VCMA-20 Series
HVAC
Applications
Designed for automatic collection and removal of
condensate from air conditioning, refrigeration and dehumidification equipment when gravity drainage is not possible or practical. Also suitable for high efficiency oil and gas-fired condensing furnace and condensing boiler equipment
Features
1/2 gallon collection tank
Vertical centrifugal pump design
Automatic start and stop operation
Some models equipped with float (solid polymer)
activated switch for automatic high level water detection (safety overflow switch)
NO and NC operation (set to NO from factory for equipment shut down connection)
Models equipped with safety overflow switch include
two 5” switch lead wires
3/8” O.D. barbed discharge adapter with built-in
check valve
Three 1-1/8” diameter inlet openings (two fitted with
removable cap plug)
Thermally protected, fan cooled motor
Built-in wall mount tabs on tank
Removable pump float locking tab for safety during
transportation (remove at time of installation)
Maximum water temperature: 140 ºF
6 ft, 3-conductor cable with grounded 3-prong plug
Some models include 20’ x 3/8” I.D. vinyl
discharge tubing
Wastewater • Water Systems • HVAC • Industrial • Engineered Products
Construction
Motor — 1/30 hp
Discharge — 3/8" OD barbed
Housing/tank cover — ABS
Volute — ABS
Tank — ABS
Impeller — Glass filled polypropylene
Check valve — Acetal
Engineering Data
"
"
"
"
"
Specications
Item
No.
554421
554451
554431
554425
554455
554435
554461
NOTE: GPH is through check valve.
Model
No.
VCMA-20UL
VCMA-20UL
VCMA-20ULT
VCMA-20ULS
VCMA-20ULS
VCMA-20ULST
VCMA-20ULST
"
"
"
"
"
Discharge
Size HP Volts Hertz Amps Watts
3/8" OD Barbed 1/30 115 60 1.5 93 80 70 48 0 20 8.7 6 5.00
3/8" OD Barbed 1/30 230 50/60 0.5 75 80 70 48 0 17 7.4 6 5.00
3/8" OD Barbed 1/30 115 60 1.5 93 80 70 48 0 20 8.7 6 6.00
3/8" OD Barbed 1/30 115 60 1.5 93 80 70 48 0 20 8.7 6 5.00
3/8" OD Barbed 1/30 230 50/60 0.5 75 80 70 48 0 17 7.4 6 5.00
3/8" OD Barbed 1/30 115 60 1.5 93 80 70 48 0 20 8.7 6 6.30
3/8" OD Barbed 1/30 230 60 0.5 75 80 70 48 0 17 7.4 6 6.30
Performance (GPH@Head) Shutoff
Cord
Length (ft)
Weight
(lbs)1' 5' 10' 20' Ft PSI
"
"
"
Replacement Parts
Item Part Number
Tank 154401 Cover, motor 154421 Float arm 154452 Switch holder 154471 Switch 950337
P.O. Box 12010 Oklahoma City, OK 73157-2010 Phone: 1.800.701.7894 Fax: 1.800.678.7867 www.LittleGiantPump.com
Performance Data
Flow - Liters/Hour
0 100 200 300
25
20
15
230 V
10
Head - Feet
5
0
0 20 40 60 80 100
Flow - Gallons/Hour
7
6
5
4
3
Head - Meters
2
1
0
Form 995125 – 08/12