Lochinvar CWL0647PM User Manual

COPPER-FIN
®
WATER HEATER
Submittal Sheet
CW-Sub-13
COPPER-FIN® GAS WATER HEATERS (MODELS CW 0497-2067)
Standard Features
• 81% Thermal Efficiency
• Electronic Temperature Control
• Fan Assisted Combustion
• Sealed Combustion Chamber
• Stainless Steel Burners
• Low NOx Operation Exceeds the most Stringent Air Quality Requirements
• ASME Copper Finned Tube Heat Exchanger
• 160 psi Working Pressure
• Gasketless Heat Exchanger Design
• All Bronze Circulating Pump
• Pump Delay w/ Freeze Protection
• Remote Tank Thermostat
• Glass-Lined Water Surfaces
• Referenced Gas Valves
• Loch-Heat Ceramic Tile Combustion Chamber
• Hot Surface Ignition
• ASME Temperature & Pressure Relief Valve
• Adjustable High Limit w/ Manual Reset
• Flow Switch
• 24 Volt Control System
• BMS Terminal Strip
• Combustion Air Filter
• 5 Year Limited Warranty on Heat Exchanger (See warranty for details)
Optional Equipment
Alarm Bell Contacts on any Failure Contacts for Air Louvers Cupro-Nickel Heat Exchanger High and Low Gas Pressure
Switch w/ Manual Reset Low Water Cut-Off Stack Frame
MP2 Sequencer
Available Firing Systems
M9 HSI (Standard) M7 California Code
Registered under U.S. Patent 5,989,020
HLW
Copper-Fin® Gas Water Heater Dimensions & Specifications
Input GPH @ Inlet Outlet Model Max. 100°F Gas Water Water Vent Shipping Number Btu/hr Rise A B C D E F G Conn. Conn. Conn. Size Weight
CWN0497PM 495 486 31-1/2” 45-1/4” 22-1/4” 12-1/2” 9-1/2” 22-3/4” 29-1/2” 1-1/4” 2” 2” 6” 490 CWN0647PM 645 633 31-1/2” 56-3/4” 22-1/4” 12-1/2” 9-1/2” 28-1/2” 29-1/2” 1-1/4” 2” 2” 8” 555 CWN0747PM 745 731 31-1/2” 64” 22-1/4” 12-1/2” 9-1/2” 32” 29-1/2” 1-1/4” 2” 2” 8” 610 CWN0987PM 985 967 36” 48-1/4” 33-1/2” 15-3/4” 8-1/2” 8-1/2” 33-1/4” 2” 2-1/2” 2-1/2” 10” 900 CWN1257PM 1,255 1,232 36” 58-1/2” 33-1/2” 15-3/4” 9-1/2” 10-1/2” 33-1/4” 2” 2-1/2” 2-1/2” 12” 1,020 CWN1437PM 1,435 1,409 36” 68-3/4” 33-1/2” 15-3/4” 10-1/2” 10-1/2” 33-1/4” 2” 2-1/2” 2-1/2” 12” 1,065 CWN1797PM 1,795 1,762 36” 82-1/4” 33-1/2” 15-3/4” 11” 11” 33-1/4” 2” 2-1/2” 2-1/2” 14” 1,265 CWN2067PM 2,065 2,027 36” 92-1/2” 33-1/2” 15-3/4” 11” 11” 33-1/4” 2” 2-1/2” 2-1/2” 14” 1,400
Change ‘N’ to ‘L’ for LP gas models.
Water connections for models (CW 0497-0747) are 2” NPT on 6-1/2” centers. Water connections for models (CW 0987-2067) are 2-1/2” NPT on 11-1/4” centers.
Performance data is based on manufacturer test results.
Venting Options
Outdoor Vent Cap and Pump Cover
Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000
Lochinvar.com
Approx. Model No. Fans Controls Pump Total Amps
497 3.6 3.6 5.8 13 647 3.6 3.6 5.8 13 747 3.6 3.6 5.8 13 987 3.4 4.6 7.4 15.4 1257 3.4 4.6 7.4 15.4 1437 3.8 4.6 7.4 15.8 1797 3.8 4.6 7.4 15.8 2067 3.8 4.6 7.4 15.8
5/15—Printed in U.S.A.
Loading...