Lochinvar 45, 000—500, 000 Btu/hr Models Installation And Service Manual

1
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
Factory warranty (shipped with appliance) does not apply to appliances improperly installed or improperly operated.
1. Excessive water hardness causing a lime buildup in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements).
This manual supplies information for the installation, operation and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation.
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliance which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify carrier.
Hot Water Heating Boiler
Water Heater/Domestic Hot Water Supply Boiler
45,000—500,000 Btu/hr Models
RB/RW-i&s-07
INSTALLATION AND SERVICE MANUAL
WARRANTY
NOTE: Retain this manual for future reference.
SPECIAL INSTRUCTIONS TO OWNER
WARNING:
Improper Installation, Adjustment, Alteration, Service or Maintenance
can cause injury or property damage.
Refer to this manual. For assistance or
additional information consult a qualified
installer, service agency or the gas supplier.
CHECKING EQUIPMENT
Use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
DO NOT
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
The appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
-
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING:
— WHAT TO DO IF YOU SMELL GAS —
2
The information contained in this manual is intended for use by qualified professional installers, service technicians or gas suppliers. Consult your local expert for proper installation or service procedures.
Your conventionally vented gas appliance must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting.
1. Boilers and water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your appliance.
3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this appliance, vent-air intake system or any location from which fumes could reach the appliance or vent-air intake system.
The equipment shall be installed in accordance with installation regulations in force in the local area where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installa­tion shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers
CONTENTS
Warranty
Safety Warnings ......................................................................1
Codes ..................................................................................2
Location ..................................................................................3
Clearances................................................................................4
Combustion/Ventilation Air Requirements ............................4
Conventional Venting ..............................................................7
Masonry Chimney Installations ............................................10
Sidewall Venting ....................................................................10
Automatic Vent Damper........................................................11
Gas Supply ............................................................................12
Gas Pressures & Piping..........................................12
Manifold Pressure Adjustment ..............................15
Supply Pressure Measurement ..............................16
Water Connections ................................................................17
Relief Valve............................................................................19
Flow Switch ..........................................................................19
Gas Valve ..............................................................................20
Electrical Requirements ........................................................21
Temperature Adjustment ......................................................22
Temperature Limit Control....................................................22
Blocked Vent and Flame Roll-out System............................22
Lighting Instructions ............................................................24
Ignition & Control Timings ..................................................29
Freeze Protection ..................................................................29
Maintenance ..........................................................................30
Flame Patterns........................................................30
Burner Cleaning ....................................................31
Heat Exchanger Inspection ....................................32
Lubrication ............................................................32
Gas Train................................................................................33
Heating Boiler ......................................................................34
Installation Requirements ......................................34
Pump Requirements ..............................................34
Pressure Drop Chart ..............................................34
Boiler Pump Operation ..........................................34
Typical Piping ........................................................35
Bypass Requirements ............................................35
Low Temperature Systems ....................................36
Boiler Flow Rates ..................................................37
Temperature Rise Chart ........................................38
Placing Boiler in Operation ..................................38
Boiler Temperature Control ..................................40
Remote Thermostat Control Connection ............................40
Water Heater/Domestic Hot Water Supply Boiler................40
Water Velocity Control ..........................................41
Temperature Rise....................................................41
Water Chemistry ....................................................42
Piping Requirements ..............................................42
Pump Requirements ..............................................43
Temperature Adjustment ........................................43
Risk of Scald Warnings..........................................44
USER WARNING
IMPORTANT:
Consult and follow local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult your local gas utility company to authorize and inspect all gas and flue connections.
WARNING:
Should overheating occur or the gas supply fail to
shut off, do not turn off or disconnect the electrical
supply to the pump. Instead, shut off the gas
supply at a location external to the appliance.
WARNING:
To minimize the possibility of serious personal injury, fire or damage to your appliance, never violate the following safety rules.
CODES
3
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
2. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.
5. DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.
6. The appliance must be installed on a level, noncombustible floor. A concrete over wood construction is not considered a noncombustible floor. Maintain required clearances from combustible surfaces.
7. The appliance must not be installed on carpet or other combustible material.
8. For installation on a combustible floor only when installed on special base:
Appliances installed over a combustible floor MUST use the Special Combustible Floor Base Kit. The appliance must be centered on the base as shown in Figure 4. The correct part number for the required base kit is noted on the rating plate of each appliance and listed in Table A.
Safety Code for Controls and Safety Devices for Auto­matically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA-B149.1 and/or B149.2 and/or local codes.
This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided as specified in the ANSI standards for gas-fired appliances, ANSI Z21.13.
INSTALLATION PROCEDURE
FIG. 2
Front View
399,000—500,000
Btu Models
Front View
45,000—360,000
Btu Models
FIG. 3
Rear View
45,000—500,000
Btu Models
LOCATION OF UNIT
FIG. 1
4
Clearances from Combustible Construction:
Right Side - 6" Rear - 6" Left Side - 6" (24" suggested for service) Front - (24" suggested for service)
45,000 - 180,000 BTU Models - 6" 199,000 - 500,000 BTU Models - ALCOVE*
Top - (measured from draft hood)
45,000 - 180,000 BTU Models - 14" 199,000 - 500,000 BTU Models - 29"
*An ALCOVE is a closet enclosure without a front door.
Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the appliance.
TABLE - A
COMBUSTIBLE FLOOR BASE KITS
Input BTU/hr Kit Number
45,000 CFK3045
75,000 CFK3090
90,000 CFK3090
135,000 CFK3135
180,000 CFK3180
199,000 CFK3225
225,000 CFK3225
270,000 CFK3270
315,000 CFK3315
360,000 CFK3360
399,000 CFK3399
500,000 CFK3500
CLEARANCES FROM
COMBUSTIBLE CONSTRUCTION
FIG. 4
FIG. 5A
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The mechanical room MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.
COMBUSTION AND VENTILATION
AIR REQUIREMENTS
FOR CONVENTIONALLY
VENTED APPLIANCES
FIG. 5B
Clearances
Models
45,000–180,000
Clearances
Models
199,000–500,000
Combustion Floor Base
29"
6"
6"
6"
14"
5
1. If air is taken directly from outside the building with no duct, provide two permanent openings:
a. Combustion air opening, with a minimum free
area of one square inch per 4000 Btu/hr input (5.5cm
2
per kW). This opening must be located within 12" (30 cm) of the bottom of the enclosure.
b. Ventilation air opening, with a minimum
free area of one square inch per 4000 Btu/hr input (5.5cm
2
per kW). This opening must be located within 12" (30cm) of the top of the enclosure.
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the mechanical room, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11cm
2
per kW).
3. If air is taken from another interior space that is adequately ventilated, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22cm
2
per kW) of input, but not less than 100 square inches (645 cm
2
).
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7cm
2
per kW). This opening must be located within 12" (30cm) of the top of the enclosure.
Combustion Air Direct from Outside
FIG. 6
Combustion Air Through Ducts
Combustion Air from Interior Space
Combustion Air from Outside
Single Opening
FIG. 8
FIG. 7
FIG. 9
6
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above require­ments are for the appliance only, additional gas fired appliances in the mechanical room will require an increase in the net free area to supply adequate combus­tion air for all appliances. Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to National Standard CAN B149.1 or B149.2. Check all local code requirements for combustion air.
All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the mechanical room. Each opening must have net free area as specified in the chart above. Single openings shall be located within 12" (30 cm) of the ceiling.
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the mechanical room may deplete the combustion air supply and/or cause a down draft in the venting system, spilling flue products into the room. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the
TABLE - B
MINIMUM RECOMMENDED COMBUSTION AIR SUPPLY
TO MECHANICAL ROOM
Combustion Air Source
Input Outside Air*/2 Outside Air*/1 Inside Air/2 Btu/hr Openings Openings Openings
45,000 12 in
2
15 in
2
100 in
2
75,000 19 in
2
25 in
2
100 in
2
90,000 23 in
2
30 in
2
100 in
2
135,000 34 in
2
45 in
2
135 in
2
180,000 45 in
2
60 in
2
180 in
2
199,000 50 in
2
67 in
2
200 in
2
225,000 56 in
2
75 in
2
225 in
2
270,000 68 in
2
90 in
2
270 in
2
315,000 79 in
2
105 in
2
315 in
2
360,000 90 in
2
120 in
2
360 in
2
399,000 100 in
2
133 in
2
400 in
2
500,000 125 in
2
167 in
2
500 in
2
CAUTION:
Under no circumstances should the mechanical room ever be under a negative pressure. Particu­lar care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.
7
mechanical room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.
Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable provisions of the local building codes.
Adequate combustion and ventilation air must be supplied to the mechanical room in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The distance of the vent terminal from adjacent buildings, windows that open and building openings MUST comply with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
Vent connection is made directly to the top of the appliance. This appliance is designed with a built-in draft diverter. No additional draft diverter is required. The connection from the appliance vent to the common vent or chimney must be made as direct as possible.
The negative draft in a conventional vent installation must be within the range of a negative 0.02 to 0.05 inches water to insure proper operation. All draft readings are made while the appliance is in stable operation (approximately 2 to 5 minutes).
Multiple appliance installations with combined venting or common venting with other negative draft appliances require that each appliance must have draft within the proper range. If the draft measured above the appliance’s built-in draft hood exceeds the specified range in a dedicated chimney for a single appliance installation or in combined venting with other negative draft appliances, a barometric damper must be installed to control draft.
On a conventionally vented, negative draft appliance, the connection from the vent to the chimney or vent termination on the outside of the building MUST be made with listed Type “B” doublewall (or equivalent) vent connectors and must be direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for doublewall vent to properly size all vent connectors and stacks. The Type “B” vent and accessories, such as firestop spacers, thimbles, caps, etc., MUST be installed in accordance with the manufacturer’s listing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
VENTING
TABLE - C
VENT PIPE SIZES
Input BTU/hr Flue Size
45,000 3"
75,000 5"
90,000 5"
135,000 5"
180,000 6"
199,000 6"
225,000 7"
270,000 7"
315,000 8"
360,000 8"
399,000 10"
500,000 10"
Conventional Negative Draft
Vertical Venting
FIG. 10
A CONVENTIONAL NEGATIVE DRAFT
VENTING SYSTEM
8
Any vent materials used must be listed by a nationally recognized test agency for use as vent material.
Locate appliance as close as possible to chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° elbows, reductions and restrictions. Horizontal portions of the venting system shall be supported to prevent sagging. Horizontal runs must slope upwards not less than 1/4 inch per foot (21 mm/m) from the appliance to the vent terminal. Follow manufacturer’s instructions.
Do not use an existing chimney as a raceway for a flue pipe if another appliance or fireplace is vented through the chimney.
The weight of the venting system must not rest on the appliance. Adequate support of the venting system must be provided in compliance with local codes and other applicable codes. All connections should be secured with rustproof sheet metal screws.
Vent connectors serving appliances vented by natural draft shall not be connected to any portion of a mechanical draft system operating under positive pressure. Connection to a positive pressure chimney may cause flue products to be discharged into the living space causing serious health injury.
Common venting systems may be too large when an existing appliance is removed. At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining connected to the common venting system are not in operation.
(a) Seal any unused opening in the common
venting system.
(b) Visually inspect the venting system for proper
size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors
and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
(d) Place in operation, the appliance being
inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
(e) Test for spillage at the draft hood/relief opening
after five minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each
appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions of use.
(g) Any improper operation of the common venting
system should be corrected so that the installation conforms to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment.
9
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination. The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
The vent cap should have a minimum clearance of 4 feet (1.22m) horizontally from and in no case above or below, unless a 4 foot (1.22m) horizontal distance is maintained from electric meters, gas meters, regulators and relief equipment.
The venting system shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
VENTING TERMINATION
FIG. 11
Vent Termination from Peaked Roof
10’ or Less from Ridge
FIG. 12
Vent Termination from Peaked Roof
More Than 10’ from Ridge
RIDGE
MORE THAN 10'
3' MIN
2' MIN
10'
CHIMNEY
FIG. 13
Vent Termination from Flat Roof
10’ or Less from Parapet Wall
Vent Termination from Flat Roof
More Than 10’ from Parapet Wall
10’ OR LESS
3’
WALL OR PARAPET
CHIMNEY
NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN DISTANCE FROM WALLS OR PARAPETS IS MORE THAN 10’.
FIG. 14
10
The venting system shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building.
Do not terminate the vent in a window well, stairwell, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bottom of the vent terminal shall be located at least 12 inches (30cm) above grade.
To avoid a blocked vent condition, keep the vent cap clear of snow, ice, leaves, debris, etc.
Flue gases will form a white plume in winter. Plume could obstruct window view.
Flue gas condensate can freeze on exterior surfaces or on the vent cap. Frozen condensate on the vent cap can result in a blocked vent condition. Flue gas condensate can cause discoloration of exterior building surfaces. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue gases from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to generate proper draft. This will result in condensing of flue gases, damage the masonry flue/tile, insufficient draft and possible spillage of flue gases into an occupied living space. Carefully inspect all chimney systems before installation. If there is any doubt about the sizing or condition of a masonry chimney, it must be relined with a properly sized and approved chimney liner system.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue gases. A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of condensate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined. An unlined masonry chimney must not be used to vent flue gases from this high efficiency appliance. An unlined chimney must be relined with an approved chimney liner system when a new appliance is being attached to it. Metallic liner systems (Type “B” doublewall, flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
This appliance is NOT approved for sidewall venting with the negative draft venting system as shipped from the factory. An induced draft fan MUST be used if the installation requires that the flue gases be vented out a sidewall. A properly sized and installed induced draft fan may also be used to vent the flue gases vertically if required by jobsite restrictions. The induced draft fan must be listed by a nationally recognized test agency, be properly sized and installed per the recommendations of the induced draft fan manufacturer and meet local code requirements. Use care to ensure that the mechanically supplied draft does not exceed the range of a negative
IMPORTANT:
Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness. Also check for corrosion or deterioration. Immediately correct any problems observed in the venting system.
MASONRY CHIMNEY
INSTALLATION
SIDEWALL VENTING
Sidewall Venting with an
Induced Draft Fan
FIG. 15
11
0.02 to 0.05 inches water to ensure proper operation. If draft exceeds the specified range, the fan must be adjusted or the installation of a barometric damper in the flue may be required to properly control draft. An induced draft fan MUST be interlocked into the appliance’s control circuit to start when the appliance calls for heat. The induced draft fan MUST also be equipped with a proving switch, properly interlocked into the appliance’s control circuit to prove fan operation before the main burners are allowed to fire. A vertical or sidewall vent termination for an induced draft fan MUST be installed per the recommendations of the fan manufacturer and provide proper clearances from any combustion or ventilation openings, windows, doors or other openings into the building. All induced draft fan installations must comply with local code requirements. Consult factory for kits available.
This heating boiler is design certified for use with the automatic vent damper, part number printed on the boiler’s rating plate. A vent damper must be installed on all residential heating boilers with inputs of less than 300,000 Btu/hr to comply with minimum efficiency requirements. A vent damper is factory supplied with residential heating boilers with inputs of 45,000 thru 270,000 Btu/hr. A vent damper is optional on heating boilers with inputs of 315,000 and 360,000 Btu/hr. A vent damper is also available as an option on water heater models with inputs of 90,000 thru 360,000 Btu/hr.
The vent damper is a useful tool for saving energy when installed inside the building envelope where air can circulate freely around the appliance. The vent damper will not save as much, if any, energy if it is installed in locations such as:
- Closet with solid, rather than louvered doors
- Outdoors
-Unheated garage
-Attic
-Crawlspace
-Mechanical room that is vented outdoors
FOR INSTALLATION AND MAINTENANCE ON THE VENT DAMPER, REFER TO THE INSTRUCTIONS SUPPLIED WITH THE VENT DAMPER.
Residential heating boilers with inputs of less than 300,000 Btu/hr must have the vent damper properly installed and the wire harness plugged into the terminal on the side of the control panel to allow the boiler to function. Larger input heating boilers and water heaters will have a plug installed in the damper terminal to allow operation without a damper. Remove damper plug from terminal to connect an optional vent damper wire harness. Damper plug MUST be in place if an optional vent damper is not used on water heaters and larger input heating boilers.
Install the vent damper to service only the single appliance for which it is intended. If improperly installed, a hazardous condition such as an explosion or carbon monoxide poisoning could result.
The damper position indicator must be in a visible location with access for service following installation. The damper must be in open position when appliance main burners are operating.
THE PART NUMBER FOR THE AUTOMATIC VENT DAMPER REQUIRED ON THIS HEATING BOILER IS PRINTED ON THE RATING PLATE. DAMPER REGULATIONS PER THE LATEST EDITION OF ANSI Z21.66.
AUTOMATIC VENT DAMPER
FIG. 16
CAUTION:
Do not install the vent damper within 6" (152 mm) of combustible materials.
Automatic Vent Damper
12
.
Verify that the appliance is supplied with the type gas specified on the rating plate. This appliance is orificed for operation up to 2000 feet altitude. The appliance will be derated 4% per 1000 feet above 2000 feet elevation. Consult the factory for installations above 2000 feet elevation. Field conversions for operation at high altitude must be performed by factory authorized personnel only. The appliance will be marked to indicate suitability for high altitude operation.
INLET PRESSURE: Measured at the inlet pressure tap located upstream of the combination gas valve(s).
Nat. Gas LPG
Max.(Inches-Water Column) 10.5"w.c. 13"w.c. Min. (Inches-Water column) 5"w.c. 11"w.c.
Maximum inlet gas pressure must not exceed the value specified. Minimum value listed is for the purposes of input adjustment.
MANIFOLD PRESSURE: Measured at the pressure tap on the downstream side of the combination gas valve(s). The gas regulator on the appliance’s combination gas valve(s) is adjustable to supply proper manifold pressure for normal operation. If adjustment of regulator pressure is required, see Manifold Adjustment Procedure. Do not increase regulator pressure
beyond specified pressure setting.
1. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5kPa).
2. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5kPa).
3. The appliance and its gas connection must be leak-tested before placing it in operation.
FIG. 17
CAUTION:
An appliance which is shut down or will not operate may experience freezing due to convective air flow down the flue pipe connected to the unit. Proper freeze protection must be provided, see Freeze Protection Section.
Vent damper must be installed directly on the flue outlet located on the top of the draft hood (see Figure
17). Do not alter the wire harness supplied with the vent damper. Follow the instructions supplied with the vent damper.
WARNING:
GAS SUPPLY
TABLE - D
SUPPLY PRESSURE
GAS PRESSURE TEST
TABLE - E
MANIFOLD PRESSURE
BTU/hr Regulator Settings
Input Gas Natural Gas L.P.
45,000 3.5" 10"
75,000 2.3" 6.9"
90,000 - 180,000 3.5" 10"
199,000 2.7" 7.7"
225,000 - 500,000 3.5" 10"
13
1. Safe operation of the appliance requires properly sized gas supply piping. See data in Table F.
2. Gas pipe size may be larger than appliance gas connection.
3. Installation of a union is suggested for ease of service.
4. Install a manual main gas shutoff valve, outside of the appliance gas connection and before the gas valve or manifold connection, when local codes require.
5. A trap (drip leg) MUST be provided in the inlet of the gas connection to the appliance.
6. The combination gas valve has an integral vent limiting device and does not require venting to atmosphere, outside the building.
7. Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.
GAS CONNECTION
TABLE - F
SUGGESTED GAS PIPE SIZE
SINGLE APPLIANCE INSTALLATIONS
Btu/hr DISTANCE FROM METER
INPUT 0-50' 51'-100' 101'-200' 201'-300' 301'-500'
45,000 1/2" 1/2" 3/4" 1" 1 1/4" 75,000 1/2" 3/4" 1" 1 1/4" 1 1/4"
90,000 1/2" 3/4" 1" 1 1/4" 1 1/4" 135,000 3/4" 1" 1 1/4" 1 1/4" 1 1/2" 180,000 1" 1" 1 1/4" 1 1/2" 1 1/2" 199,000 1" 1" 1 1/4" 1 1/2" 2" 225,000 1" 1 1/4" 1 1/4" 1 1/2" 2" 270,000 1" 1 1/4" 1 1/4" 1 1/2" 2" 315,000 1 1/4" 1 1/2" 1 1/2" 1 1/2" 2" 360,000 1 1/4" 1 1/2" 2" 2" 2 1/2" 399,000 1 1/4" 1 1/2" 2" 2" 2 1/2" 500,000 1 1/4" 1 1/2" 2" 2" 2 1/2"
For each elbow or tee, add equivalent straight pipe to total length from Table G.
TABLE - G
FITTINGS TO EQUIVALENT
STRAIGHT PIPE
Diameter Pipe (inches) 3/4" 1" 1 1/4" 1 1/2" 2" 3" 4" 5"
Equivalent length of Straight Pipe (feet)
2' 2' 3' 4' 5' 10' 14' 20'
14
All gas connections must be made with pipe joint compound resistant to the action of liquefied petroleum and natural gas. All piping must comply with local codes. Tubing installations must comply with approved standards and practices.
Install Piping to Control
1. The gas line should be a separate line direct from the meter unless the existing gas line is of sufficient capacity. Verify pipe size with your gas supplier.
2. Use new, properly threaded black iron pipe free from chips. If tubing is used, make sure the ends are cut squared, deburred and clean. All tubing bends must be smooth and without deformation. Avoid flexible gas connections. Internal diameter of flexible lines may not provide proper volume of gas.
3. Run pipe or tubing to the gas valve or manifold inlet. If tubing is used, obtain a tube to pipe coupling to connect the tubing to the gas valve or manifold inlet.
TABLE- H
MULTIPLE APPLIANCE INSTALLATIONS
GAS PIPING SIZE CHART
Length of Pipe in Straight Feet
10 20 30 40 50 60 70 80 90 100 125 150 175 200
3/4 369 256 205 174 155 141 128 121 113 106 95 86 79 74
1 697 477 384 328 292 267 246 226 210 200 179 164 149 138
1 1/4 1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
1 1/2 2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
2 4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
2 1/2 6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3 11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4 23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Nominal Iron Pipe Size, Inches
Maximum Capacity of Pipe in Thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a pressure drop of 0.5 Inch Water Column (Based on the calorific value of Natural Gas, 1025
Btu/ft
3
@ 0.60 Specific Gravity)
GAS PIPING
FIG. 18
Gas Line Connection
Gas Cock
Sediment
Trap
15
4. Install a sediment trap in the supply line to the gas valve or manifold assembly (see Figure 18).
5. Thread pipe the proper amount for insertion into gas valve or manifold inlet as shown in Table-I. DO NOT THREAD PIPE TOO FAR. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas valve.
TABLE - I
LENGTH OF STANDARD
NPT PIPE THREADS (Inches)
Pipe Size Effective Length of Thread Overall Length of Thread
1/2" 1/2" 3/4"
3/4" 9/16" 13/16"
1" 9/16" 1"
6. Apply a moderate amount of good quality pipe compound (DO NOT use Teflon tape) to pipe only, leaving two end threads bare.
7. Remove seal over gas valve or manifold inlet.
8. Connect pipe to gas valve or manifold inlet. Use wrench to square ends of the gas valve.
9. For L.P. gas, consult your L.P. gas supplier for expert installation.
1. Turn the power “OFF” at the main disconnect switch.
2. Turn gas valve control knob to “PILOT” position on standing pilot models. Ensure that the standing pilot remains on. If the pilot goes out, follow the “Lighting Instructions” for standing pilot models to light the pilot. Turn gas valve control knob to “OFF” position on spark ignition models.
3. Remove the 1/8" hex plug located on the outlet side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. See Figure 20. Minimum range of scale should be up to 5" w.c. for Natural gas models and 10" w.c. for L.P. gas models.
4. The 399,000 and 500,000 Btu/hr models will have two gas valves with a pressure regulator on each valve. Repeat the following adjustment procedure to set the manifold pressure on each gas valve. The manifold pressure for each valve should set at 3.5" w.c. for Natural gas and 10" w.c. for L.P. gas.
5. Remove the pressure regulator adjustment cap screw on the gas valve. See Figures 26, 27 and 28 for location.
6. Turn the power “ON” at the main disconnect switch.
IMPORTANT:
Upon completion of any piping connections to the gas system, leak test all gas connections with a soap solution while system is under pressure. Immediately repair any leak found in the gas train or related
components.
Do Not operate an appliance with a
leak in the gas train, valves or related piping.
GAS MANIFOLD PRESSURE
ADJUSTMENT PROCEDURE
APPLY WRENCH FROM TOP OR BOTTOM OF CONTROL TO EITHER SHADED AREA
FIG. 19
Gas Valve
FIG.20
Manifold Pressure Adjustment
Loading...
+ 33 hidden pages