LMI Excel XR User Manual

Page 1
Excel® XR Series
Electronic Metering Pump PROFIBUS DP
Manual No.: 55313 Revision Rev. Date: 0
Note:
and
enhanced control features see manual
-V0 Manual
: 04
3/2020
For enhanced control features see manual 54630
54772
Page 2
Table of Contents
Precautions ....................................................................................... 3
1.0
2.0 Introduction ...................................................................................... 5
2.1 Specifications .................................................................................................. 5
3.0 Local Operation ................................................................................ 5
3.1 Display Navigation .......................................................................................... 6
3.2 Settings ........................................................................................................... 6
3.2.1 PROFIBUS Communication Settings ...................................................... 7
4.0 PROFIBUS Software Definition........................................................ 8
4.1 PROFIBUS Configuration................................................................................ 8
4.1.1 Modules 0-8: Basic Control ..................................................................... 8
4.1.2 Modules 9-24: Operation Mode Configuration......................................... 9
4.1.3 Modules 26-42: Timed Event Configuration .......................................... 10
4.1.4 Modules 43-57: Input/Output Configuration .......................................... 11
4.1.5 Modules 58-64: System Settings ........................................................... 12
4.1.6 Modules 65-68: Read-Only Version Information ................................... 13
4.1.7 Modules 69-94: Read-Only Information ................................................ 13
5.0 Cable Wiring ................................................................................... 16
6.0 Troubleshooting ............................................................................. 18
Table of Figures
Figure 1: Display Navigation ........................................................................................... 6
Figure 2: Settings ............................................................................................................ 6
Figure 3: Internal Termination Resistors ......................................................................... 7
Figure 4: Communication Settings .................................................................................. 7
Figure 5: Connector C Pin Diagram .............................................................................. 16
Page 3

1.0 Precautions

The following precautions should be taken when working with LMI metering pumps. Please read this section carefully prior to installation.
PRECAUTIONS
Protective Clothing
ALWAYS wear protective clothing, face shield, safety glasses and gloves when working on or near your metering pump. Additional precautions should be taken depending on the solution being pumped. Refer to Safety Data Sheets (SDS) precautions from your solution supplier.
Water Pre-Prime
All LMI pumps are pre-primed with water when shipped from the factory. If your solution is not compatible with water, disassemble the Pump Head Assembly. Thoroughly dry the pump head, valves, O-rings, balls and diaphragm. Reassemble head assembly tightening screws in a crisscross pattern. Refill the pump head with the solution to be pumped before priming the pump. (This will aid in priming.)
Liquid Compatibility
CAUTION: The evaluation performed by ETL was tested with water only. The pumps are certified to NSF 61 with: sodium hypochlorite (12.5%), sulfuric acid (98.5%), sodium hydroxide (50%), and hydrochloric acid (30%). Determine if the materials of construction included in the liquid handling portion of your pump are adequate for the solution (chemical) to be pumped. Always refer to the solution supplier and the LMI Chemical Resistance Chart for compatibility of your specific LMI metering pump. Contact your local LMI distributor for further information.
Tubing Connections
Inlet and outlet tubing or pipe sizes must not be reduced. Outlet tubing size must not be increased. Make certain that all tubing is SECURELY ATTACHED to fittings prior to start-up (see section 3.3 Tubing Connections). ALWAYS use LMI supplied tubing with your pump, as the tubing is specifically designed for use with the pump fittings. It is recommended that all tubing be shielded and secure to prevent possible injury in case of rupture or accidental damage. If tubing is exposed to sunlight, black UV resistant tubing should be installed. Check tubing frequently for cracks and replace as necessary.
Fittings and Machine Threads
All fittings should be hand-tightened. An additional 1/8 - 1/4 turn after the fitting is snug may be necessary to provide a leak-proof seal. Excessive overtightening or use of a pipe wrench can cause damage to the fittings, seals, or pump head.
Most LMI pumps have straight screw machine threads on the head and fittings and are sealed by the O-rings. DO NOT use PTFE tape or pipe dope to seal these threads. PTFE Tape may only be used on NPT threads.
Plumbing
Always adhere to your local plumbing codes and requirements. Be sure installation does not constitute a cross connection. Check local plumbing codes for guidelines. LMI is not responsible for improper installations.
Page 4
Back Pressure/Anti-Syphon Valve
PRECAUTIONS
If you are pumping downhill or into low or no system pressure, a backpressure /anti-syphon device should be installed to prevent over pumping or syphoning. Contact your LMI distributor for further information.
Electrical Connections
WARNING: To reduce the risk of electrical shock, the metering pump must be plugged into a properly grounded grounding-type receptacle with ratings conforming to the data on the pump control panel. The pump must be connected to a good ground. Do not use adapters! All wiring must conform to local electrical codes. If the supply cord is damaged, it must be replaced by the manufacturer, stocking distributor, or authorized repair center in order to avoid a hazard.
Fuse and Battery
CAUTION: Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire. The battery and fuse are internal, factory serviceable parts, and must be replaced by the factory or a qualified distributor with parts of the same type and rating.
Flooding
WARNING: Install this pump in a location where flooding cannot occur.
Ground Fault Circuit Interrupter
WARNING: To reduce the risk of electric shock, install only on a circuit protected by a Ground Fault Circuit Interrupter (GFCI).
Line Depressurization
To reduce the risk of chemical splash during disassembly or maintenance, all installations should be equipped with line depressurization capability.
Over Pressure Protection
To ensure safe operation of the pump it is recommended that some type of safety / pressure­relief valve be installed to protect the piping and other system components from failing due to excessive pressure.
Chemical Concentration
There is a potential for elevated chemical concentration during periods of no flow, for example, during backwash in the system. Steps, such as turning the pump off, should be taken during operation or installation to prevent this.
See your distributor about other external control options to help mitigate this risk.
Retightening Components
Plastic materials will typically exhibit creep characteristics when under pressure over a period of time and to insure a proper fit it may be necessary to retighten the head bolts periodically. To insure proper operation, we recommend tightening the bolts to 25 inch-pounds after the first week of operation and on a monthly basis thereafter.
Page 5
Flow Display
INTRODUCTION
Spills
The accuracy of the flow value as shown on the pump display is highly dependent on the specific application. Calibration is necessary in order to display an accurate measure of the flow.
CAUTION: Spills of Dangerous chemicals should be cleaned up immediately.

2.0 Introduction

LMI's metering pumps deliver the highest level of repetitive accuracy and reliability with the capability to pump a wide range of chemicals. Our comprehensive selection of pumps means you get the right pump for the right application. Every one of our pumps is engineered to exceed expectations and is backed by a global network of highly trained field engineers and aftersales support.
The PROFIBUS DP interface conforms to the PROFIBUS DP-V0 standard for cyclic data transmission. This manual assumes the reader is familiar with commissioning and programming PROFIBUS devices.

2.1 Specifications

Table 1: PROFIBUS DP Specifications
PROFIBUS Implementation Class DP-V0
PROFIBUS Connector 5 Pin Reverse Key Female M12 (B-Code)
Maximum Cable Length 1200 meters at 9.6 Kbits/s
Slave Address Range 1-125
Line Termination On/Off (Software Configurable)
Supported transmission speeds 9600 to 12 Mbit/s (auto detected)

3.0 Local Operation

This manual covers basic features supported in the Excel® XR Series pumps and complete descriptions of PROFIBUS features.
1000 meters at 115.2 Kbits/s
200 meters at 1.5 Mbits/s
100 meters at 12 Mbits/s
Page 6
Scroll Bar
Multi-Function Icons

3.1 Display Navigation

Navigation through display screens is done using the Up, Down, and Multi-Function buttons. The settings screen is shown in the example below (Figure 1: Display Navigation). The scroll bar on the side of the display screen indicates there are more settings available on another page.
Figure 1: Display Navigation
LOCAL OPERATION

3.2 Settings

To access the settings screen (Figure 2) press Settings in the home screen. Navigate
to the function desired and press Enter . Follow the prompts to enter new settings. New
settings will need to be saved by pressing Save . Press Exit to return to the previous screen without saving.
Figure 2: Settings
Page 7

3.2.1 PROFIBUS Communication Settings

From the Settings screen, navigate to the Communication Settings icon and press Enter
. The Communication Settings screen (Figure 4) will allow for the following settings to
be adjusted:
The Slave Address can be configured via software in the range of 1-125.
The Internal Line Termination can also be enabled/disabled on this screen. The
final device on the communication bus must have line termination enabled. This can be accomplished externally or using the software enabled internal line termination. The Internal Line Termination will engage the following internal termination resistors:
LOCAL OPERATION
Figure 3: Internal Termination Resistors
Figure 4: Communication Settings
Page 8
PROFIBUS SOFTWARE DEFINITION
Module
Name
Description
Direction
Data Type
0
Device Control
Bitmask. Set the desired bit high execute the
Bit 7 - Force Homescreen Display
Input/Output
UINT8
1
Operation Mode
Bitmask. Set the desired bit high force the
Bit 5 = Timed Event (Internal)
Input/Output
UINT8
2
Manual Flow Rate Control
XX.XX in the current units (i.e. GPH/LPH). The range is 0-9999.
Input/Output
UINT16
3
Prime Flow Rate Control
XX.XX in the current units (i.e. GPH/LPH). The range is 0-9999.
Input/Output
UINT16
4
Prime Flow Duration
Seconds. The range is 1-3600.
Input/Output
UINT16
5
Power Loss Mode
Bitmask. Set the desired bit high set the
Bit 2 = Run at a configured speed
Input/Output
UINT8
6
Resume Speed
XX.XX GPH/LPH format. The range is 0-9999.
configured speed'.
Input/Output
UINT16
7
Slow Mode Setpoint
Range of 10-90 in increments of 10.
Input/Output
UINT8

4.0 PROFIBUS Software Definition

4.1 PROFIBUS Configuration

Each function available via the PROFIBUS is defined in a Module. Each Module must be loaded sequentially. If any Modules are skipped or loaded in the wrong order, the configuration will fail.

4.1.1 Modules 0-8: Basic Control

associated function: Bit 0 - Toggle OnOff Bit 1 - Toggle Prime Mode Bit 2 - Toggle 100pct Mode Bit 3 - Force IntExt Bit 4 - Toggle Slow Mode Bit 5 - Toggle Units Bit 6 - Reset Totalizer
Power Loss
associated operation mode: Bit 0 = Manual (Local only) Bit 1 = Analog (External) Bit 2 = Pulse (External) Bit 3 = Batch (External) Bit 4 = Cycle Timer (Internal)
associated option: Bit 0 = Resume Operation Bit 1 = Stay Idle
This flowrate is applied on power up if the power loss option is set to 'Run at a
Page 9
PROFIBUS SOFTWARE DEFINITION
8
Alarm Status
Bit 10 - Pulse Signal Overrange
Output
UINT16
Module
Name
Description
Direction
Data Type
9
Pulse Mode Count
Range of 1-10,000.
Input/Output
UINT16
10
Pulse Mode Volume
XXXXX.XX mL. Range is 0 to 1000000.
Input/Output
UINT32
11
Pulse Mode Units
Enumeration (0=Small, 1=Large). Large will
global units setting.
Input/Output
BOOL
12
Pulse Mode Pulse Width
msec. The valid range is 4 - 60 in increments of 4.
Input/Output
UINT8
13
Batch Mode Volume
XXXXX.XX mL. The valid range is 0 to
1000000.
Input/Output
UINT32
14
Batch Mode Time
Seconds. Range is 1-86400.
Input/Output
UINT32
15
Batch Mode Units
Enumeration (0=Small, 1=Large). Large will
global units setting.
Input/Output
BOOL
16
Batch Mode Pulse Width
msec. Range is 4 - 60 in increments of 4.
Input/Output
UINT8
17
Batch Mode Accumulate
Enumeration (0 = Off, 1 = On).
Input/Output
BOOL
18
Analog Mode P1 Flowrate
XX.XX in the current units (i.e. GPH/LPH). The range is 0-9999.
Input/Output
UINT16
19
Analog Mode P1 Current
XX.X mA. Range is 0.0-20.0.
Input/Output
UINT8
20
Analog Mode P2 Flowrate
XX.XX in the current units (i.e. GPH/LPH). Range is 0-9999.
Input/Output
UINT16
21
Analog Mode P2 Current
XX.X mA. Range is 0-200.
Input/Output
UINT8
22
Status
the period of active pumping.
Input/Output
UINT16
23
Cycle Timer Duration
Minutes. Range is 1-1439. The Duration is the inactive period.
Input/Output
UINT16
Returned as a bitmask with a high bit to indicate the status of each item: Bit 0 - Global Alarm Bit 1 - User Alarm Bit 2 - Tank Empty Bit 3 - Tank Low Bit 4 - Internal System Error Bit 5 - Motor Stall Bit 6 - Analog Loss of Signal Bit 7 - Analog Overrange Bit 8 - Motor Homing Error Bit 9 - Pulse Signal not Present

4.1.2 Modules 9-24: Operation Mode Configuration

Cycle Timer Mode
use Gallons or Liters based on global units setting. Small will use fl oz. or mL based on
use Gallons or Liters based on global units setting. Small will use fl oz. or mL based on
Minutes. Range is 1-1439. The Cycle Time is
Page 10
PROFIBUS SOFTWARE DEFINITION
24
Delay Timer
Minutes. Range is 1-1439. The Delay Timer is
cycle.
Input/Output
UINT16
25
Cycle Timer Flow Rate
XX.XX in the current units (i.e. GPH/LPH). The range is 0-9999.
Input/Output
UINT16
Module
Name
Description
Direction
Type
26
Select
Integer (1-7) that represents a day of the week.
based on the set day.
Input/Output
UINT8
27
Start Time
Hour (00-23), MM = Minute (00-59).
Input/Output
UINT16
28
Timed Event1 Duration
Integer representing minutes with a valid range of 1-1439.
Input/Output
UINT16
29
Timed Event1 Flow
Integer representing XX.XX GPH/LPH format. The range is 0-9999.
Input/Output
UINT16
30
Timed Event1 Enabled
Enumeration (0 = OFF, 1 = ON).
Input/Output
BOOL
31
Start Time
Hour (00-23), MM = Minute (00-59).
Input/Output
UINT16
32
Timed Event2 Duration
Integer representing minutes with a valid range of 1-1439.
Input/Output
UINT16
33
Timed Event2 Flow
Integer representing XX.XX GPH/LPH format. The range is 0-9999.
Input/Output
UINT16
34
Timed Event2 Enabled
Enumeration (0 = OFF, 1 = ON).
Input/Output
BOOL
35
Start Time
Hour (00-23), MM = Minute (00-59).
Input/Output
UINT16
36
Timed Event3 Duration
Integer representing minutes with a valid range of 1-1439.
Input/Output
UINT16
37
Timed Event3 Flow
Integer representing XX.XX GPH/LPH format. The range is 0-9999.
Input/Output
UINT16
38
Timed Event3 Enabled
Enumeration (0 = OFF, 1 = ON).
Input/Output
BOOL
39
Start Time
Hour (00-23), MM = Minute (00-59).
Input/Output
UINT16
40
Timed Event4 Duration
Integer representing minutes with a valid range of 1-1439.
Input/Output
UINT16
41
Timed Event4 Flow
Integer representing XX.XX GPH/LPH format. The range is 0-9999.
Input/Output
UINT16
42
Timed Event4 Enabled
Enumeration (0 = OFF, 1 = ON).
Input/Output
BOOL
Cycle Timer
the first inactive period prior to starting the

4.1.3 Modules 26-42: Timed Event Configuration

This must be set prior to configuring event
Timed Event Day
Timed Event1
Timed Event2
parameters. The other timed events will be
4 decimal digit format (HHMM). Range HH =
4 decimal digit format (HHMM). Range HH =
Data
Timed Event3
Timed Event4
4 decimal digit format (HHMM). Range HH =
4 decimal digit format (HHMM). Range HH =
Page 11
PROFIBUS SOFTWARE DEFINITION
Module
Name
Description
Direction
Data Type
43
Config
Enumeration with a range 0-5. The
5: Digital Input = PacingPulse
Input/Output
UINT8
44
Digital Input 1 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
45
Config
Enumeration with a range 0-5. The
5: Digital Input = PacingPulse
Input/Output
UINT8
46
Digital Input 2 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
47
Config
Enumeration with a range 0-5. The
5: Digital Input = PacingPulse
Input/Output
UINT8
48
Digital Input 3 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
49
Config
Enumeration with a range 0-5. The
5: Digital Input = PacingPulse
Input/Output
UINT8
50
Digital Input 4 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
51
Config
Enumeration with a range 0-2. The
2: Analog Input = Level
Input/Output
UINT8
52
Config
Enumeration with a range 0-2. The
2: Analog Input = Level
Input/Output
UINT8

4.1.4 Modules 43-57: Input/Output Configuration

enumeration is as follows: 0: Digital Input = Disabled 1: Digital Input = RemoteOnOff 2: Digital Input = FloatSwitch_Empty 3: Digital Input = FloatSwitch_Low
Digital Input 1
Digital Input 2
4: Digital Input = RemoteIntExtMode
enumeration is as follows: 0: Digital Input = Disabled 1: Digital Input = RemoteOnOff 2: Digital Input = FloatSwitch_Empty 3: Digital Input = FloatSwitch_Low 4: Digital Input = RemoteIntExtMode
Digital Input 3
Digital Input 4
Analog Input 1
enumeration is as follows: 0: Digital Input = Disabled 1: Digital Input = RemoteOnOff 2: Digital Input = FloatSwitch_Empty 3: Digital Input = FloatSwitch_Low 4: Digital Input = RemoteIntExtMode
enumeration is as follows: 0: Digital Input = Disabled 1: Digital Input = RemoteOnOff 2: Digital Input = FloatSwitch_Empty 3: Digital Input = FloatSwitch_Low 4: Digital Input = RemoteIntExtMode
enumeration is as follows: 0: Analog Input = Disabled 1: Analog Input = Pacing
Analog Input 2
enumeration is as follows: 0: Analog Input = Disabled 1: Analog Input = Pacing
Page 12
PROFIBUS SOFTWARE DEFINITION
53
Config
8: Digital Output = TimedEvent
Input/Output
UINT8
54
Digital Output 1 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
55
Config
8: Digital Output = TimedEvent
Input/Output
UINT8
56
Digital Output 2 State
Enumeration (0=NO - Normally Open, 1=NC
- Normally Closed).
Input/Output
BOOL
57
Config
Enumeration with a range 0-2. The
2: Analog Output = MirrorInput
Input/Output
UINT8
Module
Name
Description
Direction
Data Type
58
Mode
Enumeration
2=Weekly Timer
Input/Output
UINT8
59
Mode
Enumeration
2 = Batch
Input/Output
UINT8
60
Lock Style
Enumeration
5=All_Lock_Power_Password).
Input/Output
UINT8
61
Password
Integer with a range of 0000-9999.
Input/Output
UINT8
Enumeration with a range 0-8. The enumeration is as follows: 0: Digital Output = Disabled 1: Digital Output = StrokePulse 2: Digital Output = PumpRunning 3: Digital Output = PumpStandby 4: Digital Output = AlarmOut 5: Digital Output = INTEXTMode 6: Digital Output = UserAlarmOut
Digital Output 1
Digital Output 2
7: Digital Output = PumpStopped
Enumeration with a range 0-8. The enumeration is as follows: 0: Digital Output = Disabled 1: Digital Output = StrokePulse 2: Digital Output = PumpRunning 3: Digital Output = PumpStandby 4: Digital Output = AlarmOut 5: Digital Output = INTEXTMode 6: Digital Output = UserAlarmOut 7: Digital Output = PumpStopped
enumeration is as follows: 0: Analog Output = Disabled
Analog Output
1: Analog Output = Flow

4.1.5 Modules 58-64: System Settings

0 = Manual
Remote Internal
Remote External
1 = Cycle Timer
0= mA 1= Pulse
1=No_Lock 2=All_Lock, 3=All_Lock_Power_Unlock, 4=All_Lock_Password,
Page 13
PROFIBUS SOFTWARE DEFINITION
62
Clock
(XXYYMMDDXXhhmmss):
ss = Seconds (00-59)
Input/Output
UINT64
63
User Alarm Mask
Bit 10 - Pulse Signal Overrange
Input/Output
UINT16
64
System Units
Enumeration (0 = English, 1 = Metric).
Input/Output
UINT8
Module
Name
Description
Direction
Data Type
65
Version
Range is 0-65535 as an integer that must be
FFFF representing X.X.X.X.
Output
UINT16
66
Version
Range is 0-65535 as an integer that must be
FFFF representing X.X.X.X.
Output
UINT16
67
Version
Range is 0-65535 as an integer that must be
FFFF representing X.X.X.X.
Output
UINT16
68
Firmware Version
Range is 0-65535 as an integer that must be
FFFF representing X.X.X.X.
Output
UINT16
Module
Name
Description
Direction
Data Type
69
LCD Contrast
Integer representing 0-100%.
Output
UINT8
XX = Unused (N/A) YY = Year (00-99) MM = Month (1-12) DD = Day (1-31) XX = Unused (N/A) hh = Hour (01-24) mm = Minute (00-59)
Bitmask. Set desired bits high to trigger user alarm when associated alarm is active. Bit 0 - Reserved Bit 1 - Reserved Bit 2 - Tank Empty Bit 3 - Tank Low Bit 4 - Internal System Error Bit 5 - Motor Stall Bit 6 - Analog Loss of Signal Bit 7 - Analog Overrange Bit 8 - Motor Homing Error Bit 9 - Pulse Signal not Present

4.1.6 Modules 65-68: Read-Only Version Information

Main Firmware
I/O Firmware
Display Firmware
Display EEPROM
converted to hex to be read as 0000-
converted to hex to be read as 0000-
converted to hex to be read as 0000-
converted to hex to be read as 0000-

4.1.7 Modules 69-94: Read-Only Information

Page 14
PROFIBUS SOFTWARE DEFINITION
70
Model ID
Enumeration for the pump output code. The
bar)
Output
UINT8
71
Language
Enumeration
5=Chinese
Output
UINT8
72
Current Flow Rate
Integer representing XX.XX GPH/LPH format.
Output
UINT16
73
Flow Percentage
Integer representing XXX.XX%.
Output
UINT16
74
Analog Input 1
Integer representing XX.X mA.
Output
UINT16
75
Analog Input 2
Integer representing XX.X mA.
Output
UINT16
76
Analog Output
Integer representing XX.X mA.
Output
UINT16
77
Totalizer
Strokes
Integer representing number of strokes.
Output
UINT32
78
Totalizer
Volume
current unit setting.
Output
UINT64
79
Totalizer User Hours
Integer representing number of hours.
Output
UINT32
80
Totalizer
Cycles
Integer representing the number of Power Cycles.
Output
UINT16
81
Totalizer Unit Strokes
Integer representing number of strokes.
Output
UINT32
82
Totalizer Unit Volume
Integer representing Gal or L depending on current unit setting.
Output
UINT64
83
Totalizer Unit Hours
Integer representing number of hours.
Output
UINT32
84
Totalizer
Cycles
Integer representing the number of Power Cycles.
Output
UINT16
85
Volume
This is the maximum flow rate of the pump based
representing XX.XX GPH/LPH.
Output
UINT16
86
Batch Mode
Volume
current unit setting.
Output
UINT32
87
Batch Mode
Dosing Time
Integer representing number of seconds.
Output
UINT32
output code is associated with the maximum flow rate of the pump: 2: Output Code 2 - 5.6 GPH (21.2 l/h) 175 psi (12.0 bar) 3: Output Code 3 - 14.0 GPH (53.0 l/h) 75 psi (5.0 bar) 4: Output Code 4 - 18.0 GPH (68.1 l/h) 50 psi (3.5
1=English 2=French 3=Portuguese 4=Spanish
User
User
User Power
Unit Power
Calibrated
Remaining
Integer representing Gal or L depending on
on the calibration and is stored as an integer
Integer representing Gal or L depending on
Remaining
Page 15
PROFIBUS SOFTWARE DEFINITION
88
Cycle Time
Delay Left
Integer representing number of seconds.
Output
UINT32
89
Cycle Time
Time Left
Integer representing number of seconds.
Output
UINT32
90
Cycle Time
Time Left
Integer representing number of seconds.
Output
UINT32
91
Weekly
Run Time
Integer representing number of seconds.
Output
UINT32
92
Statuses
Returned as a bitmask with a high bit to indicate
Yes)
Output
UINT16
93
Status
Returned as a bitmask with a high bit to indicate
Switched)
Output
UINT16
94
Status
Returned as a bitmask with a high bit to indicate
Switched)
Output
UINT16
95
Start Batch
mode
Output
UINT8
Mode Startup
Mode Run
Mode Cycle
Event Remaining
the status of each item: Bit 0: Running Status (0 = stopped, 1 = running) Bit 1: Internal/External Operating Mode (0 = internal, 1 = external) Bit 2: Tank Low (0 = Not low, 1 = Tank Low) Bit 3: Tank Empty (0 = Not empty, 1 = Tank empty) Bit 4: 100% Mode (0 = No, 1 = Yes) Bit 5: Prime Mode (0 = No, 1 = Yes) Bit 6: Slow Mode (0 = No, 1 = Yes) Bit 7: Current Units (0 = English, 1 = Metric) Bit 8: Pump Calibration Status (0 = No, 1 = Yes) Bit 9: Keypad Locked Status (0 = No, 1 = Yes) Bit 10: Home Screen Displayed (0 = No, 1 = Yes) Bit 11: Batch Mode Dosing Active (0 = No, 1 = Yes) Bit 12: Cycle Timer Startup Delay (0 = No, 1 = Yes) Bit 13: Cycle Timer Pump Active (0 = No, 1 = Yes)
Pump
Bit 14: Weekly Timed Event Active (0 = No, 1 =
the status of each item: Bit 1: Digital Input 1 (0 = Unswitched, 1 =
Digital Input
Digital Outputs
Switched) Bit 2: Digital Input 2 (0 = Unswitched, 1 = Switched) Bit 3: Digital Input 3 (0 = Unswitched, 1 = Switched) Bit 4: Digital Input 4 (0 = Unswitched, 1 =
the status of each item: Bit 1: Digital Output 1 (0 = Unswitched, 1 = Switched) Bit 2: Digital Output 2 (0 = Unswitched, 1 =
Set ON to start a batch while the pump is in batch
Input /
Page 16
CABLE WIRING
96
Status
Enable / Disable StayPrime
Output
UINT8
97
Idle Minutes
Output
UINT16
98
Seconds
Output
UINT8
99
StayPrime
Remaining
Output
UINT32
100
StayPrime
Remaining
Seconds remaining before run ends
Output
UINT8
1
VP (5 V)
2
RxD/TxD-N
3
DGND
4
RxD/TxD-P
5
N/A
Thread: Shield (earth ground)
3
2
StayPrime
Input /
StayPrime
StayPrime Run
Idle Seconds
Run Seconds

5.0 Cable Wiring

The Excel® XR pump provides a 5-pin Reverse Key Female M12 (B-Code) connector with the following pin-out:
Stayprime Idle time
StayPrime Run time
Seconds remaining before run begins
Connector Pin #
Input /
Input /
Function
C
Figure 5: Connector C Pin Diagram
The M12 circular connector conforms to IEC 60947-5-2 or IEC 61076-2-101 per the PROFIBUS Interconnection Technology Guideline 2.142 Version 1.4. The shield of the cable should be connected to protective ground on both sides and with good conductivity.
PROFIBUS DP compliant connectors and cables should be used. The following parts have been verified:
Description Manufacturer Part Number
2 meter cable with M12 Mating connector and Flying Leads Turck RSSW 590-2M
Page 17
CABLE WIRING
Page 18
TROUBLESHOOTING
Pump does not start when commanded via PROFIBUS

6.0 Troubleshooting

PROBLEM POSSIBLE CAUSE SOLUTION
Configuration Fault 1. Not all modules included 1. Include all PROFIBUS Data Modules
2. Modules in wrong order 2. Include all PROFIBUS Data Modules in sequential order
Slave not found
1. Incorrect Slave Address 1. Verify the slave address on the pump UI matches the slave address on the master
2. Improper line termination 2. If the pump is the last slave on the bus, enable the internal line termination or use an external terminating resistor
3. Incorrect Wiring 3. Verify wiring is correct per
Figure 5: Connector C Pin Diagram
4. Pump not powered 4. Verify the pump is powered on
1. Homescreen is not displayed on pump
2. Pump is not in manual mode
1. Check the pump display and press the X button to return to the homescreen. Alternatively, use Module 90 to query whether the homescreen is displayed and Module 0 to force the homescreen to be displayed.
2. If the pump is in an external mode or a timed event or timed cycle mode, starting the pump will activate the pump, but the pump will not run unless the external trigger is provided (i.e. pulse, analog input, time of day). Change the pump to manual mode with Module 1.
Page 19
About Ingersoll Rand
Ingersoll Rand (NYSE:IR), driven by an entrepreneurial spirit and ownership mindset, is committed to helping make life better. We provide innovative and mission-critical industrial, energy, medical and specialty vehicle products and services across 40+ respected brands designed to excel in even the most complex and harsh conditions where downtime is especially costly. Our employees connect to customers for life by delivering proven expertise, productivity and efficiency improvements. For more information, visit www.IRCO.com
.
LMI is a registered trademark of Milton Roy, LLC. EXCEL is a registered trademark of Milton Roy, LLC Fluorofilm is a trademark of Milton Roy, LLC
info@lmipumps.com www.lmipumps.com
© 2017 Milton Roy, LLC
Loading...