Lochinvar CVL1000 User Manual

Total System Efficiency
Lochinvar Chilled Water Buffer Tanks are designed to create volume in a chilled water system when the system and associated piping can not provide the chiller with the volume required for efficient operation. To meet this criteria, Lochinvar has designed a Chilled Water Buffer Tank that is an ASME certified vessel and is available in various custom configurations and tank sizes.
Chiller manufacturers recommend a specific volume of water per ton of chiller capacity to maintain water temperature stability. These recommendations range from 3 to 5 gallons of system volume per ton of chiller capacity when used in a comfort cooling application to system volumes of 6 to 10 gallons per ton when used in a process cooling application where temperature stability is critical.
Chilled Water Buffer Tank
Selecting the right tank is easy. After determining how much additional volume the tank will provide, select the size and configuration of the system connections that will best connect the tank to the chilled water system.
Outstanding Features:
Vertical Internal Baffle to encourage proper mixing of fluid
125 PSI Working Pressure
ASME Sec VIII, U-Stamped Vessel
Five Year Limited Warranty
Flanged Connections
Red Oxide Paint
Optional Equipment:
“R-12” Spray Foam insulation with UV Resistant Exterior
12” x 16” Manway (300 and above)
4” x 6” Hand Hole
Automatic Air Vent
Temperature and Pressure Gauge
Lifting Lugs
Chilled Water Buffer Tank w/Upper Connections
Chilled Water Buffer Tank w/Lower Connections
Max. Model Gallon Connection Weight Number Capacity A B D E F Diameter* (lbs.)
CVU120 120 56” 28” 20” 36” 19” 6” 298 CVU200 200 86” 28” 20” 66” 29” 6” 430 CVU300 300 76” 36” 23” 53” 25” 8” 533 CVU400 400 76” 42” 25” 52” 25” 8” 818 CVU500 500 87” 42” 25” 62” 29” 8” 930 CVU750 750 100” 48” 27” 73” 33” 8” 1430 CVU1000 1000 124” 48” 27” 97” 41” 8” 1733
Notes: * For Larger Sizes Consult Factory Custom Sizes and Configurations are Available. Consult Factory for details
Max. Model Gallon Connection Weight Number Capacity A B D E F Diameter* (lbs.)
CVL120 120 56” 28” 32” 24” 37” 6” 298 CVL200 200 86” 28” 62” 24” 57” 6” 430 CVL300 300 76” 36” 49” 27” 50” 8” 533 CVL400 400 76” 42” 48” 29” 50” 8” 818 CVL500 500 87” 42” 58” 29” 58” 8” 930 CVL750 750 100” 48” 69” 31” 66” 8” 1430 CVL1000 1000 124” 48” 93” 31” 82” 8” 1733
Notes: * For Larger Sizes Consult Factory Custom Sizes and Configurations are Available. Consult Factory for details
When ordering it is necessary to specify a water connection size and type.
Buffer Tank Sizing Formula:
Buffer Tank Size = (Required System Volume) - (Actual System Volume)
CWB-01
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
©-3/10-Printed in U.S.A.
Loading...