Page 15
SE-135 Ground-Fault Ground-Check Monitor Rev. 3-D-090816
5. TECHNICAL SPECIFICATIONS
5.1 SE-135
Supply:
Option 0 ................................. 25 VA, 120-240 Vac
(+10, -45%), 50-400 Hz;
15 W, 110-250 Vdc
(+10, -25%)
Option 1 .............................. 15 W, 24-48 Vdc
(+50, -25%);
20 VA, 48 Vac
(+10, -55%), 50-100 Hz
Ground-Fault Circuit:
Digital Filter ........................ 50 to 60 Hz, Bandpass
3 dB Frequency Response ... 30 to 90 Hz
Trip-Level Settings:
SE-CS10-x ......................... .50, .75, 1.0, 1.5, 2.0, 2.5,
3.0, 5.0, 7.5, 10.0, and
12.5 A
SE-CS40-x ......................... 2, 3, 4, 6, 8, 10, 12, 20, 30,
40, and 50 A
Trip-Time Settings .............. .10, .20, .30, .40, .50, .70,
1.0, 1.3, 1.6, 2.0, and
2.5 s
Thermal Withstand:
SE-CS10-x ........................ 150 A Continuous
1,000 A for 2.5 s
(Ground-Fault Current)
SE-CS40-x ......................... 600 A Continuous
4,000 A for 2.5 s
(Ground-Fault Current)
Sensor Lead Resistance ....... 2 Ω maximum
Trip-Level Accuracy:
SE-CS10-x ........................ 5% or 0.1 A
SE-CS40-x ........................ 5% or 0.4 A
Trip-Time Accuracy ............ +50, -15 ms
Sensor Verification ............. Enabled or Disabled
Sensor-Fault Detection ........ Open and Short
Trip Mode ........................... Latching
Ground-Check Circuit:
Open-Circuit Voltage .......... 30 Vdc
Output Impedance ............... 136 Ω
Loop Current ....................... 105 mA
Induced-ac Withstand ......... 60 Vac Continuous,
120 Vac for 10 s,
250 Vac for 0.25 s
Pull-in Time ........................ ≤ 1.5 s
Trip Resistance:
Standard ............................ 28 Ω ± 10%
XGC Option ..................... 45 Ω ± 10%
Trip Time:
Standard at 50 Ω ............... 220 ± 30 ms
XGC Option at 75 Ω ........ 220 ± 30 ms
Short Detection ................... Yes
Isolation ............................... 3 kV, 60 Hz, 1 s
Test ...................................... Front-Panel Button and
Remote, N.O. Contact
Fuse Rating (F1) ................. 1.5 A, 500 Vac,
Time Delay
Fuse Part Number ............... FNQ 1½ Buss Fusetron
Trip Mode ........................... Latching or Non-Latching
Trip Relay:
CSA/UL Contact Rating ..... 8 A Resistive 250 Vac,
5 A 30 Vdc,
0.25 HP,
B300 Pilot Duty
Supplemental Contact Ratings:
Make/Carry (0.2 s) ........... 30 A
Break dc ........................... 75 W Resistive,
35 W Inductive (L/R < 0.04)
Break ac ............................ 2,000 VA Resistive,
1,500 VA Inductive
(PF > 0.4)
Subject to maximums of 8 A and 250 V (ac or dc)
Contact Configuration ......... Isolated N.O. and N.C.
Contacts
Operating Mode .................. Fail-Safe or
Non-Fail-Safe
Maximum Switching
Capacity .............................. Fig. 14
Remote-Indication Relays:
CSA/UL Contact Rating ..... 8 A Resistive 250 Vac,
8 A 30 Vdc
Supplemental Contact Ratings:
Make/Carry (0.2 s) ........... 20 A
Break dc ........................... 50 W Resistive,
25 W Inductive (L/R < 0.04)
Break ac ............................ 2,000 VA Resistive,
1,500 VA Inductive
(PF > 0.4)
Subject to maximums of 8 A and 250 V (ac or dc)
Contact Configuration ......... N.O and N.C. (Form C)
Operating Mode .................. Fail-Safe
Maximum Switching
Capacity .............................. Fig. 15
Trip Reset ................................. Front-Panel Button and
Remote, N.O. Contact
Terminal Block Rating ............. 10 A, 300 Vac,
12 AWG (2.5 mm2)
PWB Conformal Coating ......... MIL-1-46058 qualified,
UL QMJU2 recognized
Mounting Configuration ........... Panel Mount and
Surface Mount
Dimensions:
Height .................................... 213 mm (8.4”)
Width ..................................... 99 mm (3.9”)
Depth ..................................... 132 mm (5.2”)
Shipping Weight ....................... 2.3 kg (5.1 lb)
Environment:
Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Storage Temperature ............. -55 to 80°C (-67 to 176°F)
Humidity ............................. 85% Non-Condensing