Lochinvar AWL1000PM User Manual

ARMOR X2
Condensing Water Heater
Submittal Sheet
AWX-Sub-01c
ARMOR X2TM CONDENSING WATER HEATER
JOB NAME ______________________________________________________________________ LOCATION ______________________________________________________________________ ENGINEER____________________________________________________________________ WHOLESALER __________________________________________________________________ MECH. CONTRACTOR ___________________________________________________________ MODEL NO. _____________________________________________________________________ TYPE GAS ______________________________________________________________________ Btu/hr INPUT_____________________________________________________________________ RECOVERY RATE IN GPH_______________________________________@________°F RISE NOTES
Standard Features
> 96% Thermal Efficiency (AHRI Certified) > Modulating Burner with 10:1 Turndown
> Direct-Spark Ignition > Low NOx Operation > Sealed Combustion > Low Gas Pressure Operation > 2 Low Lead Circulating Pumps > Vertical & Horizontal Venting > Category IV Venting up to 100 Feet > PVC, CPVC, Polypropylene or AL29-4C
Vent Material > Sidewall Vent Termination Provided > ASME Stainless Steel Heat Exchanger > Gasketless Design > 160 psi Working Pressure > On/Off Switch > Adjustable High Limit with Manual Reset > Low Air Pressure Switch > Flow Switch > Inlet & Outlet Temperature Sensors > Two Easy Access Terminal Strips > Temperature & Pressure ASME Relief Valve > Zero Clearance to Combustible Material > Approved for Combustible Floor Installation > 1 Year Warranty on Parts > 5 Year Limited Warranty
(see warranties for details)
SMART TOUCH™ Features
> SMART TOUCH™ Touchscreen Operating Control > Full-Color Touchscreen LCD Display > Built-in Cascading Sequencer for up to 8 Water Heaters > Building Management System Integration with
0-10 VDC Input > Password Security > Low Water Flow Safety Control & Indication > Inlet & Outlet Temperature Readout > Freeze Protection > Service Reminder > Time Clock > Data Logging > Hours Running > Ignition Attempts > Last 10 Lockouts > Programmable System Efficiency Optimizers > Night Setback > Anti-Cycling > Water Heater Pump Control > High Voltage Terminal Strip > 120 VAC / 60 Hertz / 1-Phase Power Supply > Pump Contacts > Low Voltage Terminal Strip > 24 VAC Auxiliary Device Relay > Auxiliary Proving Switch Contacts > Alarm on Any Failure Contacts > Runtime Contacts > Tank Thermostat Contacts > Tank Sensor Contacts > Cascade Contacts
Optional Equipment
> Alarm Bell > Condensate Neutralization Kit > SMART TOUCH PC Software > Modbus Communications > Stainless Steel Vent Kits (1300 & 1500) > BMS Gateway to LON or BacNet
Codes & Registrations
> ANSI Z21.10.3 compliant > ASME certified, “HLW” stamp > California Code compliant > Massachusetts Code compliant > South Coast Air Quality Management District
registered
Dimensions & Specifications
ARMOR X2 Water Heater Dimensions and Specifications
GPH @ Model Btu/hr Thermal 100° Number Input Efficiency Rise
AWN1000PM 1,000,000 96.0% 1,164
AWN1300PM 1,300,000 96.0% 1,513
AWN1500PM 1,500,000 96.0% 1,745
Notes: Change ‘N’ to ‘L’ for L.P. Gas Model. No deration on L.P. models. Performance data based on manufacturer test results. 120 VAC /15 AMP circuit required. All dimensions shown in inches.
Inlet Outlet
Gas Water Water Air Vent Shipping
A B C D E F Conn. Conn. Conn. Inlet Size Wt. (lbs.)
58-3/4” 31” 48” 35” 4-1/2” 15” 1-1/2” 2 x 2” 3” 6” 6” 910
58-3/4” 31” 52-1/4” 34-3/4” 3-1/2” 6-3/4” 1-1/2” 2 x 2” 3” 6” 6” 1049
58-3/4” 31” 56-1/2” 34-3/4” 3-1/2” 6-3/4” 1-1/2” 2 x 2” 3” 6” 6” 1185
Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000
www.Lochinvar.com
HLW
10/14—Printed in U.S.A.
Loading...