Lochinvar CHA 300 G CE, CHA 100 PG CE, CHA 300 PG CE, CHA 400 G CE, CHA 400 PG CE Installation, Commissioning, User & Maintenance Instructions

...
Page 1
These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment.
IMPORTANT INFORMATION
0310569 March 2012
Installation, Commissioning, User & Maintenance Instructions
High Efficiency Water Heaters and Boilers
Charger
with Automatic Pilot Ignition
Models:
CHA 100 G CE and PG CE CHA 155 CHA
G CE and PG CE
200 G CE and PG CE CHA 300 G CE and PG CE CHA 400 G CE and PG CE CHA 500 G CE and PG CE CHA 600 G CE and PG CE CHA 700 G CE and PG CE
Page 2
Lochinvar Ltd
7 Lombard Way The MXL Centre Banbury Oxon OX16 4TJ
www.lochinvar.ltd.uk
High Efficiency Water Heaters and Boilers
Tel: +44 (0) 1295 269 981 Fax: +44 (0) 1295 271 640 Email: info@lochinvar.ltd.uk
Page 3
Instruction manual CHA 3
gis
Read this manual carefully
Warning
Read this manual carefully before starting the water heater. Failure to read the manual and to follow the printed instructions may lead to personal injury and damage to the water heater.
All rights reserved.
Nothing from this publication may be copied, reproduced and/or published by means of printing, photocopying or by any means whatsoever without the prior written approval of the supplier.
The supplier reserves the right to modify specifications stated in this manual.
Trademarks
Any brand names mentioned in this manual are registered trademarks of their respective owners.
Liability
The supplier accepts no liability for claims from third parties arising from unauthorised use, use other than that stated in this manual, and use other than in accordance with the General Conditions registered at the Chamber of Commerce.
Refer further to the General Conditions. These are available on request, free of charge.
Although considerable care has been taken to ensure a correct and suitably comprehensive description of all relevant components, the manual may nonetheless contain errors and inaccuracies.
Should you detect any errors or inaccuracies in the manual, we would be grateful if you would inform us. This helps us to further improve our documentation.
Liability
In the event of problems with your gas, electricity or water supply connections, please contact the supplier/installation engineer of your installation.
Page 4
4 Instruction manual CHA
gis
Page 5
Instruction manual CHA 5
Table of contents
1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.1 About the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.2 What to do if you smell gas- - - - - - - - - - - - - - - - - - - - - - - - - 7
1.3 Regulations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.4 Target groups - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
1.5 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
1.6 Notation conventions- - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.7 Overview of this document - - - - - - - - - - - - - - - - - - - - - - - - - 9
2 Working principle of the water heater - - - - - - - - - - - - - 11
2.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
2.2 General working principle of the water heater - - - - - - - - - - - - - - - 11
2.3 Water heater operating cycle - - - - - - - - - - - - - - - - - - - - - - - 13
2.4 Protection for the water heater - - - - - - - - - - - - - - - - - - - - - - 13
3 Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.2 Packaging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.3 Ambient conditions- - - - - - - - - - - - - - - - - - - - - - - - - - - - 16
3.4 Technical specifications - - - - - - - - - - - - - - - - - - - - - - - - - 18
3.5 Installation diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - 21
3.6 Vented water connections - - - - - - - - - - - - - - - - - - - - - - - - 22
3.7 Unvented water connections - - - - - - - - - - - - - - - - - - - - - - - 23
3.8 Gas connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 24
3.9 Flue gas discharge- - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
3.10 Electrical connection - - - - - - - - - - - - - - - - - - - - - - - - - - - 26
3.11 Checking the supply pressure and burner pressure - - - - - - - - - - - - 29
4 Conversion to a different gas category - - - - - - - - - - - - 33
4.1 Conversion of CHA 100 to 600 to another gas category - - - - - - - - - - 34
4.2 Conversion of CHA 700 to another gas category - - - - - - - - - - - - - 36
4.3 Conversion from LP gas to natural gas - - - - - - - - - - - - - - - - - - 37
4.4 Conversion from natural gas to LP gas - - - - - - - - - - - - - - - - - - 39
5 Filling - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
5.1 Filling unvented installations - - - - - - - - - - - - - - - - - - - - - - - 42
5.2 Filling vented installations - - - - - - - - - - - - - - - - - - - - - - - - 42
6 Draining - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
6.1 Draining unvented installations - - - - - - - - - - - - - - - - - - - - - - 44
6.2 Draining vented installations - - - - - - - - - - - - - - - - - - - - - - - 44
7 The control panel- - - - - - - - - - - - - - - - - - - - - - - - 45
7.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.2 Control panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.3 Explanation of icons - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.4 On/off switch- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.5 Control thermostat - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.6 Burner control reset button - - - - - - - - - - - - - - - - - - - - - - - - 46
7.7 Flue gas thermostat reset button - - - - - - - - - - - - - - - - - - - - - 46
7.8 Weekly timer circuit - - - - - - - - - - - - - - - - - - - - - - - - - - - 46
gis
Page 6
Table of contents
6 Instruction manual CHA
8 Status of the water heater - - - - - - - - - - - - - - - - - - - 47
8.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
8.2 Operating modes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
8.3 Power Anode status- - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
8.4 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 48
9 Starting the water heater - - - - - - - - - - - - - - - - - - - - 49
9.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
9.2 Starting the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
9.3 The appliance's heating cycle - - - - - - - - - - - - - - - - - - - - - - - 49
10 Shutting down - - - - - - - - - - - - - - - - - - - - - - - - - 51
10.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 51
10.2 Shut the appliance down for a brief period ('OFF' mode) - - - - - - - - - - 51
10.3 Isolating the appliance from the mains - - - - - - - - - - - - - - - - - - - 51
10.4 Shutting the appliance down for a long period - - - - - - - - - - - - - - - 51
11 Errors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.2 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.3 CHA Troubleshooting table for general errors - - - - - - - - - - - - - - - 54
11.4 CHA Troubleshooting table - no hot water - - - - - - - - - - - - - - - - - 55
11.5 CHA Troubleshooting table - Insufficient hot water - - - - - - - - - - - - - 57
12 Performing maintenance - - - - - - - - - - - - - - - - - - - - 59
12.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 59
12.2 Preparation for maintenance - - - - - - - - - - - - - - - - - - - - - - - 59
12.3 Water-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - 59
12.4 Gas-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 61
12.5 Finalising maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 62
13 Warranty (certificate) - - - - - - - - - - - - - - - - - - - - - - 63
13.1 Garantie (certificaat) - - - - - - - - - - - - - - - - - - - - - - - - - - - 63
13.2 Conditions for installation and use - - - - - - - - - - - - - - - - - - - - - 63
13.3 Exclusions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 64
13.4 Scope of the warranty - - - - - - - - - - - - - - - - - - - - - - - - - - - 64
13.5 Claims - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 64
13.6 Obligations of Lochinvar Ltd - - - - - - - - - - - - - - - - - - - - - - - - 64
14 Electrical diagram - - - - - - - - - - - - - - - - - - - - - - - 65
14.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 65
15 Declaration of Conformity - - - - - - - - - - - - - - - - - - - 71
Page 7
Instruction manual CHA 7
gis
1 Introduction
1.1 About the appliance
This manual describes how to install, service and use the CHA appliance. The CHA appliance is a gas-fired open boiler without fan. These Charger devices have a pilot flame ignition feature and flue gas discharge safety device
The CHA is an appliance of type B
11B S
.
The information in this manual applies to types: CHA 100, CHA 155, CHA 200, CHA 300, CHA 400, CHA 500, CHA 600 and CHA 700.
The water heater has been manufactured and equipped in accordance with the European standard for gas-fired storage water heaters for the production of domestic hot water (EN 89). The water heaters are therefore compliant with the European Directive for Gas water heaters, and and are entitled to bear the CE mark.
Warning
Read this manual carefully before starting the water heater. Failure to read the manual and to follow the printed instructions may lead to personal injury and damage to the water heater.
1.2 What to do if you smell gas
Warning
If you smell gas:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no telephones, plugs or bells!
Open windows and doors!
Shut off the mains gas supply valve!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or your installation engineer.
1.3 Regulations
As the (end) user, installation engineer or service and maintenance engineer, you must ensure that the entire installation complies, as a minimum, with the official local:
building regulations;
energy supplier's directives for existing gas installations;
directives and technical guidelines for natural gas installations;
safety requirements for low-voltage installations;
regulations governing the supply of drinking water;
regulations governing ventilation in buildings;
regulations governing the supply of air for combustion;
regulations governing the discharge of products of combustion;
requirements for installations that consume gas;
regulations governing indoor waste water disposal;
regulations imposed by fire service, power companies and municipality.
0063
Page 8
Introduction
8 Instruction manual CHA
1
gis
Furthermore, the installation must comply with the manufacturer's instructions.
Comment
The installation is also subject to any later amendments and/or additions to all regulations, requirements and guidelines published on or prior to the moment of installation.
1.4 Target groups
The three target groups for this manual are:
(end) users;
installation engineers;
service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is intended. See the table.
Target group symbols
Note
This water heater is not intended for use by persons with reduced physical, sensory or mental capacities, or who lack the necessary experience or knowledge, unless the person responsible for their safety is supervising them or has explained to them how the water heater should be used.
Note
This water heater is not intended to be used by children. Always supervise children, and ensure that they do not play with the water heater.
1.5 Maintenance
A service should be carried out at least once a year, both on the water side and on the gas side. Among other things, the service interval depends on the water quality, the average burning time per day and the set water temperature.
Comment
To determine the correct service interval, it is recommended to arrange for the service and maintenance engineer to check the water heater on both the water and gas side within three months following installation. Based on this check, the best service interval can be determined.
Comment
Regular maintenance extends the service life of the water heater.
Both the end user and the service and maintenance engineer are responsible for regular maintenance. They will need to establish clear agreements on this.
Comment
If the water heater is not regularly serviced, the warranty will become void.
Symbol Target Group
(End) user
Installation engineer
Service and maintenance engineer
Page 9
Instruction manual CHA 9
gis
1.6 Notation conventions
The following notation is used in this manual:
Comment
Important information.
Note
Ignoring this information can lead to the water heater being damaged.
Warning
Failure to carefully read this information may lead to danger of personal
injury, and serious damage to the water heater.
1.7 Overview of this document
The table provides an overview of the contents of this document.
Contents of this document
Chapter Target groups Description
Working principle of the water heater
This chapter describes the working principle of the water heater.
Installation This chapter describes the installation activities to be
carried out before final commissioning.
Conversion to a different gas category
This chapter describes how to convert the water heater to a different gas category and/or family of gases.
Filling This chapter describes how to fill the water heater.
Draining This chapter describes how to drain the water heater.
The control panel This chapter describes the appliance's control panel, and
how to use it.
Status of the water heater This chapter describes the status (mode or condition) that
the water heater may have, and possible actions to take.
Starting the water heater This chapter describes how to start the water heater. The
general operating cycle of the water heater is also described.
Shutting down This chapter describes how to decommission the water
heater for a brief or long period of time.
Errors This chapter is mainly intended for the installation
engineer and the service and maintenance engineer. It describes appliance errors. A troubleshooting table of possible features, causes and solutions is provided. End users may also refer to this chapter for additional information about the appliance.
Performing maintenance This chapter sets out the maintenance tasks to be carried
out.
Warranty (certificate) This chapter states the warranty terms and conditions.
Page 10
Introduction
10 Instruction manual CHA
1
gis
Page 11
Instruction manual CHA 11
gis
2 Working principle of
the water heater
2.1 Introduction
This chapter covers the following topics:
General working principle of the water heater;
Water heater operating cycle;
Protection for the water heater;
Safety of the installation.
2.2 General working principle of the water heater
Cut-away view of the water heater
Legend
Unused numbers are not applicable
2. hot water outlet
6. control panel
8. combustion chamber
9. anode
10. tank
11. heat exchanger
12. inspection and cleaning
opening
14. cold water inlet
15. drain valve
16. gas control valve
20. hot surface igniter
21. flame probe
22. chimney flue
24. insulation layer
33. draught diverter
34. flue gas thermostat sensor
35. radiation shield/condensation
tray
36. bar burners/burner tray
37. flue gas thermostat
38. safety thermostat sensor
39. high-limit thermostat sensor
40. burner control
41. control thermostat
42. high-limit thermostat
43. safety thermostat
44. frost thermostat
45. control thermostat sensor
46. frost thermostat sensor
22
33
9
11
24
10
12
15
8
351634
37238640424346142021
36
44
45
41
39
IMD- 1038 R0
Page 12
Working principle of the water heater
12 Instruction manual CHA
2
gis
In this appliance, the cold water enters the bottom of the tank through the cold water inlet (14). The heat of combustion is conducted to the water by the combustion chamber (8) and flue tubes. The heated tap water leaves the tank through the hot water outlet (2). Once the appliance is completely filled with water, it will constantly be under mains water pressure. When hot water is drawn from the appliance, it is immediately replenished with cold water.
The gas required for combustion flows via the gas control (16) into the manifold. There are orifices in the manifold. The gas is injected into the burner bars at pressure from these orifices (36). The burner bars together form the burner tray. The injection of gas into the burner bars also draws in the primary air required for combustion. The narrow opening in the orifice causes the gas flow to accelerate. This in turn causes a partial vacuum. It is this partial vacuum that draws in the air (the Venturi effect). Additional air is drawn in through the opening in the burner tray.
The hot surface igniter (20) ensures ignition of the gas/air mixture.
The flue gases released by this combustion are led through the flue tubes of the heat exchanger (11). Flue baffles are fitted inside the flue tubes. These retard the flow of the flue gases, thereby increasing the thermal efficiency of the appliance.
The flue gases are exhausted from the appliance via the draught diverter (33).
A radiation shield/condensation tray (35) is mounted below the burner tray. This prevents overheating of the floor area below the appliance, as well as serving as a collection tray for condensation water.
The insulation layer (24) prevents heat loss. The inside of the tank is enamelled to protect against corrosion. The anodes (9) offer extra protection.
Page 13
Instruction manual CHA 13
gis
2.3 Water heater operating cycle
The entire appliance is controlled by the burner control (40) and the control thermostat (41) or frost thermostat (44). The control thermostat and frost thermostat both independently measure the water temperature (T
water
). The
appliance's heating cycle is activated as soon as T
water
falls below the specified
threshold value (T
set
). The value of T
set
depends on the selected appliance operating mode (8.2 "Operating modes"). If the appliance is in the 'OFF' mode (frost protection), then this value is determined by the frost thermostat (threshold value = 20°C). If the appliance is in the 'ON' mode, then the threshold value is selectable via the control thermostat (±40°C to ±70°C).
As soon as T
water
falls below T
set
, the relevant thermostat (control or frost) will close, and the burner control will register demand. The gas control (16) is opened, and the gas is mixed with air. This mixture is ignited by the hot surface igniter (20) and the water is heated. As soon as T
water
gets higher than T
set
, the thermostat opens again. The demand will cease, and the burner control will stop the heating cycle.
The thermostats have a certain margin both when closing and opening. We refer to this margin as the hysteresis. The hysteresis cannot be adjusted.
2.4 Protection for the water heater
2.4.1 Introduction
The burner control monitors the water temperature by means of thermostats and ensures safe combustion. This is done by:
•the Water temperature protection device;
•the Flue gas backflow safeguard;
•the Flame probe;
2.4.2 Water temperature protection
By means of the frost, high-limit and safety thermostats, the burner control monitors three temperatures that are important for safety. The table explains the working principle of the thermostats with sensors.
Temperature protection
2.4.3 Flue gas backflow safeguard
The flue gases are discharged to the outside via the draught diverter (33) and the flue (22). To prevent the flue gases from flowing back into the boiler room, the discharge ducting is monitored by a feature called the Thermal Reflux Safeguard (TRS). This uses a flue gas thermostat (37) with a flue gas thermostat sensor (34) that are located in the draught diverter. Under normal circumstances this sensor will register the ambient temperature.
Protection Description
Frost thermostat When the frost thermostat sensor (46) measures a temperature of 20°C or
less, the heating cycle (2.3 "Water heater operating cycle") will start.
High-limit thermostat When the high-limit thermostat sensor (39) measures a temperature higher
than 84°C, the high-limit thermostat will open. The heat demand is terminated and the burner control halts the heating cycle until the high-limit thermostats close once more. At that moment the burner control will reset the appliance and the heating cycle will restart. The high-limit safeguard serves to prevent overheating and/or excessive formation of scale in the appliance.
Safety thermostat When the safety thermostat sensor (38) measures a temperature higher than
93°C, the safety thermostat will open. The heat demand is terminated and the burner control will immediately halt the heating cycle. The burner control will go into a lockout error state. This must be manually reset before the appliance can resume operation.
Page 14
Working principle of the water heater
14 Instruction manual CHA
2
gis
However, if the chimney is not drawing sufficiently (for example, due to a blockage in the chimney), the flue gases will 'reflux' and flow back past the flue gas thermostat sensor. The sensor will then detect an excessive temperature and the flue gas thermostat will open. The demand will cease, and the burner control will immediately stop the heating cycle. The flue gas thermostat will also lock out. It must be manually reset before the appliance can resume operation .
2.4.4 Flame probe
To ensure that no gas can flow when there is no combustion, the water heater is fitted with a flame probe (21). The burner control uses the ionisation-detecting properties of this probe for flame detection. The burner control closes the gas valve the instant it determines that there is a gas flow but no flame is present.
2.4.5 Safety of the installation
In addition to the appliance's standard built-in safety monitoring, the appliance must also be protected by an expansion vessel, expansion valve, pressure reducing valve, non-return valve and a T&P valve.
The use of an expansion vessel, expansion valve and/or pressure reducing valve depends on the type of installation: unvented or vented.
Unvented installation
With an unvented installation, an expansion valve valve and expansion vessel prevent the buildup of excessive pressure in the tank. This prevents damage being caused to the enamelled coating (in the appliance) or to the tank. A non­return valve prevents excessive pressure buildup in the water supply system. This valve also prevents water from flowing backwards from the tank into the cold water supply system. The pressure reducing valve protects the installation against an excessively high water supply pressure (> 8 bar). These components are fitted to the cold water pipe (3.6 "Vented water connections").
Vented installation
With vented installation, excess pressure is taken up by the open cold water head tank. The head height of the tank determines the working pressure in the water heater, which may not exceed 8 bar. The installation must also be fitted with a vent pipe from the hot water pipe (3.6.3 "Hot water side"), which opens into the cold water tank.
T&P valve
A T&P valve is only mandatory in an unvented installation. However, the supplier also recommends the use of a T&P valve in vented installations.
A T&P (Temperature and Pressure Relief) valve monitors the pressure in the tank and the water temperature at the top of the tank. If the pressure in the tank becomes excessive (> 10 bar) or the water temperature is too high (> 97°C), the valve will open. The hot water can now flow out of the tank. Because the appliance is under water supply pressure, cold water will automatically flow into the tank. The valve remains open until the unsafe situation has been rectified. The appliance is fitted standard with a connecting point for a T&P valve (3.7.3 "Hot water side").
Page 15
Instruction manual CHA 15
is
3 Installation
Warning
The installation must be carried out by an approved installation engineer in compliance with the general and local regulations imposed by the gas, water and power supply companies and the fire brigade.
The appliance may only be installed in a room that complies with the requirements stated in national and local ventilation regulations (1.3 "Regulations").
3.1 Introduction
This chapter describes the installation activities to be carried out before the appliance may be started up (9 "Starting the water heater"), in particular:
Packaging;
Ambient conditions;
Technical specifications;
Vented water connections;
Vented water connections;
Gas connection;
Flue gas discharge;
Electrical connection;
Checking the supply pressure and burner pressure.
For a possible conversion to a different gas category, see conversion (4 "Conversion to a different gas category").
3.2 Packaging
To avoid damaging the water heater, remove the packaging carefully.
We recommend unpacking the water heater at or near its intended location.
Note
The water heater may only be manoeuvred in an upright position. Take care that the water heater is not damaged after unpacking.
Page 16
Installation
16 Instruction manual CHA
3
is
3.3 Ambient conditions
Note
The water heater may not be used in rooms where chemical substances are stored or used due to the risk of explosion, and corrosion of the water heater. Some propellants, bleaching agents and degreasing agents etc. disperse vapours that are explosive and/or cause accelerated corrosion. If the water heater is used in a room in which such substances are present, the warranty will be void.
CHA appliances are open appliances and may only be installed in an open boiler room. They are type B
11B S
.
3.3.1 Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table shows the ambient conditions that must be adhered to for correct functioning of the electronics present in the water heater to be guaranteed.
Air humidity and ambient temperature specifications
3.3.2 Maximum floor load
Allow for the appliance's weight with respect to the maximum floor load; refer to the table.
Weight of the appliance filled with water
Air humidity and ambient temperature
Air humidity max. 93% RH at +25°C
Ambient temperature Functional: 0 <
T < 60°C
Weight (kg) of the appliance filled with water
CHA 100 507
CHA 155 507
CHA 200 510
CHA 300 581
CHA 400 576
CHA 500 525
CHA 600 526
CHA 700 584
Page 17
Instruction manual CHA 17
is
3.3.3 Working clearances
For access to the appliance, it is recommended that the following clearances are observed (see figure):
AA: around the appliance's control column and cleaning openings: 100 cm.
BB: all sides of the appliance: 50 cm.
Above the appliance (room to replace the anodes):
- 100 cm if using fixed anodes, or
- 50 cm if using flexible anodes.
If the available clearance is less than 100 cm, flexible magnesium anodes may be ordered.
Comment
When installing the appliance, be aware that any leakage from the tank and/or connections can cause damage to the immediate environment or floors below the level of the boiler room. If this is the case, the appliance should be installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least 5cm deep with a length and width at least 5cm greater than the diameter of the appliance.
Working clearances
A
A
A
A
A
A
B
B
IMD-0275 R2
Page 18
Installation
18 Instruction manual CHA
3
is
3.4 Technical specifications
The water heater is supplied without accessories. Check the dimensions (3.4 "Technical specifications"), gas data (3.4.3 "Gas data") and other specifications (3.4.2 "General and electrical specifications") of any accessories you plan to use.
3.4.1 Dimensions of the water heater
Plan and elevation of the water heater
Legend
See the table.
A
B
M
R
K
P
S
N
6
1
3
4
6
2
5
10º
37º 45º
E
G
IMD-0145 R3
Page 19
Instruction manual CHA 19
is
Dimensions (all measurements in mm unless otherwise indicated)
3.4.2 General and electrical specifications
General and electrical specifications
CHA 100
CHA 155
CHA 200
CHA 300
CHA 400
CHA 500
CHA 600
CHA 700
A) Overall height 1910 1910 1890 2155 2155 1950 2145 2145
B) Height of top of appliance 1700 1700 1700 1900 1900 1735 1810 1810
D) Diameter of appliance 710 710 710 710 710 710 710 710
F) Width 800 800 800 800 800 800 800 800
G) |Chimney flue outlet diameter 130 130 150 180 180 200 250 250
K) Gas connection height 145 145 145 145 145 145 145 145
M) Cold water supply height 505 505 505 505 505 515 590 590
N) Hot water outlet height 1545 1545 1545 1750 1750 1580 1655 1655
P) Height of cleaning opening 670 670 670 670 670 680 765 795
R) Height of drain valve connection 440 440 440 455 455 465 540 535
S) Height of T&P valve connection 1490 1490 1490 1700 1700 1700 1600 1600
1) Cold water supply connection (external) R1
1
/2R11/2R11/2R11/2R11/2R11/2R11/2R11/
2
2) Hot water outlet connection (internal) Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/
2
3) Gas control connection (internal) Rp3/4Rp3/4Rp3/4Rp3/4Rp3/4Rp3/4Rp3/4Rp1
4) Drain valve connection (internal) Rp1
1
/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/
2
5) T&P valve connection (internal) 1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
1-11.5 NPT
6) Cleaning/inspection opening Ø 100 Ø 100 Ø 100 Ø 100 Ø 100 Ø 100 Ø 100 Ø 100
DESCRIPTION CHA
100
CHA 155
CHA 200
CHA 300
CHA 400
CHA 500
CHA 600
CHA 700
Capacity (litres) 309 309 298 357 335 278 253 252
Maximum operating pressure (bar) 8 8 8 8 8 8 8 8
Empty weight (kg) 198 198 212 224 241 247 273 332
Heating time dT = 45
o
C (minutes) 38 30 23 25 17 11 8 7
Number of anodes 2 2 2 2 3 3 4 4
Number of bar burners/orifices 3 3 4 4 7 7 9 6
Number of flue tubes/flue baffles 5 5 7 6 9 12 16 17
Electrical power consumption (W) 30 30 30 30 30 30 30 60
Supply voltage (-15% +10% VAC)
230 230 230 230 230 230 230 230
Mains frequency (±1Hz) 50 50 50 50 50 50 50 50
IP class 30 30303030303030
Page 20
Installation
20 Instruction manual CHA
3
is
3.4.3 Gas data
Gas data
Description II
2H3+
Unit CHA
100
CHA 155
CHA 200
CHA 300
CHA 400
CHA 500
CHA 600
CHA 700
2H: G20 - 20 mbar
Orifice diameter mm 2.90 3.20 3.20 3.30 2.95 3.20 3.30 3.90
(1) = Blank plate (2) = Burner pressure regulator (3) = High/low regulator
1, 2 or 32 2222222
Nominal load (gross calorific value)
kW 33.9 42.1 53.4 59.9 83.2 102.5 128.4 142.4
Nominal output kW 25.6 31.9 40.4 45.3 62.9 77.6 97.1 107.7
Supply pressure mbar 20 20 20 20 20 20 20 20
Burner pressure mbar 8.5 8.6 7.8 8.5 8.5 9.2 7.8 11.5
Gas consumption (*) m3/h 3.2 4.0 5.1 5.7 7.9 9.8 12.2 13.6
General 3+
Injector orifice diameter mm 1.60 1.70 1.60 1.75 1.50 1.70 1.75 2.25
(1) = Blank plate (2) = Burner pressure regulator (3) = High-low control
1, 2 or 31 1111113
G30 - 30 mbar (butane)
Nominal load (gross calorific value)
kW 33.9 42.2 53.4 59.2 80.8 100.1 127.5 140.3
Nominal output kW 26.3 32.7 41.4 45.9 62.6 77.6 98.8 108.8
Supply pressure mbar 30 30 30 30 30 30 30 30
Burner pressure
(†)
mbar- -------
Gas consumption
(*)
kg/h 2.5 3.1 3.9 4.3 5.9 7.3 9.3 10.2
G31 - 37 mbar (propane)
Nominal load (gross calorific value)
kW 33.1 41.4 52.8 58.2 78.4 98.3 125.5 136.2
Nominal output kW 25.6 32.0 40.8 45.0 60.6 75.9 97.0 105.2
Supply pressure mbar 37 37 37 37 37 37 37 37
Burner pressure
(†)
mbar- -------
Gas consumption
(*)
kg/h 2.4 3.0 3.8 4.2 5.6 7.0 9.0 9.7
(*) Based on 1013.25 mbar and 15 °C. (†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to the supply pressure. In practice, however, the burner pressure will be lower.
Page 21
Instruction manual CHA 21
is
3.5 Installation diagram
The figure shows the Installation diagram. This diagram is referred to in the sections describing the actual connection procedure.
Installation diagram
Legend
Unused numbers are not applicable
1. pressure reducing valve (mandatory)
3. T&P valve (mandatory)
4. stop valve (recommended)
5. non-return valve (mandatory)
6. circulation pump (optional)
7. top to bottom circulation pump (optional)
9. drain valve
10. manual gas valve (mandatory)
11. service stop valve (mandatory)
12. temperature gauge (recommended)
14. draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
17. 3-way aeration valve (recommended)
18. cold water head tank
19. float switch
A. cold water supply B. hot water supply C. circulation pipe D. gas supply E. overflow pipe H. overflow protection
Page 22
Installation
22 Instruction manual CHA
3
is
3.6 Vented water connections
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations (1.3 "Regulations").
3.6.1 Cold water side
See (A) in the installation diagram (3.5 "Installation diagram").
1. Fit an approved stop valve (4) on the cold water side between the cold water head tank (18) and the water heater, as required by applicable regulations.
3.6.2 Shunt pipe
You can connect a top to bottom circulation pump to prevent stacking of the water in the water heater.
1. Optional: Depending on the draw-off pattern, fit a shunt pipe (Ø 22 mm), a stop valve (11) and a top-to-bottom circulation pump (7).
2. Fit a non-return valve (5).
3. Fit a stop valve (11).
3.6.3 Hot water side
See (B) in the installation diagram (3.5 "Installation diagram").
Comment
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve (3).
2. Optional: fit a temperature gauge (12) so you can check the temperature of the tap water.
3. Fit a stop valve (4) in the hot water outlet pipe for servicing.
4. If a circulation pipe is required, continue by installing the circulation pipe (3.6.5 "Circulation pipe").
3.6.4 Drain valve
1. Fit the standard drain valve supplied (9).
2. If desired, fit a circulation pipe (3.6.5 "Circulation pipe"). Otherwise, fit the sealing nut and gasket (C) supplied with the drain valve, as per the diagram.
C
IMD-0122 R1
Page 23
Instruction manual CHA 23
is
3.6.5 Circulation pipe
See (C) in the installation diagram (3.5 "Installation diagram").
If an immediate flow of hot water is required at draw-off points, a circulation pump can be installed. This improves comfort, and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance of the circulation system.
2. Fit a non-return valve (5) after the circulation pump to guarantee the direction of circulation.
3. Fit two stop valves for servicing (4).
4. Connect the circulation piping to the T-piece on the drain valve (9) as per the drain valve diagram (3.6.4 "Drain valve").
3.7 Unvented water connections
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations (1.3 "Regulations").
3.7.1 Cold water side
See (A) in the installation diagram (3.5 "Installation diagram").
1. Fit an approved stop valve (4) on the cold water side as required by the applicable regulations (1.3 "Regulations").
2. The maximum working pressure of the water heater is 8 bar. Because the pressure in the water pipe at times can exceed 8 bar, you must fit an approved pressure-reducing valve (1).
3. Fit a non-return valve (5) and an expansion vessel (16).
4. Fit an expansion valve (15) and connect the overflow side to an open waste water pipe.
3.7.2 Shunt pipe
You can connect a top to bottom circulation pump to prevent stacking of the water in the water heater.
1. Optional: Depending on the draw-off pattern, fit a shunt pipe (Ø 22 mm), a stop valve (11) and a top-to-bottom circulation pump (7).
2. Fit a non-return valve (5).
3. Fit a stop valve (11).
3.7.3 Hot water side
See (B) in the installation diagram (3.5 "Installation diagram").
Comment
Insulating long hot water pipes prevents unnecessary energy loss.
1. Optional: fit a temperature gauge (12) so you can check the temperature of the tap water.
2. Fit the T&P valve (3).
3. Fit a stop valve (11) in the hot water outlet pipe for servicing.
Page 24
Installation
24 Instruction manual CHA
3
is
3.7.4 Drain valve
1. Fit the standard drain valve supplied (9).
2. If desired, fit a circulation pipe (3.6.5 "Circulation pipe"). Otherwise, fit the sealing nut and gasket (C) supplied with the drain valve, as per the diagram.
3.7.5 Circulation pipe
See (C) in the installation diagram (3.5 "Installation diagram").
If an immediate flow of hot water is required at draw-off points, a circulation pump can be installed. This improves comfort, and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance of the circulation system.
2. Fit a non-return valve (5) after the circulation pump to guarantee the direction of circulation.
3. Fit two stop valves for servicing (4).
4. Connect the circulation piping to the T-piece on the drain valve (9) as per the drain valve diagram (3.6.4 "Drain valve").
3.8 Gas connection
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations (1.3 "Regulations").
Note
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the water heater.
See (D) in the installation diagram (3.5 "Installation diagram").
1. Fit a manual gas valve (10) in the gas supply pipe.
2. Blow the gas pipe clean before use.
3. Close the manual gas valve.
4. Fit the gas supply pipe to the gas control valve.
Warning
After fitting, check for leaks.
C
IMD-0122 R1
Page 25
Instruction manual CHA 25
is
3.9 Flue gas discharge
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations (1.3 "Regulations").
Fit a vertical chimney pipe (2) of at least 0.5 metres length to the opening of the draft diverter, before fitting the rest of the chimney materials according to current regulations (1.3 "Regulations").
Installing the draught diverter
Comment
Use flue gas discharge materials that comply with the
regulations (1.3 "Regulations").
Comment
Make sure that the chimney discharges into an area approved for this type
of appliance.
Legend
1 draught diverter 2 flue gas discharge
>0,5m
_
IMD-0148 R2
2
1
Page 26
Installation
26 Instruction manual CHA
3
is
3.10 Electrical connection
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations (1.3 "Regulations").
3.10.1 Preparations
Note
The appliance is phase-sensitive. It is absolutely essential to connect the mains live (L) to the live of the appliance, and the mains neutral (N) to the neutral of the appliance.
Note
There must also be no potential difference between neutral (N) and earth ( ). Contact the supplier if this is the case.
For more information or to order this isolating transformer, please contact the supplier.
The figure shows a view of the electrical connector block, and the table shows the appropriate connections.
Connector block
1. In preparation, first remove the protective cover from the control column:
2. Undo the 4 screws (A).
3. Remove the protective cover (B) from the electrical part.
Legend
A. screws B. cover C. terminal block
1
15
C
A
B
IMD-0149 R1
Page 27
Instruction manual CHA 27
is
The connector block (C) is now visible.
Comment
Please consult (14 "Electrical diagram") the appropriate electrical diagram
for details of the connections of the electrical components.
Terminal block
3.10.2 Introduction
Topics covered in this paragraph, in sequence:
Preparations;
Connecting the mains power;
Flue gas discharge safety device;
Weekly timer circuit;
Extra error signal ("Alarm OUT")..
3.10.3 Connecting the mains power
The water heater is supplied without a power cable and isolator.
Comment
In order to receive electrical power, the water heater has to be connected to the mains power by means of a permanent electrical connection. A double-pole isolator with a contact gap of at least 3 mm must be fitted between this permanent connection and the water heater. The power cable must have cores of at least 3 x 1.0 mm 2 .
Warning
Leave the water heater electrically isolated until you are ready to
commission it.
1. Feed the power cable through the metric strain relief in the top of the control
column.
2. Connect the earth ( ), live (L1) and neutral (N) of the power cable to
terminals 1 to 3 of the connection block according to the table.
3. Tighten the strain relief so that the cable is clamped.
4. If you do not need to make any more connections, then fit the protective
cover back on the control column.
5. Connect the power cable to the isolator.
3.10.4 Flue gas discharge safety device
1. Feed the cable for the weekly timer circuit through the metric strain relief in
the top of the control column.
2. Connect the weekly timer circuit to points 7 (L) and 8 (N) of the connector
block
3. Tighten the strain relief so that the cable is clamped.
4. If you do not need to make any more connections, then fit the protective
cover back on the control column.
Mains voltage
Flue gas
thermostat
Week timer circuit
Un
used
Potential-free
contact
L1 N N N L L L L - NO P NC
123456789101112131415
Page 28
Installation
28 Instruction manual CHA
3
is
3.10.5 Weekly timer circuit
1. Cut the image of the weekly timer from the operating panel.
2. Place the weekly timer in the opening thus created.
3. Connect the cables to points 7 (N), 8 (L) and 11 (L) using wire end sheaths.
4. Connect the cable with the crimped terminal clip onto position B4 on the ON/OFF switch.
5. If you do not need to make any more connections, then fit the protective cover back on the control column.
3.10.6 Extra error signal ("Alarm OUT").
Alarm OUT is a potential free terminal that is switched when an error is detected. Devices (e.g. one or more lights) can be connected to this in order to signal the fault (max. 250V, 10A).
The device or devices may be connected in either a circuit with a make-contact (light illuminated when there is an error) or a circuit with a break-contact (light illuminated during normal use).
1. Feed the extra signalling cable through the metric strain relief in the top of the control column.
2. Connect the extra signalling device to points 13 (N) and 14 (P) and/or 14 (P) and 15 (NC) as show in the Terminal block.
3. Tighten the strain relief so that the cable is clamped.
4. If you do not need to make any more connections, then fit the protective cover back on the control column.
Page 29
Instruction manual CHA 29
is
3.11 Checking the supply pressure and burner pressure
Comment
Before starting the appliance and/or checking the supply pressure and
burner pressure, you must fill (5 "Filling") the appliance.
Note
Before starting up for the first time or after conversion, you must always
check the supply pressure and burner pressure.
Comment
The easiest way to check the gas pressures is by using two pressure
gauges. This procedure assumes that these two gauges are available.
Gas control for CHA 100 to 600
Legend
Unused numbers are not applicable
1. burner pressure regulator
2. burner pressure regulator
cap
3. burner pressure regulator
adjusting screw
4. gas control connector
5. blank plate
6. supply pressure nipple
7. gas control
8. manifold test nipple
1
4
5
6
7
2
8
3
IMD-0127 R1
Page 30
Installation
30 Instruction manual CHA
3
is
Gas control for CHA 700
3.11.1 Preparations
1. Isolate the appliance from the power supply (10.3 "Isolating the appliance
from the mains").
2. There are two test nipples on the gas control. Test nipple (6) is used to check the supply pressure. The other test nipple on the gas control is not used. The manifold test nipple (8) is used to measure the burner pressure. Sealing screws are located inside the test nipples. Loosen both sealing screws by a few turns. Do not completely loosen them; they can be difficult to re-tighten.
3. Connect a pressure gauge to the manifold test nipple (8).
4. Open the gas supply and bleed the air from the mains gas supply via test nipple (6).
5. Connect a pressure gauge to the manifold test nipple (6) when gas starts to flow from this nipple.
6. Switch on the power to the appliance using the isolator on the appliance.
7. Set the control thermostat to the maximum temperature and start the appliance running by setting the ON/OFF switch to position I.
8. The heating cycle will start, and after a short time the burner tray will ignite.
9. After the burner tray has ignited, wait approximately 1 minute before reading the dynamic pressures.
Legend
Unused numbers are not applicable
1. burner pressure regulator
2. burner pressure regulator cap
3. burner pressure regulator adjusting screw
6. supply pressure nipple
7. gas control
8. manifold test nipple
9. high-low control
1
9
6
7
8
2
3
IMD-0129 R1
Page 31
Instruction manual CHA 31
is
10. Use the pressure gauge to read the supply pressure at test nipple (6). Refer to the gas data table (3.4.3 "Gas data").
Comment
Consult the mains gas supply company if the supply pressure is not correct.
11. Use the pressure gauge to read the burner pressure at nipple (8). Refer to the gas data table (3.4.3 "Gas data").
Comment
If the burner pressure is not correct and the appliance is fitted with a blank
plate or high-low control, you will not be able to adjust the pressure. In this case, consult your installation engineer or supplier. If the appliance is indeed fitted with a burner pressure regulator, the pressure can be adjusted (3.11.2 "Adjusting the pressure").
3.11.2 Adjusting the pressure
1. Remove the cap (2) from the burner pressure regulator.
2. Depending on the correction required, correct the burner pressure by turning adjustment screw (3):
- Adjustment screw anticlockwise: burner pressure decreases.
- Adjustment screw clockwise: burner pressure increases.
3. Cover the opening of the adjusting screw and check the burner pressure against the value given in thegas data table (3.4.3 "Gas data").
4. If the pressure reading is not correct, repeat the burner pressure adjustment until the correct pressure is reached.
5. Fit the cap (2) back on the burner pressure regulator.
3.11.3 Finalising
1. Shut off the gas supply.
2. Disconnect the two pressure gauges and retighten the sealing screws in the test nipples.
3. Replace the cover.
Page 32
Installation
32 Instruction manual CHA
3
is
Page 33
Instruction manual CHA 33
is
4 Conversion to a
different gas category
Note
The conversion may only by carried out by a competent person.
If the appliance has to operate on a different family of gases (liquid petroleum gas or natural gas) or other gas category, other than that for which the appliance has been configured at the factory, then the appliance will have be adapted using a special conversion kit.
Note
You must check the supply pressure and burner pressure once the
conversion is complete.
This chapter covers the following:
Conversion of CHA 100 to 600 to another gas category.
Conversion of CHA 700 to another gas category.
Page 34
Conversion to a different gas category
34 Instruction manual CHA
4
is
Exchanging orifices
4.1 Conversion of CHA 100 to 600 to another gas category
1. Isolate the appliance from the power supply (10.3 "Isolating the appliance
from the mains").
2. Shut off the gas supply.
Note
The burner may be hot.
3. Unscrew the cover plate (1) from the burner support.
4. Use a suitable tool to remove the retaining strips (2). Note that the retaining strips have very sharp edges. Withdraw the retaining strips straight upwards.
Comment
The radiation shield / condensation tray can be temporarily loosened to
simplify disassembly of the burner.
5. Remove the burners one by one from their brackets at the front. To do this, you first move them away from you and then downwards. The orifices will now be accessible
6. Remove the orifices.
Legend
1. cover plate
2. retaining strips
3. orifice with stamped figures
1
3
2
IMD-0126 R1
Page 35
Instruction manual CHA 35
is
7. Select and fit the correct orifices from the conversion kit, based on the gas data table (3.4.3 "Gas data"). The orifice diameter is stamped on the orifice itself, see (3).
8. Re-fit the burners back in their original position.
9. Re-fit the retaining strips.
10. If the radiation shield / condensation tray was loosened, re-fasten it.
Conversion of gas control
11. Check whether there is a burner pressure regulator (1) attached to the gas control, or simply a blank plate (5).
Comment
If the supply pressure for a gas category is the same as the burner pressure
(see the gas data table (3.4.3 "Gas data")) then the gas control must be fitted with a blank plate with cork gasket. A burner pressure that deviates in comparison to the supply pressure requires the use of a burner pressure regulator with rubber gasket. Each conversion kit contains all the necessary components.
12. If the blank plate or burner pressure regulator need to be replaced:
- Unscrew the connector (4) of the gas control.
- If necessary, remove the blank plate or burner pressure regulator (5)
or burner pressure regulator (1).
- If necessary, fit the blank plate or burner pressure regulator supplied
with the conversion kit.
- Fit the connector (4) of the gas control.
Legend Unused numbers are not applicable
1. burner pressure regulator
4. gas control connector
5. blank plate
6. supply pressure test nipple
7. gas control
1
4
5
6
7
IMD-0131 R1
Page 36
Conversion to a different gas category
36 Instruction manual CHA
4
is
13. Check the supply pressure and burner pressure (3.11 "Checking the supply
pressure and burner pressure").
14. Remove the sticker showing the new gas category from the conversion kit, and attach it below the appliance's rating plate. This clearly indicates that the appliance may no longer be run on the gas for which it was originally supplied.
15. Start the appliance (9 "Starting the water heater").
4.2 Conversion of CHA 700 to another gas category
4.2.1 Introduction
This paragraph describes:
Conversion from LP gas to natural gas
Conversion from natural gas to LP gas
Conversion of gas control
Legend
Unused numbers are not applicable
1. burner pressure regulator
7. gas control
9. high-low control
1
9
7
IMD-0132 R1
Page 37
Instruction manual CHA 37
is
4.3 Conversion from LP
gas to natural gas
Installing and removing add-on components
1. Carry out steps 1 through 9 (4.1 "Conversion of CHA 100 to 600 to another
gas category").
2. Detach the high-low control (9)
Legend
Unused numbers are not applicable
4. timers
5. bracket
6. 6-contact terminal strip 7 pull reliefs
8. 9-contact terminal strip
9. metric pull relief
10. high-low control lead
4
9
7
5
10
6
8
IMD-0130 R1
Page 38
Conversion to a different gas category
38 Instruction manual CHA
4
is
3. Fit the burner pressure regulator (1) including the sealing gasket from the conversion set. Attach the burner pressure regulator to the gas control using the two small screws supplied. (7).
Installing and removing add-on components
Legend Unused numbers are not applicable
4. timers
5. bracket
6. 6-contact terminal strip
7. strain relief
8. 9-contact terminal strip
9. metric strain relief
10. high-low control lead
4
9
7
5
10
6
8
IMD-0130 R1
Page 39
Instruction manual CHA 39
is
4. Detach the leads between the 6contact terminal strip(6) and the 9contact terminal strip (8). These are the leads for the timers, high-low control, gas control, hot surface igniter and flame probe.
5. Remove the timers (4), bracket (5), wiring harness (not shown) and 9contact terminal strip.
6. Turn the metric strain relief (9) with the high-low control lead (10) to loosen it. Remove this lead.
7. Fit the stop plug from the conversion set in the place of the metric strain relief.
8. Connect the cables of the gas control, the hot surface igniter and flame probe to the 6contact terminal strip as indicated in the electrical diagram (14 "Electrical diagram").
9. Clamp the gas control cable in one of the supplied strain reliefs (7). Do the same for the leads of the hot surface igniter and flame probe.
10. Check the supply pressure and burner pressure (3.11 "Checking the supply
pressure and burner pressure").
11. Remove the sticker showing the new gas category from the conversion kit, and attach it below the appliance's rating plate. This clearly indicates that the appliance may no longer be run on the gas for which it was originally supplied.
12. Start the appliance (9 "Starting the water heater").
4.4 Conversion from natural gas to LP gas
1. Carry out steps 1 through 9 (4.1 "Conversion of CHA 100 to 600 to another
gas category").
2. Detach the burner pressure regulator (1).
3. Fit the high-low controller (9) including the sealing gasket from the conversion set. Attach the high-low control to the gas control using two small screws.
4. Detach the leads from the gas control, the hot surface igniter and the flame probe from the 6contact connector strip (6) and the strain relief (7).
5. 5. Fit the timers (4) including cable harness plus 9contact connector strip (6) from the conversion kit, to the control column.
6. Remove the stop plug (not shown) from the underside of the control column and replace this with the metric strain relief (9) from the conversion kit.
7. Draw the high-low control lead (10) through the strain relief and tighten the strain relief by turning it until the lead is clamped.
8. Connect the high-low control lead (10) plug to the high-low control (9).
9. Connect the cables from the timers, highlow control, gas control and the hot surface igniter as shown in the electrical diagram (14 "Electrical diagram").
10. Check the supply pressure and burner pressure (3.11 "Checking the supply
pressure and burner pressure").
11. Remove the sticker showing the new gas category from the conversion kit, and attach it below the appliance's rating plate. This clearly indicates that the appliance may no longer be run on the gas for which it was originally supplied.
12. Start the appliance (9 "Starting the water heater").
Page 40
Conversion to a different gas category
40 Instruction manual CHA
4
is
Page 41
Instruction manual CHA 41
gis
5 Filling
Installation diagram
Legend
Unused numbers are not applicable
1. pressure reducing valve (mandatory)
3. T&P valve (mandatory)
4. stop valve (recommended)
5. non-return valve (mandatory)
6. circulation pump (optional)
7. top to bottom circulation pump (optional)
9. drain valve
10. manual gas valve (mandatory)
11. service stop valve (mandatory)
12. temperature gauge (recommended)
14. draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
17. 3-way aeration valve (recommended)
18. cold water head tank
19. float switch
A. cold water supply B. hot water supply C. circulation pipe D. gas supply E. overflow pipe H. overflow protection
Page 42
Filling
42 Instruction manual CHA
5
gis
5.1 Filling unvented installations
To fill the water heater, proceed as follows:
1. Open the stop valve (11) in the hot water pipe and, if present, the stop valves (4) for the circulation pump (6).
2. Close the drain valve (9).
3. Open the nearest hot water draw-off point (14).
4. Open the stop valve (4) on the cold water side (A) so that cold water flows into the water heater.
5. Completely fill the water heater. When a full water jet flows from the nearest draw-off point, the water heater is full.
6. Bleed the entire installation of air, for example by opening all draw-off points.
7. The appliance is now under water supply pressure. There should be no water coming out of the expansion valve (15) or out of the T& valve (3). If there is, the cause might be:
- The T&P valve is defective or incorrectly fitted.
- The water supply pressure is greater than the specified 8 bar.
Rectify this by fitting a pressure reducing valve (1).
- The expansion valve in the protected cold supply set-up is defective or
incorrectly fitted.
5.2 Filling vented installations
To fill the water heater, proceed as follows:
1. Open the stop valve (11) in the hot water pipe and, if present, the stop valves (4) for the circulation pump (6).
2. Close the drain valve (9).
3. Open the nearest hot water draw-off point (14).
4. Open the stop valve (4) on the cold water side (A) so that cold water flows into the water heater.
5. Completely fill the water heater. When a full water jet flows from the nearest draw-off point, the water heater is full.
6. Bleed the entire installation of air, for example by opening all draw-off points.
7. The water heater is now under water supply pressure. There should be no water coming out of the T&P valve (3). If this does happen, the T&P valve might be defective or incorrectly fitted.
Page 43
Instruction manual CHA 43
gis
6 Draining
Installation diagram
Legend
Unused numbers are not applicable
1. pressure reducing valve (mandatory)
3. T&P valve (mandatory)
4. stop valve (recommended)
5. non-return valve (mandatory)
6. circulation pump (optional)
7. top to bottom circulation pump (optional)
9. drain valve
10. manual gas valve (mandatory)
11. service stop valve (mandatory)
12. temperature gauge (recommended)
14. draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
17. 3-way aeration valve (recommended)
18. cold water head tank
19. float switch
A. cold water supply B. hot water supply C. circulation pipe D. gas supply E. overflow pipe H. overflow protection
Page 44
Draining
44 Instruction manual CHA
6
gis
6.1 Draining unvented installations
Some service activities require the water heater to be drained. The procedure is as follows:
1. Shut down the appliance by setting the ON/OFF switch on the control panel to position 0.
2. Isolate the water heater from the power supply by putting the isolator between the appliance and the mains power supply to position 0.
3. Shut off the gas supply (10).
4. Close the stop valve (11) in the hot water pipe.
5. Close the supply valve of the cold water supply (A).
6. Open the drain valve (9).
7. Bleed the appliance (or installation) so that it drains completely.
6.2 Draining vented installations
Some service activities require the water heater to be drained. The procedure is as follows:
1. Shut down the appliance by setting the ON/OFF switch on the control panel to position 0.
2. Isolate the water heater from the power supply by putting the isolator between the appliance and the mains power supply to position 0.
3. Shut off the gas supply (10).
4. Close the stop valve (11) in the hot water pipe.
5. Close the stop valve (4) between the cold water head tank and the cold water inlet.
6. Open the drain valve (9).
7. Bleed the appliance (or installation) so that it drains completely.
0063
RESET
4
3
1
2
IMD-0473 R1
0063
RESET
4
3
1
2
IMD-0473 R1
Page 45
Instruction manual CHA 45
gis
7 The control panel
7.1 Introduction
Topics covered in this chapter, in sequence:
Control panel
Explanation of icons
On/off switch;
Control thermostat
Burner control reset button
Flue gas thermostat reset button;
Weekly timer circuit.
7.2 Control panel
This figure shows the control panel.
The control panel
The control panel comprises:
an ON/OFF switch (with positions I/0/II)
a reset button
a control thermostat with rotary knob
two status LEDs;
weekly timer (optional);
Power Anode indicator LED (optional).
7.3 Explanation of icons
The table explains the meanings of the icons.
Icons and their meaning
7.4 On/off switch
Using the ON/OFF switch, set the appliance to the ON mode (position 'I'), OFF mode (position '0'), or the weekly program mode (position 'II'). See 'Operating
modes'.
The appliance remains live, even when in the OFF mode. This ensures that the frost protection remains activated.
Comment
To isolate the appliance electrically, you must use the isolator between the appliance and the mains power supply.
7.5 Control thermostat
Use the rotary knob on the control thermostat to set the desired water temperature to between ±40°C and ±70°C. The knob rotates over a scale of 1 to 4. The table shows the temperatures corresponding to each position.
Temperature setting
Name Meaning
ON/OFF switch
'ON' mode/'OFF' mode
Reset button Reset burner control
Temperature control
Set water temperature (Tset)
0063
RESET
4
3
1
2
IMD-0473 R1
1 Week timer Sets the weekly water
heating program
2 Power Anode
indicator LED
Shows the Power Anode status
3 Error LED Burner control lockout
4 Voltage lamp Shows whether there is
voltage (power) for the burner control
Position Temperature
1 approx. 40°C
2 approx. 50?
3 approx. 60?
4 approx. 70?
Name Meaning
Page 46
The control panel
46 Instruction manual CHA
7
gis
7.6 Burner control reset button
An error can cause the burner control to lock out. When this happens, the red LED on the control panel will illuminate. After eliminating the cause of the error, you can reset the appliance using the reset button.
Comment
Before resetting, always eliminate the cause of the
error.
The appliance's error conditions (8.3 "Power Anode
status") and how to resolve them are described in the
error condition summary (11 "Errors").
7.7 Flue gas thermostat reset button
A malfunction in the flue gas discharge, e.g. a blockage in the chimney, can lead to the flue gas thermostat locking out. This state is evident when the push button on the flue gas thermostat has been activated (refer to the figure). Once the cause has been removed, and the sensor has cooled down sufficiently, press this push button to reset (if the sensor is not sufficiently cooled down, the flue gas thermostat will immediately lock out again). The appliance will then automatically start up again, if there is demand. If this is not the case, please consult the error condition summary (11 "Errors").
Comment
The draught diverter may be hot.
Flue gas thermostat reset button
7.8 Weekly timer circuit
Optionally, you can use the week timer to program when the appliance must fulfil demand. Set the ON/OFF switch to the 'II' position to activate the weekly timer circuit.
Weekly timer
The weekly disk (2) of the timer (1) is divided into seven one-day segments: 'Monday' through 'Sunday'. Each day is divided into 12 segments of 2 hours each by the setting tabs (5).
To set a two-hour period during which the appliance must respond to demand, press the tab for that period outwards.
The current time can be read from the (12-hour) clock hands (3).
Set the day and time as follows: to set roughly, turn the week disk (2) in the direction of the arrow until the current day of the week is aligned with the marker arrow; for fine setting, turn the large hand clockwise until the current time is set. The manual switch (4) must always be in the central position (this activates the timer program).
IMD-0151 R1
Legend
1timer 2 weekly disc 3 pointers 4 manual switch 5tabs
32154
IMD-0474 R0
Page 47
Instruction manual CHA 47
gis
8 Status of the water
heater
8.1 Introduction
Topics covered in this chapter, in sequence:
Operating modes;
Power Anode status;
Error conditions
8.2 Operating modes
When running, the appliance has three basic operating modes, namely:
ISOLATED
In this mode the appliance is off and all components are electrically dead. The isolator (switch between the appliance and the power supply) is turned off. On the control panel:
- The ON/OFF switch is in position 0;
- the green LED is off.
WEEK PROGRAM (optional)
In this position the appliance only meets demand during the periods set by the timer. Outside these periods, only frost protection is active.
On the control panel:
- The ON/OFF switch is in position II.
- The water temperature can be set by turning the knob on the control thermostat, see paragraph '5.5 Control thermostat'.
- The period during which demand must be fulfilled can be programmed using the week timer, see paragraph 5.6 'Weekly timer circuit'.
- the green LED is illuminated.
Comment
If no week timer is installed, the 'II' mode is the
same as the '0' mode.
OFF
In this mode, the frost protection is activated. The isolator is set to position I. On the control panel:
- the ON/OFF switch is in position 0;
- the green LED is illuminated.
Contractor
In this mode the appliance continuously fulfils demand. On the control panel:
- the ON/OFF switch is in position I
- The water temperature can be set by turning the knob on the control thermostat, see paragraph '5.5 Control thermostat'.
- the green LED is illuminated.
8.3 Power Anode status
If the appliance is fitted with a Power Anode, there is an extra indicator lamp on the operating panel. Depending on the status of the appliance, this lamp will be lit either green or red, or it will be off:
Green
This state indicates that the Power Anode is working correctly.
Red
This state indicates an error, and the Power Anode is not working.
Off
This state indicates that the Power Anode is not working.
Comment
If there is an error with the Power Anode (red), or if the Power Anode is not working (off), this will have no effect on the hot water supply.
Page 48
Status of the water heater
48 Instruction manual CHA
8
gis
8.4 Error conditions
If the water heater goes into an "error" condition, you will be unable to draw hot water. The frost protection will also be out of operation. These error conditions are divided into three groups:
Lockout error from the flue gas thermostat
The safety (pushbutton) on the flue gas thermostat in the draught diverter has been activated. After removing the cause, the pushbutton (7.6 "Burner
control reset button") must be pressed to restart
the appliance.
Lockout error from the flue gas thermostat
When this happens, the red LED on the control panel will be illuminated. The burner control is locked out. After eliminating the cause, the appliance must be returned to service by pressing the reset button (7.6 "Burner control reset button").
Blocking errors
You can recognise this condition from the fact that the appliance does not start running even though the water temperature is lower than the setting that you have defined using the control thermostat (7.5 "Control thermostat"). These errors disappear automatically once the cause of the error has been removed, after which the appliance resumes operation by itself.
The cause of the error cannot be seen on the control panel. For a detailed overview of error conditions, please refer to the error tables (11 "Errors").
If, as end-user, you find the appliance in an error condition, you may attempt to restart the appliance by pressing the reset button once. However, if the error returns or occurs several times in a short time, you must contact your service and maintenance engineer.
Page 49
Instruction manual CHA 49
gis
9 Starting the water
heater
9.1 Introduction
Topics covered in this chapter, in sequence:
Starting the appliance.
The appliance's heating cycle.
9.2 Starting the appliance
Start the water heater as follows:
1. Fill the water heater (5 "Filling").
2. Open (3.5 "Installation diagram") the manual gas valve.
3. Switch on the power to the water heater using the isolator between the water heater and the power supply.
4. Use the ON/OFF switch on the control panel to put the appliance in 'ON' mode (position 'I') or the weekly program mode (position 'II'); see paragraph
6.2 'Operating modes'.
5. Set the desired water temperature using the control thermostat (7.5 "Control thermostat").
If there is a heat demand, the appliance will run through the heating cycle (9.3 "The appliance's
heating cycle").
9.3 The appliance's heating cycle
The appliance's heating cycle is activated when the measured water temperature (T
water
) falls below the
threshold value (T
set
). This threshold value depends on the currently selected appliance operating mode. If the appliance is in the 'OFF' mode (frost protection), for example, this value is 20°C. If the appliance is in the 'ON' mode, this threshold value can be selected, for example, position 3 (±60°C).
The heating cycle runs successively through the following states:
1. HEAT DEMAND;
2. WAITING TIME;
3. PRE-GLOW;
4. IGNITION;
5. RUNNING;
6. WAITING TIME.
The complete cycle is explained in the example set out below.
Comment
The appliance runs through an identical cycle
when frost protection is activated.
1. The control thermostat sensor measures the water temperature. The water temperature falls below the set temperature of (for example) 60°C, causing the control thermostat to close. The burner control now detects a demand and starts the heating cycle.
2. Following demand, the waiting time starts. This waiting time ensures that ignition takes place safely. The waiting time lasts about 15 seconds.
3. Once the waiting time is over (audible 'clicking' of the relay in the burner control) the pre-glowing of the hot surface igniter is started
4. After about 12 seconds (pre-)glowing, the gas control is opened and ignition can take place.
5. After ignition, the flame is detected and the appliance will be running. This means that actual heating has started.
6. When the water reaches the set temperature, the demand ceases. The gas control closes, and the burner tray is extinguished. A new waiting time begins, of about 10 seconds.
7. After this waiting time, the appliance enters an idle state, and waits until the water temperature again falls below the set temperature.
With any subsequent heat demand, the heating cycle will resume from step 1.
Page 50
Starting the water heater
50 Instruction manual CHA
9
gis
Page 51
Instruction manual CHA 51
gis
10 Shutting down
10.1 Introduction
Topics covered in this chapter:
Shut the appliance down for a brief period ('OFF'
mode);
Isolating the appliance from the mains;
Shutting the appliance down for a long period.
10.2 Shut the appliance down for a brief
period ('OFF' mode)
To disable the device for a short period, you must switch on the frost protection using the appliance heating cycle (2.3 "Water heater operating cycle").
You can use the frost protection to prevent water freezing in the appliance. Activate frost protection by switching the ON/OFF switch on the control panel to the 0 position.
10.3 Isolating the appliance from the mains
The appliance may only be isolated from mains power in the correct way. The correct procedure is as follows:
1. Shut down the appliance by putting the ON/OFF switch to position 0.
2. Isolate the appliance from the power supply by setting the isolator between the appliance and the mains power supply to position 0.
10.4 Shutting the appliance down for a long
period
If the device is to be shut down for a longer period, you must drain the appliance (6 "Draining").
Page 52
Shutting down
52 Instruction manual CHA
10
gis
Page 53
Instruction manual CHA 53
gis
11 Errors
11.1 Introduction
This chapter covers the following errors:
Gas smell
Water leakage
Explosive ignition.
Poor flame profile.
Power Anode.
No hot water
Insufficient hot water
11.2 Error conditions
If the water heater goes into an "error" condition, you will be unable to draw hot water. The frost protection will also be out of operation. These error conditions are divided into three groups:
Lockout error from the flue gas thermostat
The safety (pushbutton) on the flue gas thermostat in the draught diverter has been activated. After removing the cause, the pushbutton (7.6 "Burner
control reset button") must be pressed to restart the appliance.
Lockout error from the flue gas thermostat
When this happens, the red LED on the control panel will be illuminated. The burner control is locked out. After eliminating the cause, the appliance must be returned to service by pressing the reset button (7.6 "Burner control reset button").
Blocking errors
You can recognise this condition from the fact that the appliance does not start running even though the water temperature is lower than the setting that you have defined using the control thermostat (7.5 "Control
thermostat").
These errors disappear automatically once the cause of the error has been removed, after which the appliance resumes operation by itself.
The following pages provide troubleshooting tables for each type of error.
Comment
Footnotes referred to from within any table are shown at the bottom of the
last page of that table.
Page 54
54 Instruction manual CHA
11.3 CHA Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General faults and failures
Feature Cause Measure Comment
Gas smell Gas leak
Warning
Close the main gas valve at once.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Immediately contact your installation engineer or local gas
company.
Water leakage Leakage from a water
connection (threaded)
Tighten the threaded connection If the leak persists, consult your installation engineer
Leakage from another nearby water water heater or pipe segment
Trace the leak
Leakage from the water heater tank
Consult the supplier and/or manufacturer
Condensation Before drawing off (too much) hot tap water, wait until the water in
the heater has reached the set temperature.
Explosive ignition
Poor flame profile
Incorrect supply pressure and/or burner pressure
Set the correct supply pressure and/or burner pressure. (3.11 "Checking the supply pressure and burner
pressure")
If ignition is not improved, consult your installation engineer.
Contaminated burner Clean the burner(s) (12.4.2 "Clean the burner(s)")
Contaminated orifice Clean the orifice(s) (12.4.3 "Clean the orifice(s)")
Inadequate air supply Improve the air supply by better ventilating the boiler room.
Page 55
Instruction manual CHA 55
11.4 CHA Troubleshooting table - no hot water
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Power Anode If the error cannot be rectified, contact your installation engineer
• Indicator lamp is red
• Anodes not making contact with the water
• Break in one of the cables
• Anode poorly earthed
3. Check to see that all connections have been made properly
4. Check that the Power Anode is properly connected; see Electrical Diagram (14 "Electrical diagram").
5. Check to see that all connections have been made properly
6. Check all cables for breaks and replace if any are found.
• Indicator lamp is off No electrical supply to the potentiostat
Check the electrical supply
Feature Cause Measure Comment
Page 56
56 Instruction manual CHA
No hot water
Feature Cause Measure Comment
Green LED OFF
and
Red LED OFF
No supply voltage present
1. Check whether the isolator is ON.
2. Check whether there is power to the isolator
3. Check whether there is power to the electrical connector block
4. Check whether there is power to the burner control
5. Check fuse in the burner control
The measured voltage must be 230 V
AC (-15%, +10%)
See the electrical diagram (14 "Electrical diagram"). If the error cannot be rectified, contact your installation engineer
Green LED ON
and
Red LED OFF
Blockage in the flue gas discharge (the flue gas thermostat has cut out)
1. Trace the blockage
2. Remove the blockage
3. Reset flue gas thermostat
(7.7 "Flue gas thermostat reset
button")
.
When a demand is detected, the appliance will restart
Page 57
Instruction manual CHA 57
Green LED ON
and
Red LED ON
There are three possible causes for this error. In order to determine the cause, you must cause the error to appear again:
1. Reset the appliance by pressing the reset button 1x
2. If nothing happens, then the reset button has been pressed too often (maximum 5 times
in a single heating cycle). Disconnect the appliance from the mains and then restart it. SeeIsolating the appliance from the mains and steps 3 through 5 of Starting the water
heater.
3. Decide which type of cause (a) or (b) describes the situation.
If the error cannot be resolved or is persistent, contact your installation engineer
(a) three unsuccessful start attempts in a row
1. No gas:
- Check that the gas valve is open
- Check whether the gas control is opening (clicking of the gas control)
- Check the leads of the gas control
2. No ignition:
- Check whether the hot surface igniter lights up
- Check the electrical supply to the hot surface igniter.
- Check the leads of the glow igniter
3. No flame detection:
- Check that the Phase (L) and Neutral (N) are correctly connected (from the mains) to the appliance
- Check whether the flame probe is defective
- Check that the flame probe leads are properly connected
(b) The safety thermostat has cut out
1. The safety thermostat has cut out correctly:
- Reset the appliance
- Check whether the high-limit thermostat is working
- Check that the circulation pump (if present) is working
2. The safety thermostat has cut out without apparent reason:
- Check whether the thermostat is defective
- Check whether the sensor of the thermostat is defective
Feature Cause Measure Comment
Page 58
58 Instruction manual CHA
11.5 CHA Troubleshooting table - Insufficient hot water
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
Insufficient hot water
Feature Cause Measure Comment
Insufficient hot water Water temperature
setting (T
set
) is too low
Set the control thermostat (7.5 "Control thermostat") to a higher value
Hot water supply is used up
1. Reduce hot water consumption and give the water heater time to heat up.
2. If this error persists, check whether the high-limit thermostat is switching. If this is the case, check that the circulation and/or top to bottom circulation pump are working.
If the error has not been rectified, and no other cause can be found, isolate the appliance from the mains (10.3 "Isolating the appliance
from the mains"), shut off the manual gas valve and alert your
installation engineer.
Page 59
Instruction manual CHA 59
s
12 Performing
maintenance
12.1 Introduction
Note
Maintenance may only be performed by a qualified service and
maintenance engineer.
At each service, the appliance undergoes maintenance on both the water side and the gas side. The maintenance must be carried out in the following order.
1. Water-side maintenance
2. Water-side maintenance
3. Gas-side maintenance
4. Finalising maintenance
Comment
To order spare parts, it is important to write down the appliance type and model, and the full serial number of the appliance. These details can be found on the rating plate. Only by ordering with this information can you be sure to receive the correct spare parts.
12.2 Preparation for maintenance
To test whether all components are still working properly, complete the following steps:
1. On the control panel, set the ON/OFF switch to position 0.
2. Set the control thermostat (note the original setting) to the highest position, and put the ON/OFF switch back to position I.
3. If there is no demand, draw some hot water off to create demand.
4. Check whether the heating cycle (9.3 "The appliance's heating cycle") is running correctly .
5. Set the control thermostat back to the original setting, and put the ON/OFF switch back to position I.
6. Check the supply and burner pressures (3.11 "Checking the supply
pressure and burner pressure") and adjust them where necessary.
7. Check that all components of the chimney flue system are properly attached.
8. Test the operation of the overflow valve of the protected cold supply setup. The water should spurt out.
9. Test the overflow operation of the T&P valve. The water should spurt out.
10. Check the drainpipes from the discharge points of all valves and remove any scale deposits that may be present.
11. Drain the appliance (6 "Draining").
12.3 Water-side maintenance
12.3.1 Introduction
The following steps must be carried out on the water side:
1. Checking the anodes.
2. Descaling and cleaning the tank.
Page 60
Performing maintenance
60 Instruction manual CHA
12
s
12.3.2 Checking the anodes
Timely replacement of the anodes extends the service life of the appliance. The appliance's anodes must be replaced as soon as they are 60% or more used up (take this into consideration when determining the maintenance frequency).
1. Disconnect the plug of the flue gas thermostat from the connector on the appliance.
2. Disconnect the draught diverter from the flue gas discharge.
3. Unscrew the screws from the lid on top of the appliance.
4. Remove the lid from the appliance, including the draught diverter.
5. Remove the sealing ring from the appliance.
6. Undo the anodes using suitable tools.
7. Check the anodes, and if necessary, replace them.
8. Now also check the flue baffles (12.4.4 "Checking the flue baffles"). Replace them, if necessary.
9. Place a new sealing ring on the rim of the tank and re-fit the lid.
10. Insert the plug of the flue gas thermostat into the connector on the appliance.
12.3.3 Descaling and cleaning the tank
Scale and lime build-up prevent effective conduction of the heat to the water. Periodic cleaning and descaling prevents build-up of these deposits. This increases the service life of the water heater, and also improves the heating process.
Take the rate of scale formation into account when deciding on the service interval. Scale formation depends on the local water composition, the water consumption and the water temperature setting. A water temperature setting of maximum 60°C is recommended for the prevention of excessive scale build-up.
To guarantee a good, watertight seal around the cleaning opening, replace the gasket (6), the O-ring (7), washers (4), bolts (3) and if necessary the lid (5) with new parts before reassembly (see diagram). A special set is obtainable from the supplier/manufacturer.
To simplify descaling and cleaning of the tank, the appliance is equipped with two cleaning openings.
1. Remove the cover plate (1) on the outer jacket (see the figure).
2. Carefully remove the insulation (2) and set it to one side. This will be needed again later.
2
6
7
1
4
5
3
IMD-0235 R2
Page 61
Instruction manual CHA 61
s
3. Undo the bolts.
4. Remove the lid, the gasket and the O-ring.
5. Inspect the tank and remove the loose scale deposits and contamination.
6. If the scale cannot be removed by hand, descale the appliance with a descaling agent. Contact the supplier/manufacturer for advice on what descaling agent to use.
7. Close the cleaning opening. To avoid damage to the tank, tighten the bolts that fasten the lid with a torque no greater than 50 Nm. Use suitable tools for this. To seal the cleaning opening properly, we recommend tightening the bolts in the sequence shown in the diagram.
12.4 Gas-side maintenance
12.4.1 Introduction
The following steps must be carried out on the gas side:
1. Clean the burner(s).
2. Clean the orifice(s).
3. Checking the flue baffles.
12.4.2 Clean the burner(s)
1. Detach the burner(s)
2. Remove all contamination present on the burner(s).
3. Fit the burner(s)
12.4.3 Clean the orifice(s)
1. Detach the orifice(s)
2. Remove all contamination present in the orifice(s).
3. Fit the orifice(s)
1
3
6
2
4
5
IMD-0282 R1
Page 62
Performing maintenance
62 Instruction manual CHA
12
s
12.4.4 Checking the flue baffles
Warning
The flue baffles may be hot.
1. Carry out steps 1 through 7 of the anode (1 "Disconnect the plug of the flue
gas thermostat from the connector on the appliance.") check.
1. Remove the flue baffles from the appliance.
2. Check the flue baffles for rust, and remove any which is present.
3. Check the flue baffles for wear, and replace any worn flue baffles.
4. Place a new sealing ring on the rim of the tank and re-fit the lid.
5. Insert the plug of the flue gas thermostat into the connector on the appliance.
12.5 Finalising maintenance
To finalise the maintenance, carry out the following steps:
1. Fill the appliance (5 "Filling").
2. Start the appliance up (9 "Starting the water heater")
Page 63
Instruction manual CHA 63
gis
13 Warranty (certificate)
If within 1 (one) year of the invoice date or commissioning date of a water heater supplied by Lochinvar Ltd, following verification, and at the sole discretion of Lochinvar Ltd, an assembly or part (with exclusion of the tank) proves to be defective or fails to function correctly due to manufacturing and/or material defects, then Lochinvar Ltd shall repair or replace this assembly or part.
13.1 Garantie (certificaat)
If within 3 (three) years of the invoice date or commissioning date of a water heater supplied by Lochinvar Ltd, following verification, and at the sole discretion of Lochinvar Ltd, the enamel-lined steel tank proves to be leaking due to rust or corrosion occurring on the water side, then Lochinvar Ltd shall offer to replace the defective water heater with an entirely new water heater of equivalent size and quality The warranty period given on the replacement water heater shall be equal to the remaining warranty period of the original water heater that was supplied.
13.2 Conditions for
installation and use
The warranty set out in articles 1 and 2 will apply solely under the following conditions:
a. The water heater is installed under strict adherence to Lochinvar Ltd
installation instructions for the specific model, and must be in accordance with the relevant requirements of the Gas Safety Regulations, Building Regulations, I.E.E. Regulations and the byelaws of the local water undertaking. The installation should also be in accordance with any relevant requirements of the local gas distributor and local authority.
b. The water heater remains installed at the original site of installation.
c. The water heater is used exclusively with drinking water, which at all
times can freely circulate (a separately installed heat exchanger is mandatory for heating saline water or corrosive water).
d. The tank is safeguarded against harmful scaling and lime build-up by
means of periodic maintenance.
e. The water temperatures in the heater do not exceed the maximum
setting of the thermostats, which form a part of the water heater.
f. The water pressure and/or heat load do not exceed the maximum values
stated on the water heater rating plate.
g. The water heater is installed in a non-corrosive atmosphere or
environment.
h. The water heater is connected to a protected cold supply arrangement,
which is: approved by the relevant authority; with sufficient capacity for this purpose; supplying a pressure no greater than the working pressure stated on the water heater; and where applicable by a likewise approved temperature and pressure relief valve, fitted in accordance with installation instructions of Lochinvar Ltd applying to the specific model of water heater, and further in compliance with Building Regulations, local authority installation byelaws and the Water Supply (Water Fittings) Regulations 1999 .
i. The water heater is at all times fitted with cathodic protection. If sacrificial
anodes are used for this and these anodes have reduced in size by more than 40% at any point along their length or if they are severely pitted, new anodes should be fitted. Particular attention should be paid to the ends of each anode to ensure excessive localized depletion has not
Page 64
Warranty (certificate)
64 Instruction manual CHA
13
gis
occurred. Where anodes are covered with particles they should be cleaned; for reference, when new, the anode has a diameter of 21 mm. When power anodes are used, it is important to ensure that they continue to work properly.
13.3 Exclusions
The warranty set out in articles 1 and 2 will not apply in the event of:
a. damage to the water heater caused by an external factor;
b. misuse, neglect (including frost damage), modification and incorrect
and/or unauthorized use of the water heater;
c. contaminants or other substances having been allowed to enter the tank;
d. any attempts at repair to a defective water heater other than by an
approved service engineer.
13.4 Scope of the warranty
The obligations of Lochinvar Ltd pursuant to the specified warranty are limited to free delivery from the warehouse of the replacement assemblies, parts or water heater, respectively. Labor, installation and any other costs associated with the replacement will not be accepted by Lochinvar Ltd.
13.5 Claims
A claim on grounds of the specified warranty must be submitted to the dealer from whom the water heater was purchased, or to another authorized dealer of Lochinvar Ltd. Inspection of the water heater as referred to in articles 1 and 2 shall take place in one of the laboratories of Lochinvar Ltd
13.6 Obligations of Lochinvar Ltd
Lochinvar Ltd grants no other warranty or guarantee over its water heaters nor the (assemblies or parts of) water heaters supplied for replacement, other than the warranty expressly set out in these conditions.
Under the terms of the supplied warranty, Lochinvar Ltd is not liable for damage to persons or property caused by (assemblies or parts, or the glass-lined steel tank of) a (replacement) water heater that it has supplied.
Page 65
Instruction manual CHA 65
is
14 Electrical diagram
14.1 Introduction
This section gives the electrical diagrams for:
Electrical diagram for CHA 100 to 700 natural gas, CHA 100 to 600 LPG
Electrical diagram for CHA 700 LPG
Page 66
Electrical diagram
66 Instruction manual CHA
14
is
14.1.1 Electrical diagram for CHA 100 to 700 natural gas, CHA 100 to 600 LPG
1 = brown, 2 = blue, 3 = yellow/green, 4 = black, 5 = white
2
1
L
1
3
4
N
230V AC
L
50Hz
N
NN
O
C
P
A
HGJ
P
O
2
N
N
L
L
I
N
N
Q
I 0 II
4
K L
M
LLLL
1234
M
R1
121 2 345 131415
L
23
L
4
12
12
1
4
1
1
42121444 333 43
11
B
1
C
4
3
12
4
3
11
12
4
N
TV
L
L"N
HN1
G
HOT
LA
GNX
FACE
SUR-
M
I
FUSE
F1
N
4
NO P NC
87N
L
4 444
976 81011
2 1144
444
421 365
2 3445
12
4
3
5
1
4
2
4
11
F
E
4
11
1
D
3
3
0305905 R0
Page 67
Instruction manual CHA 67
is
TERMINAL STRIP CONNECTIONS:
Earth
N Neutral
LLive
L
1
Phase input of controller
L
2
Phase input of thermal reflux safeguard
L
3
Phase input of safety circuit for releasing temperature regulation
NO Normal open
P PVC supply
NC Normal closed
COMPONENTS:
A Burner control
N Neutral
Earth
L' Phase input to controller
L" Phase output
TH Phase input of thermostat circuit
GV1 Phase output to gas control
MAX Phase input to safety thermostat
LG Phase output to hot surface igniter
I Ionisation detection = output
NO Normal open
P Phase input to alarm
NC Normal closed
F1 Fuse (T5A)
R1 Relay max. 250V, 10A
B Frost thermostat
C Control thermostat
D On/off/on switch
E Safety thermostat
F High-limit thermostat
G Gas valve
H Hot surface igniter
J Flame probe
K Error signal
L Operational signal
M Reset button
N Thermal reflux safeguard
OPTIONAL COMPONENTS:
O Control isolator
P CORREX Power Anode control
Q Weekly timer circuit
Page 68
Electrical diagram
68 Instruction manual CHA
14
is
14.1.2 Electrical diagram for CHA 700 LPG
1 = brown, 2 = blue, 3 = yellow/green, 4 = black
4
11
F
E
4
11
1
D
3
3
4
12
12
1
4
1
1
42121444 333 43
11
B
1
C
4
3
12
4
3
11
12
4
N
TV
L
L"N
HN1
G
HOT
LA G
NX
FACE
SUR-
M
I
FUSE
F1
P
2
1
L
1
3
4
N
220-240V AC
L
50Hz
N
NN
O
C
P
A
R
Q
2
N
N
L
L
I
N
N
S
I 0 II
4
M
N
O
LLLL
1234
M
R1
121 2 345 131415
L
23
L
4
NO P NC
87N
L
4 44 4
976 81011
2 1144
444
421 365
2 3444
12
3
G
12
K
JH
45
768
321 444 2
3
9
2
2
3L2
L
N
18
4L424162A18
16
L
A
1
1
T
T
4
L
1
1
1
1
15
L
L
A
1
2
4
15
2
N
L
A
2
LNNLINL
4
1
4
2
3
0306159 R0
Page 69
Instruction manual CHA 69
is
TERMINAL STRIP CONNECTIONS:
Earth
N Neutral
LLive
L
1
Phase input of controller
L
2
Phase input of thermal reflux safeguard
L
3
Phase input of safety circuit for releasing temperature regulation
NO Normal open
P PVC supply
NC Normal closed
COMPONENTS:
A Burner control
N Neutral
Earth
L' Phase input to controller
L" Phase output
TH Phase input of thermostat circuit
GV1 Phase output to gas control
MAX Phase input to safety thermostat
LG Phase output to hot surface igniter
I Ionisation detection = output
NO Normal open
P Phase input to alarm
NC Normal closed
F1 Fuse (T5A)
R1 Relay max. 250V, 10A
B Frost thermostat
C Control thermostat
D On/off/on switch
E Safety thermostat
F High-limit thermostat
G Gas control
H Hot surface igniter
J Flame probe
K High-low control
LTimer
M Error signal
N Operational signal
O Reset button
P Thermal reflux safeguard
OPTIONAL COMPONENTS:
Q Control isolator
R CORREX Power Anode control
S Weekly timer circuit
Page 70
Electrical diagram
70 Instruction manual CHA
14
is
Page 71
Instruction manual CHA 71
is
15 Declaration of
Conformity
Commercial Gas Fired Storag e Water Hea ter
CHA 100, CHA 155, CHA 20 0, CHA 300, CHA 40 0, CHA 500,
CHA 600, CHA 700
Ga s App liance Directiv e - 90 /396/EC
Low Voltage Direct ive - 2006/95/EC
EMC Directive - 200 4/108/E C
Stan dards use d:
- EN89: 1999
- EN5016 5: 19 97
Stan dards use d:
- EN6033 5-1: 19 94
- EN5016 5: 19 97
Stan dards use d:
- EN5501 4-1: 19 93
- EN5501 4-2: 19 97
- EN6100 0-3-2: 1995
- EN6100 0-3-3: 1995
- EN5016 5: 19 97
March 1, 2012
EEC - Declaration of Conformity
Supplier:
her eby d eclare s that t he followi ng pr oducts:
Product description:
Product models:
on th e assumption th at the i nstal latio n ins truct ions have been followed a re comp liant to:
as sta ted in the EC t ype-ex amina tion repo rt by KIWA-Gastec Certifi cati on BV, the Netherla nds.
Company: Date: Signature:
D. J. Pe pper
Managing D irector
Lochinvar Limited
7 Lom bard Way The MXL Centre Banbury - United Kingdom
L och inva r Li mit ed
Page 72
Declaration of Conformity
72 Instruction manual CHA
15
is
Page 73
Instruction manual CHA 73
Index
A
ambient conditions 16 ambient temperature 16
B
burner pressure 29
C
connecting the circulation pipe 23, 24 connecting the cold water side 22, 23 connecting the hot water side 23 control thermostat 45 conversion to a different gas category 33
D
document contents 9 draining 43
E
electrical connection 26
F
filling 41 flame probe 14
G
gas category, conversion to different 33 gas connection 24 general specifications 3
H
humidity 16
I
installation diagram 21 installation engineer 8, 9 isolator 27
J
join
circulation pipe 23, 24 cold water side 22, 23 electrical 26, 27 gas 24 hot water side 23 shuntleiding 22, 23
L
liability 3
M
mains power 27 maintenance
burner 61 finalizing 62 gas-side 61 orifice 61 performing 59 preparation 59 water-side 59
N
notation conventions 9
O
operating cycle 13
P
packaging 15 protection 13
S
scale 60 service 8 service engineer 8 shutting down
electrically isolating 51 long period 51
short period 51 specifications 18 supply pressure 29 symbol
installation engineer 8
service engineer 8
user 8
T
target groups 8 top to bottom circulation pump 22, 23 trademarks 3
U
user 8
gis
Page 74
0310 569 1.0 UK
Index
Instruction manual CHA