Service Manual
9
Sequence of operation
Table 1A_Sequence of Operation - Space Heating and DHW
1 Service (continued)
OPERATION DISPLAY
1. The manual reset high limit must be closed before any
action will take place.
HTR: Standby
OUT: 123.8F(129)
2. Upon a call for heat the control turns on the appropriate
pumps (system and boiler pumps for space heating; DHW
pump for DHW call). The flow switch and low water cutoff (if
equipped) must close.
HTR: Standby
OUT: 123.8F(129)
3. • If the unit is equipped with a proof of closure valve, the
proof of closure switch must be closed. The proof of
closure valve is then energized. The gas pressure
switch(es) (if equipped) must close.
• If the contact for the louvers is closed, the louver proving,
blocked drain switch, and auto reset high limit (water
heater only) inputs must close.
• If the air pressure switch is open, the prepurge cycle then
begins by starting the combustion blower. Once started,
the air pressure switch must close.
HTR: Standby
OUT: 123.8F(129)
4. After the 10 second prepurge, the blower slows down and
the hot surface igniter (HSI) is energized. The HSI is heated
for at least 15 seconds.
HTR: PREPURGE
OUT: 123.9F(129)
5. Once the HSI is hot, the trial for ignition begins with the
opening of the gas valve.
HTR: IGNITION
OUT: 123.9F(129)
6. If the SMART SYSTEM control does not sense flame within
7 seconds of the opening of the gas valve, then it will lock
out.
HTR: POSTPURGE, PREPURGE
OUT: 123.9F(129)
7. If the SMART SYSTEM control senses flame within 7
seconds, it will fire the burner to maintain the set point. On
B9 and M9 models, the firing rate will modulate as required
to hold the actual temperature at the set point. If the boiler
lights due to a space heating call for heat, and the ramp
delay function is active (default is disabled), the modulation
will be held to a series of increasing limits after the burner
has lit.
HTR: SH 20% RATE
OUT: 124.8F(129)
8. If the space heating call for heat is active, and the DHW
thermostat closes, the control will turn on the DHW pump,
wait 2 seconds, and then turn off the boiler pump. This will
divert the hot water away from the heating zone(s) and send
it to the DHW tank instead. The control will then modulate
(B9 and M9 models only) to maintain the outlet temperature
to the DHW boiler set point.
HTR: DHW 85% RATE
OUT: 177.8(180)