Lochinvar ARMOR 151 - 801 User Manual

Service Manual
Models:
151 - 801
This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water Heater Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Save this manual for future reference.
AWII-SER Rev A
2
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Hazard Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PLEASE READ BEFORE PROCEEDING . . . . . . . . . . . . 3
Handling Ceramic Fiber Materials . . . . . . . . . . . . . . . . . . . 3
When servicing water heater . . . . . . . . . . . . . . . . . . . . 3
Water heater operation . . . . . . . . . . . . . . . . . . . . . . . . 3
WHAT IS IN THIS MANUAL . . . . . . . . . . . . . . . . . . . . . . . 4
1. SERVICE
The Armor Water Heater Display . . . . . . . . . . . . . . . . . . . . 5
Control Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Display Panel Menu Access . . . . . . . . . . . . . . . . . . . . . . 10
Display Panel Parameter Access . . . . . . . . . . . . . . . . . . . 11
Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-13
Viewable and Changeable Control Parameters . . . . . . . 14-18
2. MAINTENANCE
Maintenance and Annual Startup . . . . . . . . . . . . . . . . . . 19-23
3. TROUBLESHOOTING
Before Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Check Control Module Fuses . . . . . . . . . . . . . . . . . . . . . 24
Table 3A - Troubleshooting Chart - No Display . . . . . . . . 25
Checking Temperature Sensors . . . . . . . . . . . . . . . . . . . 26
Table 3E - Troubleshooting Chart - Noisy System . . . . . 27
Table 3F - Troubleshooting Chart - Fault Messages . . . . 28-35
Combustion Analysis Procedure . . . . . . . . . . . . . . . . . . . 36
Table 3G - Flue Products . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 3H - Troubleshooting Chart - Combustion Levels . 36
Gas Valve Adjustment Procedure . . . . . . . . . . . . . . . . . . 37-38
Revision Notes . . . . . . . . . . . . . . . . . . . . . . . . . Back Cover
Contents
Service Manual
Please read before proceeding
Installer – Read all instructions, including this manual and the Armor Water Heater Installation and Operation Manual, before installing. Perform steps in the order given.
Have this water heater serviced/inspected by a qualified service technician at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
When calling or writing about the water heater – Please have the water heater model and serial number from the water heater rating plate.
Consider piping and installation when determining water heater location (see the Armor Water Heater Installation and Operation Manual).
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
3
Handling ceramic fiber materials
REMOVAL OF COMBUSTION CHAMBER LINING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
¢ Avoid breathing dust and contact with skin
and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
¢ Apply enough water to the combustion chamber
lining to prevent airborne dust.
¢ Remove the combustion chamber lining from the
water heater and place it in a plastic bag for disposal.
¢ Wash potentially contaminated clothes separately
from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
¢ Eye: Irrigate immediately. ¢ Breathing: Fresh air.
WARNING
NOTICE
WARNING
When servicing water heater –
• To avoid electric shock, disconnect electrical supply before performing maintenance.
• To avoid severe burns, allow the water heater to cool before performing maintenance.
Water heater operation –
• Do not block flow of combustion or ventilation air to the water heater.
• Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
• Do not use this water heater if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
4
Service Manual
What is in this manual?
Service
The Armor water heater display
• Display panel readout, buttons and their functions
Control module inputs
• Control module inputs and options
Control module outputs
• Control module outputs and options
General
• How the water heater operates
• How the control module operates
• Access modes -- user and installer
• Sequence of operation -- Water Heating
Control panel menu access
•Accessing programming mode and locating menus (See separate guide covering the PC interface.)
Control panel parameter access
• Accessing and changing parameters from the display panel
Quick start information -- parameter table
• An index of available adjustments and readouts, where to access them and where to find detailed information.
Armor water heater operation
• A: General
• B: Data Logging
• C: Functions
• D: DHW Settings
• E: Anti-Cycling
• F: Control Modes
• G: Circulation Pumps
• H: BMS
• I: Service Notification
Maintenance
• Service and maintenance schedules
• Address reported problems
• Inspect water heater area and water heater interior
• Clean condensate trap
• Check all piping for leaks
• Check air openings
• Flue vent system and air piping
• Check water system
• Check water heater relief valve
• Inspect ignition electrode
• Check ignition ground wiring
• Check all water heater wiring
• Check control settings
• Perform start-up and checks
• Check burner flame
• Check flame signal
• Check flue gas temperature
• General maintenance
• Review with owner
• Cleaning the water heater heat exchanger
• Oiled bearing circulators
Troubleshooting
• Troubleshooting table - No display
• Checking temperature sensors
• Sensor tables
• Troubleshooting table - Fault messages displayed on the water heater interface
• Combustion analysis procedure
• Gas valve adjustment procedure
1 Service
Service Manual
5
NAVIGATION DIAL
(PRESS OR TURN)
RIGHT SELECT KEY
(SOFT KEY)
LEFT SELECT KEY
(SOFT KEY)
RESET KEY
The Armor water heater display
The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the NAVIGATION dial (in the center):
MENU = Left SELECT Key SETPOINTS = NAVIGATION Dial - Pressing Down SHDN = Right SELECT Key
1 Service
6
Service Manual
Control inputs
GAS PRESSURE SWITCH
DHW THERMOSTAT
FLOW SW ITCH
TANK SENSOR
SEQUENCER / BUILDING
MANAGEMENT SYSTEM
LOW WATER CUTOFF
INLET TEMPERATURE
SENSOR
OUTLET TEMPERATURE
SENSOR
FLUE GAS SENSOR
LOW VOLTAGE
CONNECTION
BOARD
AIR PRESSURE SWITCH
LOUVER PROVING SWITCH
FLAME SENSOR
BLOCKED DRAIN SWITCH
DISPLAY PANEL
PC INTERFACE
SMART SYSTEM
CONTROL BOARD
Service Manual
7
LOW VOLTAGE
CONNECTION
BOARD
SMART SYSTEM
CONTROL BOARD
ALARM BELL
LOUVER RELAY
RUN TIME CONTACTS
SEQUENCER / BUILDING
MANAGEMENT SYSTEM
WATER HEATER PUMP
IGNITOR
BLOWER
GAS VALVE
DISPLAY PAN EL
PC INTERFACE
BUILDING RECIRCULATION PUMP
Control outputs
1 Service (continued)
1 Service
8
Service Manual
General Operation
How the water heater operates
The Armor water heater uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation. The blower pulls in gas and air and pushes flue products out of the water heater through the heat exchanger and flue piping. The control module regulates blower speed to control water heater firing rate. The gas valve senses the amount of air flowing into the water heater and allows only the right amount of gas to flow.
Sequence of operation
Table 1A shows control module normal sequences of operation for water heating operation.
Access modes
User
The user can adjust tank target temperatures by pressing the NAVIGATION dial when “$SETPOINTS” is flashing at the bottom of the display. The date and time, and the temperature units can also be changed.
Installer
Most parameters are available only to the installer, accessible by entering the installer password (5309).
Saving parameters (reference the Parameter Table -
Table 1D on pages 12 and 13 of this manual)
Please note that the brackets ([]) denote screen status.
NOTICE
To save parameters and exit programming:
Press the RIGHT SELECT [SAVE] key and then press the RIGHT SELECT [HOME] key.
To enter a parameter and continue programming:
Press the RIGHT SELECT [SAVE] key 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the RIGHT SELECT [HOME] key when finished programming in order to save the changes made.
Service Manual
9
Table 1A Sequence of operation
1 Service (continued)
OPERATION DISPLAY
1. The control will turn on the water heater pump (always ON except in Night Setback). The flow switch and/or LWCO must close.
2. The control turns on power to the louver relay. The louver proving switch, air pressure switch, and blocked drain switch must close.
3. The control starts a 15 second prepurge cycle.
4. The control starts a 4 second trial for ignition by firing the spark electrode and opening the gas valve.
5. If flame is not detected within 1 second after the sparking ends, the control will perform a 10 second post-purge, then start another prepurge cycle and try to light the burner again. On the 501 and larger models, the control will lock out if this second attempt also fails. On the 400 and smaller models, the control will perform a total of 4 attempts before locking out.
6. If flame is detected, it holds the firing rate steady for 5 seconds to let the flame stabilize, then it begins to modulate the firing rate based on a set point or some other command (such as a 0-10V BMS signal).
7. Once the call for heat is satisfied, the control will turn off the burner. The blower will continue to run during a 10 second postpurge.
8. The water heater pump will continue to run for its respective
pump delay time before turning off. A 60 second anti-cycle period will start, which will delay any new call for heat until it times out.
9. In Standby, ready to start a new cycle.
1 Service
10
Service Manual
Display panel menu access
Table 1B Use this procedure to access menus from the display panel
BUTTON
SCREEN
STATUS
OPERATION DISPLAY
[SHDN] Press the RIGHT SELECT soft key [SHDN].
[YES] Press the LEFT SELECT soft key [YES].
[MENU]
Press and hold the LEFT SELECT soft key [MENU] for five (5) seconds.
Rotate the NAVIGATION dial clockwise until 5 is displayed (first digit on the left).
Press the NAVIGATION dial to select the next digit. Rotate the NAVIGATION dial clockwise until 3 is shown in the display.
Press the NAVIGATION dial 2 times to move to the last digit. Rotate the NAVIGATION dial counterclockwise until 9 is displayed.
[SAVE] Press the RIGHT SELECT soft key [SAVE].
Rotate the NAVIGATION dial counterclockwise to select a category.
Service Manual
11
Display panel parameter access
Table 1C This is a typical example of accessing a parameter, shown for parameter DHW Settings, TANK MIN Setpt
1 Service (continued)
BUTTON
SCREEN
STATUS
OPERATION DISPLAY
This example shows how to access parameter Temperature Settings. The first display shown is at the beginning of the menu listings, after entering the installer access code.
Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to DHW SETTINGS.
Press the NAVIGATION dial one time.
Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to TANK MIN SETPT.
Press the NAVIGATION dial one time.
Rotate the NAVIGATION dial to the desired temperature.
[SAVE] Press the RIGHT SELECT soft key [SAVE] one time.
[EXIT]
Press the LEFT SELECT soft key [EXIT] if all desired changes have been made.
[HOME] Press the LEFT SELECT soft key [HOME].
1 Service
12
Service Manual
Parameter table
Table 1D This table lists SMART SYSTEM control module parameters and where to access them
Menu
Sub
Item
Description
See
Page
User Access Installer Access
Display Modify Display Modify
A
1 Date and Time 14 Yes Yes Yes Yes
2 Software Version (read only) 14 No No Ye s No
3 Temperature Units (ºC/ºF) 14 Yes Yes Yes Yes
4 DHW Night Setback Offset 14 No No Ye s Yes
5 DHW Night Setback On Times 14 No No Ye s Yes
6 DHW Night Setback Off Times 14 No No Ye s Yes
7 Display Timeout 14 No No Ye s Yes
B
1 Reset Last 10 Errors 15 No No Ye s Yes
C
1 Service Mode Delay 15 No No Ye s Yes
D
1 Tank Set Point 15 Yes Yes Yes Yes
2 Tank Set Point Offset 15 Yes Yes Yes Yes
3 Tank Set Point Differential 15 No No Ye s Yes
4 Tank Minimum Set Point 15 No No Ye s Yes
5 Tank Maximum Set Point 15 No No Ye s Yes
E
1 Anti-Cycling Time 15 No No Ye s Yes
2 Anti-Cycling Override Differential 15 No No Ye s Yes
GENERAL
DATA
LOGGING
FUNCTIONS
DHW SETTINGS
ANTI-
CYCLING
1 Service (continued)
Service Manual
Menu
Sub
Item
Description
See
Page
User Access Installer Access
Display Modify Display Modify
F
1 BMS Tstat Input (Active/Inactive) 16 No No Yes Yes
2 BMS (Active/Inactive) 16 No No Yes Yes
3 ModBus (Active/Inactive) 16 No No Ye s Yes
4 ModBus T/O (Timeout) 16 No No Ye s Yes
5 Cascade Address 16 No No Yes Yes
6 Cascade Type (L/L / EFF) 16 No No Ye s Yes
7 Max Cascade Outlet Set Point 17 No No Ye s Yes
8 Min On/Off Time 17 No No Ye s Yes
9 Min Next On Time 17 No No Ye s Yes
10 Boiler Size 17 No No Ye s Yes
G
1 DHW Pump Delay 17 No No Yes Yes
2 DHW Pump Anti-Seize Delay 17 No No Ye s Yes
H
1 BMS Type (Power / Set Point) 18 No No Ye s Yes
2 Volts at Min 18 No No Ye s Yes
3 Volts at Max 18 No No Ye s Yes
4 Rate at Min Volts 18 No No Ye s Yes
5 Rate at Max Volts 18 No No Ye s Yes
6 Set Point at Min Volts 18 No No Ye s Yes
7 Set Point at Max Volts 18 No No Ye s Yes
8 On Volts 18 No No Ye s Yes
9 Off Differential Volts 18 No No Ye s Yes
I
1 Service Notification Months 18 No No Ye s Yes
2 Service Notification Running Time 18 No No Ye s Yes
3 Service Notification Cycles 19 No No Ye s Yes
4 Reset Maintenance Reminder 19 No No Ye s Yes
5 Installer Name and Phone Number 19 No No Ye s Yes
CONTROL MODES
CIRCULATION
PUMPS
13
SERVICE
BMS
NOTIFICATION
Parameter table
Table 1D (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them
1 Service
14
Service Manual
Viewable and changeable control parameters
CAUTION
Before changing parameters, note the settings so that the unit can be returned to its original operating parameters.
A: General
Date and Time
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the water heater is first installed or anytime the water heater has been powered off for more than four (4) hours. To set the clock, parameter A1 must be accessed.
Software Version
The software version allows the user to view the software version in use by the control. This software controls the operation of the water heater. When a new software version becomes available, the existing control can be replaced with a new control to update the software.
Software version is read only.
Temperature units (°C / °F)
The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A3. The default is °F.
Domestic Hot Water (DHW) Night Setback Offset
The unit’s internal clock can be set up to run at a lower set point temperature during unoccupied times. When in night setback, the control reduces the set point by a fixed amount. It subtracts the DHW night setback offset from the tank set point (parameter E2).
NOTE: The DHW night setback will not work without a tank sensor installed.
The installer may adjust the DHW night setback offset by accessing parameter A4. The minimum setting is 0°F (0°C) and the maximum setting is 90°F (50°C).
Domestic Hot Water (DHW) Night Setback On Times
This is the time at which the DHW Night Setback Offset becomes active. There are 7 start times and 7 stop times. Both may be set to any time within a 7-day week. These settings are referred to as triggers. Multiple start or stop triggers may be set within a single day, if desired. When a start trigger and a stop trigger are set to the same time, the stop trigger has priority. The installer may adjust the DHW start triggers in parameter A5. This screen shows the start trigger number, the day of the week, and the time of day.
1. When the screen is first accessed, start trigger number 1 is shown. If a different trigger number is desired, the installer can rotate the NAVIGATION dial until the desired trigger number is displayed. Once the desired trigger number is selected, the installer can press the NAVIGATION dial and the day of the week will start to flash.
2. The installer can adjust the day of the week to the one he wishes to set. Once the day is set, the installer can press the NAVIGATION dial and the hour will begin to flash.
3. After setting the hour, the installer can press the NAVIGATION dial and the minutes will flash. Once all settings have been made, the installer can press the RIGHT SELECT [SAVE] key. The installer can now select a different trigger and adjust the settings for that trigger.
4. Once all adjustments are made, the installer can press the RIGHT SELECT [SAVE] key to save all of the new settings and return to the A menu, or press the LEFT SELECT [EXIT] key to return to the A menu without saving the changes.
Domestic Hot Water (DHW) Night Setback Off Times
The stop triggers for the DHW night setback feature can be adjusted by accessing parameter A6. The adjustment procedure for these parameters is identical to the space heating start triggers described above.
Display Timeout
This is the time in which the display remains illuminated. The range is 10 seconds to 10 minutes. The default is 3 minutes.
NOTICE
The internal clock does not adjust for Daylight Savings Time and therefore, will require a manual adjustment.
Please note that the brackets ([]) denote screen status.
NOTICE
1 Service (continued)
15
Service Manual
Tank Minimum Set Point
This setting controls the minimum user set point for the tank temperature. The installer can adjust this by accessing parameter D4. The minimum setting is 60°F (16°C) and the maximum setting is the maximum tank set point (parameter D5).
Tank Maximum Set Point
This setting controls the maximum user set point for the tank temperature. The installer can adjust this by accessing parameter D5. The minimum setting is the minimum tank set point (parameter D4) and the maximum setting is 185°F (85°C).
E: Anti-Cycling
Anti-Cycling Time
Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. The control will block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops below parameter E2. This parameter can be changed by the installer by accessing parameter E1. The time range for this parameter is 0 minutes to 10 minutes. The default value is 1 minute.
Anti-Cycling Override Differential
The control will bypass the anti-cycling time if the water temperature drops too quickly. The control will use the water temperature the water heater was at when it shut off as the starting point. If the temperature drops below the temperature parameter the control will abort anti-cycling and allow the water heater to fire. This parameter can be changed by the installer by accessing parameter E2. The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).
B: Data Logging
Reset last 10 errors
The reset last 10 errors function clears the last 10 errors log.
C: Functions
Service Mode Delay
By pressing the pin button on the front of the display for five (5) seconds, the control will be placed in Service Mode. This will override all other heat demands. The Service Mode allows the installer to set the unit to either maximum firing rate or minimum firing rate for the purpose of combustion analysis. The delay sets the length of time the water heater will stay in the Service Mode if no keys have been pressed before going back to its original state. This parameter can only be changed by the installer by accessing parameter C1. The time range of this parameter is 0 to 30 minutes. The default value is 20 minutes.
D: DHW Settings
Tank Set Point
By installing a tank sensor, the SMART SYSTEM control can perform the tank thermostat function. The SMART SYSTEM control automatically detects the presence of this sensor, and generates a DHW call for heat when the tank temperature drops below the tank set point differential (parameter D3), and finishes the call for heat when the tank temperature reaches tank set point. This parameter can be changed by the installer by accessing parameter D1. The temperature range of this parameter is 68°F (20°C) to 190°F (88°C). The default value is 125°F (52°C).
Tank Set Point Offset
The tank set point offset measures how far the actual temperature must go above the set point before the call for heat ends (the water heater will turn off). This parameter can be changed by the installer by accessing parameter D2.
Tank Set Point Differential
When a tank sensor is installed, the tank temperature must drop this amount below the tank set point (parameter D1) before the heater will turn on. The installer can adjust this setting by accessing parameter D3. The minimum setting is 0° (0°C), and the maximum is 40°F (22°C). The default setting is 6°F (3°C).
Service Manual
16
1 Service
F: Control modes
BMS Thermostat Input (Active / Inactive)
When controlling the water heater through the 0 - 10V BMS input or through ModBus, the water heater can be enabled one of two ways. With parameter F1 set to ACTIVE, the water heater will be enabled by closing the Tank Thermostat input. With parameter F1 set to INACTIVE, the water heater will be enabled by the voltage level on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus. The default value is INACTIVE.
BMS (Active / Inactive)
The set point or modulation of the water heater may be controlled through the 0 - 10V BMS input or through ModBus. When parameter F2 is set to INACTIVE, the 0 ­10V input will be ignored. When set to ACTIVE, the set point or modulation will be controlled by the voltage on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0
- 10V input value received through ModBus. The default value is INACTIVE.
ModBus (Active / Inactive)
When BMS is set to ACTIVE (see BMS Active / Inactive) and the water heater is being controlled through ModBus, set parameter F3 to ACTIVE. Otherwise, set the ModBus parameter to INACTIVE. Note that the water heater can still be monitored by ModBus with this parameter set to INACTIVE. The default value is INACTIVE.
ModBus T/O (Timeout)
The ModBus T/O is the amount of time the unit controls will wait to receive a communication string from the BMS controller before reverting back to its own internal parameters. This is used to prevent unwanted operation should ModBus communication be lost. Therefore, the ModBus commands need to be refreshed within this time period. This parameter is adjustable by the installer by accessing parameter F4. The default value is 10 seconds.
Cascade Address
The water heater designated as the Leader needs to be programmed with address 0. All the Member water heaters require addresses from 1 to 7, and the addresses must be different for each Member. The addresses can be in any order, regardless of the order in which the units are wired together. This parameter is adjustable by the installer by accessing parameter F5. The tank sensor must be connected to the Leader water heater. The default address is 1.
If installing the water heaters in an existing system with existing Armor water heaters with old style controls, the new water heaters should be programmed as the Leader and/or the higher number addresses.
Cascade Type (L/L / EFF)
There are two (2) options for the way a Cascade divides the load between its heaters. The first is Lead/Lag, designated at L/L in the menu. This method will modulate the last two (2) water heaters only. When the last water heater reaches 100% and the calculated load is still increasing, it will start the next water heater at 20% and reduce the previous water heater to 80%. When the calculated load is decreasing and the last water heater gets down to 20% fire, it will hold it there and start lowering the firing rate on the next-to-last water heater. When the next-to-last water heater reaches 20%, it will turn the last water heater off and raise the rate of the next-to-last water heater to 40%, thus eliminating the sudden drop in total output of the Cascade.
The other Cascade divider method is Efficiency Optimization, designated as EFF in the menu. This method is used, as the name implies, when it is desired to have the most efficient system. When the first water heater reaches a certain rate (default = 90%), it lowers its rate to 45% and turns on the next water heater at 45%. The two (2) water heaters then modulate at the same rate.
As the calculated load increases further and both water heaters ramp up to 90%, it lowers the rate of the first two (2) water heaters to 60% and brings the next water heater on at 60%. The three (3) water heaters then modulate together. As the calculated load decreases, the water heaters will reach a lower threshold (default = 30%), at which time the last water heater (the third in our example) will turn off and the Cascade will increase the rates of the remaining water heaters to provide the equivalent total output as before ((3 x 30%) / 2 = 45% in our example).
1 Service (continued)
Service Manual
17
Maximum Cascade Outlet Set Point
This parameter determines the set point used by the individual water heaters in a Cascade. When a water heater is commanded to fire by the Leader water heater, it will attempt to achieve this temperature at its outlet. The Leader water heater will limit the modulation of the water heater in order to hold the temperature at the tank sensor to the user set point. If any of the water heater outlet temperatures reach the maximum cascade outlet set point, the water heater will then modulate down on its own in order to keep its outlet temperature within the maximum cascade outlet set point. Therefore, this parameter can be used to limit the outlet temperatures of all the water heaters in a Cascade. This parameter is adjustable by the installer by accessing parameter F7. The default maximum cascade set point is 185°F (85°C).
Minimum On/Off Time
In order to prevent units in a Cascade from short cycling, this parameter defines the minimum ON and OFF time for each unit. The installer can adjust this time by accessing parameter F8. The minimum setting is 0 seconds and the maximum setting is 10 minutes. The default is 30 seconds.
Minimum Next On Time
In order to reduce the risk of temperature overshoot with a Cascade, this parameter defines the minimum time delay from starting one unit until the next unit may be started. The installer can adjust this time delay by accessing parameter F9. The minimum setting is 0 minutes and the maximum setting is 10 minutes. The default is 60 seconds.
Boiler Size
Not used.
G: Circulation pumps
DHW Pump Delay
The DHW pump delay parameter sets the length of time the pump (if connected) will run after a DHW demand has been satisfied. This parameter is adjustable by the installer by accessing parameter G1. The time range for this parameter is 0 minutes to 40 minutes. The default time is 30 seconds.
DHW Pump Anti-Seize Delay
If the water heater pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by parameter G2. The range of this setting is 0 seconds to 40 minutes. The default setting is 20 seconds.
H: BMS
BMS Type (Power / Set Point)
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the 0 - 10V signal can be interpreted as either a modulation command or a set point. When parameter H1 is set to POWER, the 0 - 10V signal will control the modulation. When set to SETPOINT, the 0 - 10V signal will control the tank set point. The default setting is SETPOINT.
Volts at Minimum
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameter H2 should be set to the minimum voltage signal sent to the SMART SYSTEM control. The range of this parameter is 0.0V to the Volts at Minimum value (parameter H3). The default setting is 2.0V.
Volts at Maximum
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameter H3 should be set to the maximum voltage signal sent to the SMART SYSTEM control. The range of this parameter is the Minimum value (parameter H2) to 10.0V. The default value is 10.0V.
Rate at Minimum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Minimum parameter (H2) is set by parameter H4. The minimum value is 0% and the maximum is the Power at Maximum Volts setting H5. The default value is 20%.
Rate at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Maximum parameter (H3) is set by parameter H5. The minimum value is the Power at Minimum Volts setting H4 and the maximum is 100%. The default value is 100%.
Set Point at Minimum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Minimum parameter (H2) is set by parameter H6. The minimum value is 32°F (0°C) and the maximum is the Set Point at Maximum Volts setting H7. The default value is 70°F (21°C).
1 Service
Service Manual
18
Service Notification Cycles
When the water heater control determines that a scheduled service is due based on the number of water heater cycles, the water heater display will alternate the standard water heater display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter I3. The range for this parameter is 0 cycles to 100,000 cycles. The default is 50,000 cycles.
Reset Maintenance Reminder
Once servicing has been completed, the service notification counter should be reset. This parameter can be reset by the installer by accessing parameter I4. Once accessed, press the RESET key to reset the service notification counter.
Installer Name and Phone Number
When a Maintenance Reminder timer or counter has expired, a Maintenance Reminder screen will appear on the display. By programming the installer’s name and phone number, this information will appear on the Maintenance Reminder Screen at that time. This can be programmed by accessing parameter I5. When selected, another menu will appear with PHONE and NAME.
1. Rotate the NAVIGATION dial to point to the name/phone number to program and press the NAVIGATION dial. The screen will now display the selected item (either PHONE or NAME).
2. Press the NAVIGATION dial again. A cursor will appear at the bottom of the screen. By rotating the NAVIGATION dial, various numbers and characters will appear. When the desired number/character is found, press the NAVIGATION dial. The cursor will move to the next position.
3. Repeat this procedure until the entire message is entered. If you make a mistake and wish to back up one character, select the back arrow () character and press the NAVIGATION dial.
4. When finished, press the RIGHT SELECT [SAVE] key to return to the previous menu.
Please note that the brackets ([]) denote screen status.
NOTICE
Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Maximum parameter (H4) is set by parameter H7. The minimum value is the Set Point at Minimum Volts setting H6 and the maximum is 190°F (88°C). The default value is 180°F (82°C).
On Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, parameter H8 determines the 0 ­10V BMS input voltage at which the water heater is enabled. The minimum value is 0.5V and the maximum is 10.0V. The default value is 2.0V.
Off Differential Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, parameter H9 determines how far below the On Volts setting H8 the 0 - 10V BMS input voltage must be in order to disable the water heater. The minimum value is 0.2V and the maximum is the On Volts setting H8. The default value is 1.0V.
I: Service Notification
Service Notification in Months
When the water heater control determines that a scheduled service is due based on days of installation, the water heater display will alternate the standard water heater display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter I1. The time range for this parameter is 0 months to 36 months. The default time is 0 months.
This feature has been disabled by the manufacturer. To enable this feature change parameter I1 to the desired time range.
Service Notification Running Time
When the water heater control determines that a scheduled service is due based on the hours of actual operation, the water heater display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing parameter I2. The time range for this parameter is 0 hours to 100,000 hours. The default time is 8,760 hours.
2 Maintenance
Service Manual
19
Maintenance and annual startup
Table 2A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if necessary;
• Clean condensate trap and fill with fresh
water
• Check for leaks (water, gas, flue,
condensate)
• Verify flue and air lines in good condition
and sealed tight
• Check system water pressure/system
piping/expansion tank
• Check control settings
• Check ignition and flame sense electrodes
(sand off any deposits; clean and reposition)
• Check wiring and connections
• Perform start-up checkout and
performance verification per Section 10 in the Armor Installation and Operation Manual.
• Flame inspection (stable, uniform)
• Flame signal (at least 10 microamps at high fire)
• Clean the heat exchanger if flue
temperature is more than 54°F above return water temperature.
• Check Delta T (Temperature Rise)
If combustion or performance indicate need:
• Clean heat exchanger
• Remove and clean burner using compressed air only
• Clean the blower wheel
ANNUAL START-UP
Owner maintenance
Daily
• Check water heater area
• Check pressure/temperature gauge
Monthly
• Check vent piping
• Check air piping
• Check air and vent termination
screens
• Check relief valve
• Check condensate drain system
• Check air vents
• Check Delta T (Temperature
Rise)
Every
6 months
• Check water heater piping (gas
and water) for leaks
• Operate relief valve
2 Maintenance
20
Service Manual
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the water heater. Failure to perform the service and maintenance could result in damage to the water heater or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The water heater should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the water heater designated in Table 2A and explained on the following pages must be performed to assure maximum water heater efficiency and reliability. Failure to service and maintain the water heater and system could result in equipment failure.
Electrical shock hazard – Turn off power to the water heater before any service operation on the water heater except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect water heater area
1. Verify that water heater area is free of any combustible materials, gasoline and other flammable vapors and liquids.
2. Verify that air intake area is free of any of the contaminants listed in Section 1 of the Armor Water Heater Installation and Operation Manual. If any of these are present in the water heater intake air vicinity, they must be removed. If they cannot be removed, reinstall the air and vent lines per this manual and the Armor Water Heater Installation and Operation Manual.
Inspect water heater interior
1. Remove the front access cover and inspect the interior of the water heater.
2. Vacuum any sediment from inside the water heater and components. Remove any obstructions.
Clean condensate trap
1. Inspect the condensate drain line, condensate PVC fittings, and condensate trap.
2. Remove the PVC cap retaining screw from the PVC cap (FIG. 2-1).
3. Remove the 2 inch PVC cap with the switch located at the top of the trap (FIG. 2-1).
4. Remove any sediment in the trap.
5. Fill with fresh water until the water begins to pour out of the drain.
6. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
7. Replace the retaining screw.
Eliminate all system or water heater leaks. Leaking water may cause severe property damage.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual.
Check all piping for leaks
The condensate trap must be filled with water during all times of water heater operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.
WARNING
WARNING
WARNING
WARNING
WARNING
Figure 2-1 Condensate Trap
RETAINING
SCREW
2” PVC CAP WITH
BLOCKED DRAIN SWITCH
PVC TEE ASSEMBLY
(FACTORY SUPPLIED)
CONDENSATE FROM
HEAT EXCHANGER
TO FLOOR
DRAIN
2 Maintenance (continued)
21
Service Manual
Flue vent system and air piping
1. Visually inspect the entire flue gas venting system and air piping for blockage, deterioration or leakage. Repair any joints that show signs of leakage. Verify that air inlet pipe is connected and properly sealed.
2. Verify that water heater vent discharge and air intake are clean and free of obstructions.
Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.
Check water system
1. Verify all system components are correctly installed and
operational.
2. Verify system pressure is at least 12 PSI.
3. Watch the system pressure as the water heater heats up
(during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove air
vent caps and briefly push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
Check expansion tank
1. Expansion tanks provide space for water to move in and out
as the water expands due to temperature increase or contracts as the water cools. Tanks may be diaphragm or bladder type. See Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for suggested best location of expansion tanks and air eliminators.
Check water heater relief valve
1. Inspect the relief valve and lift the lever to verify flow.
Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual before proceeding further.
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the water heater relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the water heater until a new relief valve has been installed.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
WARNING
WARNING
WARNING
2 Maintenance
Service Manual
22
2 Maintenance
Inspect ignition and flame sense electrodes
1. Remove the ignition and flame sense electrodes from the water heater heat exchanger access cover.
2. Remove any deposits accumulated on the ignition/flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones.
3. Replace ignition/flame sense electrode, making sure gasket is in good condition and correctly positioned.
Check ignition ground wiring
1. Inspect water heater ground wire from the heat exchanger access cover to ground terminal strip.
2. Verify all wiring is in good condition and securely attached.
3. Check ground continuity of wiring using continuity meter.
4. Replace ground wires if ground continuity is not satisfactory.
Check all water heater wiring
1. Inspect all water heater wiring, making sure wires are in good condition and securely attached.
Check control settings
1. Set the SMART SYSTEM control module display to Parameter Mode and check all settings. See Section 1 of this manual. Adjust settings if necessary. See Section 1 of this manual for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
Perform start-up and checks
1. Start water heater and perform checks and tests
specified in Section 10 - Start-up of the Armor Water Heater Installation and Operation Manual.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
Check burner flame
1. Inspect flame through observation window.
2. If the flame is unsatisfactory at either high fire or low fire, turn off water heater and allow water heater to cool down. Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air. Do not use compressed air to clean burner if performed inside a building.
3. Remove the burner, reference FIG. 2-2 below.
4. When replacing the burner, ensure gasket is in good condition and positioned correctly (FIG. 2-2).
Figure 2-2 Burner Assembly
Service Manual
2 Maintenance (continued)
Check flame signal
1. At high fire the flame signal shown on the display should be at least 10 microamps.
2. A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode.
3. See Section 3 - Troubleshooting in this manual for other procedures to deal with low flame signal.
Review with owner
1. Emphasize the need to perform the maintenance schedule specified in this manual.
2. Remind the owner of the need to call a licensed contractor should the water heater or system exhibit any unusual behavior.
3. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
Oiled bearing circulators
1. The circulator shipped with the Armor water heater is water­lubricated. No oiling is required.
2. Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions. Over-oiling will damage the circulator.
Check Delta T
1. Check the Delta T using Table 2C as a reference.
Water Heater Pump Applications
Model
*Pipe
Size
Armstrong Grundfos
Flow Rate
(GPM)
Loss
(FT/HD)
Temp.
Rise
151 1-1/4" E8 -- 16 16.6 18°F 200 1-1/4" E8 -- 21 11.8 18°F 286 2" E17 -- 30 17.1 18°F 400 2" E24 -- 39 21 18°F 501 2" E22 -- 53 26 18°F 601 2" E22 -- 53 26 22°F
701 2" -- TP 40-160 63 32 22°F
801 2" -- TP 40-160 67 31 24°F
Table 2C Water Heater Pump Applications / Recommended Temperature Rise
The water heater contains ceramic fiber materials. Use care when handling these materials per the instructions on page 3 of this manual. Failure to comply could result in severe personal injury.
WARNING
Cleaning heat exchanger
For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 2B - Heat Exchanger Cleaning Kits.
1. Shut down water heater:
• Follow the “To Turn Off Gas to Appliance” instructions for the water heater in Section 10 ­Startup of the Installation and Operation Manual.
• Do not drain the water heater unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.
2. Allow time for the water heater to cool to room temperature if it has been firing.
3. Remove the nuts securing the heat exchanger access cover to the heat exchanger and set aside.
4. Remove the heat exchanger access cover, burner, and
gas/air arm assembly.
7. Brush the heat exchanger while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger.
8. Finish cleaning using a clean cloth dampened with warm water. Rinse out debris with a low pressure water supply.
9. Allow the heat exchanger to thoroughly dry.
10. Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble.
11. Close isolation valves on piping to isolate water heater from system. Attach a hose to the water heater drain and flush water heater thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the water heater.
12. Perform start-up and check-out procedures in the Check Flame and Combustion - Section 10 - Startup of the Installation and Operation Manual.
13. Replace the access cover and restore water heater to operation.
Table 2B Heat Exchanger Cleaning Kits
Model
Kit
Number
Part
Number
Component Description
151
-
400
KIT30063
CTN20005 Rear Refractory Cover
MSC20083* Nylon 4" Wheel Brush*
MSC20084 3mm Allen Wrench
MSC20086 1/4" x 24" Drill Extension
501
-
801
KIT30064
CTN20005 Rear Refractory Cover
MSC20083* Nylon 4" Wheel Brush*
MSC20085 1/4" x 12" Drill Extension
MSC20086 1/4" x 24" Drill Extension
* Do NOT use a metal brush. Only use the kit provided brush or an equivalent replacement nylon brush.
CAUTION
5. Remove the condensate hose from the heat exchanger end. Connect a field supplied 3/4" diameter hose to a drain pan. Using field supplied means, cover the refractory in the back of the combustion chamber of the heat exchanger.
6. Use a vacuum cleaner to remove any accumulation on the water heater heating surfaces. Do not use any solvent.
23
3 Troubleshooting
Service Manual
24
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the water heater before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.
Never jumper (bypass) any device except for momentary testing as outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.
Before troubleshooting:
1. Have the following items: a. Voltmeter that can check 120 VAC, 24 VAC, and
12 VDC. b. Continuity checker. c. Contact thermometer.
2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to water heater.
3. Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.
4. Make sure all external limit controls are installed and operating.
Check the following:
1. Wire connectors to control module are securely plugged in at the module and originating control.
2. Gas pressures:
• Maximum: 14 inches w.c. (natural and LP) with no flow (lockup) or with water heater on
• Minimum: 4 inches w.c. (natural), 8 inches w.c. (LP) with gas flowing (verify during water heater startup)
Check control module fuses
ALWAYS check control module fuses before replacing control module or any major components (blower, etc.). If one of these fuses is blown, it can prevent the control module or other components from operating.
1. Turn OFF power to the water heater at the external line switch.
2. Remove top access cover.
3. Remove the control module cover.
4. Inspect fuses F1, F2 and F3, see FIG 3-1 below.
Figure 3-1 Control Module Fuses
5. The water heater is shipped with three (3) spare fuses in a plastic bag attached to the control module cover.
6. If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15 amps, and F1 is 5 amps).
Note: Fuses F1, F2 and F3 are all slow blow fuses.
Do not jumper fuse or replace with any fuse except as specified. Failure to comply could result in severe personal injury, death, or substantial property damage.
7. Install control module cover and top access cover after fuse inspection.
8. Restore power to the water heater at the external line switch and verify water heater operation (Section 10 - Start-up in the Armor Water Heater Installation and Operation Manual) after completing water heater service.
WARNING
WARNING
NOTICE
WARNING
F3 - .80 AMP FUSE
24V DC POWER SUPPLY
F1 - 5 AMP FUSE
PUMPS
F2 - 3.15 AMP FUSE
BLOWER
25
Service Manual
3 Troubleshooting (continued)
Table 3A Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit. • Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the ON position.
• Check 120 VAC through the ON/OFF switch.
• Check wiring harness connection between display board and main control board. Connect harness at both points.
- No voltage through the switch. • Replace switch.
- Bad display board. • Replace board.
- Bad main control board. • Replace the main control board.
- Blown fuse. • Replace fuse F3 on the main control board, see page 24 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied. • Review remote thermostat setting.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault descriptions on pages 28 - 35 of this manual for corrective actions.
Unit Does Not
Modulate Above
50%
- Water heater controlled by BMS.
• Check BMS parameter settings. Optional PC software required.
- Flue sensor open.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare to Table 3D on page 26 of this manual.
Service Manual
26
3 Troubleshooting
Table 3B - Inlet System Sensor Resistance vs. Temperature
Temperature °F
Resistance Ω
Temperature °F
Resistance Ω
50 18,780 158 1,990
68 12,263 176 1,458
86 8,194 194 1,084
104 5,592 212 817
122 3,893 -- --
140 2,760 -- --
Checking temperature sensors
The water heater temperature sensors (inlet water, outlet water, system water, and flue) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.
It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Armor Water Heater Installation and Operation Manual for correct terminal location.
S1a
(Wire Color - R/BK and Y)
S1b
(Wire Color - G and Y)
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
50 19,553 158 2,004 50 40,030 158 3,478
68 12,690 176 1,464 68 25,030 176 2,492
86 8,406 194 1,084 86 16,090 194 1,816 104 5,715 212 816 104 10,610 212 1,344 122 3,958 122 7,166 140 2,786 140 4,943
Table 3C - Outlet Water Sensor Resistance vs. Temperature
S3a
(Wire Color - W/B and Y)
S3b
(Wire Color - PR and Y)
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance
50 40,030 158 3,478 50 258,500 158 16,870
68 25,030 176 2,492 68 125,500 176 12,000
86 16,090 194 1,816 86 80,220 194 8,674 104 10,610 212 1,344 104 52,590 212 6,369 122 7,166 122 35,270 140 4,943 140 24,160
Table 3D - Flue Sensor Resistance vs. Temperature
3 Troubleshooting (continued)
27
Service Manual
Table 3E Troubleshooting Chart - Noisy System
FAULT CAUSE CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural gas pressures should be between 4 inches w.c. and 14 inches w.c. LP gas pressures should be between 8 inches w.c. and 14 inches w.c.
• Refer to Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual for detailed information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Gas Valve Adjustment Procedure on
pages 37-38 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Armor Water Heater Installation and Operation Manual.
- Dirty/damaged burner.
• Refer to page 22 in this manual for the burner removal
and inspection procedure. Clean or replace the burner as necessary.
- Low water flow through the heat exchanger.
• Refer to Section 6 - System Piping of the Armor Water
Heater Installation and Operation Manual for minimum flow rates.
- Air in the piping system. • Properly purge all air from the piping system.
- Low system water pressure. • Verify system pressure is a minimum of 12 PSI.
No Pump
Operation
- Blown fuse.
• Replace fuse F1 on the control board, see page 24 of
this manual.
- Faulty pump. • Replace pump.
- Faulty pump relay. • Replace pump relay.
- Internal fault on control board. • Replace main control board.
Relief Valve
Opening
- System pressure exceeds relief valve setting.
• Lower the system pressure below the 150 PSI rating of the supplied relief valve.
Service Manual
28
3 Troubleshooting
Table 3F Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Gas Pressure SW
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART SYSTEM
display to reset.)
Either the manual reset low gas pressure switch or the manual reset high gas pressure switch tripped.
• Reset the pressure switches.
• Measure the supply gas pressure to determine cause of failure. Natural gas pressures should be between 4 - 14 inches w.c.
• Refer to Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual for detailed information concerning the gas supply.
• Correct the supply gas pressure if necessary.
• Check for a loose or misplaced jumper if pressure switches are not installed.
Flow Switch
(will require a manual
reset once condition has
been corrected. Press the RESET button on the SMART SYSTEM
display to reset.)
The flow switch is not making.
• Check water heater pump operation on a call for heat.
• Check for closed valves or obstructions in the water heater piping.
• Verify system is full of water and all air has been purged from the system.
• Check for loose or misplaced jumpers if flow switch is not installed.
Blown fuse. • Replace fuse F2 on the control board, see page 24 of
this manual.
Blocked Drain SW
(will require a manual
reset once condition has
been corrected. Press the RESET button on the SMART SYSTEM
display to reset.)
The blocked drain switch has detected excessive condensate build up inside the unit.
• Check condensate tube from unit to floor drain for
proper installation and obstructions.
• Inspect condensate trap for blockage. Clean if necessary.
• Check for loose wiring connection at wire harness plug.
• Bad blocked drain switch. Replace switch.
APS
Open
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART SYSTEM
display to reset.)
Air pressure switch contacts are open.
• Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals.
• Air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Armor Water Heater Installation and Operation Manual for proper lengths.
• Check for obstruction or blockage in the air intake pipes or at terminations.
• Check reference hoses connected to the air pressure switch for blockage or obstruction.
• Inspect the burner. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Inspect the heat exchanger. Reference page 23 of this manual for removal and cleaning procedures. Replace if necessary.
• Faulty air pressure switch. Replace switch.
29
Service Manual
3 Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Anti-cycling
The main control board has received a call for heat too quickly after the previous call for heat has ended.
• The control board will release the call for heat after a set time period.
• The control board will release the call for heat if the outlet temperature drops too quickly.
Flame Fail Ign
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART SYSTEM
display to reset.)
The unit has failed to prove main burner ignition after four (4) attempts.
Exception: Models 501 - 801 will lock out after one retry for ignition. It will require a manual reset before attempting to fire again.
• Inspect spark electrode and associated wiring for damage and connection. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Check for proper electrical grounding of the unit.
• Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. Refer to Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual for detailed information concerning the gas supply.
• Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are correctly installed and that there are no obstructions.
• Check for 24 VAC to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board.
• If 24 VAC is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the GV / Relay Fail fault.
• If 24 VAC is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve.
• Inspect flame sensor and associated wiring. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Inspect the burner. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Replace the main control board.
Service Manual
30
3 Troubleshooting
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
No Flame
Running
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART
SYSTEM display to
reset.)
The unit was running and lost the flame signal. This condition occurred four (4) straight times.
Exception: Models 501 - 801 will lock out after one retry for ignition. It will require a manual reset before attempting to fire again.
• Inspect spark electrode and associated wiring for damage and connection. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Check for proper electrical grounding of unit.
• Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. Refer to Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual for detailed information concerning the gas supply.
• Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are installed correctly and there are no obstructions.
• Check for 24 VAC to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board.
• If 24 VAC is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the GV / Relay Fail fault.
• If 24 VAC is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve.
• Inspect flame sensor and associated wiring. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Inspect the burner. Reference page 22 of this manual for removal and cleaning procedures. Replace if necessary.
• Replace the main control board.
3 Troubleshooting (continued)
31
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Flame Sequence
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
The flame detector circuit is seeing a flame signal while no flame is present.
• Check supply voltage for proper polarity.
• Check external wiring for voltage feedback.
• Check the flame rod and make sure it is clean.
• Check the internal wiring for bad connections.
• Replace main control board.
Auto Reset
High Limit
The outlet water temperature has exceeded the setting of the automatic reset high limit.
• Verify that the system is full of water and that all air has been properly purged from the system.
• Verify that the water heater is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Armor Installation and Operation Manual for the proper piping methods for the Armor water heater.
• Check 120 vac to water heater pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.
• Replace the main control board if necessary.
• If 120 vac is present on a call for heat and the water heater pump is not operating, replace the pump.
• If the system pump is a variable speed pump, ensure that the system flow is not less than the water heater flow.
• If operating on something other than an outlet sensor, check temperature setting of the main control board.
• If the manual reset high limit has tripped, check setting of the device.
• Check resistance of water sensors and compare to Table B on page 26 of this manual. Replace sensor if necessary.
• Replace high limit.
Manual Reset
High Limit
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
The outlet water temperature has exceeded the fixed setting of the manual reset high limit.
• Verify that the system is full of water and that all air has been properly purged from the system.
• Verify that the water heater is piped properly into the heating system. Refer to Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for the proper piping methods for the Armor water heater.
• Check 120 VAC to water heater pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.
• Replace the main control board if necessary.
• If 120 VAC is present on a call for heat and the water heater pump is not operating, replace the pump.
• If the manual reset high limit has tripped, check setting of the device.
• Check resistance of water sensors and compare to Table 3C on page 26 of this manual. Replace sensor if necessary.
• Replace high limit.
3 Troubleshooting
Service Manual
32
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Fan Low
OR
Fan Speed Low
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
The actual fan RPM is 30% lower than what is being called for.
• Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Armor Water Heater Installation and Operation Manual for proper lengths.
• Check for obstruction or blockage in the vent/air intake pipes or at terminations.
• Check the wiring connections at the fan and at the main control board.
• Replace the fan.
• Replace the main control board.
Blown fuse.
• Replace fuse F4 on the control board, see page 24 of this manual.
GV/Relay
Fail
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
The main control board did not detect the gas valve.
• Check wiring harness connection at the gas valve and at the main control board.
• Replace the gas valve wire harness.
• Replace the gas valve.
• Replace the main control board.
Fan High
OR
Fan Speed High
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
The actual fan RPM is 30% higher than what is being called for.
• Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Armor Water Heater Installation and Operation Manual for proper lengths.
• Check for obstruction or blockage in the vent/air intake pipes or at terminations.
• Check the wiring connections at the fan and at the main control board.
• Replace the fan.
• Replace the main control board.
Sensor Open
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
Either the inlet water or outlet water temperature sensor has been disconnected.
• Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare the resistance to the tables on page 26 of this manual.
• Replace the sensor if necessary.
Service Manual
33
3 Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Sensor Shorted
(will require a manual
reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display
to reset.)
Either the inlet water or outlet water temperature sensor has been shorted.
• Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare the resistance to the tables on page 26 of this manual.
• Replace the sensor if necessary.
Louver Proving
(will require a manual
reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display
to reset.)
An optional remote proving switch is not making.
• Check function of remote devices.
• Check for loose or misplaced jumper if auxiliary proving switch is not installed.
Flue Temp High
The stack temperature has exceeded the set parameters for the water heater.
• Inspect the heat exchanger. Reference page 23 of this manual for the procedure on how to clean the flue side of the heat exchanger.
• Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3D on page 26 of this manual. Replace the sensor if necessary.
• Verify that the vent/air intake pipes are properly installed and that there are no obstructions.
• Replace the main control board.
Scaling has reduced water flow. • Deliming may be required.
Delta T High
The temperature rise across the heat exchanger has exceeded the set parameters for the water heater.
• Verify that the system is full of water and that all air has been properly purged from the system.
• Verify that the water heater is piped properly into the heating system. Refer to Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for the proper piping methods for the Armor water heater.
• Check for 120 VAC to the water heater pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary.
• If 120 VAC is present on a call for heat and the water heater pump is not operating, replace the pump.
• Verify that the water heater pump is set to the proper speed or that the pump is the proper size. Reference Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for water heater pump specifications.
3 Troubleshooting
34
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Outlet Temp High
Outlet water temperature has exceeded the maximum outlet water temperature.
• Verify that the system is full of water and that all air has been properly purged from the system.
• Verify that the water heater is piped properly into the heating system. Refer to Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for the proper piping methods for the Armor water heater.
• Check for 120 VAC to the water heater pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary.
• If 120 VAC is present on a call for heat and the water heater pump is not operating, replace the pump.
• Replace the main control board.
Rem Ctrl Flt
External control is cycling too often.
• Check set point of the external control.
• Check the wiring between the external control and the unit.
• Replace the control.
Service Blk
While the unit is in Service Mode, the outlet temperature has exceeded 185°F.
• Establish a heating load to remove the heat from the water heater loop.
• Verify that the system is full of water and that all air has been properly purged from the system.
• Verify that the water heater is piped properly into the heating system. Refer to Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for the proper piping methods for the Armor water heater.
• Check 120 VAC to the water heater pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary.
• If 120 VAC is present on a call for heat and the water heater pump is not operating, replace the pump.
• Verify that the water heater pump is set to the proper speed or that the water heater pump is the proper size. Reference Section 6 - System Piping of the Armor Water Heater Installation and Operation Manual for water heater pump specifications.
Service Manual
35
3 Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Low 24 VAC
120 VAC input to the main control board has dropped below 80 VAC.
• Check 120 VAC supply to the transformer.
• Check wiring connections at the low voltage terminal strip.
• Check the wire size/length to remote devices.
• Replace the transformer.
Watch Dog Error
The main control board has detected an internal fault.
• Replace the main control board.
Write EEProm
The main control board has detected an internal fault.
• Replace the main control board.
CRC Parameters
The main control board has detected an internal fault.
• Replace the main control board.
No Error Stored
The main control board has detected an internal fault.
• Replace the main control board.
Fatal Error
Parameters
The main control board has detected an internal fault.
• Restore the default parameters.
• Replace the main control board.
• Replace the display board.
3 Troubleshooting
36
Service Manual
Combustion Analysis Procedure
1. Turn the main power off to the water heater by placing the “On/Off” switch in the OFF position.
2. Remove the flue temperature sensor from the flue pipe connection. Note: Combustion measurements will be made at this point.
3. Turn the main power on to the water heater by placing the “On/Off” switch in the ON position.
4. Place the water heater into the active position by pressing the RIGHT SELECT [ON] key (see page 5).
5. Locate the pinhole button below the RESET button on the display board (see page 5). Insert a thin wire (such as a paper clip) into the hole and press the button once and hold for 5 seconds to place the water heater into Service Mode. In Service Mode the water heater will fire at ignition speed and will then modulate up to full fire.
6. Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor.
7. Once the water heater has modulated up to full fire, measure the combustion. The values should be in the range listed in Table 3G above. The CO levels should be less than 150 ppm for a properly installed unit.
If the combustion is not within the specified range, reference the chart below for possible causes and corrective actions.
Table 3H Troubleshooting Chart - Combustion Levels
POSSIBLE CAUSE CORRECTIVE ACTION
Vent/Air Intake Length
or Obstruction
• Refer to Section 3 - General Venting of the Armor Water Heater Installation and Operation Manual for the proper venting and air intake methods for the Armor water heater.
• Check for obstructions at the vent/air intake terminals.
Gas Supply Pressure
• Refer to Section 7 - Gas Connections of the Armor Water Heater Installation and Operation Manual for the proper gas supply for the Armor water heater.
Dirty/Damaged Burner
• Refer to page 22 of this manual for burner removal and cleaning procedures.
• Replace burner if necessary.
Gas Valve Adjustment
• Refer to pages 37-38 of this manual for the gas valve adjustment procedure.
Table 3G Flue Products
Natural Gas Propane
CO
2
O
2
CO
2
O
2
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%
8. Once the combustion analysis is complete, test the safety shutoff device by turning the manual shutoff valve to the OFF position and ensuring that the water heater shuts down and registers an alarm. Open the manual shutoff valve, reset the control, and return to Service Mode.
9. Turn the main power off to the water heater and replace the flue temperature sensor into the flue pipe connection.
10. Place the water heater back into normal operation.
You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.
WARNING
Service Manual
37
3 Troubleshooting (continued)
Gas valve adjustment procedure
If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures in this section are model specific.)
Models 151 - 286
Locate the throttle adjustment screw on the side of the venturi valve (FIG. 3-2). Using a screwdriver, turn the screw a 1/4 turn clockwise to decrease CO2levels or a 1/4 turn
counterclockwise to increase CO2levels. After performing one adjustment on the valve, follow the Combustion Analysis
Procedure on page 36 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3H on page 36 or replace the gas valve.
Figure 3-2 Gas Valve Adjustment: Models 151 - 286
Model 400
Locate the throttle adjustment screw on the top of the gas valve, see FIG. 3-3. Using a screwdriver, turn the screw 1/8 turn counterclockwise to increase CO
2
levels or 1/8 turn
clockwise to decrease CO
2
levels. After one adjustment on
the valve, follow the Combustion Analysis Procedure on page 36 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3H on page 36 or replace the gas valve.
Figure 3-3 Gas Valve Adjustment: Model 400
THROTTLE ADJUSTMENT
SCREW
38
Model 501
Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2levels or a 1/4 turn clockwise
to decrease CO2levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 36 of this manual
to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3H on page 36 or replace the gas valve.
Figure 3-4 Gas Valve Adjustment: Model 501
Service Manual
3 Troubleshooting
Models 601 - 801
Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn
counterclockwise to increase CO2levels or a 1/4 turn clockwise to decrease CO2levels. After one adjustment on
the valve, follow the Combustion Analysis Procedure on page 36 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3H on page 36 or replace the gas valve.
THROTTLE
ADJUSTMENT
SCREW
(REMOVE BLUE CAP)
Figure 3-5 Gas Valve Adjustment: Models 601 - 801
Notes
39
Revision Notes: Revision A (ECO #C06238) initial release.