ARMOR
Condensing Water Heater
Submittal Sheet
AWP-Sub-08
ARMORTM CONDENSING WATER HEATER PACKAGE SYSTEM
JOB NAME ______________________________________________________________________
LOCATION ______________________________________________________________________
ARCH./ENGR.____________________________________________________________________
WHOLESALER __________________________________________________________________
MECH. CONTRACTOR ___________________________________________________________
MODEL NO. _____________________________________________________________________
TYPE GAS ______________________________________________________________________
Btu/hr INPUT_____________________________________________________________________
RECOVERY RATE IN GPH_______________________________________@________°F RISE
NOTES
Standard Features
> Up to 98% Thermal Efficiency
> Modulating Burner with 5:1 Turndown
> Direct-Spark Ignition
> Low NOx Operation
> Sealed Combustion
> Low Gas Pressure Operation
> Vertical & Horizontal Direct-Vent
> PVC, CPVC or SS Venting up to 100 Feet
> PVC/CPVC Sidewall Vent Termination
> Stainless Steel Heat Exchanger
> All Welded Construction, Gasketless Design
> 160 psi Working Pressure
> ASME Construction (AW 286-800)
> Natural to L.P. Conversion Kit
> All Bronze Circulating Pump
> On/Off Switch
> Flow Switch
> ASME Temperature & Pressure Relief Valve (286-801)
> Temperature & Pressure Gauge (AW 501-801)
> Downstream Test Valves (AW 501-801)
> Adjustable Leveling Legs
> Tank Sensor
> Adjustable High Limit w/ Manual Reset
> Automatic Reset High Limit
> Condensate Trap
> Zero Clearances to Combustible Material
> 5 Year Limited Warranty (See Warranty for Details)
> 1 Year Parts Warranty (See Warranty for Details)
Smart System Features
> SMART SYSTEM Digital Operating Control
> Multi Color Graphic LCD Display
> Built in Cascading Sequencer for up to 8 Water Heaters
> Lead Lag
> Efficiency Optimization
> Building Management System Integration
> Modbus Communication (Optional)
> 0-10VDC Input to Control Modulation or Set point
> 0-10VDC Modulation Rate Output
> 0-10VDC Input to Enable/Disable call for heat
> Access to BMS Settings Through Graphic LCD Display
> Low Water Flow Safety Control & Indication
> Inlet & Outlet Temperature Sensors & Readout
> Flue Temperature Sensor
> Water Heater Pump Control
> Pump Delay with Freeze Protection
> Pump Exercise
> Night Setback
> Building Recirculation loop Pump Control*
> Night Setback of Building Recirculation Loop*
> Time Clock
> Maintenance Reminder
> Ability to program name and number into the product
as contact
> High Voltage Terminal Strip
> 120 VAC / 60 Hertz / 1 Phase Power Supply
> Pump Control Contacts
> Water Heater Pump Control Contacts
> Building Recirculation Pump Control Contacts
> Low Voltage Terminal Strip
> 24 VAC Auxiliary Device Relay
> Auxiliary Proving Switch Contacts
> Flow Switch Contacts
> Alarm on Any Failure Contacts
> Runtime Contacts
> Tank Sensor Contacts
> Cascade Contacts
> 0-10 VDC BMS External Control Contact
> 0-10VDC Boiler Rate Output Contacts
> Modbus Contacts
*Exclusive to Lochinvar
Optional Equipment
> Alarm Bell
> Condensate Neutralization Kit
> High & Low Gas Pressure Switches
(AW 501-801)
> Concentric Vent Kit
(3” & 4” PVC/CPVC only)
> ModBus Communications
> SMART SYSTEM PC Software
> Room Air Vent Kits
> Stack Frame
Firing Control Systems
> M9 Standard Construction
> M7 California Code
(AW 286-801)
> M13 CSD1 / FM / GE Gap
(AW 501-801)

ARMOR Condensing Water Heater Dimensions & Specifications
TNORF
"4/3 7
"2/1 51
"4/1 11
H
"4/3 92
"4/1 03
J
"2/1 51
I
K
"4/3 3 G
F
E
D
C
"2/1 6
A
"4/1 1 - "4/1
ELBATSUJDA
TELNI RIA
EULF
LACIRTCELE
SNOITCENNOC
SAG
TELNI
TELTU
O
NIARD
TPN "4/3
ETASNEDNOC
NIARD
TNORF
"8
"2/1 51
"93
"2/1 93
"4/3 31
I
K
"4/3 81
H
J
"
4/3 3
G
F
D
E
C
"9
A
"4/1 1 - "4/1
ELBATSUJDA
TELNI RIA
EULF
LACIRTCELE
SNOITCENNOC
SAG
TELNI
TELTU
O
NIARD
TPN "4/3
ETASNEDNOC
NIA
RD
Models 150-199
Models 285-800
Model Btu/hr GPH @ Gas Water Air Vent Shipping
Number Input 100° Rise A C D E F G H I J K Conn. Conn.
AWN151PM 150,000 174 33-1/4” 18” 12-1/4” 11-1/2” 10” 1-1/2” 21-1/4” 23” 1-3/4” 12” 1/2” 1-1/4” 3” 3” 165
AWN200PM 199,999 235 33-1/4” 22-1/4” 16-1/2” 15-3/4” 14-1/4” 5-1/4” 21-1/4” 23” 1-3/4” 16-1/4” 1/2” 1-1/4” 3” 3” 185
AWN286PM 285,000 339 42-1/2” 19-3/4” 12-3/4” 13-1/2” 6” 2” 34” 31” 11-3/4” 4-1/4” 3/4” 2” 4” 4” 235
AWN400PM 399,999 475 42-1/2” 27” 21” 20-3/4” 14” 3-1/2” 34” 34” 18-3/4” 2” 1” 2” 4” 4” 295
AWN501PM 500,000 594 42-1/2” 31-1/2” 21” 25” 14” 3-1/2” 35” 35” 22” 5-3/4” 1” 2” 4” 4” 335
AWN601PM 600,000 713 42-1/2” 36-1/4” 25” 21” 14” 3-1/2” 36” 32-3/4” 19-1/2” 5-1/2” 1” 2” 4” 4” 380
AWN701PM 700,000 832 42-1/2” 40-1/4” 29” 23” 17” 3-1/2” 36” 32-3/4” 23-1/2” 3-1/4” 1” 2” 4” 6” 461
AWN801PM 800,000 950 42-1/2” 45-1/4” 33-1/4” 23” 17” 3-1/2” 36” 32-3/4” 27-3/4” 3-1/4” 1” 2” 4” 6” 527
Inlet Size Wt. (lbs.)

Armor Package Systems Gas Water Heater Dimensions & Specifications
PS Configuration PU Configuration
AW 150-500 with a 119-504 gallon capacity
Jacketed and Insulated Lock-Temp Vertical Tank.
AW 150-500 with a 119-504 gallon capacity
Jacketed and Insulated Lock-Temp Vertical Tank.
VERTICAL ROUND JACKETED TANK DIMENSIONS
Gallon HT D
119 62-1/2” 28” 345
200 77-1/4” 32” 600
257 91” 34” 1108
318 80” 40” 1290
432 80” 46” 1,512
504 92” 46” 1,623
Weight
T
NOTE: If overall dimensions are critical consult factory.
All package systems are skid mounted.
*Add 3” to tank HT for I-Beam skid.
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
NOTE: Tanks over 500 gallon are available for package
systems. Vertical tanks over 650 gallons require breakaway
frames for shipping purposes. Consult factory for details.
Package systems with multiple units or storage tanks 752 gallons and larger
will be designed as a “Breakaway” system. Breakaway systems are factory
disassembled for shipping purposes and require some field reassembly.
Consult factory for details.
www.Lochinvar.com
9/10—Printed in U.S.A.