Lochinvar 45, 000 - 260, 000 Btu-hr User Manual

Installation & Service Manual
Models: 45,000 - 260,000 Btu/hr
This manual supplies information for the installation, operation, and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
SBR-I-S Rev A
2
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
WARNING
CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Contents
HAZARD DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PLEASE READ BEFORE PROCEEDING . . . . . . . . . . . . 3-4
RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
THE SOLUTION --HOW IT WORKS . . . . . . . . . . . . . . . . . . . 6-8
1. DETERMINE BOILER LOCATION
Location of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . . . 10-12
2. VENTING
A Conventional Negative Draft Venting System . . . . . . . 13-14
Vertical Vent Termination Clearances . . . . . . . . . . . . . . . 15
Masonry Chimney Installation . . . . . . . . . . . . . . . . . . . . . 16
Inspection of a Masonry Chimney . . . . . . . . . . . . . . . 16
Automatic Vent Damper . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3. GAS CONNECTIONS
Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas Pressure Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gas Manifold Pressure Adjustment Procedure . . . . . . . . 20
Checking Gas Supply Pressure . . . . . . . . . . . . . . . . . . . 21
Combination Gas Valves . . . . . . . . . . . . . . . . . . . . . . . . . 22
4. WATER CONNECTIONS
Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Water Flow Switch (if equipped) . . . . . . . . . . . . . . . . . . . 23
Low Water Cutoff (if equipped) . . . . . . . . . . . . . . . . . . . . 24
Typical Heating Boiler Installations . . . . . . . . . . . . . . . . . 24-25
Piping of the Boiler System . . . . . . . . . . . . . . . . . . . . . . . 25
Performance Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Primary/Secondary Boiler Piping . . . . . . . . . . . . . . . . . . . 27-28
Low Temperature Bypass Requirements . . . . . . . . . . . . . 28
Boiler Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Primary / Secondary Piping . . . . . . . . . . . . . . . . . . . . 29-31
Full System Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-33
5. ELECTRICAL CONNECTIONS
Boiler Operating Temperature Control . . . . . . . . . . . . . . . 34
Room Thermostat or Remote Thermostat Connection . . 34
Auxiliary Device Connection to Terminal Strip . . . . . . . . . 34
Pump Wiring for a Heating Boiler . . . . . . . . . . . . . . . . . . 35
Temperature Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 35
Temperature Control Settings . . . . . . . . . . . . . . . . . . . . . 35
Maximum Set Point Determination . . . . . . . . . . . . . . . . . 36
Outdoor Air Reset Option . . . . . . . . . . . . . . . . . . . . . . . . 38
Additional Temperature Controls . . . . . . . . . . . . . . . . . . . 38
Blocked Vent and Flame Roll-Out / Flame Interlock Switch . 39
6. STARTUP
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Lighting Instructions for Spark Ignition Pilot Models (M9) . . . . 40
Safety Shutoff Test for Spark Ignition Pilot System . . . . . . 41
Intermittent Pilot Spark Ignition System (M9) . . . . . . . . . . . . 42
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7. MAINTENANCE
Maintenance and Annual Startup . . . . . . . . . . . . . . . . . . 43-48
8. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 49
9. DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3
Installation & Service Manual
Please read before proceeding
NOTICE
This is a gas appliance and should be installed by a licensed electrician and/or certified gas supplier. Service must be performed by a qualified service installer, service agency or the gas supplier.
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
What to do if you smell gas –
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Warranty –
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Experience has shown that improper installation or system design, rather than faulty equipment, is the cause of most operating problems.
1. Excessive water hardness causing a lime/scale build-up in the copper tube is not the fault of the equipment and is not covered under the manufacturer’s warranty (see Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper tube may be caused by too much water velocity through the tubes and is not covered by the manufacturer’s warranty (see Boiler Flow Rates and Temperature Rise for flow requirements).
Checking equipment –
Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the appliances which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on the packing slip with those actually received. In case there is damage or a shortage, immediately notify the carrier.
Do not use this appliance if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in severe personal injury, death, or substantial property damage. Refer to this manual for assistance or additional information, consult a qualified installer, service agency or the gas supplier.
Owner warning –
NOTE: Retain this manual for future reference.
The information contained in this manual is intended for use by qualified professional installers, service technicians, or gas suppliers. Consult your local expert for proper installation or
service procedures.
IMPORTANT
Consult and follow all local Building and Fire Regulations and other Safety Codes that apply to this installation. Consult your local gas utility company to authorize and inspect all gas and flue connections.
Your conventionally vented gas appliance must have a supply of fresh air circulating around it during burner operation for proper gas combustion and proper venting.
WARNING
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
4
Installation & Service Manual
Please read before proceeding
WARNING
To minimize the possibility of serious personal injury, fire, or damage to your appliance, never violate the following safety rules:
1. Boilers are heat producing appliances. To avoid damage or injury, do not store materials against the appliance or the vent-air intake system. Use proper care to avoid unnecessary contact (especially children) with the appliance and vent-air intake components.
2. Never cover your appliance, lean anything against it, store trash or debris near it, stand on it or in any way block the flow of fresh air to your appliance.
3. UNDER NO CIRCUMSTANCES must flammable materials such as gasoline or paint thinner be used or stored in the vicinity of this appliance, vent-air intake system or any location from which fumes could reach the appliance or vent-air intake system.
Codes –
The equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made. In the absence of such requirements, the installation shall conform to the latest edition of the National Fuel Gas Code, ANSI Z223.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. All boilers conform to the latest edition of the ASME Boiler and Pressure Vessel Code, Section IV. Where required by the authority having jurisdiction, the installation must comply with the Canadian Association Code, CAN/CGA­B149.1 and/or B149.2 and/or local codes.
This appliance meets the safe lighting performance criteria with the gas manifold and control assembly provided as specified in the ANSI standards for gas-fired appliances, ANSI Z21.13 and ANSI Z21.10.3.
5
Ratings
Notes:
1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.
3. Use only the vent materials and methods specified in the Installation and Service Manual.
4. The Solution is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation.
5. Ratings have been confirmed by the Hydronics Institute, Section of AHRI.
Maximum allowed working pressure is located on the rating plate.
NOTICE
Installation & Service Manual
Solution Boiler
I=B=R Rating
Model Number
Note: Change “N” to
“L” for L.P. gas models.
Input MBH
(Note 4)
Min Max
Gross
Output
MBH
(Note 1,5)
Net
I=B=R
Ratings
Water,
MBH
(Note 1,5)
CBN045 23 45 37 32
CBN075 38 75 62 54
CBN090 45 90 75 65
CBN135 68 135 112 97
CBN180 90 180 149 130
CBN215 108 215 178 155
CBN260 130 260 216 188
Other Specifications
Boiler Water
Content Gallons
Water
Connections
Gas
Connections
Vent
Size
(Note 3)
0.87 1 1/2" 1/2" 4"
0.91 1 1/2" 1/2" 5"
0.91 1 1/2" 1/2" 5"
0.95 1 1/2" 1/2" 6"
0.99 1 1/2" 3/4" 7"
1.02 1 1/2" 3/4" 7"
1.06 2" 3/4" 8"
Figure A High Altitude Label Location
UNIT EQUIPPED FOR
HIGH ALTITUDE
UP TO 2000 FT.
The Solution - How it works...
1. Control panel cover
The control panel cover provides access to the thermostat, ignition module, and transformer.
2. Burner (not shown)
The burner is a cylindrical stainless steel tube used to regulate burner flame.
3. Drain port
Location from which the heat exchanger can be drained.
4. Flue outlet
The flue outlet allows the connection of the vent pipe to the unit.
5. Gas connection
The gas pipe connection on this appliance is 1/2", or 3/4" NPT. To deliver the correct amount of gas volume to the appliance it may be necessary to have a larger gas line reduced at the appliance. Please reference the National Fuel Gas Code charts for more details.
6. Gas valve
The gas valve allows the proper amount of gas to pass into the burner for combustion.
7. Heat exchanger
The heat exchanger allows system water to flow through specially designed tubes for maximum heat transfer. The glass lined headers and copper finned tubing are encased in a jacket that contains the combustion process.
8. High limit sensor
Device that monitors the outlet water temperature to ensure safe operation. If the temperature exceeds its setting, it will break the control circuit, shutting the appliance down.
9. Ignition module
The ignition module responds to a call for heat signal to provide burner operation.
10. Junction box
The junction box contains the connection points for the line voltage power and all pumps.
11. Performance loop
A pumped bypass provides constant flow through the heat exchanger when the building system flow is reduced.
12. Performance Loop Pump
The pump ensures adequate flow to operate the unit.
13. Pilot (not shown)
The pilot is a spark ignition device used to light a pilot flame which in turn is used to light the main burners.
14. Pump relay
The pump relay energizes the pump on a call for heat.
15. Relief valve
The relief valve is a safety device that ensures the maximum pressure of the appliance is not exceeded.
16. Sight Glass
The sight glass provides a view of the burner surface, burner flame, and the pilot flame.
17. Temperature and pressure gauge
The temperature and pressure gauge monitors the outlet temperature of the appliance as well as the system water pressure.
18. Temperature sensor
This sensor monitors inlet water temperature. If selected as the controlling sensor, the appliance will maintain the setpoint at this sensor.
19. Terminal strip
The boiler is equipped with a terminal strip on the left side of the unit to allow easy connection to contact points.
20. Top panel
Removable panel to gain access to the internal components.
21. Thermostat
The thermostat monitors the water temperature via a temperature sensor and will initiate a call for heat when the water temperature drops below the setpoint plus the differential on the thermostat.
22. Transformer
The transformer reduces 120 VAC supply voltage to 24 VAC for the control circuit.
23. Water inlet (system return)
The water inlet is a 1 1/2" pipe connection that receives water from the system and delivers it to the heat exchanger.
24. Water outlet (system supply)
The water outlet is a 1 1/2" pipe connection that supplies water to the system with connections for a flow switch, a relief valve, and a temperature and pressure gauge.
25. Gas manifold pipe
Delivers gas from the gas valve to the main burners through a number of orifices.
Installation & Service Manual
6
Models 45,000 - 90,000 Btu/hr Front View
Models 45,000 - 90,000 Left Side (inside unit)
Models 45,000 - 90,000 Right Side (inside unit)
Models 45,000 - 90,000 Rear View
The Solution - How it works... (continued)
Installation & Service Manual
7
10
17
15
8
3
5
4
20
1
19
23
11
14
16
25
22
21
7
18
9
12
6
24
8
Installation & Service Manual
The Solution - How it works...
Models 135,000 - 260,000 Btu/hr Left Side (inside unit)
Models 135,000 - 260,000 Btu/hr Right Side (inside unit)
Models 135,000 - 260,000 Btu/hr Rear View
Models 135,000 - 260,000 Btu/hr Front View
3
3
7
18
12
24
6
10
17
15
8
3
5
4
1
19
20
11
23
14
21
25
22
9
Installation & Service Manual
1 Determine boiler location
NOTICE
Clearances from combustible construction are noted on the appliance rating plate.
Location of unit
1. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict combustion air flow. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
2. The appliance must be installed indoors where it is protected from exposure to wind, rain and weather.
3. The appliance must be installed so that the ignition system components are protected from water (dripping, spraying, rain, etc.,) during appliance operation and service (circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent spaces that open to the garage and are not part of the living space of a dwelling unit must be installed so that all burners and burner ignition devices have a minimum clearance of not less than 18" (46cm) above the floor. The appliance must be located or protected so that it is not subject to physical damage by a moving vehicle.
5. DO NOT install this appliance in any location where gasoline or flammable vapors are likely to be present.
6. All units have been approved for alcove installation (an ALCOVE is a closet enclosure without a front door).
7. The appliance must not be installed on carpet.
8. All units have been approved for use on combustible surfaces.
9. Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the appliance.
Figure 1-1_Alcove Installation - Models 45,000 ­180,000 Btu/hr
Figure 1-2_Alcove Installation - Models 215,000 ­260,000 Btu/hr
9
Recommended Service Clearances:
Left - 24” Front - 24”
14" TOP
6 " RIGHT
6 " REAR
18 " FRONT
18 " LEFT
Recommended Service Clearances:
Left - 24” Front - 24”
29" TOP
6 " RIGHT
6 " REAR
18 " FRONT
18 " LEFT
Installation & Service Manual
10
Figure 1-3_Combustion Air Direct from Outside
Combustion and ventilation air requirements for conventionally vented appliances
Provisions for combustion and ventilation air must be in accordance with, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The room where the appliance is installed MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.
1. If air is taken directly from outside the building with no duct, provide two permanent openings (see FIG. 1-3):
(a) Combustion air opening, with a minimum free
area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be
located within 12" (30 cm) of the floor.
(b) Ventilation air opening, with a minimum free
area of one square inch per 4000 Btu/hr input (5.5 cm
2
per kW). This opening must be
located within 12" (30 cm) of the ceiling.
Figure 1-4_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the room where the appliance is installed, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11cm
2
per kW) (see FIG. 1-4).
Figure 1-5_Combustion Air from Interior Space
3. If air is taken from another interior space that is adequately
ventilated, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22cm
2
per kW) of input, but not less than 100 square
inches (645cm2) (see FIG. 1-5).
1 Determine boiler location
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm
2
per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-6).
Figure 1-6_Combustion Air from Outside Single Opening
Combustion air require ments are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to National Standard CAN B149.1. Check all local code re quire ments for combustion air.
All dimensions are based on net free area in square inch es. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are pro vid ed, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the room where the appliance is installed. Each opening must have a net free area as specified in Table 1B (on page 12). Single openings shall be located with in 12" (30 cm) of the ceiling.
CAUTION
Under no circumstances should the room where the appliance is installed ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the appliance.
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as freon, tricholorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure.
The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the equipment room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.
Installation & Service Manual
11
1 Determine boiler location (continued)
Installation & Service Manual
12
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
Input
Btu/hr
*Outside Air from
2 Openings Directly from
Outdoors
*Outside Air from 1 Opening Directly from Outdoors, in
2
*Outside Air from
2 Ducts Delivered from
Outdoors
**Inside Air from
2 Ducts Delivered from
Interior Space
To p
Opening, in
2
Bottom
Opening, in
2
To p
Opening, in
2
Bottom
Opening, in
2
To p
Opening, in
2
Bottom
Opening, in
2
45,000
12
(78 cm2)
12
(78 cm2)
15
(97 cm2)
23
(149 cm2)
23
(149 cm2)
100
(646 cm2)
100
(646 cm2)
75,000
19
(123 cm2)
19
(123 cm2)
25
(162 cm2)
38
(246 cm2)
38
(246 cm2)
100
(646 cm2)
100
(646 cm2)
90,000
23
(148 cm2)
23
(148 cm2)
30
(194 cm2)
45
(291 cm2)
45
(291 cm2)
100
(646 cm2)
100
(646 cm2)
135,000
34
(220 cm2)
34
(220 cm2)
45
(291 cm2)
68
(439 cm2)
68
(439 cm2)
135
(871 cm2)
135
(871 cm2)
180,000
45
(291 cm
2
)
45
(291 cm
2
)
60
(388 cm
2
)
90
(581 cm
2
)
90
(581 cm
2
)
180
(1,162 cm
2
)
180
(1,162 cm
2
)
215,000
54
(349 cm2)
54
(349 cm2)
72
(465 cm2)
108
(697 cm2)
108
(697 cm2)
215
(1,388 cm2)
215
(1,388 cm2)
260,000
65
(420 cm2)
65
(420 cm2)
87
(562 cm2)
130
(839 cm2)
130
(839 cm2)
260
(1,678 cm2)
260
(1,678 cm2)
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.
*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).
The distance of the vent terminal from adjacent build ings, windows that open and building open ings MUST comply with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 In stal la tion Code for Gas Burn ing Appliances and Equip ­ment.
Vent connection is made directly to the top of the ap pli ance. This appliance is designed with a built-in draft diverter. No additional external draft hood is re quired. The connection from the appliance vent to the common vent or chimney must be made as direct as possible.
Vent installations for connection to gas vents or chimneys must be in accordance with “Vent ing of Equipment,” of the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1, in Canada, the latest edi tion of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable pro vi sions of the local building codes.
Adequate combustion and ventilation air must be sup plied to the room where the appliance is installed in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Stan dard B149 Installation Code for Gas Burning Ap pli anc es and Equipment, or applicable pro vi sions of the local building codes.
1 Determine boiler location
Installation & Service Manual
13
2 Venting
A Conventional Negative Draft Venting System
The negative draft in a conventional vent in stal la tion must be within the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. All draft read ings are made while the appliance is in stable op er a tion (approximately 2 to 5 minutes).
Multiple appliance installations with combined vent ing or common venting with other negative draft ap pli anc es require that each appliance must have draft with in the proper range. If the draft mea sured above the appliance’s built-in draft diverter ex ceeds the specified range in a dedicated chimney for a single appliance installation or in combined venting with other negative draft appliances, a baro met ric damper must be
in stalled to control draft.
Figure 2-1_Conventional Negative Draft Vertical Venting
TABLE - 2A
VENT PIPE SIZES
Input Btu/hr Flue Size
45,000 4"
75,000 5"
90,000 5"
135,000 6"
180,000 7"
215,000 7"
260,000 8"
On a conventionally vented, negative draft ap pli ance, the connection from the vent to the chimney or vent termination on the outside of the building MUST be made with listed Type “B” double wall (or equivalent) vent connectors and must be direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for dou ble wall vent to properly size all vent connectors and stacks. The Type “B” vent and accessories, such as firestop spacers, thim bles, caps, etc., MUST be installed in accordance with the manufacturer’s list ing. The vent connector and firestop must provide correct spacing to combustible surfaces and seal to the vent connector on the upper and lower sides of each floor or ceiling through which the vent connector passes.
Any vent materials used must be listed by a na tion al ly recognized test agency for use as vent ma te ri al.
Locate appliance as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° el bows, reductions and restrictions. Horizontal por tions of the venting system shall be supported to prevent sagging. Horizontal runs must slope up wards not less than 1/4 inch per foot (21 mm/m) from the appliance to the vent terminal. Follow manufacturer’s instructions.
Do not use an existing chimney as a raceway for a flue pipe if another appliance or fireplace is vented through the chimney.
The weight of the venting system must not rest on the appliance. Adequate support of the venting sys tem must be provided in compliance with local codes and other applicable codes. All connections should be secured with rustproof sheet metal screws.
Vent connectors serving appliances vented by nat u ral draft shall not be connected to any portion of a me chan i cal draft system operating under positive pres sure. Connection to a positive pressure chim ney may cause flue products to be discharged into the living space causing serious health injury.
Common venting systems may be too large when an existing appliance is removed. At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while other appliances remaining con nect ed to the common venting system are not in operation.
(a) Seal any unused opening in the common venting
system.
(b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
(c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer ex haust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
(e) Test for spillage at the draft hood/relief opening after 5
minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning ap pli anc es to their previous conditions of use.
(g) Any improper operation of the common venting
system should be corrected so that the installation conforms to the latest edition of the Na tion al Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment. When resizing any por ­tion of the common venting system, the common venting system should be resized to ap proach the min ­i mum size as determined using the appropriate tables in Part 11 in the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the latest edition of CGA Stan dard B149 Installation Code for Gas Burning Appliances and Equipment.
Installation & Service Manual
2 Venting
14
Vertical Vent Termination Clearances
Figure 2-2_Vent Termination from Peaked Roof 10' or Less from Ridge
Figure 2-4_Vent Termination from Flat Roof 10' or Less from Parapet Wall
Figure 2-3_Vent Termination from Peaked Roof More than 10' from Ridge
Figure 2-5_Vent Termination from Flat Roof More Than 10' from Parapet Wall
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the high est point of the roof within a 10 foot (3.05m) radius of the termination. The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.
A vertical terminal less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.
The vent cap should have a minimum clearance of 4 feet (1.22m) horizontally from and in no case above or below, unless a 4 foot (1.22m) horizontal distance is maintained from electric meters, gas meters, reg u la tors and relief equipment.
The venting system shall terminate at least 3 feet (0.9m) above any forced air inlet within 10 feet (3.05m).
The venting system shall terminate at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (30cm) above any door, window or gravity air inlet into any building.
Do not terminate the vent in a window well, stair well, alcove, courtyard or other recessed area. The vent can not terminate below grade. The bot tom of the vent terminal shall be located at least 12 inches (30cm) above grade.
To avoid a blocked vent condition, keep the vent cap clear of snow, ice, leaves, debris, etc.
Flue gases will form a white plume in winter. Plume could obstruct window view.
Flue gas condensate can freeze on exterior sur fac es or on the vent cap. Frozen condensate on the vent cap can result in a blocked vent condition. Flue gas condensate can cause discoloration of exterior build ing surfaces. Adjacent brick or masonry sur fac es should be protected with a rust resistant sheet metal plate.
NOTICE
Examine the venting system at least once a year. Check all joints and vent pipe con nec tions for tightness. Also check for corrosion or de te ri o ra tion. Immediately correct any problems ob served in the venting system.
2' MIN
10' OR LESS
3' MIN
CHIMNEY
RIDGE
Installation & Service Manual
15
2 Venting (continued)
10' OR LESS
10' OR LESS
MORE THAN 10'
10'
2' MIN
RIDGE
CHIMNEY
3' MIN
2' MIN
CHIMMEY
WALL OR PARAPET
2' MIN
3' MIN
CHIMMEY
10' OR MORE
3'
NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN DISTANCE FROM WALLS OR PARAPETS IS MORE THAN 10'.
WALL OR PARAPET
CHIMNEY
Installation & Service Manual
16
Masonry Chimney Installation
A masonry chimney must be properly sized for the installation of a gas fired appliance. Venting of an appliance into a cold or oversized masonry chimney can result in op er a tion al and safety problems. Exterior masonry chim neys, with one or more sides exposed to cold out door tem per a tures, are more likely to have venting problems. The temperature of the flue gases from an appliance may not be able to suf fi cient ly heat the ma son ry structure of the chim ney to generate proper draft. This will result in condensing of flue gases, damage the masonry flue/tile, insufficient draft and possible spill age of flue gases into an occupied living space. Care ful ly in spect all chimney systems before installation. If there is any doubt about the sizing or condition of a masonry chimney, it must be relined with a prop er ly sized and approved chimney liner system.
Inspection of a Masonry Chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue gas es. A clay tile lined chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any signs of con den sate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must be relined. An unlined masonry chimney must not be used to vent flue gases from this appliance. An unlined chimney must be relined with an approved chimney liner system when a new appliance is be ing attached to it. Metallic liner systems (Type “B” double wall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Sidewall Venting - Negative Draft
Figure 2-6_Unit with Fan Assisted Venting
The in duced draft fan MUST also be equipped with a prov ing switch, properly interlocked into the ap pli ance’s con trol circuit to prove fan operation before the main burn ers are allowed to fire. A vertical or sidewall vent termination for an induced draft fan MUST be in stalled per the recommendations of the fan manufacturer and provide proper clearances from any combustion or ventilation openings, win dows, doors or other open ings into the building. All induced draft fan in stal la tions must comply with local code requirements.
Fan Assisted Venting
A Power Venter Kit is available on Models 45,000 - 135,000 Btu/hr only (see Table 2B).
TABLE - 2B
VENT MATERIALS
Kit
Number
Input
Btu/hr
Material
KIT3103
45,000 PVC Rated (CPVC Optional)
75,000 PVC Rated (CPVC Optional)
KIT3104
90,000 CPVC Rated
135,000 CPVC Rated
Minimum Vent Length = 12 Equivalent Feet*
(ALL UNITS)
Maximum Vent Length = 25 Equivalent Feet*
(ALL UNITS)
* Equivalent Feet: 90° Elbow = 5 Feet
45° Elbow = 3 Feet
2 Venting
This appliance is NOT approved for sidewall venting with the negative draft venting system as shipped from the factory. An induced draft fan MUST be used if the installation requires that the flue gases be vented out a sidewall unless a power venter is used, see Fan Assisted Venting. A properly sized and in stalled induced draft fan may also be used to vent the flue gases ver ti cal ly if required by jobsite re stric tions. The induced draft fan must be listed by a nationally recognized test agency, be properly sized and installed per the rec om men da tions of the in duced draft fan manufacturer and meet local code requirements. Use care to ensure that the me chan i cal ly supplied draft does not exceed the range of a negative 0.02 to 0.05 inches water column to ensure proper operation. If draft exceeds the spec i fied range, the fan must be adjusted or the installation of a baro met ric damper in the flue may be required to prop er ly control draft. An induced draft fan MUST be interlocked into the appliance’s control circuit to start when the appliance calls for heat.
Installation & Service Manual
17
The vent damper is a useful tool for saving energy when installed inside the living space where air can cir cu late freely around the appliance. The vent damper will not save as much, if any, energy if it is installed in locations such as:
- Unheated garage
- Attic
- Crawlspace
- Mechanical room that is vented outdoors
For installation and maintenance on the vent damper, refer to the instructions supplied with the vent damper.
Residential heating boilers with inputs of less than 300,000 Btu/hr must have the vent damper prop er ly installed and the vent damper wire harness plugged into the ter mi nal block on the side of the control panel to allow the boiler to function. Larger input heating boilers will have a jumper plug installed in the ter mi nal block to allow operation without a damper. Remove the jumper plug from the terminal block to connect an optional vent damper wire harness. The jumper plug MUST be in place if an optional vent damper is not used on larger input heating boilers.
CAUTION
Do not install the vent damper within 6" (152 mm) of combustible materials.
Install the vent damper to service only the single ap pli ance for which it is intended. If improperly installed, a hazardous condition such as an ex plo sion or carbon monoxide poisoning could result.
The damper position indicator must be in a visible lo ca tion with access for service following in stal la tion. The damper must be in an open position when appliance main burners are operating.
The part number for the automatic vent damper required on this heating boiler is printed on the rating plate. Vent damper regulations are design certified per the latest edition of ANSI Z21.66.
VENT DAMPER
Figure 2-7_Vent Damper and Vent Damper Terminal Block
WARNING
The vent damper must be installed directly on the flue outlet located on the top of the draft hood (see FIG. 2-7). Do not alter the wire har ness sup plied with the vent damper. Follow the instructions supplied with the vent damper.
CAUTION
An appliance which is shut down or will not operate may experience freezing due to con vec tive air flow down the flue pipe connected to the unit. Proper freeze protection must be pro vid ed, see Freeze Pro tec tion.
Automatic Vent Damper
This heating boiler is design certified for use with the automatic vent damper (FIG. 15) part number printed on the boiler’s rating plate. A vent damper must be installed on all residential heating boilers with inputs of less than 300,000 Btu/hr to comply with minimum efficiency requirements. A vent damper is factory supplied with residential heating boilers with inputs of 45,000 thru 260,000 Btu/hr.
2 Venting (continued)
18
3 Gas connections
Installation & Service Manual
Gas Supply
Verify that the appliance is supplied with the type gas spec i fied on the rating plate. This appliance is orificed for operation up to 2000 feet altitude. The ap pli ance will be derated 4% per 1000 feet above 2000 feet el e va tion. Consult the factory for installations above 2000 feet elevation. Field conversions for operation at high altitude must be performed by certified per son nel only. The appliance will be marked to indicate suitability for high al ti tude operation.
GAS SUPPLY PRESSURE: Measured at the inlet pres sure tap located upstream of the combination gas valve(s) see FIG. 3-5, page 22.
TABLE - 3A
GAS SUPPLY PRESSURE
Max. (Inches Water Column)
Natural Gas LP Gas
14 14
Min. (Inches Water Column) 4.5 11
Maximum inlet gas pressure must not exceed the val ue specified. Minimum value listed is for the purposes of input adjustment.
MANIFOLD PRESSURE: Measured at the pres sure tap on the downstream side of the com bi na tion gas valve(s) (see FIG. 3-5, page 22). The gas regulator settings for single stage and two stage operation are factory set to supply proper manifold pressure for normal operation. To check manifold pressure, see Manifold Ad just ment Procedure. Do not increase manifold pressure beyond spec i fied pressure settings shown below in Table 3B.
TABLE - 3B
MANIFOLD PRESSURE
Input Gas
Btu/hr
Single and Two-Stage
Two Stage
Full or High Fire
Settings
Low Fire Settings
Natural
Gas
LP Gas
Natural
Gas
LP Gas
45,000 3.5" 10" 0.9" 2.5"
75,000 2.4" 7" 0.9" 2.5"
90,000 - 180,000 3.5" 10" 0.9" 2.5"
215,000 - 260,000 3.5" 10" 0.9" 2.5"
Gas Pressure Test
1. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5kPa).
2. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5kPa).
3. The appliance and its gas connection must be leak-tested before placing it in operation.
Gas Connection
1. Safe operation of the appliance requires properly sized gas supply piping. See data in Table 3C.
2. Gas pipe size may be larger than appliance gas connection.
3. Installation of a union is suggested for ease of service, see FIG. 3-1 on page 19.
4. Install a manual main gas shutoff valve, outside of the appliance gas connection and before the gas valve or manifold connection, when local codes require.
5. A trap (drip leg) MUST be provided by the installer in the inlet of the gas connection to the appliance, see
FIG. 3-1 on page 19.
6. The combination gas valve has an integral vent lim it ing device and does not require venting to atmosphere, outside the building.
7. Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.
TABLE - 3C
FITTINGS TO EQUIVALENT STRAIGHT PIPE
Diameter Pipe (inches)
3/4 1 1 1/4 1 1/2 2 3 4 5
Equivalent Length of Straight Pipe (feet)
2 2 3 4 5 10 14 20
TABLE - 3D
GAS CONNECTIONS
Btu/hr
INPUT
Pipe Size
45,000 - 135,000 1/2"
180,000 - 260,000 3/4"
3 Gas connections (continued)
19
Installation & Service Manual
TABLE - 3E
GAS PIPING SIZE CHART
Nominal Iron Pipe
Size
Inches
Length of Pipe in Straight Feet
Maximum Capacity of Pipe in Thousands of
Btu/hr per hour
for gas pressures
of 13.5 Inches
Water Column
(0.5 PSIG) or less
and a pressure
drop of 0.5 Inch
Water Column
(Based on NAT
GAS, 1025
Btu/hr per Cubic
Foot of Gas and
0.60 Specific Gravity)
10 20 30 40 50 60 70 80 90 100 125 150 175 200
3/4 369 256 205 174 155 141 128 121 113 106 95 86 79 74
1 697 477 384 328 292 267 246 226 210 200 179 164 149 138
1 1/4 1,400 974 789 677 595 543 502 472 441 410 369 333 308 287
1 1/2 2,150 1,500 1,210 1,020 923 830 769 707 666 636 564 513 472 441
2 4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820
2 1/2 6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300
3 11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
4 23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Gas Piping
Figure 3-1_Gas Line Connection
All gas connections must be made with pipe joint com pound resistant to the action of liquefied pe tro leum and natural gas. All piping must comply with local codes. Tubing installations must com ply with ap proved standards and practices. Reference FIG. 3-1 for a typical installation.
Install Piping to Control
1. The gas line should be a separate line direct from the meter unless the existing gas line is of sufficient capacity. Verify pipe size with your gas sup pli er.
2. Use new, properly threaded black iron pipe free from chips. If tubing is used, make sure the ends are cut squared, deburred and clean. All tubing bends must be smooth and without deformation. Avoid flexible gas connections. Internal diameter of flexible lines may not provide proper volume of gas.
3. Run pipe or tubing to the gas valve or manifold inlet. If tubing is used, obtain a tube to pipe coupling to connect the tubing to the gas valve or man i fold inlet.
4. DO NOT OVER TIGHTEN. Over tightening may result in damage to the gas valves. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas valve.
5. Apply a moderate amount of good quality pipe compound (DO NOT use Teflon tape) to pipe only, leaving two end threads bare.
6. Remove seal over gas valve or manifold inlet.
7. Connect pipe to gas valve or manifold inlet. Use wrench to square ends of the gas valve (FIG. 3-2).
GAS VALVE
GAS SHUTOFF VALVE
TRAP (DRIP LEG)
Installation & Service Manual
20
APPLY WRENCH FROM TOP OR BOTTOM
OF GAS CONTROL TO EITHER SHADED AREA
APPLY WRENCH
TO FLANGE ONLY
WHEN FLANGE IS
NOT USED
WHEN FLANGE
IS USED
Figure 3-2_Wrench
8. For L.P. gas, consult your L.P. gas supplier for expert installation.
IMPORTANT
Upon completion of any piping con nec tions to the gas system, leak test all gas con nec tions with a soap solution while system is un der pressure. Immediately repair any leaks found in the gas train or related components. Do Not op er ate an appliance with a leak in the gas train, valves or related piping.
Gas Manifold Pressure Adjustment Procedure
3.5"
MANOMETER
GAS VALVE
PRESSURE REGULATOR ADJUSTMENT (UNDER CAP SCREW)
OUTLET PRESSURE TAP
PILOT OUTLET
GAS CONTROL KNOB
RED RESET BUTTON
INLET PRESSURE TAP
Figure 3-3_Manifold Pressure Adjustment
1. Turn the power “OFF” at the main dis con nect switch.
2. Turn gas valve control knob to “OFF” po si tion.
3. Remove the 1/8" hex plug located on the out let side of the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. See FIG. 3-3. Minimum range of scale should be up to 5" w.c. for Natural gas mod els and 10" w.c. for L.P. gas models.
4. Remove the pressure regulator adjustment cap screw on the gas valve. See FIG. 3-3 for location.
5. Turn the power “ON” at the main dis con nect switch.
6. Turn gas valve control knob to “ON” po si tion.
7. Set the thermostat(s) to call for heat.
8. Observe gas regulator pressure when all burn ers are firing. See Table 3B, Manifold Pressure (page 18) for proper regulator pressure settings.
9. If adjustment is necessary, turn regulator ad just ment screw clockwise to raise regulator gas pres sure, counterclockwise to lower gas pres sure, to proper setting. NOTE: Adjustment fitting is plas tic and may require slightly greater turning force than a metal fitting.
10. Turn the power “OFF” at the main dis con nect switch.
NOTICE
Do not increase regulator pres sure beyond specified pressure setting.
11. Turn gas valve control knob to “OFF” position.
12. Remove fitting from the gas valve and re place the 1/8" hex plug that was previously removed and tighten.
13. Turn the gas valve control knob to “ON” position.
14. Turn the power “ON” at the main dis con nect switch. The appliance is now ready to op er ate.
If manifold pressure can not be properly adjusted, use the procedure on page 21 to check gas supply pressure with a manometer connected to the inlet pressure tap on the gas control.
3 Gas connections
Installation & Service Manual
21
Checking Gas Supply Pressure
Figure 3-4_Gas Supply Pressure
1. Turn the power “OFF” at the main dis con nect switch.
2. Turn gas valve control knob to the “OFF” position.
3. Shut off gas supply at the manual valve in the gas piping
to the appliance. If fuel supply is L.P. gas, shut off gas supply at the tank.
4. Remove the 1/8" hex plug, located on the “inlet” side of
the gas valve and install a fitting suitable to connect to a manometer or magnahelic gauge. Range of scale should be 14" w.c. or greater to check inlet pressure. See FIG.’s 3-3 and 3-4 for location.
5. Turn on gas supply at the manual valve, turn on L.P. gas
at tank if required.
6. Turn the power “ON” at the main dis con nect switch.
7. Follow the “Lighting Instructions” in Section 6 - Startup
to light the pilot . Turn gas valve control knob to the “ON” position.
8. Set the thermostat(s) to call for heat.
9. Observe the gas supply pressure with all burn ers firing. Ensure inlet pressure is within specified range. Check gas supply pressure with all other gas fired appliances in operation to en sure prop er gas volume during periods of peak gas usage.
10. If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agen cy to determine necessary steps to provide prop er gas pressure to the control.
11. If the gas supply pressure is within the spec i fied range, proceed with the following steps to return the appliance to service.
12. Turn the power “OFF” at the main dis con nect switch.
13. Turn gas valve control knob to “OFF” position.
14. Shut off gas supply at the manual valve in the gas piping to the appliance. If fuel supply is L.P. Gas, shut off gas supply at the tank.
15. Remove the manometer and related fittings from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve.
16. Turn on gas supply at the manual valve, turn on L.P. Gas at tank if required.
17. Turn the power “ON” at the main dis con nect switch.
18. Turn the gas valve control knob to the “ON” position. Spark ignition models will au to mat i cal ly light the pilot on a call for heat.
19. Set the thermostat to call for heat. The appliance is now ready to operate.
IMPORTANT
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see the “Main te nance Section ­Normal Flame Pattern”. Turn system off and allow burners to cool, then cycle burners again to en sure proper ignition and flame characteristics.
3 Gas connections (continued)
GAS SUPPLY PRESSURE
MANOMETER
GAS VALVE
Combination Gas Valves
A
Figure 3-5_M9 Gas Valve
Venting of Combination Gas Valves
The combination gas valve regulator used on all mod els is equipped with an integral vent limiting orifice. The vent limiter ensures that the volume of gas emitted from the valve does not exceed the maximum safe leak age rate allowed by agency re quire ments. Com bi na tion gas valve/regulators equipped with integral vent limiters are not re quired to have vent or relief lines piped to the outdoors. A dust cap is provided at the vent termination point on the valve to prevent block age of the vent limiter by foreign material. The com bi na tion gas valve regulator with an integral vent limiter complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the manufacturer with out the in stal la tion of additional vent lines.
Two Stage Burner Control System
The 45,000 thru 260,000 Btu/hr boilers (M9) are equipped with a two stage burner control system.
Each unit has a combination gas valve to control the gas supply to the burners. The com bi na tion valve con sists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open po si tion at all times when the appliance is in service. Each gas valve has pres sure taps located on the inlet and outlet sides. Manifold pressure is adjusted using the regulator located on the valve. The manifold pres sure is pre set at the factory and adjustment is not usu al ly re quired. If the manifold pressure is to be ad just ed, follow the “Gas Manifold Pressure Ad just ment Pro ce dure”, page 20 for proper adjustment.
3 Gas connections
22
Installation & Service Manual
PRESSURE REGULATOR ADJUSTMENT (UNDER CAP SCREW)
INLET PRESSURE TAP
WIRING TERMINALS
S CONTROL KNOB
G
OUTLET PRESSURE TAP
PILOT OUTLET
Relief Valve
Figure 4-1_Relief Valve
This appliance is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Ves sel Code, Section IV (“Heating Boilers”). The re lief valve(s) is mounted directly into the heat ex chang er inside the header (see FIG. 4-1). To pre vent water damage, the dis charge from the relief valve shall be piped to a suit able floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year.
CAUTION
Avoid contact with hot discharge water.
Water Flow Switch (if equipped)
Figure 4-2_Water Flow Switch - Top Connections
A water flow switch is available as a factory sup plied option on all heating boilers (see FIG. 4-2). The flow switch should be wired between terminals X and B. Remove the jumper between the X and B terminals on the terminal strip. This wiring connection installs the flow switch in the 24 VAC safety cir cuit to prove water flow before main burner ig ni tion. A flow switch installed with the fac to ry sup plied minimum adjustment setting requires a spe cif ic minimum flow to make the switch and start burner operation. The flow rate required is a function of the diameter of pipe and tee used for installation. Ensure that the pump installed on the boiler will supply adequate flow to make the flow switch con tacts and operate the boil er.
A water flow switch meets most code re quire ments for a low water cut off device on boil ers requiring forced cir cu la tion for operation.
4 Water connections
23
Installation & Service Manual
RELIEF VALVE
FLOW SWITCH
FLOW
Low Water Cutoff (if equipped)
A hot water boiler installed above radiation level must be provided with a low water cutoff device either as part of the unit or installed at the time the boiler is installed. An electronic low water cutoff is available as a kit on all units. Low water cutoffs should be in spect ed every six months, including flushing of float types.
TABLE - 4A
MINIMUM REQUIRED FLOW
FOR HEATING BOILER
Input Btu/hr GPM Flow
45,000 1.9
75,000 3.1
90,000 3.7
135,000 5.6
180,000 7.4
215,000 8.9
260,000 10.7
NOTICE
Minimum flow is based on a 40°F tem per a ture rise across the boiler. Minimum flow may not prove a flow switch installed in the boiler piping. Use care when operating a boiler at or near the min i mum recommended flow because conditions unique to the installation (system pressure, operation of multiple zone valves, glycol, variations in flow, etc.,) may result in overheating of the boiler water caus ing noise or nui sance operation of safety limit con trols. Typical heat ing boiler applications will op er ate with a 20°F to 30°F temperature rise across the boiler.
Typical Heating Boiler Installations
General Plumbing Rules
1. Check all local codes.
2. For serviceability of the boiler, always install unions.
3. Always pipe pressure relief valves to an open drain.
4. Locate system air vents at the highest point of the system.
5. Expansion tank must be installed near the boil er and on the suction side of the pump.
6. Support all water piping.
Placing the Boiler in Operation
Filling the System: All air must be purged from the system for proper operation. An air scoop and air vent must be located close to the boiler outlet and there should be a minimum distance between the cold water feed and the system purge valve.
1. Close all drain cocks and air vents.
2. Open the makeup water valve and slowly fill the system.
3. If a makeup water pump is employed, ad just the pressure to provide a minimum of 12 psi at the highest point in the system. If a pressure regulator is also installed in the line, it should be adjusted to the same pressure.
4. Close all valves. Purge one circuit at a time as follows:
A. Open one circuit drain valve and let the water drain for
at least five minutes. Ensure that there are no air bubbles visible in the wa ter stream before closing the drain valve.
B. Repeat this procedure for each circuit.
5. Open all valves after all circuits have been purged. Make sure there are no system leaks.
NOTICE
Do not use petroleum based stop leak products. All system leaks must be repaired. The constant addition of make-up water can cause damage to the boiler heat exchanger due to scale accumulation. Scale reduces flow and heat transfer, causing overheating of the heat exchanger.
6. Run the system circulating pump for a min i mum of 30 minutes with the boiler turned off.
7. Open all strainers in the system and check for debris.
8. Recheck all air vents as described in step 4, General Plumbing Rules.
4 Water connections
24
Installation & Service Manual
9. Inspect the liquid level in the expansion tank. The system must be full and under normal operating pressure to ensure proper water level in the expansion tank. Ensure that diaphragm type ex pan sion tanks are properly charged and not water logged.
10. Start the boiler according to the Section 6 - “Start-Up Instructions” in this manual. Operate the system, including the pump, boiler and radiation units, for one hour.
11. Recheck the water level in the expansion tank. If it exceeds half the tank volume, open the tank to reduce the water level. Recheck pres sure charge on diaphragm type tanks.
12. Shut down the entire system and vent all ra di a tion units and high points in the system.
13. Close the water makeup valve and check the strainer and pressure reducing valve for sediment or debris. Reopen the water makeup valve.
14. Verify system pressure with the boiler pres sure gauge before beginning regular operation.
15. Within three days of start-up, recheck and bleed all air vents and the expansion tank using these instructions.
TABLE - 4B
SYSTEM TEMPERATURE RISE CHART
Based on Boiler Output in Btu/hr
Btu/hr
10°F T 20°F T 30°F T 40°F T
Input Output GPM Ft/hd GPM Ft/hd GPM Ft/hd GPM Ft/hd
45,000 36,900 7.4 0.6 3.7 0.2 2.5 0.2 1.9 0.2
75,000 61,500 12.3 1.3 6.2 0.4 4.1 0.3 3.1 0.2
90,000 73,800 14.9 1.4 7.4 0.5 5.0 0.3 3.7 0.2
135,000 110,700 22.3 3.2 11.1 1.2 7.4 0.6 5.6 0.3
180,000 147,600 29.7 5.1 14.9 1.6 9.9 0.7 7.4 0.4
215,000 176,300 -- -- 17.0 1.3 11.8 0.8 8.9 0.4
260,000 213,200 -- -- 21.5 2.1 14.3 0.9 10.7 0.5
Piping of the Boiler System
The drawings in this section (see FIG’s 4-7 thru 4-11) show typical heating boil er piping installations. Before beginning the in stal la tion, consult local codes for specific plumb ing re quire ments. The installation should provide unions and valves at the inlet and outlet of the boil er so it can be isolated for service. The boiler cir cu lat ing pump, air sep a ra tor, expansion tank and oth er components required for proper installation must be purchased locally. An air separation device must be supplied in the in stal la tion piping to eliminate trapped air in the system. Lo cate a system air vent at the highest point in the sys tem. The system must also have a properly sized expansion tank installed. Typically, an air charged di a phragm-type expansion tank is used. The expansion tank must be installed close to the boiler and on the suction side of the system pump to ensure proper op er a tion.
CAUTION
This boiler system should not be operated at less than 12 PSIG.
4 Water connections (continued)
25
Installation & Service Manual
Hot water pip ing must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and con trac tion. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the relief valve section on page 23 of this manual.
CAUTION
A leak in a boiler system will cause the system to intake fresh water constantly, which will cause the tubes to accumulate a lime/scale build up. This will cause a NON-WARRANTABLE FAILURE.
Water Connections
Heating Boilers with inputs of 45,000 - 260,000 Btu/hr have 1 1/2" NPT inlet and outlet connections.
CAUTION
Field installed reducing bushings may de crease flow re sult ing in boiler noise or flashing to steam.
Circulator Pump Requirements
This is a low mass, high efficiency hot water boil er which must have adequate flow for quiet, efficient op er a tion. The boiler circulating pump must be field supplied. The boiler circulator pump must operate con tin u ous ly while the boiler is firing. Pump selection is critical to achieve proper op er a tion. A pump should be selected to achieve proper system design water temperature rise. A heat ex chang er pressure drop chart (Table 4C) is provided to assist in proper pump selection. Also provided is a System Temperature Rise Chart (Table 4B on page 25). This table provides GPM and boiler head-loss at various temperature rises for each boiler based on Btu/hr input. Temperature rise is the difference in boiler inlet temperature and boiler outlet temperature while the boiler is firing. Example: The boiler inlet tem per a ture is 160°F and the boiler outlet temperature is 180°F, this means that there is a 20°F tem per a ture rise across the boiler.
TABLE - 4C
HEAT EXCHANGER PRESSURE DROP CHART
CB 315
CB 360
CB 399
CB 500
FT/HD
Gallons per Minute
0
5
10
15 20 25
30
35
7
6
5
4
3
2
1
0
4 Water connections
26
Installation & Service Manual
Circulator Pump Specifications
1. Maximum operating pressure for the pump must exceed system operating pressure.
2. Maximum water temperature should not ex ceed nameplate rating.
3. Cast iron circulators may be used for closed loop systems.
4. A properly sized expansion tank must be in stalled near the boiler and located on the suction side of the pump.
PUMP INSTALLATION AND MAIN TE NANCE: The boiler circulating pump must be purchased lo cal ly. For installation and maintenance information on the circulator pump, refer to the pump man u fac tur ers in struc tion package included with the pump.
4 Water connections (continued)
27
Installation & Service Manual
Figure 4-3_Boiler Wiring - Circulation Pump to Junction Box
Circulator Pump Operation
Boilers are equipped with a relay for controlling the circulation pump for the hot water loop. The relay turns ON and OFF in response to the “W” input from the wall thermostat or zone control.
The field installed boiler pump MUST NOT exceed 1 h.p. For continuous pump operation, wire the system pump to the 120V supply. The pump should be connected at the junction box as shown in FIG. 4-3.
PERFORMANCE LOOP
These units are equipped with an integral performance loop, which is designed to provide efficiency optimization by maintaining a constant flow through the unit’s heat exchanger loop when building system flow is reduced. The performance
loop assembly is standard equipment and is NOT to be used as a system or boiler pump.
NOTICE
The performance loop is dedicated to the unit and does not affect the building’s system or primary/secondary flow characteristics and will not circulate the building.
It is acceptable to remove the performance loop as long as the following requirements are met:
1. The boiler is piped to the system in primary/secondary fashion.
2. The system setpoint is 140°F or higher.
3. The boiler circulating pump is sized for the appropriate flow through the boiler.
4. The system sensor is installed in an acceptable location for sensing the system supply temperature.
5. If water temperature is below 140°F a low temperature bypass must be installed, (VAL30000 - 1 1/2" LTV Valve Kit) and follow the piping diagram in FIG. 4-4.
NOTICE
If removal of the performance loop is necessary, consult the manufacturer for a Solution Without a Performance Loop (KIT30068).
WARNING
Failure to install the system sensor can cause operation problems such as nuisance high limit trips.
Primary/Secondary Boiler Piping
A pri ma ry/secondary pip ing system may also be in stalled to ensure proper boiler flow rates. Primary/sec ond ary piping is also ideal for systems using a mixture of propylene glycol and water. A primary/secondary piping system uses a dedicated pump to supply flow to the boiler only. This pump is sized based on de sired boiler flow rate, boiler head loss and head loss in the sec ond ary system piping only. The secondary pump, in ­stalled in the boiler piping, ensures a constant wa ter flow rate to the boiler for proper operation. Boiler installation with a primary/secondary piping sys tem can prevent noise problems caused by low sys tem water flows. A primary/secondary piping system is recommended on any boiler where low water flow conditions may present an operational problem.
120V
SUPPLY
TO
UNIT
TO
CIRCULATION
PUMP
TO PERFORMANCE
LOOP PUMP (OPT.)
Full Flow Application
It is acceptable for the Solution boiler to be installed in a full flow application, as long as the following requirements are met:
1. The performance loop is in place and functional.
2. The system flow is not lower than the minimum boiler flow.
3. The boiler setpoint is 140°F or higher.
4. If water temperature is below 140°F you must install a low temperature bypass, VAL30000, and follow the piping diagram shown in FIG. 4-7.
Boiler Flow Rates
CAUTION
The maximum flow rate through the boil er with a copper heat exchanger must not ex ceed 30 GPM.
The heat exchanger is generally capable of op er at ing within the flow rates of a residential heating system. Should the flow rate exceed the maximum allowable flow rate through the boiler 30 GPM) an external bypass must be installed. The bypass should be fully sized with a balancing valve to al low for proper ad just ment of flow. Flow rate can be determined by measuring the temperature rise through the boiler.
The basic guide for minimum flow in this boiler is based on a 40°F temperature rise in most in stal la tions. Low er flow and a higher temperature rise is acceptable if the boiler system is specifically de signed for the char ac ter is tics of a higher tem per a ture rise. A system not specifically designed for a higher temperature rise may experience over heat ing of the boiler water. This can cause short burn er on cycles, system noise and in ex treme cases, a knocking flash to steam. These con di tions can lead to operational problems and non-war rant able fail ures of the boiler. High temperature rise systems must be designed by a qualified engineer.
Low Temperature Bypass Requirements
Inlet water temperatures below 140°F (60°C) can excessively cool the prod ucts of combustion re sult ing in condensation on the heat exchanger and in the flue. Condensation can cause operational prob lems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system and related components. The bypass allows part of the boiler discharge water to be mixed with the cooler boiler return water to in crease the boiler inlet temperature above 140°F (60°C). This should prevent the prod ucts of com bus tion from condensing in most in stal la tions. The bypass should be fully sized with a bal anc ing valve to allow for proper adjustment. A valve must also be provided on the boiler discharge, after the by pass. Closing this discharge valve forces water through the bypass. Start boiler adjustment with the bypass valve in the full open position and the boiler discharge valve half open. A small amount of the high er temperature boiler discharge water is mixed with the system water to maintain the de sired lower system tem per a ture.
WARNING
Varying the flow through a Solution boiler can cause harmonic noises and high limit trips if the flow is below the minimum boiler flow rate found in Table 4A.
4 Water connections
28
Installation & Service Manual
CAUTION
At no time should the system pressure be less than 12 PSIG.
A boiler operated with an inlet temperature of less than 140°F (60°C) must have a bypass to prevent problems with condensation. A bypass as shown in FIG. 4-8 (see page 33) must be piped into the system at the time of installation.
A primary/secondary piping system is ideal for sys tems filled with a propylene glycol and water mix ture. A glycol and water mixture is more dense than water only and may result in a lower boiler flow rate. A lower boiler flow may cause noisy operation or short cycling of the burners. A larger secondary pump may be used on a primary/sec ond ary system to pro vide an increased boiler flow rate. A glycol and water system may require from 10 to 20% more flow to compensate for the in creased density of the glycol and its effect on the heat transfer process in the boiler. The exact in crease in flow that may be required is based on the type and percentage of glycol added to the boiler system. Consult the manufacturer of the glycol for additional recommendations when using a gly col and water fill for your boiler system.
The installer must ensure that the boiler has ad e quate flow without excessive temperature rise. The tem per a ture rise on a multiple zone system should be made when only the zone with the longest length and/or high est head loss is open. Low system flow can result in overheating of the boiler water which can cause short burner on cycles, system noise and in extreme cases, a knocking flash to steam. System noise may also indicate an oversized boiler.
Primary/Secondary Boiler Piping
(continued)
Primary / Secondary Piping
Figure 4-4_Primary / Secondary Piping of a Single Boiler
4 Water connections (continued)
29
Installation & Service Manual
PRESSURE
MAKE UP WATER
TO
SYSTEM
BACKFLOW
PREVENTER
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
BALL VALVE
(TYPICAL)
REDUCING VALVE
PRESSURE
GAUGE
AIR SEPARATOR
NOT TO EXCEED APART
12"
FROM
SYSTEM
EXPANSION
TANK
DRAIN POINT
(TYPICAL)
UNION
(TYPICAL)
TEMPERATURE / PRESSURE
GAUGE
BOILER CIRCULATOR
DRAIN
PRESSURE
RELIEF VALVE
Y-STRAINER
(RECOMMENDED)
SOLUTION
BOILER
Figure 4-5_Single Boiler - Primary / Secondary with Low Temperature Bypass
Primary / Secondary Piping
4 Water connections
30
Installation & Service Manual
PRESSURE REDUCING VALVE
PRESSURE
GAUGE
AIR SEPARATOR
12"NOT TO EXCEED APART
PREVENTER
MAKE UP WATER
TO
SYSTEM
BACKFLOW
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
FROM
SYSTEM
BALL VALVE
(TYPICAL)
EXPANSION
TANK
DRAIN POINT
(TYPICAL)
UNION
(TYPICAL)
TEMPERATURE / PRESSURE
GAUGE
LOW TEMPERATURE BYPASS
BOILER CIRCULATOR
DRAIN
PRESSURE
RELIEF VALVE
Y-STRAINER
(RECOMMENDED)
SOLUTION
BOILER
Primary / Secondary Piping
Figure 4-6_Multiple Boilers Zoned with Circulators
BOILER 1
(LEADER)
INDIRECT
DHW TANK
ANTI-SCALD
MIXING VALVE
COLD
WATER
IN
TEMPERATURE /
PRESSURE
GAUGE
AIR SEPARATOR
ZONE #1
ZONE #2
ZONE #3
ZONE #4
BALL VALVE
(TYPICAL)
UNION
(TYPICAL)
PRESSURE
RELIEF VALVE
DRAIN POINT
(TYPICAL)
MAKE UP WATER
HOT
WATER
OUT
BOILER CIRCULATOR
BACKFLOW
PREVENTER
PRESSURE
REDUCING VALVE
PRESSURE
GAUGE
EXPANSION
TANK
ZONE #1
ZONE #2
ZONE #3
ZONE #4
ZONE CIRCULATORS
(TYPICAL)
FLOW CHECK
VALVE
SYSTEM SUPPLY
SENSOR
(WHEN USED)
RECIRCULATION
LOOP
AQUASTAT
RELIEF VALVE
Y-STRAINER
(RECOMMENDED)
MAY SUBSTITUTE LOW LOSS HEADER
NOT TO EXCEED 12" APART
BOILER 2
(LEADER 1)
4 Water connections (continued)
31
Installation & Service Manual
Figure 4-7_Single Boiler Full System Flow
Full System Flow
4 Water connections
32
Installation & Service Manual
PRESSURE REDUCING VALVE
BACKFLOW
PREVENTER
MAKE UP WATER
SYSTEM SUPPLY SENSOR
SYSTEM CIRCULATOR
TO
SYSTEM
BALL VALVE
(TYPICAL)
PRESSURE
GAUGE
AIR SEPARATOR
FROM
SYSTEM
EXPANSION
TANK
UNION
(TYPICAL)
TEMPERATURE / PRESSURE
GAUGE
DRAIN
PRESSURE
RELIEF VALVE
Y-STRAINER
(RECOMMENDED)
SOLUTION
BOILER
Installation & Service Manual
33
SOLUTION
BOILER
BACKFLOW
PREVENTER
PRESSURE REDUCING VALVE
PRESSURE
GAUGE
TEMPERATURE / PRESSURE
GAUGE
AIR SEPARATOR
EXPANSION
TANK
BALL VALVE
(TYPICAL)
UNION
(TYPICAL)
PRESSURE RELIEF VALVE
MAKE UP WATER
FROM SYSTEM
BOILER CIRCULATOR
SYSTEM CIRCULATOR
TO
SYSTEM
SYSTEM SUPPLY SENSOR
DRAIN
Y-STRAINER
(RECOMMENDED)
3-WAY VALVE W/BYPASS PIPE
Figure 4-8_Single Boiler Full System Flow with Low Temperature Bypass
Full System Flow
4 Water connections (continued)
34
Installation & Service Manual
5 Electrical connections
This appliance is wired for 120 VAC service. The appliance, when installed, must be electrically ground ed in accordance with the requirements of the authority having jurisdiction or in the absence of such re quire ments, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. When the unit is in stalled in Canada, it must conform to the CSA C22.1, Ca na di an Electrical Code, Part 1 and/or local Electrical Codes.
1. All wiring between the appliance and field
in stalled devices shall be made with type T wire [63° F(35° C) rise].
2. Line voltage wire exterior to the appliance must be
enclosed in approved conduit or approved metal clad cable.
3. The pump must run continuously when the appliance is
being fired.
4. To avoid serious damage, DO NOT en er gize the
appliance until the system is full of water. Serious damage may result.
5. Provide the unit with proper overload protection.
6. Install a wall thermostat on the inside wall. DO NOT
install the thermostat in an area affected by drafts, sunlight, light fixtures, hot or cold water pipes or near a fireplace. See “Room Thermostat or Remote Thermostat Connection to Terminal Strip” (this page), for prop er wiring con nec tion.
Boiler Operating Temperature Control
The operating temperature control is located in the control panel, behind the control panel front ac cess door. The sensing element for the operator is placed in a bulbwell installed in the heat exchanger. Carefully observe the inlet water temperature on the initial boiler on cycles. The exact temperature set point is based on your system’s requirements. Turn the con trol set point dial to the desired operating water tem per a ture. Observe the boiler discharge tem per a ture after each set point adjustment to ensure prop er operation.
Room Thermostat or Remote Thermostat Connection to Terminal Strip
A room thermostat or remote temperature control may be connected to the boiler. The room ther mo stat should be installed on an inside wall, away from the influences of drafts, hot or cold water pipes, lighting fixtures, televisions, sun rays or fire plac es. Follow the manufacturers instructions supplied with the ther mo stat for proper installation and ad just ment. The boiler is equipped with a terminal strip on the left side of the control panel to allow easy connection (FIG. 5-1).
Remove the jumper between the R and W terminals on the terminal strip. Refer to the chart in this section (Table 5A) to determine maximum allowable length and wire gauge recommended to connect the switching con tacts of the room thermostat to the R and W terminals on the terminal strip. Connection to the terminal strip will allow the room thermostat to make and break the 24VAC boiler control circuit turning the boiler on and off based on the room ambient temperature re quire ments. Set the boiler operating temperature control as described in this section.
A
B
Figure 5-1_Terminal Strip Connections
Auxiliary Device Connection to Terminal Strip
A terminal connection strip is provided for ease of connection for Power Venting Systems, see FIG. 5-1, inset A.
A field supplied powered venter or powered louver/damper may be connected to the Solution boiler via a terminal strip located on the left side of the unit, see FIG. 5-1, inset B.
A 24 VAC relay can be powered from this location when a call for heat has been established. A device proving switch can be interlocked back to the appliance to ensure its operation before the appliance is allowed to fire.
Reference the wiring diagram on page 50 of this manual.
TABLE - 5A
TERMINAL STRIP WIRING
Wire Gauge
Allowable Length
Maximum
12 GA 100 ft.
14 GA 75 ft.
16 GA 50 ft.
18 GA 30 ft.
35
Installation & Service Manual
5 Electrical connections (continued)
Pump Wiring for a Heating Boiler
The heating boiler circulating pump must be pur chased locally. The max i mum load for the pump switched by the internal pump relay must not exceed 1 HP. The current draw for a field installed 120 VAC pump MUST be add ed to the boiler’s current draw to de ter mine the minimum wire size for 120 volt service.
TABLE - 5B
AMP DRAW DATA
45,000 thru 260,000 Btu/hr Models
FIRING CONTROLS
MAXIMUM
TOTAL AMPS
@ 120 VAC
M9 with Performance Loop Pump 1.25
TEMPERATURE CONTROL
PUMP RELAY
MANUAL RESET HIGH LIMIT (IF EQUI PPED)
IGNITION MODULE
TRANSFORMER
Figure 5-2_Intermittent Pilot System M9 Control Panel
Temperature Adjustment
Operating Temperature Control
NOTICE
The temperature controller is pre-set at the factory with test settings. You may need to adjust the settings to meet your specific needs.
WARNING
Return water temperatures must not be less than 140°F. If lower return water temperatures are required, follow the instructions for Low Temperature Bypass Requirements, see page 28.
Locating Temperature Control
Remove the control panel door on the front of the unit in order to locate and access the temperature control.
Temperature Control Settings
Remove the control panel door on the front of the unit in unless your unit is specified as a boiler only with an outdoor air reset option. If your unit is a boiler only with an outdoor air reset option, there are additional controls for this option. They are explained under Outdoor Air Reset Option, page 38.
The three setting knobs on the temperature control are for Set point, Differential, and High-Fire Offset (see FIG. 5-3).
Figure 5-3_Temperature Control
Maximum Set Point Determination
The maximum set point for the control is factory set. Boilers can be set to 240°F max.
These maximum set points are established by cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller. The maximum set point is determined as shown below in Table 5C.
TABLE - 5C
MAXIMUM SET POINT DETERMINATION
OJ1 OJ2
MAX.
SET POINT
Connected Connected 240°F
Cut Connected 190°F
Connected Cut 200°F
Cut Cut 160°F
NOTICE
Anytime that OJ1 is the only jumper cut, a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 190°F.
Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.
High-Fire Offset
The temperature control operates a two-stage firing system. The two stages are High-Fire and Low-Fire. High-Fire operates all burners at full rate while Low-Fire operates the burners at approximately one-half rate.
The High-Fire Offset knob specifies the number of degrees below set point that the High-Fire stage shuts down. At that point, the unit will continue to operate at the Low-Fire stage until the set point is reached.
The High-Fire Offset knob has settings between 0°F and 20°F. If set at 0°F, the High-Fire Offset is disabled and the unit will operate the High-Fire stage until the set point is reached and the temperature control shuts the unit off.
If the High Fire Offset knob is set to 0 or 1, the delay will be 10 seconds; if set to 2 or above the delay will be 120 seconds.
Boiler Application
Standard boiler units are equipped with one inlet water temperature sensor. A system sensor is also provided for use as a remote system sensor. Boilers with the outdoor air reset option also have an outside air temperature sensor.
Temperature Control Sensors
This is a two-stage temperature control that controls the burner ignition and pump functions. This temperature controller can measure up to three different sensor inputs, depending upon how the unit is set up. They are as follows:
1. Inlet Water Temperature Sensor
2. System Sensor
3. Outside Air Temperature Sensor
Inlet Water Temperature Sensor
This sensor measures the inlet water temperature coming into the unit.
The inlet water temperature sensor is placed into the inlet bulbwell on the boiler. This sensor is installed by the factory in new units.
System Sensor
Depending upon how your unit is set up, this sensor can be used as a system sensor in a boiler system or a tank sensor for water heater applications. Connect this sensor to the two blue wires in the upper left-hand corner of the control panel.
Set Point
The Set Point knob specifies the target inlet water temperature in degrees, Fahrenheit. After the water temperature reaches the set point, the temperature control shuts off the burners.
Differential
The Differential specifies the number of degrees below the set point that the control will allow the water temperature to drop before it brings the unit back on again.
Installation & Service Manual
5 Electrical connections
36
5 Electrical connections (continued)
37
Installation & Service Manual
Outdoor Air Temperature Sensor
The outside air temperature sensor will only be used for boiler systems. The outside air sensor is optional. This sensor allows you to tie boiler operation to the outdoor air temperature. As outside temperatures drop, the control will increase the temperature setting of the boiler. As outdoor temperatures rise, the control will decrease the temperature to the selected set point of the boiler. You can set the control to shut the boiler off when a desired outdoor air temperature level is reached.
You must purchase the sensor from the appliance manufacturer. The sensor comes with a housing that helps protect the sensor from the elements. Mount the air sensor housing outdoors, under the eve of the roof. Make sure the housing is out of direct sunlight. This will ensure that the sensor will accurately read the true outdoor temperature. Connect the outdoor air temperature sensor to the terminal block on the outdoor air reset board. For more information on wiring the sensor, see Wiring of Remote Sensors, this page.
Wiring of Remote Sensors
To wire remote sensors, follow the guidelines below. Take care to correctly wire sensors to the unit. Erratic temperature readings can be caused by poor wiring practices. Twist the wires between the unit and the remote sensor. Turn wires at least three or four turns per linear foot of wiring. This provides protection against some types of electrical interferences.
1. Do not route temperature sensor wiring with building
power wiring.
2. Do not locate temperature sensor wiring next to control
contactors.
3. Do not locate temperature sensor wiring near electric
motors.
4. Do not locate temperature sensor wiring near welding
equipment.
5. Make sure good mechanical connections are made to the
sensor, any interconnecting wiring and the controller.
6. Do not mount sensor with leadwire end pointing up in an
area where condensation can occur.
7. Use shielded wiring to connect the sensor to the control
when the possibility of an electrically noisy environment exists. Shielded cable is recommended on all cable runs of more than 25 feet in length.
NOTICE
Ground the cable shield at the connection to the boiler temperature control only. Do not ground the shielded cable at the sensor end.
To maintain temperature accuracy, sensor wires should be 18 AWG two conductor (18/2). Use shielded wire if required.
Installation of Remote Sensors
1. Turn OFF the main electrical power and the main manual gas shutoff to the appliance.
2. Remove the side access panel from the appliance to gain access to the thermostat.
3. Locate the sensor in the kit. Determine the location of the remote sensor and measure the amount of wire needed to connect the sensor to the thermostat. See Wiring of the Remote Sensors for guidelines.
4. Use twisted pair wire, minimum 18 gauge or larger. See Table 5A, page 34 regarding distance versus wire gauge. Ensure all wire insulation is trimmed to reveal at least 3/8" of exposed wire.
5. Connect the measured wire to the sensor wire using wire caps (see FIG. 5-4). Install .250 x .032 insulated female quick connect terminals to the end of the wires. Feed the wires through the access hole located on the back of the unit and secure the connectors to the thermostat connections (Sys/Tank) CN5 and CN6 located in the upper right-hand of the thermostat.
6. Turn on the electrical power and the main manual gas shutoff to the appliance.
7. Replace the side access panel.
8. Fire the appliance and resume operation.
Figure 5-4_Installation of Remote Sensors
ACCESS HOLE
CONNECT THE MEASURED WIRE TO THE SENSOR WIRE
Installation & Service Manual
38
Outdoor Air Reset Option
For boilers ordered with the Outdoor Air Reset option, there is an additional control (FIG. 5-5). There are three setting knobs for Shutdown, Outdoor Air Max., and Ratio. There is also a switch to turn the outdoor air shutdown feature On or Off. An O.A. Sensor is also included.
R4R4
R6R6
R8R8
R16R16
R15R15
C7C7
C9C9 C10C10
VR2VR2
VR3VR3
OJ1OJ1
OJ2OJ2
D4D4
J4J4
CN1CN1
CN2CN2
CN9CN9
CN7CN7
CN8CN8
CN3CN3
CN4CN4
CN5CN5
CN6CN6
W1W1
TST2314TST2314
2020
1515
1010
55
(F-)0(F-)0
1515
1414
1313
1212
1111
10
99
88
77
66
55
OFFOFF
120120
240240
220220
200200
160160
140140
SETPOINTSETPOINT
DIFFERENTIALDIFFERENTIAL
HIGH-FIREHIGH-FIRE
OFFSETOFFSET
(c)2002 L.C.(c)2002 L.C.
SHUTDOWN
45
50
45
1.3
O.A. MAX.
70
40
VR1
65
RATIO
VR2
0.6
0.5
0.7
1.4
1.5
W1 W2
W3
60
50
7040
55
60
VR3
65
DISABLE
O.A. SHUTDOWN
1.0
0.9
0.8
1.2
1.1
O.A. SENSOR
ENABLE
ON
SW1
55
CN1
Shutdown
The Shutdown knob specifies the outdoor air lockout temperature at which the control would prevent the unit from operating.
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum outdoor air temperature specified by this knob setting. When the outdoor air temperature is above the specified setting, the unit will not function in the O.A. Reset Mode, but will continue to run at the selected set point temperature.
Note that the set point knob will now indicate the “minimum” boiler temperature. Target temperature is determined by the ratio and outdoor air temperature below the O.A. Max setting.
Ratio
The Ratio knob allows control over the reset ratio to be used during Outdoor Air Reset. The allowable ratios are as low as
0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5° for every 1.0° drop in outdoor air temperature up to the maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5° for every 1.0° drop in outdoor air temperature up to the maximum set point temperature.
If the outdoor design and boiler design temperatures are known, the Ratio setting can be calculated using the following formula:
Ratio = (boiler design temperature - operator set point)
(O.A. Max. setting - outdoor design temperature)
Note that the reset set point cannot exceed the maximum set point of the boiler thermostat.
These settings are illustrated graphically in FIG. 5-6.
Figure 5-5_Optional Outdoor Air Reset Control
Figure 5-6_Outdoor Air Control Example Chart
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns the outdoor air shutdown feature On and Off. Disabling the Outdoor Air Shutdown feature allows the unit to operate regardless of the outdoor air temperature. This is needed for indirect domestic hot water systems for example.
Additional Temperature Controls
High Water Temperature Limit Con trol
The appliance is supplied with a fixed setting, auto-reset high water temperature limit control. The setting of this control limits max i mum discharge water tem per a ture. If water temperature exceeds the setting, the limit will break the con trol circuit and shut down the appliance. The limit control will only be reset after the water tem per a ture has cooled well below the setting of the limit. The auto-reset high water temperature limit control is mount ed in the outlet side of the front header.
5 Electrical connections
5 Electrical connections (continued)
39
Installation & Service Manual
Blocked Vent and Flame Roll-Out / Flame Interlock Switch
Figure 5-7_Blocked Vent Switch Location
/
Figure 5-8_Flame Roll-Out / Flame Interlock Switch Location
All units are equipped with manual reset blocked vent and flame roll-out / flame interlock switches. These temperature switches are located in the controls compartment and in the relief opening of the boiler’s built-in draft hood. Each switch has a red reset button. In the event the system has actuated to shut off the main burner gas supply, wait for the boiler to cool, then press the red reset to return the boiler to operation. Op er a tion of a blocked vent and/or flame roll-out / interlock switch usually indicates a problem with the venting system, obstruction of the heat ex chang er flue gas passageway and/or a combustion air supply prob lem. The cause for operation of the blocked vent and/or flame roll-out / interlock switch must be determined and corrected. If the boiler cannot be restored to normal operation, contact a qualified ser vice in stall er, service agency or the gas supplier.
OUTER AIR DEFLECTOR
UPPER FRONT JACKET PANEL
BLOCKED VENT SWITCH INVERTED TO SHOW RESET UNDERNEATH
DRAFT HOOD
FRONT OF UNIT
DETAIL A
LOWER FRONT JACKET PANEL
HEX FILLER BRACKET
FLAME ROLL-OUT SWITCH INTERLOCK SWITCH
40
6 Start-up
Installation & Service Manual
Initial Start-up
Follow the Lighting Instructions on the label applied to the appliance.
A. On boilers with the system pump delay option, the
operating temperature control will energize the pump relay which energizes the pump on a call for heat. The operating temperature control will de­energize the pump relay approximately 30 seconds after the call for heat ends. If either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
On boilers, the pump will operate whenever the “W” terminal is energized.
B. Location - The appliance should be located within a
room having a temperature safely above freezing [32°F(0°C)].
C. Shutdown and Draining - If, for any rea son,
the appliance is shut off, the following pre cau tion ary measures must be taken:
1. Shut off gas supply,
2. Shut off water supply.
3. Shut off electrical supply.
4. Drain the heat exchanger completely. Re move one 3/8" NPT plug or bulbwell from the inlet side and one from the outlet side of the front head er of the heat exchanger.
5. Drain the pump. Remove the 3/4" plug in the performance loop.
Pre-start Checklist
1. Inspect the burners to be sure they are prop er ly aligned.
2. Inspect the pilot gas line, thermocouple leads, ignition leads and wire connections to the gas valve to be sure none were damaged during shipment.
3. Check to ensure that gas connections have been made properly and the gas line is purged of air.
4. Check to ensure that water connections are tight and the appliance and piping system have been properly filled.
5. Ensure that discharge from the relief valve has been piped to a floor drain.
6. Verify that properly sized combustion and ven ti la tion air openings are provided and not obstructed in any way.
7. Check carefully for gas leaks.
8. Read the appliance’s safety warnings, light ing instructions and check out procedure carefully, be fore firing the system.
Lighting Instructions for Spark Ignition Pilot Models
FOR YOUR SAFETY READ BEFORE
OPERATING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING, smell around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to turn the gas control knob.
Never use tools. If the knob will not turn by hand, don’t try to repair it, call a qualified ser vice technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance. The pos si ble damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
6 Start-up (continued)
41
Installation & Service Manual
Operating Instructions
1. STOP! Read the safety information first.
2. Remove the control panel door.
3. Set the thermostat to the lowest setting (OFF).
4. Turn off all electrical power to the appliance.
5. This appliance is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
6a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the “OFF” position.
6b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position.
7. Wait five (5) minutes to clear out any gas, then smell for gas, including near the floor. If you smell gas, STOP! Follow the steps in the “What To Do If You Smell Gas” section in the safety information on page 40. If you do not smell gas go on to the next step.
8a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve counterclockwise to the “ON” position.
8b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve counterclockwise to the line on the collar around the knob. Al low the knob to “pop” up, and continue rotation to the “ON” position.
9. Turn on all electric power to the appliance.
10. Set the thermostat to the desired setting.
11. Re-install the control panel door.
12. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
To Turn Off Gas to Appliance
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
3a. 45,000 - 135,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the “OFF” position. Do not force.
3b. 180,000 - 260,000 Btu/hr models, rotate the gas control
knob on the gas valve clockwise to the line on the collar around the knob. Depress the knob and continue rotation to the “OFF” position. Do not force.
WARNING
Should overheating occur or the gas fail to shut off, turn off the external manual gas valve to the appliance.
Safety Shutoff Test for Spark Ignition Pilot System
1. Turn “OFF” gas supply to the appliance.
2. Turn thermostat to highest setting.
3. Turn electric power “ON”.
4. Pump relay pulls in to start pump.
5. The ignition will begin sparking at the pilot.
6. The ignition module will lock out after the 90 second trial for ignition period.
7. Immediately call a qualified serviceman or in stall er to repair an ignition system that fails to lock out and properly shut down burner operation.
8. After successful completion of the test, re ad just the thermostat to normal setting.
9. Turn “ON” gas supply.
10. Turn power “OFF” then “ON” to reset ignition module.
11. If ignition system fails to operate properly, re pair work must be performed by a qualified serviceman or installer.
Installation & Service Manual
42
Ignition and Control Timings
M9 Intermittent Spark Ignition Pilot Mod els
Pilot Trial for Ignition Period - 90 Seconds
Pilot Failure Response Time - 0.8 Seconds at less than 1.0 µA flame current
Pump Delay Timing (Optional on Boilers) - 30 Seconds after burner shut down
Freeze Protection
1. For boilers with the pump delay option, if either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.
2. Location - Heating boilers must be located in a room having a temperature safely above freezing [32°F(0°C)].
3. Caution - A room where the appliance is installed and operating under a negative pressure may experience a downdraft in the flue of an appliance which is not firing. The cold outside air pulled down the flue may freeze a heat exchanger. This condition must be cor rect ed to provide adequate freeze protection.
4. Freeze protection for a heating boiler or hot water supply boiler using an indirect coil can be provided by using hydronic system antifreeze. Follow the manufacturers instructions. DO NOT use un di lut ed or automotive type antifreeze.
5. A snow screen should be installed to pre vent snow and ice accumulation around the appliance vent ing system in cold climates.
6. Shut-down and Draining - If for any rea son, the appliance is to be shut off, the following precautionary measures must be taken:
(a) Shut off gas supply.
(b) Shut off water supply.
(c) Shut off electrical supply.
(d) Drain the unit completely. Remove one threaded
plug or bulbwell from the inlet side of the front header and one from the outlet side of the front header on the heat exchanger. Blow all wa ter out of the heat exchanger.
(e) Drain pump and piping.
Freeze Protection for a Heating Boiler System (if required)
1. Use only properly diluted inhibited glycol an ti freeze designed for hydronic systems. Inhibited propylene glycol is recommended for systems where incidental contact with drinking water is possible.
CAUTION
DO NOT use undiluted or automotive type antifreeze.
2. A solution of 50% propylene glycol will pro vide maximum protection of approximately -30°F.
3. Follow the instructions from the glycol an ti freeze manufacturer. The quantity of glycol an ti freeze required is based on total system volume including ex pan sion tank volume.
4. Glycol is more dense than water and chang es the viscosity of the system. The addition of glycol will decrease heat transfer and in crease frictional loss in the heating boiler and re lat ed piping. A larg er pump with more capacity may be required to maintain desired flow rates in a glycol system.
5. Local codes may require a back flow preventer or actual disconnect from city water supply when glycol antifreeze is added to the system.
Water Treatment
In hard water areas, water treatment should be used to reduce the introduction of minerals to the sys tem. Minerals in the water can collect in the heat exchanger tubes and cause noise on operation. Excessive build up of minerals in the heat ex chang er can cause a non-warrantable failure.
Intermittent Pilot Spark Ignition System
WARNING
The ignition module is not repairable. Any mod i fi ca tion or repairs will invalidate the warranty and may create hazardous conditions that result in prop er ty damage, personal injury, fire, explosion and/or toxic gases. A faulty ignition module must be re placed with a new module.
6 Start-up
43
Installation & Service Manual
Maintenance and annual startup
Service technician
(see the following pages for instructions)
General:
• Address reported problems
• Inspect interior; clean and vacuum if necessary;
• Check for leaks (water, gas, flue)
• Examine venting system
• Check system water pressure/system piping/expansion tank
• Check control settings
• Check wiring and connections
• Flame inspection (stable, uniform)
• Check flue gas passageways
• Inspect and clean the burners
• Perform start-up checkout and performance verification per Section 6 - Start-up.
If combustion or performance indicate need:
• Clean heat exchanger
• Remove and wash burners
ANNUAL START-UP
Owner maintenance
(see the User’s Information Manual for instructions)
Daily
• Check appliance area
• Check pressure/temperature gauge
Monthly
• Check vent piping
• Check relief valve
Periodically
• Test low water cutoff (if used)
• Reset button (low water cutoff)
Every
6 months
• Check appliance piping (gas and
water) for leaks
• Operate relief valve
End
of season
months
• Shut appliance down (unless boiler used for domestic hot water)
Table 7A_Service and Maintenance Schedules
7 Maintenance
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the appliance or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 7A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.
Electrical shock hazard – Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect appliance area
1. Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.
Inspect appliance interior
1. Remove the outer access panels and inspect the interior of the appliance.
2. Vacuum any sediment from inside the appliance and components. Remove any obstructions.
Eliminate all system or appliance leaks. Continual fresh makeup water will reduce appliance life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
1. Inspect all water and gas piping and verify to be leak free.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 3 - Gas Connections.
Check all piping for leaks
WARNING
WARNING
WARNING
WARNING
CAUTION
Label all wires prior to dis con nec tion when servicing controls. Wiring errors can cause improp er and dangerous operation.
Listed below are items that must be checked to en sure safe reliable operation. Verify proper op er a tion after servicing.
Flue vent system and air supply
1. Examine the venting system at least once a year. Check more often in the first year to de ter mine in spec tion interval. Check all joints and pipe connections for tightness, corrosion or deterioration. Clean louvers and/or screens in the combustion air intake system as required. Have the entire system, including the venting system, periodically inspected by a qualified service agency.
2. Check for gastight seal at every connection, seam of air piping, and vent piping periodically inspected by a qualified service agency.
Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
WARNING
Check water system
1. Verify all system components are correctly installed and operational.
2. Check the cold fill pressure for the system. Verify it is correct (must be a minimum of 12 PSI).
3. Watch the system pressure as the boiler heats up (during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4. Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
7 Maintenance
Installation & Service Manual
44
7 Maintenance (continued)
45
Installation & Service Manual
Check Expansion Tank
1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 - Water Connections for suggested best location of expansion tanks and air eliminators.
Check Relief Valve
1. Inspect the relief valve and lift the lever to verify flow.
Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 4 - Water Connections before proceeding further.
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
WARNING
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
WARNING
46
Installation & Service Manual
Check All Wiring
1. Inspect all wiring, making sure wires are in good condition and securely attached.
Check Control Settings
1. Adjust settings if necessary. See Section 5 - Electrical Connections for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.
Check Burner Flame
Visually check main burner flames at each start-up after long shutdown periods or at least every six months. A burner viewport is located on the burner mounting flange.
Perform Start-up and Checks
1. Start appliance and perform checks and tests specified in Section 6 - Start-up.
2. Verify cold fill pressure is correct and that operating pressure does not go too high.
The area around the burner viewport is hot and direct contact could result in burns.
WARNING
NORMAL
A
YELLOW TIP
B
D
FLAME LIFT
C
YELLOW FLAME
WARNING: The area around the burners is hot and direct contact could result in burns!
Figure 7-1_Flame Pattern Illustration
Normal Flame: A normal flame is blue, with slight yellow tips, with a well defined inner cone and no flame lifting.
Ye l l o w T ip : Yellow tip can be caused by blockage or partial obstruction of air flow to the burner(s).
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to the burner(s) or excessive gas input. This condition MUST be cor rect ed immediately.
Lifting Flames: Lifting flames can be caused by over firing the burner(s) or excessive primary air.
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
Combustion Air
This ap pli ance uses an atmospheric combustion process. Combustion air is provided to the burners by the gas injection pressure into the venturi of the burn ers. The burners do not have an adjustable air shutter. Ad e quate combustion air must be supplied to the room where the appliance is installed to ensure proper burner operation. Check frequently to be sure the flow of com bus tion and ventilation air to the unit is not obstructed. When the main burn ers light, observe the burn er flame. Flames should be light blue in color with slight yellow tips; flames should be settled on burner head with no lifting when supplied with correct vol ume of combustion air.
Check Flue Gas Passageways
Any sign of soot around the outer jacket, at the burn ers or in the areas between the fins on the cop per heat exchanger indicates a need for cleaning. The following cleaning procedure must only be per formed by a qualified serviceman or installer. Prop er service is required to maintain safe operation. Properly installed and ad just ed appliances sel dom need flue cleaning.
All gaskets on disassembled components must be replaced with new gaskets on re as sem bly. Gasket kits are available from your distributor.
NOTICE
Heat Exchanger / Burner Access
WARNING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline Silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines:
7 Maintenance
7 Maintenance (continued)
47
Installation & Service Manual
Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the jobsite conditions. Current NIOSH recommendations can be found on the NIOSH website at (http://www.cdc.gov/niosh/homepage.html). NIOSH approved respirators, manufacturers and phone numbers are also listed on this website.
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to
prevent airborne dust.
Remove combustion chamber lining from the appliance
and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from
other clothing. Rinse clothes thoroughly.
NIOSH stated First Aid:
Eye: Irrigate immediately. Breathing: Fresh air.
a. Turn “OFF” main power to the appliance.
b. Turn “OFF” external manual gas shutoff valve to
appliance.
c. Remove the control panel door.
d. Remove the outer air deflector (FIG. 7-2)
e. Disconnect gas valve wiring and remove gas manifold
assembly.
f. Remove ignition wire leading to the pilot assembly
from the ignition module.
g. Disconnect the wiring from the flame rollout/interlock
switch, see FIG. 5-8, page 39.
h. Remove the lower front jacket panel.
i. Remove the control panel mounting screws. When
removing the control panel, lay the control panel to the side with the wiring intact, being careful not to damage any of the wiring.
Remove the combustion chamber door. Use caution to prevent damage to burn ers, refractory, pilot or wiring.
Inspection and Cleaning
j. Check the heat exchanger surface for sooting. The
external surfaces of the copper tubes should be free of any soot deposits. (A slight black smudge is normal with some types of gases.) If abnormal soot deposits are present, the heat exchanger must be cleaned and the cause of the soot problem corrected. Proceed as follows:
k. Remove soot from burners and bottom of the finned
tubes with a stiff bristle brush. Dirt may also be removed from burner ports by rinsing the burner thor ough ly with water. Drain and dry burners before re-installing. Damaged burners must be re placed.
An appliance installed in a dust or dirt con tam i nat ed atmosphere will require cleaning of the burners on a 3 to 6 month schedule or more often, based on severity of contamination. Contaminants can be drawn in with the combustion air. Non-combustible particulate mat ter such as dust, dirt, concrete dust or dry wall dust can block burner ports and cause non-warrantable failure. Use extreme care when operating an appliance for temporary heat during new construction. The burners will probably re quire a thorough cleaning before the appliance is placed in service.
l. Remove gas manifold as described in steps a. thru e. in
“Heat Exchanger/Burner Access.”
m. Loosen mounting screws and remove front control
panel.
n. Loosen screws on the upper front jack et panel and
remove toward front of the appliance. Use caution to prevent damage to re frac to ry on the doors inner surface.
o. Check “V” baffles on top of the heat ex chang er.
Remove and clean if necessary.
p. Remove soot from the heat exchanger with a stiff
bristle brush. Soot may also be re moved from the heat exchanger by washing thoroughly with detergent and water. Remove the heat exchanger before using water for cleaning. Rinse thoroughly and dry before re-installing. Use a vacuum to remove loose soot from surfaces and in ner chamber.
q. Remove the heat exchanger (HEX) filler bracket
(FIG. 7-2).
r. The heat exchanger can be removed by sliding towards
the front of the appliance. Once the heat exchanger is removed from the ap pli ance, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces.
Installation & Service Manual
48
s. Ensure that all burner ports are cleaned to remove
any soot. See Inspection and Cleaning Procedure, page 47.
t. Carefully re-install the heat exchanger, “V” baffles,
jacket panels, and wires.
u. Reassemble all gas and water piping. Test for gas
leaks.
v. Cycle the appliance and check for prop er operation.
/
Figure 7-2_Outer Air Deflector and HEX Filler Bracket
Water Circulating Pump
Inspect pump ev ery 6 months and oil if required. Use SAE 30 non-detergent oil or lubricant specified by pump man u fac tur er.
Clear Area
1. Keep appliance area clear and free from com bus ti ble materials, gasoline and other flammable vapors and liquids.
2. Check frequently to be sure the flow of com bus tion and ventilation air to the boiler is not obstructed.
Inspection of Heat Exchanger Waterways
Appliances operated in hard water areas should have periodic inspections of the tubes to be sure that no sediment or scale accumulates on the heat transfer sur fac es. Inspection plugs are located at both ends of the heat exchanger. In spec tion plugs should be removed and tubes inspected at the end of the first 45 days of operation and again at the end of 90 days of operation. If no scale accumulation is ob served, inspections can be made at the end of each six months of op er a tion.
IMPORTANT
Upon completion of any testing on the gas system, leak test all gas connections with a soap solution while main burners are operating. Im me di ate ly repair any leak found in the gas train or re lat ed components. Do Not operate an appliance with a leak in the gas train, valves or related piping.
Gas Train and Controls
GAS FLOW
Figure 7-3_Gas Train
Review with owner
1. Review the User’s Information Manual with the owner.
2. Emphasize the need to perform the maintenance schedule specified in the User’s Information Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.
4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
7 Maintenance
OUTER AIR DEFLECTOR
UPPER FRONT JACKET PANEL
DETAIL A
LOWER FRONT JACKET PANEL
HEX FILLER BRACKET
FLAME ROLL-OUT SWITCH INTERLOCK SWITCH
49
Installation & Service Manual
8 Troubleshooting
Step 1:
Step 2:
Step 3:
Is the spark ignitor sparking?
No
Yes
Check continuity on the spark cable. Check for 24 VAC on the 24v terminal (gray wire) on the i
g
nition module.
No
Is there 24 VAC (purple wire) on the 4-pin connector plug on the tem
p
erature controller?
Yes
Replace ignition module.
No
Check 24 VAC at R and W on the terminal strip.
Check each of the following for an open:
-white and purple wire on the LWCO plug
-rollout switch
-manual reset high limit
-spill switch If any of these devices are open, press the reset
b
utton.
Yes
Is there 24 VAC (tan wire) on the 4-pin connector plug on the temperature controller?
Yes
Check each of the following for an open:
- X and B on the terminal strip
-purple and gray wires on the vent damper plug
-V and P on the terminal strip
-auto reset high limit
No
Check voltage to and from the transformer.
No
Check incoming 120 VAC.
Check for an open sensor. If no open sensor, make sure there’s a call for heat. If call for heat is present, replace temperature control.
No
Is the pilot staying on?
No
Yes
Check the pilot tube for gas. Check draft.
Is the gas valve getting 24 VAC to the MV terminal?
No
Replace the ignition module.
Yes
Check gas pressure and make sure gas valve knob is on.
Yes
Troubleshooting Guide: M9 Solution Boilers
50
Installation & Service Manual
Schematic Diagram - M9 Unit
45,000 - 260,000 Btu/hr Models
Wiring Diagram - M9 Unit
45,000 - 260,000 Btu/hr Models
9 Diagrams
51
Notes
Revision A (ECO #C03746) initial release.
SBR-I-S Rev A
5/10
Loading...