Lochinvar COPPER-FIN II CF501, COPPER-FIN II CF1261, COPPER-FIN II CF1441, COPPER-FIN II CF1801, COPPER-FIN II CF2071 Designer's Manual

...
Page 1
DESIGNER’S GUIDE COPPER-FIN II®WATER HEATER
400,000 – 2,070,000 Btu/hr
Page 2
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
The designer’s guide you are now holding has been designed to make it more convenient for you to select the perfect Lochinvar water heater for your projects and provide correct specifications for your teams.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope this manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built water heaters and boilers.
Sincerely,
Lochinvar Corporation
Nashville, TN • 615-889-8900 • Fax: 615-547-1000
Page 3
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 1
Codes . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . .6
Contaminants . . . . . . . . . . . . . . . . . . . .7
Determining Total “Free Area” . . . . . . . .7
Electrical Requirements . . . . . . . . . . . .20
Gas Supply . . . . . . . . . . . . . . . . . . . .17
General Venting . . . . . . . . . . . . . . . . . .7
Location of Unit . . . . . . . . . . . . . . . . . .2
Low Water Temperature Delivery . . . . .18
Outdoor Use . . . . . . . . . . . . . . . . . . . .4
Outdoor Installation . . . . . . . . . . . . . .16
Pump Operation . . . . . . . . . . . . . . . . .19
Relief Valve . . . . . . . . . . . . . . . . . . . .20
Venting Options . . . . . . . . . . . . . . . . . .9
Water Connections . . . . . . . . . . . . . . .18
Water Treatment . . . . . . . . . . . . . . . . .19
Water Velocity Control . . . . . . . . . . . .19
Figures & Tables Index
FIG. 1 Models CF 991-2071
Requirements For Installation
Over Combustible Floor . . . . .3
FIG. 2 Models CF 401-751
Special Combustible
Floor Base . . . . . . . . . . . . . . .4
FIG. 3 Water Heater Equipment
& Control Orientation . . . . . . .5
FIG. 4-7 Combustion &
Ventilation Air . . . . . . . . . . .6,7
FIG. 8 Barometric Damper
Installation . . . . . . . . . . . . . . .9
FIG. 9 Multiple Unit Barometric
Damper Installation . . . . . . .10
FIG. 10 Powered Sidewall Venting
(Powered Vent Cap Shown) . . .10
FIG. 11 Powered DirectAire Horizontal
(Powered Vent Cap Shown) . . .11
FIG. 12 Vertical Vent & Air Inlet . . . . .13
FIG. 13 Vertical Vent & Sidewall
Air Inlet . . . . . . . . . . . . . . . .13
FIG. 14 Aire-Lock Direct Vent . . . . . . .14
FIG. 15 Sidewall Vent . . . . . . . . . . . .15
FIG. 16 Outdoor Venting . . . . . . . . .16
TABLE A. Combustible Floor Kits . . . . . . .3
TABLE B. Clearances From
Combustibles . . . . . . . . . . . . .4
TABLE C. Flue Sizes & Inlet
Air Pipe Sizes . . . . . . . . . . . .9
TABLE D. Powered Sidewall Vent Kits . .11 TABLE E. Power DirectAire
®
Horizontal
Vent Kits . . . . . . . . . . . . . . .12
TABLE F. DirectAire Vertical Air
Inlet Kits . . . . . . . . . . . . . . .14
TABLE G. Direct Vent Kits . . . . . . . . . . .15
TABLE H. Sidewall Vent Kits . . . . . . . . .16
TABLE I. Outdoor Kits . . . . . . . . . . . .17
TABLE J. Gas Supply Pipe Sizing . . . .17
TABLE K. Inlet Gas Pressure . . . . . . . . .18
TABLE L. Required Temperature Rise . .19 TABLE M. Required Pump Performance .19 TABLE N. Common Water
Manifold Sizes . . . . . . . . . . .20
TABLE O. Amp Draw . . . . . . . . . . . . .20
Water Heater Piping Diagrams
Single Heater – Single Tank . . . . . . . . .A1
Single Heater – Two Tanks . . . . . . . . .A2
Two Temperature Installation
Single Heater – Single Tank . . . . . . . . .A3
Two Heaters – Single Tank . . . . . . . . .A4
Two Heaters – Two Tanks . . . . . . . . . .A5
Multi-Stack Frame
Two Heaters Single Tank . . . . . . . . . . .A6
Table of Contents
Page 4
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or B149.2 and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
2 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
1.
Lochinvar
o
Water Velocity
(See page 19 for Required
Temperature Rise chart.)
o
Factory Supplied Pump
Capacity
(See page 19 for Pump Operation.)
o
Manifold Pipe Size
When using more than one heater
(See page 20 for Common Water
Manifold Size for Multiple Water
Heater Installation Table.)
o
Storage Tank Circulating
Tappings
(See page 20 for Manifold Pipe
Size.)
o
Placement of Cold Water
Inlet and Building Return
(See Pages Appendix A for Water
Heater Piping Diagrams.)
o
Water Hardness
(
See page 19 for Water Treatment
Information.)
In designing
a water heater system,
pay special attention to:
Page 5
The indoor units must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
The appliance must be installed on a level, non-combustible floor. Concrete over wood is not considered a non-combustible floor. Maintain required clearances from combustible surfaces.
For installation on a combustible floor only when installed on special base: Units installed over a
combustible floor MUST use the Special Combustible Floor Base. The unit must be centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or
concrete blocks from 8to 12thick and extending 24beyond the sides.
• The blocks must be placed in line so
that the holes line up horizontally to provide a clear passage through the blocks.
This procedure should also be
followed if electrical conduit or radiant heat distribution piping runs through the floor and beneath the appliance.
• Ensure that combustible floor base meets local fire code requirements.
• The correct kit number for the required base is noted on the rating plate of each unit and listed in Table A.
2.
3.
4.
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 3
(FIG. 1) CF 991-2071 REQUIREMENTS FOR
INSTALLATION OVER COMBUSTIBLE FLOOR
(TABLE A)
COMBUSTIBLE FLOOR KITS
MODEL NUMBER KIT NUMBER
CF401 CFK3301
CF501 CFK3302
CF651 CFK3303
CF751 CFK3304
Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit or any of its components.
Page 6
4 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Outdoor models require the installation of an optional vent cap. Instructions for placement of the vent cap are included in the venting section.
Outdoor models must not be installed directly on the ground. The outdoor unit must be installed on a concrete brick, block or other non-combustible pad. Outdoor models have additional special location and clearance requirements. (See Outdoor Venting Pg. 16)
SPECIAL LOCATION: OUTDOOR USE
Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See Outdoor Installation, in the venting section on page 16.
Lochinvar
5.
(FIG. 2) MODELS CF 401-751 INSTALLED WITH
OPTIONAL COMBUSTIBLE FLOOR BASE
(TABLE B) – CLEARANCES FROM COMBUSTIBLES
CLEARANCES CF 401-751 CF 991-2071
Right Side 1 3”
Rear 1 3”
Left Side 6 3”
(24for Service) (24for Service)
Front ALCOVE* ALCOVE*
(24for Service) (30for Service)
Top 1 3”
Flue 1** 1**
Hot Water Pipes 1 1”
* Alcove is a closet without a door. ** Consult local codes and/or vent manufacturer.
Page 7
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 5
(FIG. 3) WATER HEATER EQUIPMENT AND CONTROL ORIENTATION.
OPERATOR INTERFACE
PANEL
GAS
CONNECTION
DRAIN
LEFT SIDE
OPERATOR INTERFACE
PANEL
BURNER INSPECTION PORT
FRONT
AIR INLET
HOT WATER
OUTLET
COLD WATER
INLET
FLUE PRODUCTS VENT
120V ELECTRICAL
CONNECTION
TERMINAL
STRIP
CF401-751
CF991-2071
FLUE PRODUCTS VENT
GAS CONNECTION
TERMINAL STRIP
DRAIN
BURNER INSPECTION PORT
LEFT SIDE
FRONT
COLD WATER INLET
HOT WATER OUTLET
AIR INLET
BACK
Page 8
6 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
COMBUSTION & VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada, the latest edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and Equipment; or applicable provisions of the
local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two
permanent openings:
A. Combustion air opening with a minimum free area of one square inch per 4000 Btu input (5.5cm
2
per kW).
This opening must be located within 12 (30 cm) of the bottom of the enclosure.
B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu input (5.5cm
2
per kW). This opening
must be located within 12” (30cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu input (11cm
2
per kW).
If air is taken from another interior space, each of the two openings
specified above should have a net free
Lochinvar
1.
2.
3.
EXAMPLE OF
SIZING FOR
COMBUSTION
& VENTILATION
AIR OPENINGS
(WATER HEATER
WITH 2,070,000
Btu/hr INPUT):
When combustion and
ventilated air is taken
from directly outside the
building (FIG. 4), divide
the total BTU’s by 4,000.
This yields 517.5 sq.in.
of “Free Area” without
restriction.
(2,070,000 ÷ 4000 =
517.5 sq.in.)
Since the air opening is
50% closed due to
screens and louvers, the
total opening must be
multiplied by 2.
(517.5 sq. in. x 2 =
1,035 sq.in.)
This project requires one
Ventilation Air Opening
with net “Area” of
1,035 square inches with
louver dimensions of 30
x 35and one
Combustion Air Opening
with net “Area” of
1,035 square inches with
louver dimensions
of 30x 35”.
(FIG. 4) COMBUSTION AIR DIRECT FROM OUTSIDE
(FIG. 5) COMBUSTION AIR THROUGH DUCTWORK
(FIG. 6) COMBUSTION AIR FROM AN
INTERIOR SPACE
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
Page 9
area of one square inch for each 1000 Btu (22cm
2
per kW) of input, but not less
than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free area of one square inch per 3000 Btu input (7cm
2
per kW). This
opening must be located within 12 (30cm) of the top of the enclosure.
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the water heater. Burning chemical fumes results in the formation of corrosive acids which attack the water heater, cause improper combustion and premature failure of the water heater and vent. These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
These water heaters are classified as Category I appliances when tested to the latest ANSI Standard. This classification requires all conventionally vented combustion products to be vented using Category I listed vent pipe.
Additionally, it is recommended that this vent material be double wall construction or insulated in the field. A Category I appliance operates with a non-positive static vent pressure and with flue loss greater than 17 percent.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly. The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 7
4.
(FIG. 7) COMBUSTION AIR FROM OUTSIDE,
SINGLE OPENING
CAUTION!
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a down draft in the venting system. If a fan is used to supply combustion air to the equipment room, it must by sized such to make sure that it does not cause drafts which could lead to nuisance operational problems with the water heater.
Page 10
8 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Category I double wall vent (or equivalent) connectors and sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel Gas Code.
The Category I vent and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the vent manufacturer’s listing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in an existing building should be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code.
The weight of the venting system must not rest on the water heater. The venting system must be adequately supported in compliance with local codes and other applicable codes.
Vent Terminations
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.6m) above the highest point of the roof when within a 10 foot (3.05m) radius.
Additionally, vertical terminations must be a minimum of 3 feet (0.9m) above the roof line, and when less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
Vent caps should have a minimum clearance of 4 feet (1.2m) horizontally from, and in no case above or below [unless a 4 feet (1.2m) horizontal distance is maintained], electric meters, gas meters, regulators and relief equipment.
Maintain a distance of at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m) and a distance of at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet.
Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30cm) above grade and clear of snow, ice, leaves or other debris.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows, and building openings
Lochinvar
Page 11
must be consistent with the National Fuel Gas Code Z223.1 or in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
VENTING OPTIONS
Conventional Venting
A conventional venting system utilizes the natural buoyancy of the heated flue products to generate a negative draft. This draft forces flue products to rise vertically through a rooftop flue termination. The vent connection is made directly to the top of the unit and combustion air supplied from the mechanical room. Properly sizing vent material and the use of a barometric damper (when required) will lead to proper vent operation.
A barometric damper is required when draft exceeds 0.08 inches of negative water column. When installed and adjusted properly, a barometric damper will maintain draft between 0.02 and 0.08 inches of negative water column ensuring proper operation.
The minimum flue pipe diameters for all models, utilizing negative draft venting are as follows:
Size vent material using the “FAN” category of vent sizing tables in the latest edition of the National Fuel Gas Code. “FAN” applies to fan-assisted combustion appliances in Category I.
Multiple unit installations with combined venting also require barometric dampers to regulate draft at each unit. Again, the negative draft must be within the range of
0.02 to 0.08 inches of negative water
column to ensure proper operation.
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 9
NOTE:
Flue gases will form a
white plume in winter.
Plume could obstruct
window view. Flue gas
condensate can freeze
on exterior surfaces or
on the vent cap. Flue
gas condensate can
cause discoloration of
exterior building
surfaces. Adjacent brick
or masonry surfaces
should be protected with
a rust resistant sheet
metal plate.
(FIG. 8) BAROMETRIC DAMPER INSTALLATION
(TABLE C)
FLUE SIZES AND INLET AIR PIPE SIZES
MODEL FLUE SIZE DIRECTAIRE
NUMBER INLET SIZE
CF401 6
6
CF501 6
6
CF651 8
8
CF751 8
8
CF991 10
10
CF1261 12
12
CF1441 12
12
CF1801 14
12
CF2071 14
12
NOTE:
A vent system should
never be sized based
only on the vent
connection diameter of
the appliance. For proper
vent design and sizing,
please consult the
National Fuel Gas Code
(ANSI Z223.1).
Page 12
10 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
For this type of installation, it is best to use a draft control for each water heater located on the riser between the vent outlet and the breeching - Location “A”. When this riser is too short to permit the installation of a draft control, locate a separate control for each water heater on the main breeching as illustrated in Location “B”. If, because of general crowding or other reasons, neither of these locations are possible, use a single large control in the breeching between the water heater nearest the chimney and the chimney, as shown in Location “C”.
All draft readings are made while unit is in stable operation (approximately 5 minutes running time).
Masonry Chimney
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to
generate proper draft. This will result in condensing of flue products, damage of the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space.
Carefully inspect all chimney systems during the project design phase. If there is any doubt about the sizing or condition of a masonry chimney, it is prudent to reline the chimney with a properly sized and approved chimney liner system. Metallic liner systems (Type “B” doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Powered Sidewall Venting
This venting system uses a powered vent cap assembly which pulls the flue products out of the stack. The fan in the powered vent cap generates a negative draft at the unit. Combustion air is drawn from the mechanical room (See Combustion and Ventilation Air Requirements, page 6).
Lochinvar
(FIG. 9) MULTIPLE UNIT BAROMETRIC
DAMPER INSTALLATION
(FIG. 10) POWERED SIDEWALL VENTING
(POWERED VENT CAP SHOWN)
NOTE:
Venting of a high
efficiency appliance into
a cold or oversized
masonry chimney can
result in operational and
safety problems.
NOTE:
Common venting
systems may be too
large when an existing
unit is removed. Be
careful to resize any
common venting system
when new appliances
are installed or existing
appliances are replaced.
Page 13
Powered Sidewall Vent Kits
Models CF401-751 utilize a powered vent cap which has a fan mounted inside the cap. The powered vent cap must be placed on an exterior wall. The powered sidewall vent cap and accessories are included in a venting kit, which must be furnished by Lochinvar in accordance with CSA International requirements.
This venting kit includes the powered sidewall fan/cap, proving switch and all necessary relays to interlock with the water heater control system.
Models CF991-2071 utilize an inline fan, which is positioned on the inside of the sidewall and connected to a vent hood mounted on the sidewall exterior. The inline fan and accessories are included in a venting kit, which must be furnished by Lochinvar in accordance with CSA International requirements.
This venting kit includes the inline fan, exterior vent hood, a tapered vent adapter, barometric damper, proving switch and all necessary relays to interlock with the water heater control system.
The connection from the vent to the sidewall fan/powered vent cap must be made with listed Type “B” double wall (or equivalent) vent and accessories. The installer supplies this vent pipe material.
For models CF401-751, maximum total equivalent length of the vent pipe cannot exceed 50 equivalent feet (15.24m). Models CF991-2071 allow a maximum total equivalent length of 100 feet (30.48m). Subtract 5 feet (1.52m) for each elbow in the vent.
Power DirectAire
®
Horizontal
This vent system requires the installation of two vent pipes directly to the unit, one pipe for flue products and one for combustion air. Both vent pipes are installed horizontally with a sidewall termination point. The vent connection is made directly to the top of the unit and utilizes either the powered vent cap or inline fan as described in the side wall venting section (Pages 10-11).
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 11
(TABLE D) POWERED SIDEWALL VENT KIT PART NUMBERS
MODEL FLUE SIZE* SIDEWALL VENT NUMBER CAP KIT
CF401 6
SVK3006
CF501 6
SVK3006
CF651 8
SVK3008
CF751 8
SVK3008
CF991 10
SVK3009
CF1261 12
SVK3010
CF1441 12
SVK3010
CF1801 14
SVK3012
CF2071 14
SVK3012
(FIG. 11) POWER DIRECTAIRE®HORIZONTAL
(POWERED VENT CAP SHOWN)
3’
12”
Page 14
The combustion air supply system has specific vent material and installation requirements. The air inlet pipe connects directly to the water heater to supply combustion air. The combustion air inlet pipe will be a dedicated system with one air inlet pipe per water heater. The air inlet pipe must be connected to a combustion air inlet cap.
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and the following instructions:
The combustion air inlet cap must be installed at least 1 foot (0.30m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination if it is located within 10 feet (3.05m) of the flue outlet.
The combustion air inlet cap must not be installed closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Both the combustion air inlet cap and the powered vent cap/inline fan vent hood must be installed on the same wall and in the same pressure zone.
The Horizontal DirectAire system requires installation of a single wall pipe to supply combustion air from outdoors directly to the water heater. The use of double wall vent material is recommended in cold climates to prevent the condensation of airborne moisture.
For models CF401-751, maximum total equivalent length of the vent pipe and combustion air inlet pipe cannot exceed 50 equivalent feet (15.24m). Models CF991-2071 allow a maximum total equivalent length of 100 feet (30.48m) for each pipe. Subtract 5 feet (1.52m) for each elbow in the vent.
Power DirectAire
®
Horizontal Kits
Models CF401-751 vent kit includes the powered sidewall fan/cap, proving switch, air inlet cap and all necessary relays to interlock with the water heater control system. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
Models CF991-2071 vent kit includes the inline fan, exterior vent hood, a tapered vent adapter, barometric damper, proving switch, air inlet cap and all necessary relays to interlock with the water heater control system. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
The installer supplies all vent pipe material.
Lochinvar
12 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
(TABLE E) POWER DIRECTAIRE® HORIZONTAL
KIT PART NUMBERS
MODEL FLUE SIZE DIRECT AIR HORIZONTAL NUMBER INLET SIZE DIRECTAIRE KIT
CF401 6
6
HDK3031
CF501 6
6
HDK3031
CF651 8
8
HDK3032
CF751 8
8
HDK3032
CF991 10
10
HDK3026
CF1261 12
12
HDK3027
CF1441 12
12
HDK3027
CF1801 14
12
HDK3028
CF2071 14
12
HDK3028
Page 15
DirectAire® Vertical
This vent system requires the installation of two pipes directly to the unit, one vertical pipe with a roof top termination for the flue products and one pipe for combustion air. The combustion air pipe may terminate horizontally with a sidewall air inlet or vertically with a roof top air inlet. Vent connection is made directly to the top of the unit.
No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.02 to 0.08 inches of negative water column. The flue may be combined with the vent from any other negative draft, Category I appliances.
Multiple unit installations common vented with other negative draft appliances require that each water heater must have a barometric damper. The common vent and connectors from multiple water heaters must be sized per the requirements of the venting tables for Type “B” double wall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1.
The air inlet pipe connects directly to the water heater to supply combustion air. The maximum distance for the air inlet pipe is 50 equivalent feet. Subtract 5 feet (1.52m) for each elbow in the air inlet pipe.
Single wall vent material is used to supply the combustion air to each unit. The use of double wall vent material is recommended in cold climates to prevent the condensation of airborne moisture.
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and instructions in this manual.
The combustion air inlet cap must be installed at least one foot (0.30m) above ground level and above normal snow levels. The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap), if it is located within 10 feet (3.05m) of the flue outlet.
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 13
EXAMPLE OF
COMBINED AIR
INLET SIZING Two 8air inlet pipes
(50.3 in2area each) have
a total area of 100.6 in
2
and will require a 12
(113.1 in2area) common
air inlet pipe.
NOTE:
The use of double wall
vent material for the
combustion air inlet pipe
is recommended in cold
climates to prevent the
accumulation of
condensation on the pipe
exterior.
CAUTION!
Water heaters which
are shut down or will
not operate may
experience freezing due
to convective air flow in
the air inlet pipe
connected to the unit.
Proper freeze
protection must be
provided.
(FIG. 12) VERTICAL VENT AND AIR INLET
3’
12”
(FIG. 13) VERTICAL VENT AND SIDEWALL AIR INLET
Page 16
14 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
The combustion air inlet cap must not be installed closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
The vertical air inlet point for the combustion air inlet cap must be installed at least one foot (0.30m) above the rooftop and above normal snow levels. Lochinvar is required to supply a vent kit for DirectAire applications. Each kit includes either a sidewall or roof top combustion air inlet cap to supply air to a single water heater (See Table F, Page 14).
Aire-Lock
TM
Direct Vent
This vent system utilizes the internal blower of the unit to draw all combustion air from outside and vent the by-products of
combustion to the outdoors. This vent system requires the installation of two vent pipes directly to the unit, one pipe for flue products and one pipe for combustion air. Both vent pipes can terminate horizontally at a sidewall or vertically at the rooftop. It is a requirement that both vent pipes terminate in the same pressure zone. The vent system has specific vent material and installation requirements.
The vent piping for flue products uses AL29­4C vent material and must be sealed “gas­tight” at all vent joints. The vent connection is made directly to the top of the unit. The maximum distance for the flue pipe is 50 equivalent feet (15.2m). Subtract 5 feet (1.52m) for each elbow in the flue pipe. The flue products vent pipe is a dedicated system with one flue pipe per unit.
The combustion air supply pipe connects directly to the unit to supply combustion air. The maximum distance for the air inlet pipe is 50 equivalent feet (15.2m). Subtract 5 feet (1.52m) for each elbow in the air inlet pipe.
Lochinvar
(TABLE F)
DIRECTAIRE VERTICAL SIDEWALL & ROOFTOP AIR INLET KITS
MODEL NUMBER VENT SIZE AIR INLET SIDEWALL AIR ROOFTOP AIR
SIZE* INLET KIT INLET KIT
CF401 6 6” SVK3047 VDK3026
CF501 6 6” SVK3047 VDK3026
CF651 8 8” SVK3048 VDK3027
CF751 8 8” SVK3048 VDK3027
CF991 10 10 SVK3040 VDK3023
CF1261 12 12 SVK3041 VDK3024
CF1441 12 12 SVK3041 VDK3024
CF1801 14 12 SVK3041 VDK3024
CF2071 14 12” SVK3041 VDK3024
(FIG. 14) AIRE-LOCK DIRECT VENT
Page 17
The combustion air inlet pipe is a dedicated system with one air inlet pipe per unit. The air inlet pipe must be connected to the Direct Vent (DV) box adapter. The air inlet pipe must be sealed.
Aire-Lock
TM
Horizontal Direct Vent Kits
The vent kit includes a DV box adapter; sidewall air inlet cap and sidewall vent termination. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
Vertical Direct Vent Termination
You must use the vent termination recommended by the vent manufacturer for vertical direct vent terminations.
The installer supplies all vent pipe material.
The combustion air inlet cap must be installed at least 1 foot (0.30m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination if it is located within 10 feet (3.05m) of the flue outlet.
The combustion air inlet cap must not be installed closer than 10 feet (3.05m) from an inside corner of an L-shaped structure.
Both the combustion air inlet cap and the flue gas vent termination must be installed in the same pressure zone.
Sidewall Vent
This vent system utilizes the internal blower of the unit to vent the by-products of combustion to the outdoors. This vent system requires the installation of one pipe for flue products. The vent pipes terminates horizontally at a sidewall. The vent system has specific vent material and installation requirements. The vent piping for flue products uses AL29-4C vent material and must be sealed "gastight" at all vent joints. The vent connection is made directly to the top of the unit. The maximum distance for the flue pipe is 50 equivalent feet (15.2m). Subtract 5 feet (1.52m) for each elbow in the flue pipe. The flue products vent pipe is a dedicated system with one flue pipe per unit.
Sidewall Vent Kits
The vent kit includes a sidewall vent termination assembly to provide pressure equalization. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 15
(TABLE G)
AIRE-LOCK DIRECT VENT KIT PART NUMBERS
MODEL FLUE AIR PART NUMBER SIZE INLET SIZE NUMBER CF401 6
6
DVK3004
CF501 6
6
DVK3004
CF651 8
8
DVK3005
CF751 8
8
DVK3005
CF991 10
10
DVK3000
CF1261 12
12
DVK3001
CF1441 12
12
DVK3001
CF1801 14
12
DVK3002
CF2071 14
12
DVK3002
(FIG. 15) SIDEWALL VENT
Page 18
16 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Lochinvar
The installer supplies all vent pipe material.
Combined Air Inlet Points
In most installations, the combustion air inlet pipe will be a dedicated system with one air inlet pipe per water heater.
Multiple air inlets may be combined to a single common connection if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
The air inlet point for multiple water heater air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors.
The total length of the combined air inlet pipe must not exceed a maximum of 50 (15.25m) equivalent feet. Subtract 5 feet (1.52m) for each elbow in the air inlet pipe. Deduct the restriction in area provided by any screens, grills or louvers installed in the common air inlet point. These are common on the sidewall air inlet openings. Screens, grills or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials used.
OUTDOOR INSTALLATION
Units are self venting and can be used outdoors when installed with the optional Outdoor Cap. This cap mounts directly to the top of the water heater and covers the flue outlet and combustion air inlet openings on the jacket. No additional vent piping is required. Maintain a minimum clearance of 3” (76 mm) to combustible surfaces and a minimum of 3 (76 mm) clearance to the air inlet.
An outdoor unit should not be located so that high winds can deflect off of adjacent walls, buildings or shrubbery causing recirculation. Recirculation of flue products may cause operational problems, bad combustion or damage to controls. The unit should be located at least 3 feet (0.91m) from any wall or vertical surface to prevent adverse wind conditions from affecting performance.
Multiple unit outdoor installations require 48(1.22m) clearance between each vent cap. The outdoor cap must be located 4 feet (1.22m) below and 4 feet (1.22m) horizontally from any window, door, walkway or gravity air intake.
(FIG. 16) OUTDOOR VENTING
(TABLE H)
SIDEWALL VENT KIT PART NUMBERS
MODEL FLUE PART NUMBER SIZE NUMBER
CF401 6
SVK3043
CF501 6
SVK3043
CF651 8
SVK3044
CF751 8
SVK3044
NOTE:
Some discoloration
to building exterior
or unit surfaces
can be expected.
Adjacent brick or
masonry surfaces
should be protected
with a rust resistant
sheet metal plate.
NOTE:
Outdoor models must
have an optional
vent cap and air inlet
shield installed.
Page 19
The combustion air inlet of the outdoor cap must be located at least one foot (0.30m) above grade and above normal snow levels. The water heater must be at least 10 feet (3.05m) away from any forced air inlet and at least 3 feet (0.91m) outside any overhang.
Do not install in locations where rain from building runoff drains will spill onto the water heater.
Lochinvar must furnish an outdoor vent kit in accordance with CSA international requirements. Each kit includes the flue outlet/combustion air inlet, assembly, gasket and pump cover.
Freeze Protection­Outdoor Installation
A snow screen should be installed to prevent snow and ice accumulation around the appliance or its venting system.
If for any reason the unit is to be shut off:
(a.) Shut off water supply. (b.) Drain unit completely. (c.) Drain pump and piping.
If freeze protection is not provided for the system, a low ambient temperature alarm or automatic drain system is recommended.
GAS SUPPLY
The gas pressure regulator supplied is for low pressure service. If upstream pressure exceeds 6 oz. (10.5" water column), an intermediate gas pressure regulator, of the lock up type, must be installed.
The gas line should be a separate line direct from meter, unless the existing gas line is of sufficient capacity. Verify pipe size with your gas supplier.
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 17
(TABLE I) - OUTDOOR VENT KIT PART NUMBERS
MODEL
NUMBER PART NUMBER
CF401 0DK3052 CF501 0DK3052 CF651 0DK3053 CF751 ODK3053 CF991 ODK3049 CF1261 ODK3050 CF1441 ODK3050 CF1801 ODK3051 CF2071 ODK3051
(TABLE J) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron Pipe Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
369 256 205 174 155 141 128 121 113 106 95 86 79 74
697 477 384 328 292 267 256 246 210 200 179 164 149 138
1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14” Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
11/4
3
/4
11/2
1
2
1
/2
31/2
3
2
1.
2.
Page 20
A trap (drip leg) should be provided in the inlet gas connection to the water heater.
A manual main gas shutoff valve is provided outside the jacket, upstream of the main gas valve.
In Canada, derated10% from 2,000 ­4,500 ft., over 4,500 ft. derate must be in accordance with local authorities. Consult factory for installations at higher elevations.
High Altitude Applications
Atmospheric pressure decreases as the height above sea level increases. At any altitude above sea level, a cubic foot will contain less gas than a cubic foot at sea level. Thus, the heating value of a cubic foot of fuel gas will decrease as height above sea level increases.
Specific gravity of a gas with respect to sea level also decreases with altitude. These changes in heating value and specific gravity tend to offset each other.
However, as elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced in an appliance above 2000 feet. Ratings should be reduced at the rate of 4 percent for each 1000 feet above sea level.
WATER CONNECTIONS
Inlet and Outlet Water Connections
For ease of service, install unions on inlet and outlet of the water heater.
The connection on the unit marked “Inlet” should be used for return water from the storage tank. The connection on the header marked “Outlet” should be connected to the inlet of the storage tank. (See Appendix A for Water Heater Piping Diagrams).
LOW WATER TEMPERATURE DELIVERY
A number of water heating applications may require delivered water temperature in a system below 140°F. Systems such as nursing homes and hospitals would be examples of this type of system.
A water heating system that will be operated at less than 140°F must use a mixing valve on the outlet side of the storage tank in order to ensure that the products of combustion do not condense inside the combustion chamber of the water heater.
The mixing valve allows the water heater to operate above 140°F to protect from condensation, while still allowing a delivery of colder water to the system fixtures. Also inherent in this design is the protection of occupants from water containing bacteria such as Legionella. Legionella can be significantly reduced in the water storage vessel by heating the water to a minimum of 140°F. See Appendix A for piping details.
18 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Lochinvar
(TABLE K) – INLET GAS PRESSURE
MODELS NAT. GAS
LPG
CF 401-751
Maximum Allowable 10.5 13 Minimum Allowable 4.5 8”
CF 991-2071
Maximum Allowable 10.5 13 Minimum Allowable 4.5 8”
4.
5.
EXAMPLE OF
HIGH ALTITUDE
APPLICATIONS
For example, if a unit’s
input is 100,000 Btu/hr
at sea level, the rated
input at 4000 feet of
elevation can be calculated
by derating input 4% per
1000 feet above sea
level.
[Btu/hr Input]
[1.00 - (Elevation/ 1000’
x 0.04)] = Btu/hr Input
at specified elevation.
[100,000][1.00 -
(4000’/1000’ x 0.04)] =
Btu/hr Input 4000’
elevation.
[100,000][0.84] =
84,000 Btu/hr Input at
4000’ elevation.
3.
Page 21
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 19
WATER VELOCITY CONTROL
IMPORTANT
To ensure proper velocity through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. (This must be done on initial installation and periodically rechecked).
With the correct temperature rise across the heat exchanger (See TABLE L), you may be assured of the proper velocity in the tubes and long life and economical operation from the water heater.
PUMP OPERATION
The water heater MUST be connected with a properly sized and installed, intermittent operating, all bronze pump that circulates water between heater and storage tank.
The pump is sized to heater input and water hardness. Should water hardness exceed 25 grains/350 TDS, consult factory for pump sizing.
The pump chart (Table M) is based on the following fittings:
6-90° elbows 2 ball valves 2 unions 1 cold water supply tee
Due to pump capacity the following specifications cannot be exceeded when using the standard pump:
• Not more than 45 feet of straight pipe.
• For every elbow and tee in excess of those shown above, DEDUCT 5 FEET from maximum allowable straight pipe in heater-to-tank circulating loop.
WATER TREATMENT
In hard water areas, water treatment should be used to reduce introduction of minerals into the system. Minerals in the water can collect in the heat exchanger tubes causing noise and inefficient operation. Excessive build-up of materials in the heat exchanger can cause a non-warrantable failure.
NOTE:
Care should be taken to
measure temperature
rise and maintain proper
water velocity in the
heat exchanger.
(TABLE L) - REQUIRED TEMPERATURE RISE
MODEL NUMBER TEMPERATURE RISE °F
CF401 12
CF501 15
CF651 20
CF751 23
CF991 19
CF1261 24
CF1441 27
CF1801 34
CF2071 39
(TABLE M) – REQUIRED PUMP
PERFORMANCE FOR WATER HARDNESS
OF 5 TO 25 GRAINS
MODEL GPM FT. HD AMP DRAW HORSE VOLTAGE/
POWER PHASE
CF401-751 55 10 5.8 1/4 120/1
CF991-2071 90 15 7.4 1/2 120/1
NOTE:
A larger pump must be
utilized in situations
where the distance
between the water
heater and tank exceed
those specified.
1.
2.
NOTE:
If a pressure reducing
valve or check valve is
in the system a properly
sized expansion tank
may be required.
Page 22
20 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Lochinvar
Acceptable Water Quality Levels Maximum Water Hardness = 25 Grains Minimum Water Hardness = 5 Grains Maximum Total Dissolved Solids = 350 PPM Range of Acceptable pH = 7.2 to 7.8
Standard production Lochinvar water heaters are designed to operate free of impurity build-up in the heat exchanger when properly installed and operated under the specified water quality conditions.
For installation in areas outside these parameters, please consult the factory.
Water Flow Switch
Due to the low water content (between 1 and 6 gallons) of the copper finned tube heat exchanger, a flow switch is factory installed as a low water cutoff device on models CF401 thru CF2071. The flow switch is installed in the outlet piping from the water heater and wired in series with the ignition system safety controls.
In most localities, a flow switch is acceptable as a low water cutoff device on water heaters requiring forced circulation. It is prudent to verify acceptance with the local code official.
Relief Valve
This water heater is supplied with temperature and pressure relief valve(s) sized in accordance with ASME Boiler and
Pressure Vessel Code, Section IV “Heating Boilers.”
ELECTRICAL REQUIREMENTS
(North America)
The appliance is wired for 120 volts.
All wiring between the unit and field installed devices shall be made of type T wire [63°F (35°C) rise].
The pump must be wired to run continuously when unit is firing.
It is recommended that the water heater and pump be wired on separate circuits with properly sized breakers.
NOTE:
When the unit is
installed in Canada, it
must conform to the
CAE C22.1,
Canadian Electrical
Code, Part 1,
and/or local Electrical
Codes.
NOTE:
Incorrect piping
of the cold water
supply to the
system will result
in condensate formation
on the
heat exchanger
and operational
problems. Higher water
temperatures reduce
condensate formation.
Refer to drawings in
Appendix A.
2.
1.
3.
(TABLE N) – COMMON WATER MANIFOLD
SIZE FOR MULTIPLE WATER HEATER
INSTALLATION
Pipe sizing chart provides minimum pipe size for
common manifold piping to ensure adequate flow.
NUMBER OF COMMON MANIFOLD SIZE
UNITS (Min.)
CF 401 thru 751
12 23 33
1
/2”
44 55 65
CF 991 thru 2071
12
1
/2”
24 34 45 56 66
(TABLE O) – AMP DRAW DATA
MODEL FAN(S) CONTROLS PUMP TOTAL AMPS NUMBER w/PUMP
CF401 3.6 2.7 5.0 11.3
CF501 3.6 2.7 5.0 11.3
CF651 5.4 3.4 5.0 13.8
CF751 5.4 3.4 5.0 13.8
CF991 3.2 7.2 5.8 16.3
CF1261 3.2 7.2 5.8 16.3
CF1441 6.7 7.2 5.8 19.8
CF1801 6.7 7.2 5.8 19.8
CF2071 6.7 7.2 5.8 19.8
Page 23
2005 Elm Hill Pike • Nashville, TN 37210 • 615-889-8900 • Fax: 615-885-4403
COPPER-FIN II®WATER HEATER
PIPING DIAGRAMS
APPENDIX A
Page 24
WATER HEATER PIPING DIAGRAMS
PIPING DIAGRAM SINGLE HEATER - SINGLE TANK
BUILDING HOT
WATER SUPPLY
LOCK-TEMP
STORAGE
TANK
DRAIN
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE ELBOW UNION EXPANSION
TANK
CHECK VALVE
THERMOMETER
COLD WATER SUPPLY
BUILDING RETURN
INLET
OUTLET
LOCHINVAR
WATER HEATER
LEGEND
LIT0133
A1 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
RELIEF VALVE
Page 25
PIPING DIAGRAM SINGLE HEATER - TWO TANKS
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE ELBOW UNION EXPANSION
TANK
CHECK VALVE
THERMOMETER
LEGEND
BUILDING HOT
WATER SUPPLY
LOCHINVAR WATER
HEATER
COLD WATER
SUPPLY
BUILDING
RETURN
LOCK-TEMP
STORAGE TANKS
RELIEF VALVE
DRAIN
OUTLET
INLET
LIT0135
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 A2
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 26
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE ELBOW UNION EXPANSION
TANK
CHECK VALVE
THERMOMETER
LEGEND
PIPING DIAGRAM TWO TEMPERATURE INSTALLATION - SINGLE HEATER-SINGLE TANK
HIGH TEMPERATURE
BUILDING RETURN
LOW TEMPERATURE
BUILDING RETURN
DRAIN
INLET
OUTLET
COLD WATER
SUPPLY
140
0
F HOT
WATER SUPPLY
180
0
F HOT
WATER SUPPLY
LOCK-TEMP
STORAGE TANK
LOCHINVAR
WATER HEATER
MIXING
VALVE
CHECK VALVE
RELIEF VALVE
LIT0136
A3 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 27
PIPING DIAGRAM TWO HEATERS-SINGLE TANK
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE
ELBOW UNION EXPANSION
TANK
CHECK VALVE
THERMOMETER
REDUCING
TEE
REDUCING
TEE
LEGEND
LOCHINVAR
WATER HEATER
INLET
INLET
OUTLET
OUTLET
BUILDING RETURN
DRAIN
LOCK-TEMP
STORAGE TANK
COLD WATER
SUPPLY
BUILDING
HOT WATER
SUPPLY
LIT0138
RELIEF VALVE
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION
Pipe sizing chart provides minimum pipe size for common manifold piping to insure adequate flow.
NUMBER OF COMMON MANIFOLD SIZE NUMBER OF COMMON MANIFOLD SIZE
UNITS (Min.) UNITS (Min.)
CF 401 thru 751 CF 991 thru 2071
12 12
1
/2”
23 24
33
1
/2” 34
44 45 55 56 65 66
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 A4
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Gray shaded area represents common manifold piping.
Page 28
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE ELBOW UNION EXPANSION
TANK
CHECK VALVE
REDUCING
TEE
REDUCING
TEE
LEGEND
PIPING DIAGRAM TWO HEATERS-TWO TANKS
BUILDING
RETURN
LOCHINVAR
WATER HEATER
COLD WATER
SUPPLY
LOCK-TEMP
STORAGE
TANKS
DRAIN
Gray shaded area represents common manifold piping.
INLET
INLET
OUTLET
OUTLET
BUILDING
HOT WATER
SUPPLY
RELIEF VALVE
LIT0451
THERMOMETER
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION
Pipe sizing chart provides minimum pipe size for common manifold piping to insure adequate flow.
NUMBER OF COMMON MANIFOLD SIZE NUMBER OF COMMON MANIFOLD SIZE
UNITS (Min.) UNITS (Min.)
CF 401 thru 751 CF 991 thru 2071
12 12
1
/2”
23 24
33
1
/2” 34
44 45 55 56 65 66
A5 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 29
PIPING DIAGRAM MULTI-STACK FRAME W/WATER HEATERS AND STORAGE TANK
LIT0396
Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900 A6
Page 30
20 Lochinvar DESIGNERS GUIDE COPPER- FIN II WATER HEATER 615-889-8900
Notes
Page 31
Page 32
Lochinvar Corporation • Lebanon, TN • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
CF-DG-05 (Reprint CF-DG-05 1/07) 11/07-Printed in U.S.A.
Loading...