Generator Control
Basic
T49 00 SERIES
VAR Load Sharer
Simplified Circuit Diagram
A
PF=1.0 – 0.7 ind.
12
OUT
PF ON
PF–SET.
PARALLEL
LINES
+
COM.
131314 15 16
NEXT
T4900
100 K
INCR. DECR.
12
1 2 3
4
5
6
E7800
(Motorized
Potentiometer)
M
I
N
POWER FACTOR
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
T4900
(VAR Load Sharer)
U
N
1 2 3 4 5 6 7 8 9 10 11 12
L
1
L
2
L
3
BUS
TRIP ENABLE
WATTINTEST
VOLT
VOLT
UNLOAD
I
N
OUT
IN
– –
UNLOAD or
PF=1.0
GEN
AVR
Ordering Information
ORDERING NUMBER
T4900.0010 450 V 400 V 5 A
T4900.0020 230 V – 5 A
T4900.0030 480 V 415 V 5 A
T4900.0040 110 V 63 V 5 A
T4900.0050 127 V 120 V 1 A
T4900.0060 110 V 100 V 1 A
Other supply vol tages, nominal currents and combinations are available on request.
TERMINALS
1-3 2-3
Accessories
A
T4910-07 Potentiometer with Cable for
External Power Factor Setting
External contact between terminals
12 (COM) and 28 (PF ON). Included.
Description
The T4900 VAR Load Sharer provides automatic load sharing
of reactive power [kVAR] and voltage control for parallel
running generators. The reactive load on each generator is
compared with the reactive load on the other generators
and corrected on the AVR (Automatic Voltage Regulator)
until balance is obtained. The T4900 can also be used for
power factor (PF) control in applications where one or more
generators are operated in parallel with the grid (utility). The
input to the T4900 are the voltage and the current from which
the reactive power and voltage is determined. The T4900
calculates I x sin φ, representing the reactive load.
Power factor control for parallel operation with the public
grid can be obtained by connecting an external contact
between terminals 12 (COM) and 28 (PF ON). The setting is
determined by an external potentiometer (100 kW) across
terminals 29 and 30 (PF-SET).
Features & Benefits
FEATURES BENEFITS
Adjustable delta voltage,
stability and % VAR load
deviation by front panel
potentiometers
Inputs for disabling internal
voltage control
Facilitates adjustment during installation and
commissioning. VAR Load deviation adjustment
enables paralleling of differenst size generators
Enables operation where system voltage is set
externally such as in grid-parallel operation
Enabling alternative use as power factor
Power factor control
function
controller, thus maintaining fixed power factor
(cos phi) in installations with fluctuating
inductive loads
Visual indication of voltage,
increase/decrease and
Provides quick and concise status information
unload signals
Direct line-line voltage
supply (up to 690 Vac)
Galvanic isolated inputs
DIN-rail or screw mount
Simplifies design and installation. No need for
PTs or separate power supply
Protects the unit against high AC voltage and
currents from the installation including spikes
Easy installation
Specifications
Max. Voltage 660 V
Voltage Range 110%
Voltage Dev. Adjustment 0- ±12 V
Consumption Voltage 4 VA at U
Current 0.4VA at I
Continuous Current 2 x IN
Frequency Range 35 -70 Hz
Proportional Band ±25-125% load
Dead Band Zone ±1-10% load
Contact Rating AC: 400 V, 2 A, 250 VA; DC: 110 V, 2 A, 100 W
Operating Temperature –20°C to +70°C
EMC CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2
Burn-in 50 hours before final test
Enclosure Material Polycarbonate, flame retardant
Weight 0.7 kg
Dimensions H 70 mm (2.7“); W 150 mm (5.9“); D 115 mm (4.5“)
Installation 35 mm DIN rail or 4 mm (
N
N
3
/16”) screws
© 2013 Littelfuse Protection Relays & Controls
www.littelfuse.com/t4900
Rev: 4-A-050313