Lochinvar CH1261 Installation Manual

Page 1
DD EESS II GGNN EERRSS GG UU IIDD EE CCOO PP PP EERR -- FFII NN II II®®BB OO II LL EE RR
400,000 – 2,070,000 Btu/hr
Page 2
Dear Specifier/Project Manager,
At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter into business must also accept the challenge of meeting constantly changing needs.
All information has been organized and presented in a succinct, easy-to-use manner, so you can use and share information confidently and with minimal effort.
However, it is important to remember that this guide is not intended to replace our installation manual. Installers should still refer to our installation manual for specific installation instructions.
We hope our manual will make your work easier and more productive. As always, we greatly appreciate your input on additional improvements for the future.
Thanks once again for specifying the Lochinvar family of quality standard and custom-built water heaters and boilers.
Sincerely,
Lochinvar Corporation
Lochinvar Corporation • 615-889-8900 • Fax: 615-547-1000
Page 3
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 1
Air Removal . . . . . . . . . . . . . . . . . . . . . .23
Boiler Operating Temperature Control . . . .24
Circulator Pump Operation . . . . . . . . . . .18
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Combustion & Ventilation Air . . . . . . . . . . .6
Contaminants . . . . . . . . . . . . . . . . . . . . . .7
Determining Total “Free Area” . . . . . . . . . .7
Electrical Requirements . . . . . . . . . . . . . . .24
Gas Supply . . . . . . . . . . . . . . . . . . . . . .17
General Venting . . . . . . . . . . . . . . . . . . . .7
Location of Unit . . . . . . . . . . . . . . . . . . . . .2
Low System Water Volume . . . . . . . . . . . .23
Low Water Temperature System . . . . . . . .21
Outdoor Use . . . . . . . . . . . . . . . . . . . . . . .4
Outdoor Installation . . . . . . . . . . . . . . . . .16
Primary/Secondary Piping . . . . . . . . . . . .19
Relief Valve . . . . . . . . . . . . . . . . . . . . . . .20
Remote Temperature Control . . . . . . . . . . .24
Special Design Applications . . . . . . . . . . .22
Variable Speed Pumping . . . . . . . . . . . . .19
Venting Options . . . . . . . . . . . . . . . . . . . .9
Water Flow Requirements . . . . . . . . . . . .18
Water Velocity Control . . . . . . . . . . . . . . .18
Figures & Tables Index
FIG. 1 Models CH 991-2071
Requirements For Installation
Over Combustible Floor . . . . . . .3
FIG. 2 Models CH 401- 751 Special
Combustible Floor Base . . . . . . .4
FIG. 3 Boiler Equipment &
Control Orientation . . . . . . . . . . .5
FIG. 4-7 Combustion & Ventilation Air . .6,7 FIG. 8 Barometric Damper Installation . .9
FIG. 9 Multiple Unit Barometric
Damper Installation . . . . . . . . . .10
FIG. 10 Powered Sidewall Venting . . . . .10
FIG. 11 Power DirectAire Horizontal . . .11
FIG. 12 Vertical Vent and Air Inlet . . . . .13
FIG. 13 Vertical Vent and
Sidewall Air Inlet . . . . . . . . . . .13
FIG. 14 Aire-Lock Direct Vent . . . . . . . . .14
FIG. 15 Sidewall Vent . . . . . . . . . . . . . .16
FIG. 16 Outdoor Venting . . . . . . . . . . . .16
FIG. 17 Heat Exchanger Head Loss
Models CH 401-751 . . . . . . . .19
FIG. 18 Heat Exchanger Head Loss
Models CH 991-2071 . . . . . . .19
FIG. 19 Primary/Secondary
System Piping . . . . . . . . . . . . . .20
FIG. 20 High Flow System Piping . . . . . .20
FIG. 21 Low Temperature Bypass
System Piping . . . . . . . . . . . . . .21
FIG. 22 Low Temp Bypass Piping
On/Off . . . . . . . . . . . . . . . . . .22
FIG. 23 Low Temp Bypass Piping
Proportional Stage Firing . . . . . .22
FIG. 24 Heating/Chilled
Water System . . . . . . . . . . . . . .22
FIG. 25 Buffer Tank Piping . . . . . . . . . . .23
TABLE A. Combustible Floor Kits . . . . . . . .3
TABLE B. Clearances From
Combustibles . . . . . . . . . . . . . .4
TABLE C. Flue Sizes and
Inlet Air Pipe Sizes . . . . . . . . . . .9
TABLE D. Powered Sidewall Vent Kits . . .11 TABLE E. Powered DirectAire Horizontal
Vent Kits . . . . . . . . . . . . . . . . .12
TABLE F. DirectAire Vertical Sidewall and
Rooftop Air Inlet Kits . . . . . . . .14
TABLE G. Direct Vent Kits . . . . . . . . . . . . .15
TABLE H. Sidewall Vent Kits . . . . . . . . . . .15
TABLE I. Outdoor Kits . . . . . . . . . . . . . .16
TABLE J. Gas Supply Pipe Sizing . . . . . .17
TABLE K. Inlet Gas Pressure . . . . . . . . . . .18
TABLE L. Water Flow Requirements . . . . .18
TABLE M. Minimum and Maximum
Boiler Flow Rates . . . . . . . . . . .19
TABLE N. Amp Draw Data . . . . . . . . . . . .24
Boiler Piping Diagrams
Primary/Secondary . . . . . . . . . . . . . . . .A1
Multiple Unit Primary/Secondary . . . . . . .A2
Low Temperature Boiler Bypass . . . . . . . .A3
Low Temperature Boiler Bypass w/
3-Way valve . . . . . . . . . . . . . . . . . . . . . .A4
Table of Contents
Page 4
CODES
The equipment shall be installed in accordance with those installation regulations in effect in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA- B149.1 and/or B149.2 and/or local codes.
LOCATION OF UNIT
Locate the unit so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. The pan must not restrict combustion air flow.
1.
2 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
Water Velocity
(See Page 19 for minimum and maximum boiler flow rates.)
Piping Requirements
and Specialties
(See Page 19 for water flow requirements and system piping.)
Low Water
Temperature System
(See Page 21 for piping and design recommendations.)
System and Boiler
Control
(See Page 24 for boiler operating and temperature control.)
Air Elimination and
Expansion Tank Placement
(See Page 23 for air removal information.)
In designing
a hot water heating
system, pay special
attention to:
Page 5
The indoor units must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).
The appliance must be installed on a level, non-combustible floor. Concrete over wood is not considered a non-combustible floor. Maintain required clearances from combustible surfaces.
For installation on a combustible floor only when installed on special base: Units installed over a
combustible floor MUST use the Special Combustible Floor Base. The unit must be centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or
concrete blocks from 8to 12thick and extending 24beyond the sides.
• The blocks must be placed in line so
that the holes line up horizontally to provide a clear passage through the blocks.
This procedure should also be
followed if electrical conduit or radiant heat distribution piping runs through the floor and beneath the appliance.
• Ensure that combustible floor base meets local fire code requirements.
• The correct kit number for the required base is noted on the rating plate of each unit and listed in Table A.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 3
(TABLE A)
COMBUSTIBLE FLOOR KITS
MODEL NUMBER KIT NUMBER
CH401 CFK3301
CH501 CFK3302
CH651 CFK3303
CH751 CFK3304
2.
3.
4.
(FIG. 1) CH 991-2071 REQUIREMENTS FOR INSTALLATION OVER COMBUSTIBLE FLOOR
Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit or any of its components.
Page 6
Outdoor models require the installation of an optional vent cap. Instructions for placement of the vent cap are included in the venting section.
Outdoor models must not be installed directly on the ground. The outdoor unit must be installed on a concrete brick, block or other non-combustible pad. Outdoor models have additional special location and clearance requirements. (See Outdoor Installation Pg. 16)
SPECIAL LOCATION: OUTDOOR USE
Copper-Fin II Models are approved for outdoor installations. Outdoor models have additional location and clearance requirements. These requirements must be adhered to carefully, since wind, rain, snow and cold cannot be controlled in outdoor applications. See Outdoor Installation, in the venting section on page 16.
5.
(FIG. 2) MODELS CH 401-751 INSTALLED WITH
OPTIONAL COMBUSTIBLE FLOOR BASE
4 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
(TABLE B) – CLEARANCES FROM COMBUSTIBLES
CLEARANCES CH401-751 CH991-2071
Right Side 1 3”
Rear 1 3”
Left Side 6 3”
(24” for Service) (24” for Service)
Front ALCOVE* ALCOVE*
(24” for Service) (30” for Service)
Top 1 3”
Flue 1+1”+
Hot Water Pipes 1 1”
* Alcove is a closet without a door. + Consult local codes and/or vent manufacturer.
Page 7
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 5
(FIG. 3) BOILER EQUIPMENT AND CONTROL ORIENTATION.
FLUE PRODUCTS VENT
GAS CONNECTION
TERMINAL STRIP
DRAIN
BURNER INSPECTION PORT
OPERATOR INTERFACE PANEL
LEFT SIDE
FRONT
GAS
CONNECTION
DRAIN
LEFT SIDE
OPERATOR INTERFACE PANEL
BURNER INSPECTION PORT
FRONT
AIR INLET
SYSTEM SUPPLY
SYSTEM RETURN
FLUE PRODUCTS VENT
BACK
BACK
SYSTEM RETURN
120V ELECTRICAL
CONNECTION
TERMINAL
STRIP
SYSTEM SUPPLY
AIR INLET
CH 401-751
CH 991-2071
Page 8
6 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
EXAMPLE OF SIZING
FOR COMBUSTION
& VENTILATION AIR
OPENINGS (BOILER
WITH 2,070,000
Btu/hr
When combustion and
ventilated air is taken
from directly outside the
building (FIG. 4), divide
the total BTU’s by 4,000.
This yields 517.5 sq.in.
of “Free Area” without
restriction.
(2,070,000 ÷ 4000 =
517.5 sq.in.)
Since the air opening is
50% closed due to
screens and louvers, the
total opening MUST be
multiplied by 2.
(517.5 sq. in. x 2 =
1,035 sq.in.)
This project requires one
Ventilation Air Opening
with a net area of 1,035
square inches with louver
dimensions of 30” x 35”
and one Combustion Air
Opening with a net area
of 1,050 square inches
with louver dimensions
of 30” x 35”.
COMBUSTION & VENTILATION AIR
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada, the latest edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and Equipment; or applicable provisions of the
local building codes.
The equipment room must be provided with properly sized openings to assure adequate combustion air and proper ventilation when the unit is installed with conventional venting or sidewall venting.
If air is taken directly from outside the building with no duct, provide two
permanent openings:
A. Combustion air opening with a minimum free area of one square inch per 4000 Btu input (5.5 cm
2
per kW).
This opening must be located within 12 (30 cm) of the bottom of the enclosure.
B. Ventilation air opening with a minimum free area of one square inch per 4000 Btu input (5.5 cm
2
per kW). This opening
must be located within 12” (30 cm) of the top of the enclosure.
If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two
openings should be sized based on a minimum free area of one square inch per 2000 Btu input (11cm
2
per kW).
If air is taken from another interior space, each of the two openings
specified above should have a net free
2.
3.
(FIG. 4) COMBUSTION AIR DIRECT FROM OUTSIDE
(FIG. 5) COMBUSTION AIR THROUGH DUCTWORK
(FIG. 6) COMBUSTION AIR FROM AN
INTERIOR SPACE
CAUTION: Under no circumstances should the equipment room be under a negative pressure when atmospheric combustion equipment is installed in the room.
Page 9
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 7
CAUTION!
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a down draft in the venting system. If a fan is used to supply combustion air to the equipment room, it MUST be sized to make sure that it does not cause drafts which could lead to nuisance operational problems with the boiler.
area of one square inch for each 1000 Btu (22 cm
2
per kW) of input, but not less
than 100 square inches (645 cm
2
).
If a single combustion air opening is provided to bring combustion air in directly from the outdoors,
the opening must be sized based on a minimum free area of one square inch per 3000 Btu input (7 cm
2
per kW). This
opening must be located within 12 (30 cm) of the top of the enclosure.
CONTAMINANTS
Combustion air drawn from an interior or exterior space must be free of any chemical fumes which could be corrosive to the water heater. Burning chemical fumes results in the formation of corrosive acids which attack the water heater, cause improper combustion and premature failure of the water heater and vent. These fumes are often present in areas where refrigerants, salts, and solvents are used. Therefore, be aware of swimming pool equipment, water softening, and cooling system placement.
VENTING
General
These boilers are classified as Category I appliances when tested to the latest ANSI Standard. This classification requires all conventionally vented combustion products to be vented using Category I listed vent pipe.
Additionally, it is recommended that this vent material be double wall construction or insulated in the field. A Category I appliance operates with a non-positive static vent pressure and with flue loss greater than 17 percent.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
The connection from the appliance vent to the stack must be as direct as possible and sized correctly. The horizontal breeching of a vent must have at least 1/4rise per linear foot. The horizontal portions should also be supported for the design and weight of the material employed to maintain clearances, prevent physical damage and separation of joints.
The connection from the appliance vent to the stack or vent termination outside the building must be made with listed
4.
(FIG. 7) COMBUSTION AIR FROM OUTSIDE,
SINGLE OPENING
Page 10
8 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
NOTE: Flue gases will form a white plume in winter. Plume could obstruct window view. Flue gas condensate can freeze on exterior surfaces or on the vent cap. Flue gas condensate can cause discoloration of exterior building surfaces. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
Category I double wall vent (or equivalent) connectors and sized according to vent sizing tables (FAN column) in the latest edition of the National Fuel Gas Code.
The Category I vent and accessories, such as firestop spacers, thimbles, caps, etc., must be installed in accordance with the vent manufacturer’s listing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any improper operation of the common venting system in an existing building should be corrected when new equipment is installed, so the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system, it should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code.
The weight of the venting system must not rest on the water heater. The venting system must be adequately supported in compliance with local codes and other applicable codes.
Vent Terminations
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.6 m) above the highest point of the roof when within a 10 foot (3.05 m) radius.
Additionally, vertical terminations must be a minimum of 3 feet (0.9 m) above the roof line, and when less than 10 feet (3.05 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the parapet wall.
Vent caps should have a minimum clearance of 4 feet (1.2 m) horizontally from, and in no case above or below [unless a 4 feet (1.2 m) horizontal distance is maintained], electric meters, gas meters, regulators and relief equipment.
Maintain a distance of at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3.05 m) and a distance of at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from, or 1 foot (30 cm) above any door, window or gravity air inlet.
Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30 cm) above grade and clear of snow, ice, leaves or other debris.
The distance of the vent terminal from adjacent public walkways, adjacent buildings, windows, and building openings
Page 11
must be consistent with the National Fuel Gas Code Z223.1 or in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
VENTING OPTIONS
Conventional Venting
A conventional venting system utilizes the natural buoyancy of the heated flue products to generate a negative draft. This draft forces flue products to rise vertically through a rooftop flue termination. The vent connection is made directly to the top of the unit and combustion air supplied from the mechanical room. Properly sizing vent material and the use of a barometric damper (when required) will lead to proper vent operation.
A barometric damper is required when draft exceeds 0.08 inches of negative water column. When installed and adjusted properly, a barometric damper will maintain draft between 0.02 and 0.08 inches of negative water column ensuring proper operation.
The minimum flue pipe diameters for all models, utilizing negative draft venting are as follows:
Size vent material using the “FAN” category of vent sizing tables in the latest edition of the National Fuel Gas Code. “FAN” applies to fan-assisted combustion appliances in Category I.
Multiple unit installations with combined venting also require barometric dampers to regulate draft at each unit. Again, the negative draft must be within the range of
0.02 to 0.08 inches of negative water column to ensure proper operation.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 9
(TABLE C)
FLUE SIZES AND INLET AIR PIPE SIZES
MODEL FLUE SIZE DIRECTAIRE NUMBER INLET SIZE
CH401 6 6”
CH501 6 6”
CH651 8 8”
CH751 8 8”
CH991 10 10
CH1261 12 12
CH1441 12 12
CH1801 14 12
CH2071 14 12
(FIG. 8) BAROMETRIC DAMPER INSTALLATION
Page 12
10 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
NOTE: Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems.
For this type of installation, it is best to use a draft control for each water heater located on the riser between the vent outlet and the breeching - Location “A”. When this riser is too short to permit the installation of a draft control, locate a separate control for each water heater on the main breeching as illustrated in Location “B”. If, because of general crowding or other reasons, neither of these locations are possible, use a single large control in the breeching between the water heater nearest the chimney and the chimney, as shown in Location “C”.
All draft readings are made while unit is in stable operation (approximately 5 minutes running time).
Masonry Chimney
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to
generate proper draft. This will result in condensing of flue products, damage of the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space.
Carefully inspect all chimney systems during the project design phase. If there is any doubt about the sizing or condition of a masonry chimney, it is prudent to reline the chimney with a properly sized and approved chimney liner system. Metallic liner systems (Type “B” doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Powered Sidewall Venting
This venting system uses a powered vent cap assembly which pulls the flue products out of the stack. The fan in the powered vent cap generates a negative draft at the unit. Combustion air is drawn from the mechanical room (See Combustion and Ventilation Air Requirements, page 6).
(FIG. 9) MULTIPLE UNIT BAROMETRIC
DAMPER INSTALLATION
(FIG. 10) POWERED SIDEWALL VENTING
(POWERED VENT CAP SHOWN)
NOTE: Common venting systems may be too large when an existing unit is removed. Be careful to resize any common venting system when new appliances are installed or existing appliances are replaced.
Page 13
Powered Sidewall Vent Kits
Models CH401-751 utilize a powered vent cap which has a fan mounted inside the cap. The powered vent cap must be placed on an exterior wall. The powered sidewall vent cap and accessories are included in a venting kit, which must be furnished by Lochinvar in accordance with CSA International requirements.
This venting kit includes the powered sidewall fan/cap, proving switch and all necessary relays to interlock with the water heater control system.
Models CH991-2071 utilize an inline fan, which is positioned on the inside of the sidewall and connected to a vent hood mounted on the sidewall exterior. The inline fan and accessories are included in a venting kit, which must be furnished by Lochinvar in accordance with CSA International requirements.
This venting kit includes the inline fan, exterior vent hood, a tapered vent adapter, barometric damper, proving switch and all necessary relays
to interlock with the water heater control system. The connection from the vent to the sidewall fan/powered vent cap must be made with listed Type “B” double wall (or equivalent) vent and accessories. The installer supplies this vent pipe material.
For models CH401-751, maximum total equivalent length of the vent pipe cannot exceed 50 equivalent feet (15.24 m). Models CH991-2071 allow a maximum total equivalent length of 100 feet (30.48 m). Subtract 5 feet (1.52 m) for each elbow in the vent.
Powered DirectAire
®
Horizontal
This vent system requires the installation of two vent pipes directly to the unit, one pipe for flue products and one for combustion air. Both vent pipes are installed horizontally with a sidewall termination point. The vent connection is made directly to the top of the unit and utilizes either the powered vent cap or inline fan as described in the power side wall venting section.
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 11
(TABLE D) – POWERED SIDEWALL VENT KIT PART NUMBERS
MODEL FLUE SIZE SIDEWALL VENT NUMBER CAP KIT
CH401 6 SVK3006
CH501 6 SVK3006
CH651 8 SVK3008
CH751 8 SVK3008
CH991 10 SVK3009
CH1261 12 SVK3010
CH1441 12 SVK3011
CH1801 14 SVK3012
CH2071 14 SVK3012
(FIG. 11) POWERED DIRECTAIRE®HORIZONTAL
(POWERED VENT CAP SHOWN)
3’
12”
Page 14
Lochinvar
12 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
The combustion air supply system has specific vent material and installation requirements. The air inlet pipe connects directly to the water heater to supply combustion air. The combustion air inlet pipe will be a dedicated system with one air inlet pipe per water heater. The air inlet pipe must be connected to a combustion air inlet cap.
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and the following instructions:
The combustion air inlet cap must be installed at least 1 foot (0.30 m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91 m) below the point of flue gas termination if it is located within 10 feet (3.05 m) of the flue outlet.
The combustion air inlet cap must not be installed closer than 10 feet (3.05 m) from an inside corner of an L-shaped structure.
Both the combustion air inlet cap and the powered vent cap/inline fan vent hood must be installed on the same wall and in the same pressure zone.
The Horizontal DirectAire system requires installation of a single wall pipe to supply combustion air from outdoors directly to the water heater. The use of double wall vent material is recommended in cold climates to prevent the condensation of airborne moisture.
For models CH401-751, maximum total equivalent length of the vent pipe and combustion air inlet pipe cannot exceed 50 equivalent feet (15.24 m). Models CH991-2071 allow a maximum total equivalent length of 100 feet (30.48 m) for each pipe. Subtract 5 feet (1.52 m) for each elbow in the vent.
Powered DirectAire
®
Horizontal Kits
Models CH401-751 vent kit includes the powered sidewall fan/cap, proving switch, air inlet cap and all necessary relays to interlock with the water heater control system. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
Models CH991-2071 vent kit includes the inline fan, exterior vent hood, a tapered vent adapter, barometric damper, proving switch, air inlet cap and all necessary relays to interlock with the water heater control system. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
The installer supplies all vent pipe material.
(TABLE E) POWERED DIRECTAIRE® HORIZONTAL
KIT PART NUMBERS
MODEL FLUE SIZE DIRECT AIR HORIZONTAL NUMBER INLET SIZE DIRECTAIRE KIT
CH401 6
6
HDK3031
CH501 6
6
HDK3031
CH651 8
8
HDK3032
CH751 8
8
HDK3032
CH991 10
10
HDK3026
CH1261 12
12
HDK3027
CH1441 12
12
HDK3027
CH1801 14
12
HDK3028
CH2071 14
12
HDK3028
Page 15
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 13
NOTE:
The use of double wall vent material for the combustion air inlet pipe is recommended in cold climates to prevent the accumulation of condensation on the pipe exterior.
CAUTION!
Boilers which
are shut down
or will not
operate may
experience
freezing due to
convective air
flow in the air
inlet pipe
connected to the
unit. Proper
freeze
protection MUST
be provided.
DirectAire® Vertical
This vent system requires the installation of two pipes directly to the unit, one vertical pipe with a roof top termination for the flue products and one pipe for combustion air. The combustion air pipe may terminate horizontally with a sidewall air inlet or vertically with a roof top air inlet. Vent connection is made directly to the top of the unit.
No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and a negative draft maintained between 0.02 to 0.08 inches of negative water column. The flue may be combined with the vent from any other negative draft, Category I appliances.
Multiple unit installations common vented with other negative draft appliances require that each water heater must have a barometric damper. The common vent and connectors from multiple water heaters must be sized per the requirements of the venting tables for Type “B” double wall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1.
The air inlet pipe connects directly to the water heater to supply combustion air. The maximum distance for the air inlet pipe is 50 equivalent feet. Subtract 5 feet (1.52 m) for each elbow in the air inlet pipe.
Single wall vent material is used to supply the combustion air to each unit. The use of double wall vent material is recommended in cold climates to prevent the condensation of airborne moisture.
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and instructions in this manual.
The combustion air inlet cap must be installed at least one foot (0.30 m) above ground level and above normal snow levels. The point of termination for the combustion air inlet cap must be at least 3 feet (0.91 m) below the point of flue gas termination (vent cap), if it is located within 10 feet (3.05 m) of the flue outlet.
(FIG. 12) VERTICAL VENT AND AIR INLET
3’
12”
(FIG. 13) VERTICAL VENT
AND SIDEWALL AIR INLET
Page 16
14 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
The combustion air inlet cap must not be installed closer than 10 feet (3.05 m) from an inside corner of an L-shaped structure.
The vertical air inlet point for the combustion air inlet cap must be installed at least one foot (0.30 m) above the rooftop and above normal snow levels. Lochinvar is required to supply a vent kit for DirectAire applications. Each kit includes either a sidewall or roof top combustion air inlet cap to supply air to a single water heater (See Table F).
Aire-Lock
TM
Direct Vent
This vent system utilizes the internal blower of the unit to draw all combustion air from outside and vent the by-products of
combustion to the outdoors. This vent system requires the installation of two vent pipes directly to the unit, one pipe for flue products and one pipe for combustion air. Both vent pipes can terminate horizontally at a sidewall or vertically at the rooftop. It is a requirement that both vent pipes terminate in the same pressure zone. The vent system has specific vent material and installation requirements.
The vent piping for flue products uses AL29­4C vent material and must be sealed “gas­tight” at all vent joints. The vent connection is made directly to the top of the unit. The maximum distance for the flue pipe is 50 equivalent feet (15.2 m). Subtract 5 feet (1.52 m) for each elbow in the flue pipe. The flue products vent pipe is a dedicated system with one flue pipe per unit.
The combustion air supply pipe connects directly to the unit to supply combustion air. The maximum distance for the air inlet pipe is 50 equivalent feet (15.2 m). Subtract 5 feet (1.52 m) for each elbow in the air inlet pipe.
(TABLE F)
DIRECTAIRE VERTICAL SIDEWALL & ROOFTOP AIR INLET KITS
MODEL NUMBER VENT SIZE AIR INLET SIDEWALL AIR ROOFTOP AIR
SIZE* INLET KIT INLET KIT
CH401 6 6” SVK3047 VDK3026
CH501 6 6” SVK3047 VDK3026
CH651 8 8” SVK3048 VDK3027
CH751 8 8” SVK3048 VDK3027
CH991 10 10 SVK3040 VDK3023
CH1261 12 12 SVK3041 VDK3024
CH1441 12 12 SVK3041 VDK3024
CH1801 14 12 SVK3041 VDK3024
CH2071 14 12” SVK3041 VDK3024
(FIG. 14) AIRE-LOCK DIRECT VENT
Page 17
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 15
The combustion air inlet pipe is a dedicated system with one air inlet pipe per unit. The air inlet pipe must be connected to the Direct Vent (DV) box adapter. The air inlet pipe must be sealed.
Aire-Lock
TM
Horizontal Direct Vent Kits
The vent kit includes a DV box adapter; sidewall air inlet cap and sidewall vent termination. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
Vertical Direct Vent Termination
You must use the vent termination recommended by the vent manufacturer for vertical direct vent terminations.
The installer supplies all vent pipe material.
The combustion air inlet cap must be installed at least 1 foot (0.30 m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91 m) below the point of flue gas termination if it is located within 10 feet (3.05 m) of the flue outlet. The combustion air inlet cap must not be installed closer than 10 feet (3.05 m) from an inside corner of an L-shaped structure.
Both the combustion air inlet cap and flue gas vent termination must be installed in the same pressure zone.
Sidewall Vent
This vent system utilizes the internal blower of the unit to vent the by-products of combustion to the outdoors. This vent system requires the installation of one pipe for flue products. The vent pipes terminates horizontally at a sidewall. The vent system has specific vent material and installation requirements. The vent piping for flue products uses AL29-4C vent material and must be sealed "gastight" at all vent joints. The vent connection is made directly to the top of the unit. The maximum distance for the flue pipe is 50 equivalent feet (15.2m). Subtract 5 feet (1.52m) for each elbow in the flue pipe. The flue products vent pipe is a dedicated system with one flue pipe per unit.
Sidewall Vent Kits
The vent kit includes a sidewall vent termination assembly to provide pressure equalization. Lochinvar must furnish this vent kit in accordance with CSA International requirements.
(TABLE G)
AIRE-LOCK
TM
DIRECT VENT KIT PART NUMBERS
MODEL FLUE AIR PART NUMBER SIZE INLET SIZE NUMBER CH401 6
6
DVK3004
CH501 6
6
DVK3004
CH651 8
8
DVK3005
CH751 8
8
DVK3005
CH991 10
10
DVK3000
CH1261 12
12
DVK3001
CH1441 12
12
DVK3001
CH1801 14
12
DVK3002
CH2071 14
12
DVK3002
(FIG. 15) SIDEWALL VENT
Page 18
16 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
The installer supplies all vent pipe material.
Combined Air Inlet Points
In most installations, the combustion air inlet pipe will be a dedicated system with one air inlet pipe per water heater.
Multiple air inlets may be combined to a single common connection if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
The air inlet point for multiple water heater air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air must connect directly to the outdoors.
The total length of the combined air inlet pipe must not exceed a maximum of 50 (15.25 m) equivalent feet. Subtract 5 feet (1.52 m) for each elbow in the air inlet pipe. Deduct the restriction in area provided by any screens, grills or louvers installed in the common air inlet point. These are common on the sidewall air inlet openings. Screens, grills or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials used.
OUTDOOR INSTALLATION
Units are self venting and can be used outdoors when installed with the optional Outdoor Cap. This cap mounts directly to the top of the water heater and covers the flue outlet and combustion air inlet openings on the jacket. No additional vent piping is required. Maintain a minimum clearance of 3(76 mm) to combustible surfaces and a minimum of 3(76 mm) clearance to the air inlet.
An outdoor unit should not be located so that high winds can deflect off of adjacent walls, buildings or shrubbery causing recirculation. Recirculation of flue products may cause operational problems, bad combustion or damage to controls. The unit should be located at least 3 feet (0.91m) from any wall or vertical surface to prevent adverse wind conditions from affecting performance.
Multiple unit outdoor installations require 48 (1.22 m) clearance between each vent cap. The outdoor cap must be located 4 feet (1.22 m) below and 4 feet (1.22 m) horizontally from any window, door, walkway or gravity air intake.
(FIG. 16) OUTDOOR VENTING
(TABLE H)
SIDEWALL VENT KIT PART NUMBERS
MODEL FLUE PART NUMBER SIZE NUMBER
CH401 6
SVK3043
CH501 6
SVK3043
CH651 8
SVK3044
CH751 8
SVK3044
Page 19
The combustion air inlet of the outdoor cap must be located at least one foot (0.30 m) above grade and above normal snow levels. The water heater must be at least 10 feet (3.05 m) away from any forced air inlet and at least 3 feet (0.91 m) outside any overhang.
Do not install in locations where rain from building runoff drains will spill onto the water heater.
Lochinvar must furnish an outdoor vent kit in accordance with CSA international requirements. Each kit includes the flue outlet/combustion air inlet, assembly, and gasket.
Freeze Protection­Outdoor Installation
A snow screen should be installed to prevent snow and ice accumulation around the appliance or its venting system.
If for any reason the unit is to be shut off:
(a.) Shut off water supply. (b.) Drain unit completely. (c.) Drain pump and piping.
If freeze protection is not provided for the system, a low ambient temperature alarm or automatic drain system is recommended.
GAS SUPPLY
Safe operation of unit requires properly sized gas supply piping (See TABLE J).
Gas pipe size may be larger than the heater connection.
A gas pressure regulator is suggested to help assure proper inlet gas pressure. If upstream pressure exceeds 6 oz. (10.5 inches of water column), an intermediate gas pressure regulator, of the lockup type, must be installed.
Lochinvar
DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 17
(TABLE I) - OUTDOOR VENT CAP PART NUMBERS
MODEL
NUMBER PART NUMBER
CH401 0DK3019 CH501 0DK3020 CH651 0DK3021 CH751 ODK3022 CH991 ODK3036 CH1261 ODK3037 CH1441 ODK3037 CH1801 ODK3038 CH2071 ODK3038
(TABLE J) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron Pipe Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
369 256 205 174 155 141 128 121 113 106 95 86 79 74
697 477 384 328 292 267 256 246 210 200 179 164 149 138
1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14” Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
11/4
3
/
4
11/
2
1
2
1
/2
31/2
3
2
1.
2.
3.
Page 20
18 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Lochinvar
Installation of a union is suggested for ease of service.
Install a manual main gas shut-off valve with test plug, outside of the appliance gas connection and before the gas valve, when local codes require.
A trap (drip leg) should be provided in the inlet of the gas connection to the unit.
High Altitude Applications
Atmospheric pressure decreases as the height above sea level increases. At any altitude above sea level, a cubic foot will contain less gas than a cubic foot at sea level. Thus, the heating value of a cubic foot of fuel gas will decrease as height above sea level increases.
Specific gravity of a gas with respect to sea level also decreases with altitude. These changes in heating value and specific gravity tend to offset each other.
However, as elevation above sea level is increased, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced in an appliance above 2000 feet. Ratings should be reduced at the rate of 4 percent for each 1000 feet above sea level.
WATER CONNECTIONS
Inlet and Outlet Water Connections
For ease of service, install unions on inlet and outlet of the boiler.
The connection on the unit marked “Inlet” should be used for return water from the system. The connection on the header marked “Outlet” should be connected to the system supply. (See Boiler Piping Diagrams, Appendix A).
WATER VELOCITY CONTROL
IMPORTANT - To ensure proper velocity
through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. (This must be done on initial installation and periodically rechecked). With the correct temperature rise across the heat exchanger (See TABLE L), you may be assured of the proper velocity in the tubes and long life and economical operation from the boiler.
GPM
45 57
64*
-
-
-
-
-
-
FT. HD
4.9
5.1
5.7
-
-
-
-
-
-
GPM
34 42 55
64*
83
106*
-
-
-
FT. HD
2.4
4.1
5.2
5.3
5.4
8.4
-
-
-
GPM
27 34 44 51 67 86
100*
-
-
FT. HD
1.8
2.9
4.1
4.8
5.6
6.9
9.1
-
-
GPM
23 28 37 42 55 71 81
101*
-
GPM
19 24 32 36 48 61 70 87
97*
FT. HD
1.1
1.6
3.0
4.1
2.6
4.4
6.3
10.1
-
FT. HD
0.9
1.2
2.3
3.2
2.1
4.0
5.7
8.3
10.7
GPM
17 21 28 32 42 53 61 76 87
FT. HD
0.6
0.7
1.6
2.3
1.5
2.7
3.8
6.6
9.0
INPUT 400,000 500,000 650,000 750,000
990,000 1,260,000 1,440,000 1,800,000 2,070,000
OUTPUT
336,000 420,000 546,000 630,000
831,000 1,058,400 1,209,600 1,512,000 1,738,800
TEMPERATURE RISE 15°F ΔΔT 20°F ΔΔT 25°F ΔΔT 30°F ΔΔT
35°F ΔΔT
40°F ΔΔT
(TABLE L) – WATER FLOW REQUIREMENTS
(TABLE K) – INLET GAS PRESSURE
MODELS NAT. GAS
LPG
CH401-751 Maximum Allowable 10.5 13” Minimum Allowable 4.5 8” CH991-2071 Maximum Allowable 10.5 13” Minimum Allowable 5 11”
4.
5.
6.
EXAMPLE OF
HIGH ALTITUDE
APPLICATIONS For example, if a
unit’s input is
100,000 Btu/hr
at sea level, the
rated input at
4000 feet of
elevation can be
calculated by
derating input
4% per 1000 feet
above sea level.
[Btu/hr Input]
[1.00 - (Elevation
÷ 1000’ x 0.04)]
= Btu/hr Input at
Specified
Elevation
[100,000] [1.00 -
(4000’ ÷ 1000’ x
0.04)] = Btu/hr
Input at 4000’
Elevation
[100,000] [0.84]
= 84,000 Btu/hr
Input at 4000’
Elevation
NOTE: In Table L * indicates flows in excess of maximum flow rating for copper tube HEX. Cupronickel tube HEX are recomended for these flow rates.
Page 21
CIRCULATOR PUMP OPERATION
A pump control relay is optional on CH 401-2071 heating boilers. When designing a system to utilize primary / secondary operation, specify a pump control relay for intermittent pump operation.
WATER FLOW REQUIREMENTS and SYSTEM PIPING
Lochinvar boilers are generally capable of operating within the design flow rates for the building heating system. To ensure the most efficient operation, a boiler needs adequate water flow. Pump sizing, pipe sizing, and piping layout must be taken into consideration for proper system flow.
(Table L) provides Gallons Per Minute and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. (Table M) provides maximum and minimum flow data for each model. These two charts will provide assistance in system flow design.
Variable Speed System Pump
High efficiency boilers require minimum flow rates through the heat exchangers to operate safely and efficiently. A variable speed pump that reduces the flow rate, in the main
system piping loop, below the minimum requirements of the total boiler system must not be installed.
Primary/Secondary Piping
Using a primary/secondary piping arrangement can solve many system flow complications.
This piping arrangement uses a dedicated pump to supply flow to the boiler. The pump is sized based on the required boiler flow rate, boiler head-loss and head-loss in the secondary system piping. A separate pump is used to provide the desired flow for the system. Primary/Secondary piping allows the system and the boiler(s) to operate at their optimum flow rate. The system works best when the boiler(s) are supplied with pump control relays which are used to cycle the
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 19
HEAT EXCHANGER HEAD LOSS CHART
Models 401-751
Pressure Drop in Feet Head
Flow in Gallons Per Minute
Flow in Gallons Per Minute
Pressure Drop in Feet Head
HEAT EXCHANGER HEAD LOSS CHART
Models 991-2071
(TABLE M) – MINIMUM & MAXIMUM
BOILER FLOW RATES
MODEL MINIMUM FLOW MAXIMUM FLOW NUMBER (GPM)* (GPM)
CH401
17 60 CH501 21 60 CH651 28 60 CH751 32 60 CH991 33 90 CH1261 42 90 CH1441 48 90 CH1801 61 90 CH2071 70 90
*Flow switch requires 20 GPM to allow boiler operation.
(FIG. 17) BOILER HEAD LOSS CH 401-751
(FIG. 18) BOILER HEAD LOSS CH 991-2071
IMPORTANT!
EXAMPLE
OF VARIABLE
SPEED PUMP
REQUIREMENTS:
4 - CHN2071
(Min. Flow = 70 GPM)
The combined "minimum"
flow for the boiler
system is
70 GPM x 4 = 280 GPM.
A variable speed pump
must not reduce the
system flow rate below
280 GPM.
Page 22
20 Lochinvar
DESIGNERS GUIDE
Lochinvar
secondary pump(s). When piped correctly, the secondary pump helps to prevent flow through the boiler(s) when they are not firing. Use of a primary/secondary system will eliminate the need for a System or Boiler Bypass. (Figure 19) depicts one example of primary/secondary piping.
Water Flow Switch
Due to the low water content (between 1 and 6 gallons) of the Copper Finned Tube heat exchanger, a flow switch is factory installed as a low water cutoff device on all models. The flow switch is installed in the outlet piping of the boiler and wired into the ignition system. A minimum of 20 GPM is required to make the flow switch. Per ASME CSD1 and in most localities, a flow switch is accepted as a low water cutoff for boilers requiring forced circulation. (See CSD1 CW-210) It is prudent to verify preference with the local code official.
A specially sealed flow switch and conduit are furnished for outdoor installations.
Low Water Cutoff
If this boiler is installed above radiation level, a low water cutoff device must be installed at the time of boiler installation (option, available from factory).
Relief Valve
This boiler is supplied with a pressure relief valve sized in accordance with
ASME Boiler and
Pressure Vessel Code, Section IV “Heating Boilers”.
Low Flow Systems
When the system flow rate is less than the minimum flow required for proper boiler operation, the boiler should be installed with a primary/secondary piping system.
This will allow the installation of a secondary­circulating pump sized specifically to provide a higher flow rate through the boiler and the secondary loop piping to ensure proper operation. See “Primary/Secondary Piping” for installation and piping requirements.
High Flow Systems
When the flow rate of the system exceeds the maximum allowable flow rate through the boiler (Table L), boiler bypass piping should be installed. The bypass will divert the required portion of the system flow to the boiler and bypass excess system flow. This will effectively reduce boiler flow to an acceptable rate and increase system flow. The bypass piping should be sized equal to the system piping. Figure 18 depicts the proper piping arrangement for the boiler bypass.
(FIG. 20) HIGH FLOW SYSTEM PIPING
HEATING SUPPLY
LOOP
TO FLOOR
DRAIN
MAKE-UP WATER
HEATING RETURN LOOP
LIT0471
IMPORTANT:
Operation of this boiler on low temperature systems requires special piping to insure correct operation. Consult low temperature system section for piping details.
(FIG. 19) PRIMARY/SECONDARY SYSTEM PIPING
HEATING SUPPLY
LOOP
*12” MAX
TO FLOOR
DRAIN
MAKE-UP WATER
LIT0476
HEATING RETURN LOOP
Page 23
Low Water Temperature Systems
Any boiler system operating at a temperature of less than 140°F is considered a "low water temperature system" and must be piped with a low temperature bypass. There are a number of Hydronic boiler applications that call for system water temperatures in the range of 60°F to 100°F. Typical applications are: Radiant heating systems; Water source heat pump systems; Greenhouse soil heating and irrigation systems; Process and manufacturing operations. These installations often incur problems resulting from boiler condensation, thermal stresses and poor overall system efficiency. Copper-tube boilers are particularly adaptable to these applications for several reasons:
A copper-tube boiler is an instantaneous boiler, requiring virtually no heat-up time, and having no temperature "overshoot." Result - High system efficiency.
The boiler's unique construction prevents the transfer of heat exchanger thermal stresses to other boiler components, reducing wear and tear while increasing equipment life.
Its compact, simple design and low boiler mass permits a simple bypass arrangement which will allow the system to be operated at any temperature above 60°F.
A boiler operated with an inlet temperature of less than 140°F (60°C) must have a bypass to prevent problems with condensation.
A Low Temperature bypass as shown in Figure 21 must be piped into all ON/OFF boilers at the time of installation. This piping is like a primary/secondary boiler installation with a bypass in the secondary boiler piping. Inlet water temperatures below 140°F (60°C) can excessively cool the products of combustion resulting in condensation on the heat exchanger and in the flue. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to increase the boiler inlet temperature to at least 140°F (60°C). This will prevent the products of combustion from condensing in most installations. Size Low Temperature bypass piping equal to system piping, and use fully ported control valves.
To prevent system return water temperature below 140° F from entering the inlet in a proportional stage-fired boiler, a quick acting, self contained, 3-way valve, set at 140°F, or an electric actuated 3-way valve with a sensor located on the boiler inlet pipe must be provided. To prevent manual reset high limit problems, 3-way valve minimum flow stops or a valve leak-through should be evaluated. The installation of a 3-way valve
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 21
(FIG. 21) LOW TEMPERATURE BYPASS
SYSTEM PIPING
HEATING SUPPLY
LOOP
TO FLOOR
DRAIN
MAKE-UP WATER
HEATING RETURN LOOP
LIT0473
2.
3.
1.
IMPORTANT!
An ON/OFF boiler
may be protected
with either a manual
bypass valve or a
3-way valve, but
a proportional
stage-fired boiler
MUST be protected
with a 3-way
valve ONLY.
Page 24
in the piping system as shown in Figure 22 should not restrict or vary the water flow through the boiler. Constant water flow through the boiler must be provided at all times when the boiler is operating. The boiler's operating temperature sensor can be remote mounted in a bulb well installed in the system water flow to control boiler operation at a low temperature range.
SPECIAL DESIGN APPLICATIONS
Air Conditioning Re-Heat System
When used in connection with a refrigeration system, the boiler must be installed so the chilled medium is piped in parallel with the boiler and with appropriate valves to prevent the chilled medium from entering the boiler. The piping system of the hot water boiler (when connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation) must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. The heating coil must be vented at the high point, and the hot water from the boiler must enter the coil at this point. Due to the fast heating capacity of the boiler, it is not necessary to provide a duct-stat to delay circulator operation; also, omit thermal flow checks, as the boiler is cold when the heating thermostat is satisfied. This provides greater economy overall by maintaining standby heat.
22 Lochinvar
DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
CAUTION!
For proper
operation the
system should
not be operated
at less than 12
PSIG.
(FIG. 24) HEATING/CHILLED WATER SYSTEM
Lochinvar
(FIG. 22) LOW TEMPERATURE BYPASS SYSTEM PIPING
ON/OFF FIRING ONLY
(FIG. 23) LOW TEMPERATURE BYPASS SYSTEM PIPING
PROPORTIONAL STAGED-FIRING
EXPANSION
TANK
HEATING &
COOLING
LOW WATER
FLOW SWITCH
GAS
SUPPLY
C
IN
OUT
R
BOILER
DIAGRAM NOTES:
1. VALVES "D" AND "C" MAY BE MANUAL OR AUTOMATIC- TO SUIT.
2. PROVIDE DRAIN FOR RELIEF VALVE "R" TO SAFE PLACE.
PUMP
A
E
COIL
B
D
WATER SUPPLY
3. CLOSE BOTH "A" AND "C" VALVES WHEN RUNNING CHILLER.
4. CLOSE BOTH "B" AND "D" VALVES WHEN RUNNING BOILER.
5. WATER SUPPLY VALVE REMAINS OPEN AT ALL TIMES.
CHILLER
Page 25
AIR REMOVAL
An air separation device should be placed in the installation piping, on the suction side of the system pump, to eliminate trapped air in the system. Locate a system air vent at the highest point in the system. Additionally, a properly sized expansion tank is required. Air charged, diaphragm-type compression tanks are common. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper operation.
TEMPERATURE/PRESSURE GAUGE
This boiler is equipped with a dial type temperature/pressure gauge. This gauge is factory installed in the outlet side of the heat exchanger. The gauge has one scale for reading system pressure and a separate scale for water temperature in degrees Fahrenheit.
LOW SYSTEM WATER VOLUME
System run time is very important to overall operating efficiency of the boiler. Short cycling of the boiler creates problems with condensation in the vent stack, condensation on the heat exchanger, system temperature spikes, and mechanical component failures. To prevent short cycling of the boiler, it is important to limit the boiler cycles to six or fewer per hour. A Buffer Tank is an effective way to enhance a small system load and increase heating system efficiency. Buffer tanks add water volume to the system and act as a flywheel to absorb the additional Btu's provided by the boiler when only a single zone of a large system is calling for heat.
To calculate the proper buffer tank size for a multiple zone system:
(Run Cycle) (Output - Minimum System Load)
(Temp. Rise) (8.33)(60 Min.)
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 23
(FIG. 25) BUFFER TANK PIPING
EXAMPLE OF
BUFFER TANK
APPLICATIONS
CHN1261 Boiler
Run Cycle = 10 Min.
Temp. Rise = 10°F
Min. Load =
100,000Btu/hr
(10)(1,000,000 -
100,000)
divided by
40 x 8.33 x 60
= 485 Gallons
Page 26
NOTE: When the unit is installed in Canada, it MUST conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.
(TABLE N) – AMP DRAW DATA
MODEL FAN(S) CONTROLS APPRX. TOTAL AMPS
NUMBER @ 120 VAC
CH401 3.6 2.7 6.3
CH501 3.6 2.7 6.3
CH651 5.4 3.4 8.8
CH751 5.4 3.4 8.8
CH991 3.2 7.2 10.4
CH1261 3.2 7.2 10.4
CH1441 6.7 7.2 13.9
CH1801 6.7 7.2 13.9
CH2071 6.7 7.2 13.9
1.
2.
3.
BOILER OPERATING TEMPERATURE CONTROL
In the absence of a remote temperature control, a digital operator controls the boiler operating temperature. The sensing element for the operator is placed in a bulb well, installed in the inlet side of the heat exchanger front header. Due to the location of the temperature sensor, the operator will generally require a lower temperature setpoint to achieve the desired discharge water temperature from the boiler. This sensing element location allows a boiler operating with a low to moderate flow rate to sustain longer burner “ON” cycles, based on high discharge water temperatures.
For example, a boiler operating with a 180°F discharge and a 20°F temperature rise would require approximately a 160°F to 165°F set point with the temperature sensor installed on the inlet side of the heat exchanger. The exact temperature set point is based on system requirements.
REMOTE TEMPERATURE CONTROL, CONNECTION TO TERMINAL STRIP
A remote temperature control may be connected to the boiler. The boiler is equipped with a terminal strip to allow easy connection. Connection to the terminal strip will allow the remote temperature control to make and break the 24 VAC boiler control
circuit, turning the boiler on and off based on building and system demands.
ELECTRICAL REQUIREMENTS
(North America)
The appliance is wired for 120 volts.
All wiring between the unit and field installed devices shall be made of type T wire [63°F (35°C) rise].
The pump must run continuously when the unit is firing.
It is recommended that the boiler and pump be wired on separate circuits with properly sized circuit breakers.
24 Lochinvar
DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
Page 27
BOILER PIPING DIAGRAMS
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 A1
PIPING DIAGRAM PRIMARY/SECONDARY BOILER PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
12MAX*
HEATING RETURN LOOP
HEATING SUPPLY LOOP
*AS CLOSE AS PRACTICAL – 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
MAKE-UP WATER
TO FLOOR DRAIN
LIT0476
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 28
A2 Lochinvar
DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
PIPING DIAGRAM MULTIPLE UNIT PRIMARY/SECONDARY PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
12MAX*
FROM SYSTEM
RETURN
*AS CLOSE AS PRACTICAL – 12OR 4 PIPE DIAMETERS MAXIMUM DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
TO SYSTEM SUPPLY
MAKE-UP WATER
CAP EACH MANIFOLD
LIT0475
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 29
PIPING DIAGRAM LOW TEMPERATURE BOILER-BYPASS PIPING
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
MAKE-UP WATER
HEATING RETURN
LOOP
HEATING SUPPLY
LOOP
PRIMARY - SECONDARY BOILER PIPING WITH BYPASS FOR LOW TEMPERATURE OPERATION
*AS CLOSE AS PRACTICAL – 12
OR 4 PIPE DIAMETERS MAXIMUM
DISTANCE BETWEEN MANIFOLD CONNECTIONS TO SYSTEM.
TO FLOOR
DRAIN
*12
MAX
LIT0473
Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900 A3
This illustration is for concept only and should not be used for any actual installation without engineering
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
BYPASS
Page 30
A4 Lochinvar DESIGNERS GUIDE COPPER- FIN II BOILER 615-889-8900
PIPING DIAGRAM LOW TEMPERATURE BOILER-BYPASS PIPING W/ 3-WAY VALVE
PRESSURE
REDUCING VALVE
FULL PORT
BALL VALVE
RELIEF VALVE CHECK VALVE TEE ELBOW
EXPANSION TANK TANK FITTING SYSTEM PUMP LOW WATER
CUTOFF
UNION AIR SEPARATOR
LEGEND
This illustration is for concept only and should not be used for any actual installation without engineering or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Page 31
Page 32
Lochinvar Corporation • Lebanon, TN • 615-889-8900 • Fax 615-547-1000
www.Lochinvar.com
CH-DG-05 5M-10/05-Printed in U.S.A.
Loading...