Lochinvar CH1261 Installation Manual

DD EESS II GGNN EERRSS GG UU IIDD EE CCOO PP PP EERR -- FFII NN II II®®BB OO II LL EE RR
400,000 – 2,070,000 Btu/hr
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope our manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built water heaters and boilers.
Sincerely,
Lochinvar Corporation
Lochinvar Corporation • 615-889-8900 • Fax: 615-547-1000
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 1
Air Removal . . . . . . . . . . . . . . . . . . . . . .23
Boiler Operating Temperature Control . . . .24
Circulator Pump Operation . . . . . . . . . . .18
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .6
Contaminants . . . . . . . . . . . . . . . . . . . . . .7
Determining Total “Free Area” . . . . . . . . . .7
Electrical Requirements . . . . . . . . . . . . . . .24
Gas Supply . . . . . . . . . . . . . . . . . . . . . .17
General Venting . . . . . . . . . . . . . . . . . . . .7
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low System Water Volume . . . . . . . . . . . .23
Low Water Temperature System . . . . . . . .21
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .4
Outdoor Installation . . . . . . . . . . . . . . . . .16
Primary/Secondary Piping . . . . . . . . . . . .19
Relief Valve . . . . . . . . . . . . . . . . . . . . . . .20
Remote Temperature Control . . . . . . . . . . .24
Special Design Applications . . . . . . . . . . .22
Variable Speed Pumping . . . . . . . . . . . . .19
Venting Options . . . . . . . . . . . . . . . . . . . .9
Water Flow Requirements . . . . . . . . . . . .18
Water Velocity Control . . . . . . . . . . . . . . .18
Figures & Tables Index
FIG. 1 Models CH 991-2071
Requirements For Installation
Over Combustible Floor . . . . . . .3
FIG. 2 Models CH 401- 751 Special
Combustible Floor Base . . . . . . .4
FIG. 3 Boiler Equipment &
Control Orientation . . . . . . . . . . .5
FIG. 4-7 Combustion & Ventilation Air . .6,7 FIG. 8 Barometric Damper Installation . .9
FIG. 9 Multiple Unit Barometric
Damper Installation . . . . . . . . . .10
FIG. 10 Powered Sidewall Venting . . . . .10
FIG. 11 Power DirectAire Horizontal . . .11
FIG. 12 Vertical Vent and Air Inlet . . . . .13
FIG. 13 Vertical Vent and
Sidewall Air Inlet . . . . . . . . . . .13
FIG. 14 Aire-Lock Direct Vent . . . . . . . . .14
FIG. 15 Sidewall Vent . . . . . . . . . . . . . .16
FIG. 16 Outdoor Venting . . . . . . . . . . . .16
FIG. 17 Heat Exchanger Head Loss
Models CH 401-751 . . . . . . . .19
FIG. 18 Heat Exchanger Head Loss
Models CH 991-2071 . . . . . . .19
FIG. 19 Primary/Secondary
System Piping . . . . . . . . . . . . . .20
FIG. 20 High Flow System Piping . . . . . .20
FIG. 21 Low Temperature Bypass
System Piping . . . . . . . . . . . . . .21
FIG. 22 Low Temp Bypass Piping
On/Off . . . . . . . . . . . . . . . . . .22
FIG. 23 Low Temp Bypass Piping
Proportional Stage Firing . . . . . .22
FIG. 24 Heating/Chilled
Water System . . . . . . . . . . . . . .22
FIG. 25 Buffer Tank Piping . . . . . . . . . . .23
TABLE A. Combustible Floor Kits . . . . . . . .3
TABLE B. Clearances From
Combustibles . . . . . . . . . . . . . .4
TABLE C. Flue Sizes and
Inlet Air Pipe Sizes . . . . . . . . . . .9
TABLE D. Powered Sidewall Vent Kits . . .11 TABLE E. Powered DirectAire Horizontal
Vent Kits . . . . . . . . . . . . . . . . .12
TABLE F. DirectAire Vertical Sidewall and
Rooftop Air Inlet Kits . . . . . . . .14
TABLE G. Direct Vent Kits . . . . . . . . . . . . .15
TABLE H. Sidewall Vent Kits . . . . . . . . . . .15
TABLE I. Outdoor Kits . . . . . . . . . . . . . .16
TABLE J. Gas Supply Pipe Sizing . . . . . .17
TABLE K. Inlet Gas Pressure . . . . . . . . . . .18
TABLE L. Water Flow Requirements . . . . .18
TABLE M. Minimum and Maximum
Boiler Flow Rates . . . . . . . . . . .19
TABLE N. Amp Draw Data . . . . . . . . . . . .24
Boiler Piping Diagrams
Primary/Secondary . . . . . . . . . . . . . . . .A1
Multiple Unit Primary/Secondary . . . . . . .A2
Low Temperature Boiler Bypass . . . . . . . .A3
Low Temperature Boiler Bypass w/
3-Way valve . . . . . . . . . . . . . . . . . . . . . .A4
Table of Contents
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or B149.2 and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
1.
2 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
Water Velocity
(See Page 19 for minimum and maximum boiler flow rates.)
Piping Requirements
and Specialties
(See Page 19 for water flow requirements and system piping.)
Low Water
Temperature System
(See Page 21 for piping and design recommendations.)
System and Boiler
Control
(See Page 24 for boiler operating and temperature control.)
Air Elimination and
Expansion Tank Placement
(See Page 23 for air removal information.)
In designing
a hot water heating
system, pay special
attention to:
The indoor units must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
The appliance must be installed on a level, non-combustible floor. Concrete over wood is not considered a non-combustible floor. Maintain required clearances from combustible surfaces.
For installation on a combustible floor only when installed on special base: Units installed over a
combustible floor MUST use the Special Combustible Floor Base. The unit must be centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or
concrete blocks from 8to 12thick and extending 24beyond the sides.
• The blocks must be placed in line so
that the holes line up horizontally to provide a clear passage through the blocks.
This procedure should also be
followed if electrical conduit or radiant heat distribution piping runs through the floor and beneath the appliance.
• Ensure that combustible floor base meets local fire code requirements.
• The correct kit number for the required base is noted on the rating plate of each unit and listed in Table A.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 3
(TABLE A)
COMBUSTIBLE FLOOR KITS
MODEL NUMBER KIT NUMBER
CH401 CFK3301
CH501 CFK3302
CH651 CFK3303
CH751 CFK3304
2.
3.
4.
(FIG. 1) CH 991-2071 REQUIREMENTS FOR INSTALLATION OVER COMBUSTIBLE FLOOR
Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit or any of its components.
Outdoor models require the installation of an optional vent cap. Instructions for placement of the vent cap are included in the venting section.
Outdoor models must not be installed directly on the ground. The outdoor unit must be installed on a concrete brick, block or other non-combustible pad. Outdoor models have additional special location and clearance requirements. (See Outdoor Installation Pg. 16)
SPECIAL LOCATION: OUTDOOR USE
Copper-Fin II Models are approved for outdoor installations. Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See Outdoor Installation, in the venting section on page 16.
5.
(FIG. 2) MODELS CH 401-751 INSTALLED WITH
OPTIONAL COMBUSTIBLE FLOOR BASE
4 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
(TABLE B) – CLEARANCES FROM COMBUSTIBLES
CLEARANCES CH401-751 CH991-2071
Right Side 1 3”
Rear 1 3”
Left Side 6 3”
(24” for Service) (24” for Service)
Front ALCOVE* ALCOVE*
(24” for Service) (30” for Service)
Top 1 3”
Flue 1+1”+
Hot Water Pipes 1 1”
* Alcove is a closet without a door. + Consult local codes and/or vent manufacturer.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 5
(FIG. 3) BOILER EQUIPMENT AND CONTROL ORIENTATION.
FLUE PRODUCTS VENT
GAS CONNECTION
TERMINAL STRIP
DRAIN
BURNER INSPECTION PORT
OPERATOR INTERFACE PANEL
LEFT SIDE
FRONT
GAS
CONNECTION
DRAIN
LEFT SIDE
OPERATOR INTERFACE PANEL
BURNER INSPECTION PORT
FRONT
AIR INLET
SYSTEM SUPPLY
SYSTEM RETURN
FLUE PRODUCTS VENT
BACK
BACK
SYSTEM RETURN
120V ELECTRICAL
CONNECTION
TERMINAL
STRIP
SYSTEM SUPPLY
AIR INLET
CH 401-751
CH 991-2071
6 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
EXAMPLE OF SIZING
FOR COMBUSTION
& VENTILATION AIR
OPENINGS (BOILER
WITH 2,070,000
Btu/hr
When combustion and
ventilated air is taken
from directly outside the
building (FIG. 4), divide
the total BTU’s by 4,000.
This yields 517.5 sq.in.
of “Free Area” without
restriction.
(2,070,000 ÷ 4000 =
517.5 sq.in.)
Since the air opening is
50% closed due to
screens and louvers, the
total opening MUST be
multiplied by 2.
(517.5 sq. in. x 2 =
1,035 sq.in.)
This project requires one
Ventilation Air Opening
with a net area of 1,035
square inches with louver
dimensions of 30” x 35”
and one Combustion Air
Opening with a net area
of 1,050 square inches
with louver dimensions
of 30” x 35”.
COMBUSTION & VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada, the latest edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and Equipment; or applicable provisions of the
local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two
permanent openings:
A. Combustion air opening with a minimum free area of one square inch per 4000 Btu input (5.5 cm
2
per kW).
This opening must be located within 12 (30 cm) of the bottom of the enclosure.
B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu input (5.5 cm
2
per kW). This opening
must be located within 12” (30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu input (11cm
2
per kW).
If air is taken from another interior space, each of the two openings
specified above should have a net free
2.
3.
(FIG. 4) COMBUSTION AIR DIRECT FROM OUTSIDE
(FIG. 5) COMBUSTION AIR THROUGH DUCTWORK
(FIG. 6) COMBUSTION AIR FROM AN
INTERIOR SPACE
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 7
CAUTION!
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a down draft in the venting system. If a fan is used to supply combustion air to the equipment room, it MUST be sized to make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
area of one square inch for each 1000 Btu (22 cm
2
per kW) of input, but not less
than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free area of one square inch per 3000 Btu input (7 cm
2
per kW). This
opening must be located within 12 (30 cm) of the top of the enclosure.
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the water heater. Burning chemical fumes results in the formation of corrosive acids which attack the water heater, cause improper combustion and premature failure of the water heater and vent. These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
These boilers are classified as Category I appliances when tested to the latest ANSI Standard. This classification requires all conventionally vented combustion products to be vented using Category I listed vent pipe.
Additionally, it is recommended that this vent material be double wall construction or insulated in the field. A Category I appliance operates with a non-positive static vent pressure and with flue loss greater than 17 percent.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly. The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed
4.
(FIG. 7) COMBUSTION AIR FROM OUTSIDE,
SINGLE OPENING
8 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
NOTE: Flue gases will form a white plume in winter. Plume could obstruct window view. Flue gas condensate can freeze on exterior surfaces or on the vent cap. Flue gas condensate can cause discoloration of exterior building surfaces. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
Category I double wall vent (or equivalent) connectors and sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel Gas Code.
The Category I vent and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the vent manufacturer’s listing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in an existing building should be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code.
The weight of the venting system must not rest on the water heater. The venting system must be adequately supported in compliance with local codes and other applicable codes.
Vent Terminations
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.6 m) above the highest point of the roof when within a 10 foot (3.05 m) radius.
Additionally, vertical terminations must be a minimum of 3 feet (0.9 m) above the roof line, and when less than 10 feet (3.05 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the parapet wall.
Vent caps should have a minimum clearance of 4 feet (1.2 m) horizontally from, and in no case above or below [unless a 4 feet (1.2 m) horizontal distance is maintained], electric meters, gas meters, regulators and relief equipment.
Maintain a distance of at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3.05 m) and a distance of at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from, or 1 foot (30 cm) above any door, window or gravity air inlet.
Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30 cm) above grade and clear of snow, ice, leaves or other debris.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows, and building openings
Loading...
+ 22 hidden pages