETER
HOT WATER
SUPPLY
UNION
(TYPICAL)
TEMPERATURE
& PRESSURE
RELIEF VALVE
(TYPICAL)
MIXING VALVE
BALL VALVE (TYPICAL)
FLOW CHECK VALVE (TYPICAL)
EXPANSION TANK
BUILDING RETURN
FLOW
SWITCH
WATER HEATER
WATER HEATER CIRCULATOR
STORAGE
TANK
NOTICE
Y-STRAINER
DRAIN
DIR #2000548425 00
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
52
Page 53
Installation & Service Manual
7 Domestic water heaters (continued)
Figure 7-2_Single water heater_multiple tank
FLOW CHECK
COLD WATER
SUPPLY
MIXING VALVE
THERMOMETER
VALVE (TYPICAL)
BUILDING
RETURN
HOT WATER
SUPPLY
UNION
(TYPICAL)
TEMPERATURE
& PRESSURE
RELIEF VALVE
(TYPICAL)
TORAGE TANK
(TYPICAL)
NOTICE
RELIEF VALVE ( TYPICAL )
EXPANSION TANK
TEMPERATURE/ PRESSURE GAUGE
FLOW SWITCH
WATER HEATER
WATER HEATER
ATOR
IRCUL
C
Y-STRAINER
BALL VALVE
(TYPICAL)
DRAIN
(TYPICAL)
DIR #2000548428 00
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
53
Page 54
7 Domestic water heaters
Figure 7-3_Multiple water heater_single tank
COLD WATER SUPPLY
HOT WATER
SUPPLY
TEMPERATUR
& PRESSURE
RELIEF VALVE
MIXING VALVE
THERMOMETER
(TYPICAL)
E
(TYPICAL)
UNION
FLOW CHECK VALVE ( TYPICAL )
EXPANSION TANK
TEMPERATURE/PRESSURE
Installation & Service Manual
BUILDING
RETURN
GAUGE
(TYPICAL)
PRESSURE RELIEF
VALVE
( TYPICAL )
FLOW SWI TCH
( TYPICAL )
STORAGE
NOTICE
TANK
BALL VALVE
TYPICAL)
(
WATER HEATER
DRAIN
DIR #2000548429 00
Y-STRAINER
( TYPICAL)
WATER HEATER
TOR
CIRCULA ( TYPICAL )
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
54
Page 55
Installation & Service Manual
7 Domestic water heaters (continued)
Minimum Pump Performance
Based on heating potable water with a hardness of 5 to 20 grains per gallon and total dissolved solids not exceeding 350 ppm. See “Water Chemistry”, page 49.
TABLE 7C
Water Heater Pump Applications
Model
135,000 2"
180,000 2"
199,999 2"
225,000 2"
270,000
315,000
360,000
399,999 2"
500,000 2"
Pipe Size
90,000
Water
Hardness
5 to 15 gpg TP45PAB 30 8 5°F
2"
15 to 20 gpg UPS 43-100 SF 38 8 4°F
5 to 15 gpg TP45PAB 30 8 7°F
15 to 20 gpg UPS 43-100 SF 38 8 6°F
5 to 15 gpg TP45PAB 30 8 10°F
15 to 20 gpg UPS 43-100 SF 38 8 8°F
5 to 15 gpg TP45PAB 30 8 9°F
15 to 20 gpg UPS 43-100 SF 38 8 7°F
5 to 15 gpg TP45PAB 30 8 12°F
15 to 20 gpg UPS 43-100 SF 38 8 10°F
5 to 15 gpg TP45PAB 30 8 15°F
2"
15 to 20 gpg UPS 43-100 SF 38 8 12°F
5 to 15 gpg TP45PAB 30 8 17°F
2"
15 to 20 gpg UPS 43-100 SF 38 8 14°F
5 to 15 gpg TP45PAB 30 8 20°F
2"
15 to 20 gpg UPS 43-100 SF 38 8 16°F
5 to 15 gpg TP45PAB 30 8 22°F
15 to 20 gpg UPS 43-100 SF 38 8 17°F
5 to 15 gpg TP45PAB 30 8 28°F
15 to 20 gpg UPS 43-100 SF 38 8 22°F
Grundfos
Pump
Flow
Rate
(GPM)
Remote Sensor Installation
Water heaters are provided with an extra temperature sensor that MUST BE field installed. The sensor is shipped loose in the I & O packet. This remote mounted sensor will be the primary temperature sensor which will inform the appliance’s built-in thermostat control. For domestic water heating, the sensor MUST BE installed into a bulbwell on the storage tank. This is required to maintain the desired temperature in the tank and reduce cycling of the heater.
The sensor must also be connected to two blue wires provided in the upper left-hand corner of the control panel. It will be necessary to add additional wire to reach from the appliance to the remote water source. Use twisted pair wire, minimum 18 gauge or larger. See Table 5A, page 35 regarding distance versus wire gauge.
EXTERNAL SENSOR FOR TANK, SYSTEM OR PUMP DELAY
REMOTE SENSOR CONNECTOR IS LOCATED ON SIDE OF UNIT.
NOTE: COLOR OF WIRES AND LEAD STYLES MAY VARY WITH SENSOR PROVIDED. CONNECTIONS ARE POLARITY INSENSITIVE.
Head Loss
(FT)
Temp.
Rise
Heat Exchanger
On all mod els, header inspection plugs can be removed for field in spec tion and cleaning of copper tubes. The entire heat exchanger may be easily removed from the unit.
Thermostat Settings
1. The thermostat is adjusted to a low test set ting when shipped from the factory.
2. Set the thermostat to a maximum water temperature of 125°F which will satisfy hot water demands and prevent risk of scald injury.
Households with small children or invalids may
require 120°F or lower temperature setting to re duce risk of scald in ju ry. Some states may require a lower temperature setting. Check with your gas supplier for local re quire ments governing the tem per a ture setting. Re mem­ber, no water heating sys tem will provide exact tem­per a ture at all times. Allow a few days of operation at this setting to de ter mine the correct temperature set ting consistent with your needs.
NOTICE
CAUTION
Incorrect piping of the cold water supply to the sys tem may result in excessive low temperature op er a tion causing condensate formation on the heat ex chang er and operational problems. The cold water supply piping must be installed in the dis charge piping from the heater to the storage tank. This allows the cold water to be tempered in the storage tank before entering the heater. See typ i cal installation drawings provided in this manual. Higher wa ter temperatures reduce condensate formation.
(1) This water heater, when set at the low er temperature setting, is not capable of producing hot water of sufficient temperature for sanitizing pur pos es. (2) Higher stored water temperature in creas es the ability of the water heater to supply desired quantities of hot water, however remember:
Hotter water increases the risk of scald injury.
SIDE PANEL
Figure 7-4_External Sensor for Tank, System or Pump Delay
55
Page 56
7 Domestic water heaters
Installation & Service Manual
CAUTION
Setting the temperature selector to high­er settings provides hotter water, which in creas es the risk of scald injury.
The manufacturer recommends the use of a prop er ly sized thermostatic mixing valve to supply do mes tic hot water at temperatures less than 140°F. Storing the water at a higher temperature and ther mo stat i cal ly mixing the water will increase the avail able quantity of mixed hot water, greatly reduce the possibility of con den sate formation on the heat exchanger and help pre vent the growth of water born bacteria. Adequate care MUST be taken to prevent potential scald injury when storing water at 140°F and hotter.
:DWHUWHPSHUDWXUHRYHU)&  FDQFDXVHVHYHUHEXUQVLQVWDQWO\RU GHDWKIURPVFDOGV &KLOGUHQGLVDEOHGDQGHOGHUO\DUH DWKLJKHVWULVNRIEHLQJVFDOGHG 6HHLQVWUXFWLRQPDQXDOEHIRUH  VHWWLQJWHPSHUDWXUHDWKHDWLQJ  DSSOLDQFH )HHOZDWHUEHIRUHEDWKLQJRUVKRZHULQJ ,IWKLVDSSOLDQFHLVXVHGWRSURGXFH  ZDWHUWKDWFRXOGVFDOGLIWRRKRW  VXFKDVGRPHVWLFKRWZDWHUXVH  DGMXVWWKHRXWOHWFRQWUROOLPLWRUXVH  WHPSHUDWXUHOLPLWLQJYDOYHVWRREWDLQ  DPD[LPXPZDWHUWHPSHUDWXUHRI  )&
Figure 7-5_Danger Warning
WARNING
Should overheating occur or the gas supply fail to shut off, DO NOT turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
56
Page 57
Installation & Service Manual
7 Domestic water heaters (continued)
Relief Valve
RELIEF
VALV E
FLOW
SWITCH
FLOW
Figure 7-6_Relief Valve - Water heater
This appliance is supplied with a relief valve sized in accordance with ASME Boiler and Pressure Ves sel Code, Section IV (“Heating Boilers”). The re lief valve is mounted directly into the heat ex chang er inside the header (see FIG.’s 7-6 and 7-7). To pre vent water damage, the dis charge from the relief valve shall be piped to a suit able floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION
Avoid contact with hot discharge water.
Water Flow Switch (if equipped)
A water flow switch is available as a factory sup plied option on all water heaters. The flow switch should be wired between terminals X and B. Remove the jumper between the X and B terminals on the terminal strip. This wiring connection installs the flow switch in the 24 VAC safety cir cuit to prove water flow before main burner ig ni tion. A flow switch installed with the fac to ry sup plied minimum adjustment setting requires a spe cif ic minimum flow to make the switch and start burner operation. The flow rate required is a function of the diameter of pipe and tee used for installation. Ensure that the pump installed water heater will supply adequate flow to make the flow switch con tacts and operate the water heater.
Figure 7-7_Water Flow Switch, Water heater
Pressure Only Relief Valve
This water heater/hot water supply boiler is nor mal ly supplied with a temperature and pressure re lief valve sized in accordance with applicable codes. Units may be supplied with an optional pres sure only relief valve. When a water heater/hot water supply boil er equipped with this optional re lief valve is piped to a separate storage vessel, the storage vessel must have a properly installed tem per a ture and pressure relief valve which complies with local codes.
Thermal Expansion
A relief valve which discharges periodically may be due to thermal expansion in a closed system. A hot water supply boiler installed in a closed sys tem, such as one with a backflow preventer or check valve in stalled in the cold water supply, shall be provided with means to control expansion. Con tact the water sup pli er or local plumbing inspector on how to correct this situation. Do not plug or cap the relief valve discharge!
Cathodic Protection
Hydrogen gas can be produced in a hot water sys tem that has not been used for a long period of time (gen er al ly two weeks or more). Hydrogen gas is ex treme ly flammable. To prevent the pos si bil i ty of injury under these conditions, we rec om mend the hot water faucet be open for several minutes at the kitch en sink before you use any electrical ap pli ance which is connected to the hot water sys tem. If hydrogen is present, there will be an un usu al sound such as air escaping through the pipe as the hot water begins to flow. There should be no smoking or open flames near the faucet at the time it is open.
57
Page 58
8 Maintenance
Table 8A_Service and Maintenance Schedules
Installation & Service Manual
Service technician
(see the following pages for instructions)
General:
• Address reported problems.
Inspect interior; clean and vacuum, if necessary;
Check for leaks (water, gas, flue)
• Examine venting system
Check system water pressure/ system piping/expansion tank
• Check fill water meter
Test boiler water. When test indicates, clean system water with approved system restorer following manufacturer's information.
Check control settings
Annual Startup
Check wiring and connections
Owner maintenance
(see the User’s Information Manual for
instructions)
Check appliance area
Daily
Monthly
Periodically
• Check pressure/temperature gauge
Check vent piping
Check relief valve
Test low water cutoff (if used)
Reset button (low water cutoff)
Flame inspection (stable, uniform)
Check flue gas passageways
Inspect and clean the burner
Perform start-up check out and performance verification per Section 6 - Start-up
If combustion or performance indicate need:
Clean heat exchanger
Remove and wash burner
58
Every
6 months
End
of season
months
Check appliance piping (gas and water) for leaks
Operate relief valve
Shut appliance down (unless boiler used for domestic hot water)
Page 59
8 Maintenance (continued)
Installation & Service Manual
WARNING
WARNING
WARNING
CAUTION
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the appliance or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 8A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.
Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Label all wires prior to dis con nec tion when servicing controls. Wiring errors can cause improp er and dangerous operation.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect appliance area
1. Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.
Inspect appliance interior
1. Remove the outer access panels and inspect the interior of the appliance.
2. Vacuum any sediment from inside the appliance and components. Remove any obstructions.
Check all piping for leaks
Listed below are items that must be checked to en sure safe reliable operation. Verify proper op er a tion after servicing.
WARNING
Eliminate all system or appliance leaks. Continual fresh makeup water will reduce appliance life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
Flue vent system
1. Examine the venting system at least once a year. Check more often in the first year to de ter mine in spec tion interval. Check all joints and pipe connections for tightness, corrosion or deterioration. Clean louvers and/or screens in the combustion air intake system as required. Have the entire system, including the venting system, periodically inspected by a qualified service agency.
Check water system
1. Verify all system components are correctly installed and operational.
2. Check the cold fill pressure for the system. Verify it is correct (must be a minimum of 12 PSI).
3. Watch the system pressure as the boiler heats up (during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 3
- Gas Connections.
59
Page 60
8 Maintenance
Installation & Service Manual
Check Expansion Tank
1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 - Hydronic Piping for suggested best location of expansion tanks and air eliminators.
Check fill water meter
1. Check fill water meter for water usage. If the amount exceeds 5% of your system volume, you could have a leak. Have the system checked for leaks and fixed by a qualified service technician.
Test boiler water
1. Test boiler water. Reference the Copper-Fin Installation and Operation Manual for guidelines. When test indicates, clean system water with approved system restorer following the manufacturer’s information.
Check Relief Valve
WARNING
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.
1. Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 4 - Hydronic Piping before proceeding further.
WARNING
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
60
Page 61
8 Maintenance (continued)
Installation & Service Manual
Check All Wiring
1. Inspect all wiring, making sure wires are in good condition and securely attached.
Check Control Settings
1. Adjust settings if necessary. See Section 5 - Electrical Connections for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
Perform Start-up and Checks
1. Start appliance and perform checks and tests specified in
Section 6 - Start-up.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
Check Burner Flame
Visually check main burner flames at each start-up after long shutdown periods or at least every six months. A burner viewport is located on the burner mounting flange.
WARNING
The area around the burner and burner viewport is hot. Direct contact could result in burns.
Combustion Air Adjustment
This ap pli ance uses an atmospheric combustion process. Combustion air is provided to the burners by the gas injection pressure into the venturi of the burn ers. The burners do not have an adjustable air shutter. Ad e quate combustion air must be supplied to the room where the appliance is installed to ensure proper burner operation. Check frequently to be sure the flow of com bus tion and ventilation air to the unit is not obstructed. When the main burn ers light, observe the burn er flame. Flames should be light blue in color with slight yellow tips; flames should be settled on burner head with no lifting when supplied with correct vol ume of combustion air.
Check Flue Gas Passageways
Any sign of soot around the outer jacket, at the burn ers or in the areas between the fins on the cop per heat exchanger indicates a need for cleaning. The following cleaning procedure must only be per formed by a qualified serviceman or installer. Prop er service is required to maintain safe operation. Properly installed and ad just ed appliances sel dom need flue cleaning.
NOTICE
All gaskets on disassembled components must be replaced with new gaskets on re as sem bly. Gasket kits are available from your distributor.
Figure 8-1_Flame Pattern Illustration
NORMAL
A
C
YELLOW FLAME
Normal Flame: A normal flame is blue, with slight yellow tips, with a well defined inner cone and no flame lifting.
Yellow Tip: Yellow tip can be caused by blockage or partial obstruction of air flow to the burner(s).
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner(s) or excessive gas input. This condition MUST be cor rect ed immediately.
Lifting Flames: Lifting flames can be caused by over firing the burner(s) or excessive primary air.
YELLOW TIP
B
D
FLAME LIFT
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
61
Page 62
8 Maintenance
Installation & Service Manual
Inspect and Clean Burner
WARNING
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the jobsite conditions. Current NIOSH recommendations can be found on the NIOSH website at (http://www.cdc.gov/niosh/homepage.html). NIOSH approved respirators, manufacturers and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection. Apply enough water to the combustion chamber lining to
prevent airborne dust.
Remove combustion chamber lining from the appliance
and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from
other clothing. Rinse clothes thoroughly.
NIOSH stated First Aid: Eye: Irrigate immediately. Breathing: Fresh air.
The combustion chamber insulation in this appliance contains ceramic fiber material. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline Silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines:
Heat Exchanger / Burner Access
a. Turn “OFF” main power to the appliance.
b. Turn “OFF” external manual gas shutoff valve to
appliance.
c. Remove the control panel door.
d. Remove the outer air deflector (FIG. 8-2). e. Disconnect gas valve wiring and remove gas
manifold assembly.
f. Remove ignition wire leading to the pilot assembly
from the ignition module.
g. Disconnect the wiring from the flame rollout/
h. Remove the lower front jacket panel.
i. Remove the control panel mounting screws. When
j. Remove the combustion chamber door. Use caution
interlock switch, see FIG. 8-2, page 61.
removing the control panel, lay the control panel to the side with the wiring intact, being careful not to damage any of the wiring.
to prevent damage to burn ers, refractory, pilot or wiring.
Inspection and Cleaning Procedure
DANGER
k. Check the heat exchanger surface for sooting. The
external surfaces of the copper tubes should be free of any soot deposits. (A slight black smudge is normal with some types of gases.) If abnormal soot deposits are present, the heat exchanger must be cleaned and the cause of the soot problem corrected. Proceed as follows:
l. Remove soot from burners and bottom of the finned
tubes with a stiff bristle brush. Dirt may also be removed from burner ports by rinsing the burner thor ough ly with water. Drain and dry burners before re-installing. Damaged burners must be re placed.
An appliance installed in a dust or dirt con tam i nat ed atmosphere will require cleaning of the burners on a 3 to 6 month schedule or more often, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non-combustible particulate mat ter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause non-warrantable failure. Use extreme care when operating an appliance for temporary heat during new construction. The burners will probably re quire a thorough cleaning before the appliance is placed in service.
m. Remove gas manifold as described in steps a. through
e. in “Heat Exchanger/Burner Access.”
n. Loosen mounting screws and remove front control
panel.
o. Loosen screws on the upper front jack et panel and
remove toward front of the appliance. Use caution to prevent damage to re frac to ry on the doors inner surface.
When cleaning burner, DO NOT use a steel wire brush as it may spark and create a hazardous situation causing property damage, serious injury, or death. Use a soft bristle brush when cleaning burner.
62
Page 63
8 Maintenance (continued)
Installation & Service Manual
p. Check “V” baffles on top of the heat ex chang er.
Remove and clean if necessary.
q. Remove soot from the heat exchanger with a stiff
bristle brush. Soot may also be re moved from the heat exchanger by washing thoroughly with detergent and water. Remove the heat exchanger before using water for cleaning. Rinse thoroughly and dry before re-installing. Use a vacuum to remove loose soot from surfaces and in ner chamber.
r. Remove the heat exchanger (HEX) filler bracket
(FIG. 8-2).
s. The heat exchanger can be removed by sliding
towards the front of the appliance. Once the heat exchanger is removed from the ap pli ance, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces.
t. Ensure that all burner ports are cleaned to remove
any soot. See Inspection and Cleaning Procedure, page 60.
u. Carefully re-install the heat exchanger, “V” baffles,
jacket panels, and wires.
Clear Area
1. Keep appliance area clear and free from com bus ti ble materials, gasoline and other flammable vapors and liquids.
2. Check frequently to be sure the flow of com bus tion and ventilation air to the boiler is not obstructed.
Inspection of Heat Exchanger Waterways
Appliances operated in hard water areas should have periodic inspections of the tubes to be sure that no sediment or scale accumulates on the heat transfer sur fac es. Inspection plugs are located at both ends of the heat exchanger. In spec tion plugs should be removed and tubes inspected at the end of the first 45 days of operation and again at the end of 90 days of operation. If no scale accumulation is ob served, inspections can be made at the end of each six months of op er a tion.
Pilot Flame Adjustment Procedure
The pi lot flame should envelop 3/8" to 1/2" (10 to 13mm) of the tip of the thermocouple (see FIG. 8-3).
1/2"
v. Reassemble all gas and water piping. Test for gas
leaks.
w. Cycle the appliance and check for prop er operation.
UPPER FRONT JACKET PANEL
DETAIL
LOWER FRONT JACKET PANEL
HEX FILLER BRACKET
FLAME ROLL-OUT SWITCH / INTERLOCK SWITCH
Figure 8-2_Outer Air Deflector and HEX Filler Bracket
Water Circulating Pump
Inspect pump ev ery 6 months and oil if required. Use SAE 30 non-detergent oil or lubricant specified by pump man u fac tur er.
Figure 8-3_Pilot Flame on Thermocouple
a. Remove pilot adjustment cover screw on the gas
valve. See the Gas Valve illustrations in the Lighting Instructions section (page 43) for the lo ca tion of the cover screw.
b. Turn the inner adjustment screw clock wise to decrease
or counterclockwise to increase pilot flame.
c. Replace the pilot adjustment cover screw on the valve.
Tighten firmly after adjustment to prevent gas leakage.
63
Page 64
8 Maintenance
Installation & Service Manual
IMPORTANT
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat­ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
Gas Train and Controls
GAS FLOW
Figure 8-4_Gas Train 90,000 - 399,999 Btu/hr Models
Review with owner
1. Review the User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the User’s Information Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
Figure 8-5_Gas Train 500,000 Btu/hr Model
64
Page 65
Installation & Service Manual
Replace ignition module
9 Troubleshooting
Troubleshooting Guide: 315,000 - 500,000 Btu/hr Models - Boilers 90,000 - 500,000 Btu/hr Water Heaters F9/M9
Step 1:
Step 2:
Is the spark ignitor sparking?
Yes
Is the pilot staying on?
No
No
Check continuity on the spark cable. Check for 24 VAC on the 24v terminal (gray wire) on the ignition module
Check the pilot tube for gas. Check draft
Yes
No
Check for an open sensor. If no open sensor, make sure there’s a call for heat. If call for heat is present, replace temperature control
No
Step3:
Yes
Is the gas valve getting 24 VAC to the MV terminal?
Yes
No
Check voltage to and from the transformer.
No
Check incoming 120 VAC
Is there 24 VAC (purple wire) on the 4-pin connector plug on the temperature controller?
No
Check gas pressure and make sure gas valve knob is on.
Check 24 VAC at R and W on the terminal strip.
Yes
Check each of the following for an open:
-white and purple wire on the LWCO plug
-rollout switch
-manual reset high limit
-spill switch If any of these devices are open, press the reset button.
Replace the ignition module
No
Yes
Is there 24 VAC (tan wire) on the 4-pin connector plug on the temperature controller?
Yes
Check each of the following for an open:
- X and B on the terminal strip
-purple and gray wires on the vent damper plug
-the two gray wires on the louver plug (315 and 360 models only)
-V and P on the terminal strip
-auto reset high limit
65
Page 66
Installation & Service Manual
g
9 Troubleshooting
Troubleshooting Guide: 90,000 - 270,000 Btu/hr Models - Water Heaters F1
Step 1:
Step 2:
Is the pilot lit?
Yes
Is the gas valve getting 24VAC to the MV terminal?
Yes
No
No
Check gas pressure. Check the pilot assembly and thermocouple. Clean the thermocouple and pilot or replace.
Is there 24 VAC (purple wire) on the 4-pin connector plug on the temperature controller?
Yes
Check for an open sensor. If no open sensor, make sure there’s a call for heat. If call for heat is present, replace temperature control
No
Is there 24 VAC (tan wire) on the 4-pin connector plug on the temperature controller?
Step 3:
66
Check gas pressure and make sure the gas valve knob is on
No
Check voltage to and from the transformer.
No
Check incoming 120 VAC
No
Check 24 VAC at R and W on the terminal strip.
Yes
Check each of the following for an open:
-white and purple wire on the LWCO plug
-rollout switch
-manual reset high limit
-spill switch If any of these devices are open, press the reset button.
Yes
Check each of the following for an open:
- X and B on the terminal strip
-purple and gray wires on the vent damper plug
-V and P on the terminal strip
-auto reset hi
h limit
Page 67
10 Diagrams
Installation & Service Manual
Schematic Diagram - F1 Unit
90,000 - 270,000 Btu/hr Models
Wiring Diagram - F1 Unit
90,000 - 270,000 Btu/hr Models
67
Page 68
10 Diagrams
Installation & Service Manual
Schematic Diagram - F9 Unit
315,000 - 399,999 Btu/hr Models
Wiring Diagram - F9 Unit
315,000 - 399,999 Btu/hr Models
68
Page 69
10 Diagrams (continued)
Installation & Service Manual
Schematic Diagram - M9 Unit
315,000 - 399,999 Btu/hr Models
120
LINE
BK
G
BL
BL
W
3
PR
2
5 VENT DAMPER 3
LOW WATER CUTOFF
OPERATOR
CN1-4
315&360 ONLY
PR
VENT DAMPER
4
AUTO-RESE
HIGH LIMIT
24V
IGNITION MODULE
R
R
CN2-1 CN2-2
34 5
12
T
OFF RELAY ARMING RELAY
OFF RELAY
R
CONTACTS ON ANY FAILURE
LBL20160 REV A
24VDC RELAY
BK
BK
120V
BL Y
24V
CN1-1 OPERATOR CN1-2
1LOW WATER 2
BL
CUTOFF
Y
RW
THERMOSTAT
R
ROLLOUT
PR
SWITCH
4
PR
CN1-3
T
MANUAL RESET HIGH LIMIT
PR
X
LOUVER RELAY
GY
1
1
GY
T
GAS VALVE
PV
PV
BL
PIL
OT
MV
MV
R
LOW
CN3
CN4
CN5
HIGH
O
BK
BK
BL
OPERATOR
CN6
CN7
OR
24VDC RELAY
CN8
OR
OR
W
R
Y
ARMING RELAY
R
PR
CIRCULATION
PUMP
BKPK
MOT
TRANSFORMER
Y
Y
W
24VAC RELAY
PR
PR
FLOW SWITCH
CNO
R
VENTER RELAY
2
R
Y
3
BK
MV/
MV/
PV
PV
W
BURNER GND
HIGH FIRE
W2
R2
T
INLET SENSOR
SYSTEM SENSO
T
BL
R
BL
6
FAILURE CONTACTS
Y
315&360 ONLY
W
SPILL SWITCH
1C
BK
VENTER
PROVING
V
IGNITION MODULE
G
R
TD
TIMER
R
R
BL
W
SPARK
PILOT
7
120V
NEUTRALGROUND
W
Y
PR
B
PR
P
GY
24V GND
Y
Y
Wiring Diagram - M9 Unit
315,000 - 399,999 Btu/hr Models
PILOT
MODULE
IGNITION
BURNER GND
GND
MV
24V
MV/PV
PV
Y
R
W
BL
GY
P
HI
C
PV
MV
W2
R2
LOUVER RELAY
SENSOR
SYSTEM
INLET
SENSOR
BK
R
INLET
SENSOR
O
O.A. SENSOR
CN1
ENABLE
ON
65
60
55
50
45
OUTDOOR AIR RESET
PUMP
RELAY
OR
OUTDOOR
SENSOR
VENT DAMPER
BK
BL
BL
5
SYS/
HIGH
FIRE
0.8
DISABL E
0.7
SW1
O.A. SHUTDOWN
70
VR3
55
40
50
SHUTDOWN-°F
LOW
FIRE
OR
1
TANK
10
2 W
W3
5
1 W
1.1
1.0
1.3
0.9
1.5
13
14
12
VR2
11
RATIO
10
0.5
0.6
9
8
6
7
65
60
70
200
220
VR1
180
40
O.A. MAX.-°F
45
160
0
140
PR
12
T
Y
BL
PR
SPILL
SWITCH
PR
ROLLOUT
21C
T
MANUAL RESET
HIGH LIMIT
OR
OR
LOW WATER CUTOFF
DELAY
PUMP
BK
24VDC
RELAY
(BLACK)
MANUAL
PK
G
GY
20
0
HIGH-FIRE
15
5
DIFFERENTIAL
SWITCH
PR
RESET
W
AUTO-RESET
BN OR BN BK Y
OFFSET
240
F F
SETPOINT
O
A
SPARK
BL
LBL20159 REV A
BOX DEPICTS
OPTIONAL ITE MS
GY
C
R
VENTER
VP
HIGH LIMIT
R=RED
T=TAN
W=WHITE
GY=GRAY
OR=ORANGE
PK=PINK
L=BLUE
BK=BLACK
B
BN=BROWN
Y=YELLOW
PR=PURPLE
G=GREEN
BK
LOUVER
RELAY
PLUG
3
21
GY
Y
GY
VENT
DAMPER
PLUG
GY
1
R
BL
5432
BL R Y
PR
LOW WATER
BN
FLOW
SWITCH
BL
1
CUTOFF PLUG
AUTO
RESET
B
T
X
RW
R1 W1
5
43
WPR T
21
Y R
R
Y
W
P
2
3
4
315&360 ONLY
E
W
BK
Y
OR
BN
1
2
3
4
WHEN REPLACING WIRING, US
WIRE OF EQUAL OR HIGHER
TEMPERATURE AND GAUGE.
Y
BL
G
TRANSFORMER
W
NO C
CONTACT ON
ANY FAILURE
PR
BK
Y
OR
1
2
P1
P2
W
K
BK
P
BK= BL= BN
W
BL
ACK
G
Y=
G
R
AY
R
=
R
BL
UE
O
R
=
O
R
AN PK= PR
G
PI
NK
=
PUR
PL
-
BR
O
W
N
G
=
G
R
EEN
ED
E
T
-
TA
N
W
=
W
H
I
T
Y=
YELLO
E
W
E
BO
X
D
EPI
C
T
S
O
PT
I
O
N
A
L
I
TE
M
S
DISCONNECT POWER BEFORE SERVICING
CIRCULATION
BK
PUMP
BK
BK
Y
G
PP
L
U
JUNCTION BOX
S
R
E
W
O
P
69
Page 70
10 Diagrams
Installation & Service Manual
Schematic Diagram - F9/M9 Unit
500,000 Btu/hr Models
Wiring Diagram - F9/M9 Unit
500,000 Btu/hr Models
3
GY
3
2
YGY
1 2
1
GY BK
BL
INLET
OPTIONAL
1
PUMPRLY
PR
T
T
Y
5
5
4
321
3
2
14
CHASSIS
GROUND
W
LIMIT
RESET
MANUAL
HIGH
PR
Y L B
Y
24VAC
K B
W
P
O
R2
W2
HIGH
LIMIT
BL
SYS/
TANK
CN9
LOUVER
AIR RESET BOARD
"BOILER ONLY"
OUTDOOR
24V
24COM
2
4
3
OPTIONAL
CONTACTS/PROVING
OPERATOR
PROVIDED
LOUVERS
BL
ALARM
CIRCUIT
OPTIONAL
T W
R
PR Y
R
FIELD
Y
DELAY
RELAY
BL
N.O.
COM
TIME
O
Y
ALARM
Y
P
PV
MV
PV/MV
SPARK
HOT
YBLR GYW G
PR
(+)
GROUND
SPLICE
SPLICE
GY
B
24
MODIGNITION
24V
GND
GND
BRN
PV
MV/PV
MV
PRPR
PV
PV/MV
MV
BL
W
R
1
C
Y
BL
XFMR.
24VAC
BK
W
BK
P
AC
24V
Y
C
PR
Y
T
X
NO
Y
GY
PR
R
W
W
1
2
W1
R1
FLOW
JUMPER
LIMIT
OPTIONAL
REMOTE
SWITCHES
THERMOSTAT
BK
BK
O
BK
BL
BL
BK
R
O
O
PR
INLET
OPTIONAL
SYSTEM/ TANK
GY=GRAY
R=REDPR=PURPLE
G=GREEN
PR TW
Y
R
SPLICE
POWER BEFORE SERVICING
BL=BLUE
O=ORANGE
P=PINK
T=TAN
BR=BROWN
Y=YELLOW
= WHITE
= BLACK
W
BK
SPLICE
DISCONNECT
OPTIONAL
PR PR
SPLICE
SPILL
SWITCH
Y
PR
BL
W
2
4
1
3
JUMPER
Y
W
BL
BK
T
Y
O
BK
BR
2
1
P1
P2
A
RESET
JUNCTION
MANUAL
AUTO
RESET
OPTIONAL
GROUND
SPLICE
CHASSIS
GY
GY
GY
1
2
SPLICE
W
GR
GY
P
W
BOX
PUMP
OPTIONAL
GY
BK
HIGH-LIMIT
POWER SUPPLY
AUTO-RESET
AC
24V
C
NO
NC
REV E
P
P
GY
GY
LBL2726
SWITCH
LOUVER
PROVING
CONTACTS
M
MOTOR
LINE
NEUTRAL
LOUVER
60Hz
120VAC
ON
OPERATOR
MOUNTED
RESET BOARD
SEE MANUAL
"BOILER ONLY"
I/O
FIELD
PROVIDED
CONTACTS
Hi-Fire
STG #2
Lo-Fire
STG #1
CN9
CN1
DISABLE
ENABLE
O.A.
SENSOR
SENSOR/WIRING
FIELDINSTALLED
SPARK
PILOT/
SWITCH
ROLL-OUT
OPTIONAL
HIGH LIMIT
ADJUSTABLE
ON
DELAY RELAY
BOILERS
STANDARD ON
SYSTEM PUMP
STANDARD
NC
BL
5
3
4
WATER HEATERS
PUMP
BK
P
O
O
DC
24V
CNONC
USE ELECTRICAL CONNECTION 1& 2
GY
BK
P
V
6
(+)
Y
C
POWER
VENTER
OPTIONAL
SWITCH
BK
C
NO
PROVING
NC
DAMPER
VENT
OPTIONAL
W
BK
120VAC
RELAY 24VAC
70
Page 71
Notes
71
Page 72
Revision Notes: Revision A (ECO #C06290) initial
release. Revision B (ECO C09691) reflects the update of AHRI/
ASME logos on pages 5 and 6. Revision C (ECO C12077) reflects the update of ignition
timing information on page 44 and heat exchanger information on page 51.
Revision D (ECO #C13191) reflects the addition of the CSA Low Lead Content logo on page 6.
Revision E (ECO #C14226) reflects the addition of cautionary statements and notes on page 17 beneath the “Vent Materials” table.
Revision F (ECO C16918) reflects the update of the ratings tables on pages 5 and 6 and the update of Table 3E on page 20 (R07763).
Revision G (PCP #3000006582 / CN #500006680) reflects the addition of new venting information on pages 18 and 19.
Revision H (PCP #3000021634 / CN #500011858) reflects changes made to water chemistry information on pages 4, 28-34, 47-48, 50, 52-55, 58, and 60.
CFA-I-S_MM# 100160907_DIR# 2000001336_Rev H
01/18
Loading...