Lochinvar CVU120 User Manual

CHILLED WATER
BUFFER TANK
Submittal Sheet
CWB-Sub-01
CHILLED WATER BUFFER TANK
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ARCH./ENGR.____________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ GALLON CAPACITY_____________________________________________________________ TANK CONSTRUCTION__________________________________________________________ WORKING PRESSURE___________________________________________________________ DIMENSIONS___________________________________________________________________ WATER CONNECTION SIZE______________________________________________________ WATER CONNECTION TYPE_____________________________________________________ NOTES:
Standard Features Optional Equipment
• Vertical Internal Baffle to encourage proper mixing of fluid
• 125 PSI Working Pressure
• ASME Sec VIII, U-Stamped Vessel
• Flanged Connections
• Red Oxide Paint
• 5 Year Limited Warranty (see warranty for details)
Available Configurations
Place an X in the box by the configuration that applies
Buffer Tank w/ Upper Connections Buffer Tank w/ Lower Connections
Place an X in the box by all options that apply
Temperature and Pressure Gauge R-12 Spray Foam with UV Resistant Exterior Handhole 4”x6” Automatic Air Vent Manway 12”x16” (300 & above) Lifting Lugs
Flanged Connections 3” 4” 5” 6” 8” (300 & above)
Additional Tappings 1” NPT
1.25” NPT
1.5” NPT 2” NPT
2.5” NPT 3” NPT 4” NPT
Chilled Water Buffer Tank w/Upper Connections
Chilled Water Buffer Tank w/Lower Connections
Max. Model Gallon Connection Weight Number Capacity A B D E F Diameter* (lbs.)
CVU120 120 56” 28” 20” 36” 19” 6” 298 CVU200 200 86” 28” 20” 66” 29” 6” 430 CVU300 300 76” 36” 23” 53” 25” 8” 533 CVU400 400 76” 42” 25” 52” 25” 8” 818 CVU500 500 87” 42” 25” 62” 29” 8” 930 CVU750 750 100” 48” 27” 73” 33” 8” 1430 CVU1000 1000 124” 48” 27” 97” 41” 8” 1733
Notes: * For Larger Sizes Consult Factory Custom Sizes and Configurations are Available. Consult Factory for details
Max. Model Gallon Connection Weight Number Capacity A B D E F Diameter* (lbs.)
CVL120 120 56” 28” 32” 24” 37” 6” 298 CVL200 200 86” 28” 62” 24” 57” 6” 430 CVL300 300 76” 36” 49” 27” 50” 8” 533 CVL400 400 76” 42” 48” 29” 50” 8” 818 CVL500 500 87” 42” 58” 29” 58” 8” 930 CVL750 750 100” 48” 69” 31” 66” 8” 1430 CVL1000 1000 124” 48” 93” 31” 82” 8” 1733
Notes: * For Larger Sizes Consult Factory Custom Sizes and Configurations are Available. Consult Factory for details
When ordering it is necessary to specify a water connection size and type.
Buffer Tank Sizing Formula:
Buffer Tank Size = (Required System Volume) - (Actual System Volume)
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax 615-547-1000