Lochinvar Armor151 Installation Manual

MODB-I-O Rev D
MODBUS COMMUNICATION
INSTRUCTIONS
Models:
Knight 81 - 286, Knight XL 400 - 801,
Armor 151 - 801, Wall Mount 51 - 211
and Wall Hung 55 - 399
WARNING
This manual must only be used by a qualifi ed heating installer / service technician. Read all instructions, including this manual, the Installation and Operation Manual, and the Service Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
Contents
1. INTRODUCTION
Defi nitions .................................................................... 2
Minimum System Requirements .................................. 2
2. INSTALLATION
Wall Mount, Armor, Knight and Knight XL ................... 3-4
Wall Hung .................................................................... 5
3. CONFIGURATION
Addressing ................................................................... 6
Timing Specifi cations ................................................... 7
Parity ............................................................................ 7
Data Transmission Mode ............................................. 7
ModBus Board Diagnostics ......................................... 7
Internal Faults ......................................................... 7
ModBus Function Set .................................................. 8
ModBus Exception Codes ........................................... 9
4. MEMORY MAP
Primary Data Tables ....................................................10
Memory Map............................................................10-11
Input Registers .......................................................11
Holding Registers ...................................................11
Confi guration Bits ........................................................11
5. WIRING REQUIREMENTS
Physical Wiring ............................................................12
Control Inputs/Outputs............................................ 13-14
Control Location ..........................................................15
Typical Boiler/Water Heater System Wiring................ 16
6. UNIT OPERATION
Unit Operation with ModBus Communications ............. 17-21
7. TROUBLESHOOTING ........................................... 22-23
8. DIAGRAMS
Ladder & Wiring Diagrams ..................................... 24-31
Revision Notes ................................................... Back Cover
1 Introduction
The information contained in this manual provides general guidelines for the implementation of ModBus communication with the Lochinvar Armor water heaters (151 - 801), Knight (81-286), Knight XL (400 - 801), Wall Mount (51 - 211), and Wall Hung (55 - 399) boilers.
All ModBus networks are implemented utilizing a master-slave arrangement where all boilers/water heaters are slaves and the master is a building automation system capable of communicating over a RS-485 half duplex serial connection.
Defi nitions
Abbreviation or Acronym Meaning
ASCII American Standard Code for Information Interchange BAS Building Automation System Baud (Baud Rate) Number of data bits transmitted per second (bps) EMS Energy Management System FDX Full-Duplex HDX Half-Duplex Hex Hexadecimal Number (0 - 9, A - F) I/O Box Input/Output (I/O) LSB Least Signifi cant Byte
ModBus A serial, half-duplex data transmission protocol developed by AEG Modicon MSB Most Signifi cant Byte
RS232
RS485 A standard for serial transmission of data based on the RS-485 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the RS232 Standard
RTU Remote Terminal Unit
Minimum System Requirements
BAS system or computer with a serial or USB port with a converter to RS-485 half duplex.
Unit equipped with ModBus communication board.
Shielded twisted pair communication cable.
2
2 Installation
A
ModBus Communication Instructions
ModBus installation procedure - for Models WB, AW, KB and KBX
1. Turn OFF the main electrical power to the appliance.
2. Turn OFF the main manual gas shutoff to the appliance.
3. Assemble the ModBus control board to the sheet metal base as shown in FIG. 2-1.
4. Connect the power harness from the appliance to the ModBus through the sheet metal cover hole (see FIG. 2-2).
5. Using the two (2) sheet metal screws provided in the kit, attach the pre-painted sheet metal cover over the ModBus assembly for protection from line voltage (FIG. 2-2).
6. Locate the pilot holes on the side of the jacket (left side if AW/KB/KXL or right side if WB), using the sheet metal screws provided in the kit, mount the ModBus assembly to the appliance (FIG. 2-3).
Wiring
7. Disconnect power to the transformer by removing connection “B”, see FIG. 2-4, page 4.
8. Connect A, C, D, and B (FIG. 2-4).
9. Connect the ModBus to the control board of the appliance (see FIG. 2-5 on page 4).
10. Turn on the main electrical power and the main manual gas shutoff to the appliance.
11. Confi gure the control board and unit controls per this manual and resume operation.
Figure 2-2_Attach Cover to ModBus Assembly
MODBUS ASSEMBLY
MOUNT PRE-PAINTED SHEET METAL COVER OVER THE MODBUS ASSEMBLY FOR PROTECTION FROM LINE VOLTAGE
TTACH POWER HARNESS TO MODBUS THROUGH SHEET METAL COVER HOLE
Figure 2-3_Mount ModBus Assembly to Unit
- LOCATE THE PILOT HOLES
- USING THE 4 SHEET METAL
SCREWS PROVIDED IN THE KIT MOUNT THE MODBUS ASSEMBLY TO THE UNIT (SIDE DEPENDENT ON MODEL)
Figure 2-1_Assemble ModBus Control Board
SHEET METAL BASE
BLT2007 [X4]
JKB40095
BLT7068 [X4]
NOTE: KB/KXL/AW - MOUNT MODBUS ASSEMBLY TO THE LEFT SIDE OF THE JACKET WB - MOUNT MODBUS ASSEMBLY TO THE RIGHT SIDE OF THE JACKET
3
2 Installation
Figure 2-4_Harness Connections_KB, KBX, WB, and AW
ModBus Communication Instructions
FROM POWER HARNESS
A
B G W
ROUTE THROUGH JACKET HARNESS CLIPS
USE SUPPLIED CABLE TIE TO CONNECT MODBUS POWER HARNESS TO BLOWER POWER
WIRES (RED, WHITE, GREEN)
TO TRANSFORMER
D
C
B
W
WGB
B
B
W
GY
G
R
BL
G
Figure 2-5_Connect ModBus to Control Board
CONNECT TO CONTROL BOARD FROM MODBUS*
*HARNESSES CAN ONLY BE CONNECTED ONE WAY.
4
LOW VOLTAGE CONNECTION BOARD
CONNECT TO CONNECTION BOARD FROM MODBUS*
2 Installation (continued)
ModBus Communication Instructions
Installation Procedure - for WH Models
1. Turn OFF the main electrical power to the appliance.
2. Turn OFF the main manual gas shutoff to the appliance.
3. To assemble the ModBus control board to the sheet metal, insert four (4) standoffs into the front access panel (FIG. 2-6).
4. Place the control board onto the standoffs installed in Step 3. Use the screw (provided in kit) to secure the control panel cover (FIG. 2-6).
5. Connect the wire harnesses (WRE20073, WRE20075 and WRE20077) from the appliance to the ModBus following the diagram shown in FIG. 2-7.
6. Turn on the main electrical power and the main manual gas shutoff to the appliance.
7. Confi gure the control board and unit controls per this manual and resume operation.
Figure 2-7_Harness Connections_WH
Figure 2-6_Assemble ModBus Control Board_WH
INSERT
STANDOFFS
USE SCREW TO SECURE COVER
TO FRONT PANEL
(WRE20075)
(WRE20073)
G
R
B
L
(WRE20077)
G
Y
G
W
B
W W
G
B B
5
ModBus Communication Instructions
3 Confi guration
The ModBus communication board is equipped with a set of ten dip switches that are used to set the board confi guration (address, baud rate, and parity settings). The fi rst eight are used to set the address of each board. The ninth baud rate. The tenth is parity.
Figure 3-1_ModBus Communication Board
DIP SWITCHES
LED’S
Addressing
The ModBus addressing space is comprised of 256 different address.
0 is reserved for broadcast messages from the master device
1 - 247 are free to use for each unique device
248 - 255 are reserved
To set the ModBus address the dip switches can be set in either the 0 position or the 1 position. For switches set to the 1 position their value will be added together to determine the address.
For each switch set to the 1 position it has the following value:
Dip switch 1 = 1 Dip switch 2 = 2 Dip switch 3 = 4 Dip switch 4 = 8 Dip switch 5 = 16 Dip switch 6 = 32 Dip switch 7 = 64 Dip switch 8 = 128
Any dip switch set to 0 has a value equal to 0.
Example:
To set the address of the ModBus board to 50, dip switches 2, 5, and 6 have to be set to the 1 position. The address is determined by adding the values of all the dip switches together.
Address = Value of Dip switch 1 + Value of Dip switch 2 + Value of Dip switch 3 + Value of Dip switch 4 + Value of Dip switch 5 + Value of Dip switch 6 + Value of Dip switch 7 + Value of Dip switch 8
In this example:
Address = 0 + 2 + 0 + 0 + 16 + 32 + 0 + 0 = 50
6
3 Confi guration (continued)
ModBus Communication Instructions
Timing Specifi cations
The baud rate for the ModBus board is selectable with Dip switch #9.
1 = 19200 bps 0 = 9600 bps
Each message is started by at least 3.5 character times of silence. The maximum delay between frames is 1.5 character times.
When the system temperature and/or tank temperature is provided by the BAS to the boiler, it is critical that the temperature be updated every few seconds. If the boiler does not receive updated temperatures within a timeout period (installer adjustable), the control will revert to using its own sensor inputs (if sensors are connected). The timeout is programmable as follows:
NOTICE
1. Press and hold the LEFT SELECT [MENU] key for 5 seconds.
2. Enter installer code - 5309.
3. Scroll down and select [CONTROL MODES].
4. Scroll down and select [MODBUS T/O].
5. Scroll to desired time. Press the RIGHT SELECT [SAVE] key.
Please note that the brackets ([]) denote screen status.
Data Transmission Mode
Many ModBus bus master devices can be confi gured to transmit data in either ModBus RTU or ModBus ASCII modes. Since RTU messages can be formatted to use fewer data bits and are therefore more effi cient, RTU has been chosen to be used with all Lochinvar ModBus communication. Please ensure that the master device is transmitting ModBus RTU.
ModBus Board Diagnostics
The ModBus board is equipped with three LED’s for visual diagnostics: Two yellow LED’s and one green. One yellow LED (D5) is used to indicate reception of data. The other yellow LED (D6) is used to indicate transmission of data. The green LED (D7) is used to show internal faults.
Internal Faults: Normal Operation = 1 second on, 1 second off Controller Fault = Continuously on No Burner Control Communication = 0.5 seconds on, 1.5 seconds off No ModBus Communication = 1.5 seconds on, 0.5 seconds off
ModBus Communication
The ModBus communication commands and exception codes that are supported by the ModBus communication board can be found on pages 8 and 9 of this manual.
The timeout is adjustable between 5 and 120 seconds. The default timeout is 10 seconds.
When the BAS is not providing either of these temperatures, but is still controlling the boiler (such as providing a modulation command), the BAS must refresh these commands at least every 4 minutes. If the commands are not refreshed, the boiler will revert to operating based on its own inputs.
Parity
Parity is set by the position of Dip switch #10.
0 = No Parity 1 = Even Parity
If No Parity is selected there will be two stop bits, otherwise there will be one.
7
3 Confi guration
ModBus Function Set
ModBus Communication Instructions
Function Sub Function
HEX Description
Dec HEX Dec
1 01 Read Coil Status 2 02 Read Input Status 3 03 Read Holding Registers 4 04 Read Input Registers 5 05 Force Single Coil 6 06 Preset Single Register 7 07 Read Exception Status 8 08 0 00 Diagnostic - Return Query Data
1 01 Diagnostic - Restart Communication 2 02 Diagnostic - Return Diagnostic Register 4 04 Diagnostic - Force Listen Mode
10 0A
11 0B Diagnostic - Return Bus Message Count
Diagnostic - Clear Counters and Diagnostic Registers
12 0C Diagnostic - Bus Communication Error Count 13 0D Diagnostic - Bus Exception Error Count 14 0E Diagnostic - Return Slave Message Count 15 0F Diagnostic - Return Communication Error Count 16 10 Diagnostic - Return Slave NAK Count 17 11 Diagnostic - Return Slave Busy Count 18 12 Diagnostic - Return Bus Character Overrun Count
20 14 Diagnostic - Clear Overrun Counter and Flag 11 0B Get Communication Event Counter 12 0C Get Communication Event Log 15 0F Write Multiple Coils 16 10 Write Multiple Registers 17 11 Report Slave ID 23 17 Read / Write Multiple Registers
8
ModBus Communication Instructions
3 Confi guration (continued)
ModBus Exception Codes
MODBUS Exception Codes
Code Name Meaning
The function code received in the query is not an allowable action for the server (or slave). This may be because the function code is only applicable to newer
01 ILLEGAL FUNCTION
02 ILLEGAL DATA ADDRESS
devices, and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example because it is unconfi gured and is being asked to return register values.
The data address received in the query is not an allowable address for the server (or slave). More specifi cally, the combination of reference number and transfer length is invalid. For a controller with 100 registers, the PDU addresses the fi rst register as 0, and the last one as 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 4, then this request will successfully operate (address-wise at least) on registers 96, 97, 98, 99. If a request is submitted with a starting register address of 96 and a quantity of registers of 5, then this request will fail with Exception Code 0x02 “Illegal Data Address” since it attempts to operate on registers 96, 97, 98, 99 and 100, and there is no register with address 100.
03 ILLEGAL DATA VALUE
04 SLAVE DEVICE FAILURE
05 ACKNOWLEDGE
06 SLAVE DEVICE BUSY
08 MEMORY PARITY ERROR
A value contained in the query data fi eld is not an allowable value for server (or slave). This indicates a fault in the structure of the remainder of a complex request, such as that the implied length is incorrect. It specifi cally does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program, since the MODBUS protocol is unaware of the signifi cance of any particular value of any particular register.
An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action.
Specialized use in conjunction with programming commands. The server (or slave) has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the client (or master). The client (or master) can next issue a Poll Program Complete message to determine if processing is completed.
Specialized use in conjunction with programming commands. The server (or slave) is engaged in processing a long -- duration program command. The client (or master) should re-transmit the message later when the server (or slave) is free.
Specialized use in conjuction with function codes 20 and 21 and reference type 6, to indicate that the extended fi le area failed to pass a consistency check. The server (or slave) attempted to read record fi le, but detected a parity error in the memory. The client (or master) can retry the request, but service may be required on the server (or slave) device.
0A GATEWAY PATH UNAVAILABLE
0B
GATEWAY TARGET DEVICE
FAILED TO RESPOND
Specialized use in conjunction with gateways, indicates that the gateway was unable to allocate an internal communication path from the input port to the output port for processing as the request. Usually means that the gateway is misconfi gured or overloaded.
Specialized use in conjunction with gateways, indicates that no response was obtained from the target device. Usually means that the device is not present on the network.
9
ModBus Communication Instructions
4 Memory Map
Primary Data Tables
Table Data Type Read / Write
Discrete Inputs Single Bit Read Only Coils Single Bit Read / Write Input Registers 16-Bit Word Read Only Holding Registers 16 Bit Word Read / Write
Memory Map
Coils
Address Description Default Unit Min. Max. Resolution
00001 Room Thermostat 1 0 1=ON / 0=OFF 0 1 1 00002 Room Thermostat 2 0 1=ON / 0=OFF 0 1 1 00003 Room Thermostat 3 0 1=ON / 0=OFF 0 1 1 00005 Tank Thermostat 0 1=ON / 0=OFF 0 1 1
Discrete Inputs
10002 Flow Switch 0 1=ON / 0=OFF 0 1 1 10003 Gas Pressure Switch 0 1=ON / 0=OFF 0 1 1 10004 Louver Proving Switch 0 1=ON / 0=OFF 0 1 1 10005 Air Pressure Switch 0 1=ON / 0=OFF 0 1 1 10006 Blocked Drain Switch 0 1=ON / 0=OFF 0 1 1 10007 Auto Reset High Limit 0 1=ON / 0=OFF 0 1 1 10008 Flame 0 1=ON / 0=OFF 0 1 1 10009 Room Thermostat 1 0 1=ON / 0=OFF 0 1 1 10010 Tank Thermostat 0 1=ON / 0=OFF 0 1 1
10024 Room Thermostat 2 0 1=ON / 0=OFF 0 1 1
10033 Run-time Contacts 0 1=ON / 0=OFF 0 1 1 10034 Alarm Contacts 0 1=ON / 0=OFF 0 1 1 10035 CH Pump 0 1=ON / 0=OFF 0 1 1 10036 DHW Pump 0 1=ON / 0=OFF 0 1 1 10038 Gas Valve 0 1=ON / 0=OFF 0 1 1 10039 System Pump 0 1=ON / 0=OFF 0 1 1
10
Loading...
+ 22 hidden pages