LK Systems S2, 24 V NO Assembly Instructions Manual

Page 1
1 (4)
Functional description
Normal mode for the room thermostat when in operation is displaying current room tempera­ture.
The temperature setting of the room thermostat can be changed using the “arrow up” or “ar­row down” touch buttons. When the buttons are touched, the temperature display shows more brightly. The thermostat is then displaying the set/desired room temperature. Once changes have been made with the “arrow up” or “arrow down” buttons, the thermostat returns to a redu­ced brightness level, once again displaying the current room temperature.
The thermostat comes with a function LED which shows whether the set temperature has been reached or not. If the LED is off, the set tempera­ture has been reached.
Installation
When tting, bear the following in mind:
• Fitting height, approx. 1.5 m above oor level.
• Best installed on an inner wall.
• Make sure there is circulation of air.
• Avoid secondary heat from other heat sources, such as sunlight, lighting, etc.
Electrical connection
1. Remove the back cover of the thermostat.
2. Fit the back cover to the wall. If the back cover is to be tted to an electrical box, the pattress which comes supplied with the thermostat should be used.
3. Electrical installation must be performed as per the circuit diagram below.
LK Room Thermostat S2 is an electronic room thermostat with a triac output specially adapted for the LK Floor Heating System. The room ther­mostat is used together with electrothermal ac­tuators of normally closed (NC) type. To achieve maximum energy efciency the thermostat uses so-called self-modulating technology via signal pulses to the valve actuator. The self-modulating technology adjusts the output of the underoor heating to the set temperature. Once the room temperature approaches the set temperature, the output of the heating is gradually reduced to pre­vent overheating.
LK Room Thermostat S2, 24V NC is available in two different designs, S2 and S2 EXT, where S2 EXT can be connected to LK Remote Sensor ICS/S2 for controlling e.g. oor temperature. The room thermostat is also used in so-called public environments, where the temperature setting of the thermostat can be locked by pressing buttons in combination.
Product range
• LK Room Thermostat S2 NC (Article no. 243 43 98): Basic thermostat for con­trolling room temperature
• LK Room Thermostat S2 EXT NC (Article no. 243 44 00): Thermostat for controlling room temperature or for controlling e.g. oor temperature via LK Remote Sensor ICS/S2
(Article no. 241 73 23).
Accessories
• LK Remote Sensor ICS/S2, matches room ther­mostat S2 EXT (Article no. 241 73 23)
Spare parts
• LK Pattress S2, comes supplied with the thermo­stat, (Article no. 33454)
Particular benefits to note:
• Self-modulating technology via signal pulses for maximum energy efciency.
• Modern design with polished vitreous surface and touch temperature setting.
• Intended for mounting directly on a wall, or on an electrical installation box.
• Option of connecting a remote temperature sen­sor for model S2 EXT.
• The room thermostat settings can be locked by pressing buttons in combination.
• The temperature can be reduced via a separate timer (timer not included).
• Silent thermostat function.
• Easy functional check via LED.
LK Room Thermostat S2, 24 V NC
EN.33.C.149.1511
Assembly instructions | LK Room Thermostat S2, 24 V NC
Page 2
2 (4)
EN.33.C.149.1511
Assembly instructions | LK Room Thermostat S2, 24 V NC
Temperature locking
For installation in e.g. a public environment, locking of the thermostat’s temperature setting may be needed.
• Locking is performed by pressing buttons in combination. Hold both buttons, i.e. “arrow up” and “arrow down” down for approxima­tely 20 seconds. When the function is active, the thermostat displays “LOC” for lock, i.e. the thermostat is locked. The room thermo­stat will then return to displaying the current room temperature. If someone tries to change the temperature, the thermostat will display “LOC” to show that the thermostat is locked.
• Unlocking is performed in the same way as locking, i.e. hold both buttons (i.e. “arrow up” and “arrow down”) down together for approximately 20 seconds. The room thermo­stat shows that the function has been deac­tivated by displaying “OPn” for open.
Text message for locked temperature setting
Unlocked temperature setting, displayed on unlocking
Note: If LK Connection box NC or LK Con­nection Box 1 is used, follow the circuit diagram of the product in question instead.
Removal of the thermostat back cover
24V~
1
2
45
Connecting LK Room Thermostat S2
24V~
1
2
45
11
12
Connecting LK Room Thermostat S2 EXT with option of connecting a remote sensor
Page 3
3 (4)
EN.33.C.149.1511
Assembly instructions | LK Room Thermostat S2, 24 V NC
Connection of LK Remote Sensor ICS/S2
LK Remote Sensor ICS/S2 is designed to be used together with LK Room Thermostat S2 EXT when e.g. oor temperature is to be controlled. The sensor is connected to terminal 11 and 12 of the thermostat, see circuit diagram. If necessary, the remote sensor can be connected by extension ca­ble up to 50 metres. For extension purposes, use the same cable area as the sensor, or a larger one. Note: Avoid routing in parallel with a high vol­tage installation, e.g. on cable tray.
Position the remote sensor as follows:
Concrete & screed encapsulated systems
Before applying the concrete or screed, a conduit is normally positioned approximately 1.5 met­res into the room. Note that positioning should be at a point which is representative of the sur­face/zone which is to be controlled. The end of the sensor must terminate centrally between two oor heating pipes. Seal the end of the conduit with tape or similar so that concrete cannot enter it. Try to position the conduit as high as possible in the structure, as this will result in better per­formance when controlling the oor surface tem­perature. Insert the remote sensor in the conduit before applying concrete or screed and connect to the thermostat as described above.
LK HeatFloor 22, LK EPS 30/50/70 or LK Silencio
Cut a slot in the top of the slotted board. Position a conduit in the cut slot, terminate the conduit centrally between two heat distribution plates. Note that positioning should be at a point which is representative of the surface/zone which is to be controlled. Insert the remote sensor in the conduit before laying the oor and connect to the thermostat as described above.
Underfloor heating in secondary spaced boarding
Position a conduit between two heat distribution plates and secure the conduit in the edge of the se­condary spaced boarding using conduit clamps. Note that positioning should be at a point which is representative of the surface/zone which is to be controlled. Insert the remote sensor in the conduit before laying the oor and connect to the thermostat as described above.
Switching off the temperature display and LED
The temperature display and function LED on the room thermostat can be switched off. The thermostat is still active after the temperature display and LED have been switched off. To read off or change the temperature, the temperature display comes on once one of the touch buttons is touched. The thermostat then returns to unlit mode. Switching off the temperature display is ideal for bedrooms.
• The temperature display of the room ther­mostat is switched off by holding down the right arrow button for approximately ve seconds. When the function is active, the thermostat shows “doF” for display off.
• To return to normal temperature display (on), hold the right arrow button down for approximately ve seconds. When the fun­ction is deactivated, the thermostat will show “don” for display on.
Text message for switch-off of temperature display
Text message for return to temperature display “on”
Page 4
4 (4)
EN.33.C.149.1511
Assembly instructions | LK Room Thermostat S2, 24 V NC
Temperature range for self-modulation
Self modulation 0%
Self modulation changing
Self modulation 100%
Temperature range for self-modulation, cycle time 42 min.
Energy declaration in accordance with EU 811/2013
Temperature regulator class IV
Temperature regulator’s contribution to
seasonal space heating energy efciency
2%
Dimensions
80
112
16
LK EPS 16
Position a conduit along the long side of the oor heating installation so that it is pointing towards the nearest short side. At the short side cut a jack approximately 2 metres long in the EPS board measured from the short side. The conduit is po­sitioned in this jack. Insert the remote sensor in the conduit before laying the oor and connect to the thermostat as described above. Note that positioning should be at a point which is repre­sentative of the surface/zone which is to be con­trolled.
LK Clip Rail 8/ LK Clip Rail 12
Position a conduit along the long side of the oor heating installation so that it is pointing towards the nearest short side. At the short side, route the conduit in the centre between two oor heating pipes and connect as normal approximately 1.5 metres in. Seal the end of the conduit with tape or similar so that concrete/ooring compound cannot enter it. Insert the remote sensor in the conduit before applying concrete or screed and connect to the thermostat as described above. Note that positioning should be at a point which is representative of the surface/zone which is to be controlled.
Technical Data LK Room Thermostat S2
Voltage 24 V AC (20….30 V, 50….60 Hz) NC normally closed
Switching capacity max 22 W (625 mA)
Intrinsic power 2 W
Maximum of ve LK Actuator 24 V NC items per room
thermostat
Temp. range 5–45 °C
Input for temperature reduction -3K
Cycle time for self-modulation 42 min
Range for self-modulation 2K
Colour: housing and pattress – white RAL 9003; cover
glass – polished white/ice grey
Protective class III
Protection class IP30
Storage temperature -25 to + 80 °C
Rel. humidity (warehouse) <80 % non-condensing
Operating temperature 0 to +50 °C
Remote sensor, length 3 m, type NTC 10 kΩ (option)
Dimensions 80x112 x 16 mm
Overall dimensions with pattress tted 80 x 112 mm Overall dimensions without pattress tted 65 x 98 mm
LK Systems AB, Box 66, 161 26 Bromma, Sweden | www.lksystems.se
Loading...