Littelfuse T4900 User Manual

Generator Control
Basic
T49 00 SERIES
VAR Load Sharer
Simplified Circuit Diagram
A
PF=1.0 – 0.7 ind.
12
OUT
PF ON
PF–SET.
PARALLEL
LINES
+
COM.
131314 15 16
NEXT T4900
100 K
INCR. DECR.
12
1 2 3
4 5 6
E7800
(Motorized Potentiometer)
M
I
N
POWER FACTOR
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
T4900
(VAR Load Sharer)
U
N
1 2 3 4 5 6 7 8 9 10 11 12
L
1
L
2
L
3
BUS
TRIP ENABLE
WATTINTEST
VOLT
VOLT
UNLOAD
I
N
OUT
IN
– –
UNLOAD or
PF=1.0
GEN
AVR
Ordering Information
ORDERING NUMBER
T4900.0010 450 V 400 V 5 A
T4900.0020 230 V 5 A
T4900.0030 480 V 415 V 5 A
T4900.0040 110 V 63 V 5 A
T4900.0050 127 V 120 V 1 A
T4900.0060 110 V 100 V 1 A
Other supply vol tages, nominal currents and combinations are available on request.
TERMINALS
1-3 2-3
Accessories
A
T4910-07 Potentiometer with Cable for External Power Factor Setting
External contact between terminals 12 (COM) and 28 (PF ON). Included.
Description
The T4900 VAR Load Sharer provides automatic load sharing of reactive power [kVAR] and voltage control for parallel running generators. The reactive load on each generator is compared with the reactive load on the other generators and corrected on the AVR (Automatic Voltage Regulator) until balance is obtained. The T4900 can also be used for power factor (PF) control in applications where one or more generators are operated in parallel with the grid (utility). The input to the T4900 are the voltage and the current from which the reactive power and voltage is determined. The T4900 calculates I x sin φ, representing the reactive load.
Power factor control for parallel operation with the public grid can be obtained by connecting an external contact between terminals 12 (COM) and 28 (PF ON). The setting is determined by an external potentiometer (100 kW) across terminals 29 and 30 (PF-SET).
Features & Benefits
FEATURES BENEFITS
Adjustable delta voltage, stability and % VAR load deviation by front panel potentiometers
Inputs for disabling internal voltage control
Facilitates adjustment during installation and commissioning. VAR Load deviation adjustment enables paralleling of differenst size generators
Enables operation where system voltage is set externally such as in grid-parallel operation
Enabling alternative use as power factor
Power factor control function
controller, thus maintaining fixed power factor (cos phi) in installations with fluctuating inductive loads
Visual indication of voltage, increase/decrease and
Provides quick and concise status information
unload signals Direct line-line voltage
supply (up to 690 Vac)
Galvanic isolated inputs
DIN-rail or screw mount
Simplifies design and installation. No need for PTs or separate power supply
Protects the unit against high AC voltage and currents from the installation including spikes
Easy installation
Specifications
Max. Voltage 660 V Voltage Range 110% Voltage Dev. Adjustment 0- ±12 V Consumption Voltage 4 VA at U
Current 0.4VA at I
Continuous Current 2 x IN Frequency Range 35 -70 Hz Proportional Band ±25-125% load Dead Band Zone ±1-10% load Contact Rating AC: 400 V, 2 A, 250 VA; DC: 110 V, 2 A, 100 W Operating Temperature –20°C to +70°C EMC CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2
Burn-in 50 hours before final test Enclosure Material Polycarbonate, flame retardant Weight 0.7 kg Dimensions H 70 mm (2.7“); W 150 mm (5.9“); D 115 mm (4.5“) Installation 35 mm DIN rail or 4 mm (
N
N
3
/16”) screws
© 2013 Littelfuse Protection Relays & Controls www.littelfuse.com/t4900
Rev: 4-A-050313