Littelfuse T4400 User Manual

T4400 Load Sharer
Soft load
or unload
Sync. T4400
Next T4400
0
+
-
• Automatic load sharing with voltage based speed control
• Adaptable to most speed controllers
• 2-wire communication with other T4400 Load Sharers
• Built-in frequency control
• Load / unload facility with ramp function
• Reverse power and unloaded trip
• Visual indication of voltage, generator C/B state and unload signal
• Cost effective and highly reliable compact design
• 50 hours burn-in before final test
• Operating temperature range:
-20°C to +70°C
• Flame retardant enclosure
• DIN rail or screw mounting
Application
The T4400 Load Sharer provides automatic load sharing and frequency control for parallel running generators. The load sharing is proportional, meaning that the generators will be loaded equal­ly compared to their individual capacity.
The T4400 works in connection with most electronic speed controllers.
The load on each generator is compared with the load on the other generators and corrected until balance is obtained.
Load sharing is necessary after synchronization in order to re-establish load balance and to obtain long term stability of load and system frequency.
When applied with the B9300 Power Reference Unit, one or several generators can be operated in parallel with the grid (utility).
Together with the T4000 Auto Synchro­nizer, the T4400 provides the optimal solution for generator control, both in land and marine-based applications. The T4900 VAr-Load Sharer can be used as a supplement. The combination of the T4400 and the T4900 will provide complete load sharing of both active load and reactive load.
The T4400 calculates I x cos f, represen­ting the active load. The load on each generator is compared with the load on the other generators and calculated into a control signal that is connected to the electronic speed controller for regulating the load with optimal speed and stability.
The T4400 includes a built-in frequency control and an integration function. These two features provide a very high overall stability and compensate for any drift within the speed controller.
A soft load / unload function is also
provided. When activated, the T4400 will slowly increase or decrease speed to transfer load to or from the generator. A built-in relay can automatically trip the circuit breaker when the unload procedure is completed.
The T4400 has a built-in reverse power protection with selectable limits and time delays.
Fig. 1 shows how to connect to most Woodward and Heinzmann speed controllers. For connection to other makes please refer to the section “Interfacing” on the following page.
Function
The input to the T4400 is the voltage and current, from which the active load and frequency are determined.
Fig. 1. Application diagram for T4400 and speed controller with -5V to +5V DC input.
Supply voltage / current
The supply voltage from L1 and L2 is connected to terminals 1 and 3 or 2 and 3, depending on the system voltage.
The measuring current from L3 is connected to terminals 5 and 6 with 5 referring to the generator (see the application diagram on page 3). The current measurement must be taken from the same phase on all generators.
The current is measured in the phase that is not supplying the unit. It is important to ensure that the phase sequence is correct.
This relation between the connections of voltage and current must be correct in order to achieve a correct load measure­ment. It can be checked on terminal 11 (TEST OUT), where an input of nominal current (1A or 5A) and power factor 1.0 gives +6V for correct connection.
Ramp function
The T4400 includes a ramp function. With this function activated, the unit will smoothly take over the load up to load balance.
In order to activate this function, terminals 7 (UNLOAD) and 32 should initially be bridged and so should terminals 31 (C/B) and 32 (for example with an aux. contact of the circuit breaker). Now the ramp function can be activated by opening the connection between terminals 7 (UNLOAD) and 32.
Common reference
Terminal 12 (COM.) is the common reference for terminals 8 to 13.
Unload facility
The unload facility will smoothly unload the generator. This facility works like an inverted ramp function. If activated, the load on the generator will be reduced and maintained at a low level.
In order to activate, terminals 31 (C/B) and 32 should initially be bridged. The unload function is then activated by connecting terminal 7 (UNLOAD) to 32.
Unload trip
When the load passes below 5% load, a trip signal is provided as a normally open (NO) contact on terminal 20-21 and a normally closed (NC) contact on 21-22. This trip signal can be used to trip the circuit breaker.
Reverse power trip
The reverse power trip operates at 10% with a delay of 10 sec., but it can be reduced to 5% by bridging terminals 17 and 18 and to 5 sec. delay by bridging 18 and 19. A resistor of 510kW between 17 and 18 gives 7.5%, a resistor of 2.7M between 18 and 19 gives 7.5 sec. delay. The trip signal is provided as a normally open (NO) contact on term. 23-24 and a normally closed (NC) contact on 24-25.
Frequency control
The electronic speed controller will control the frequency of the generator. However, the frequency control of some speed controllers will drift with time. In order to compensate for this, the T4400 includes frequency control.
The system frequency can be set to 60Hz with terminals 29 and 30 bridged or 50Hz with these terminals open. Further adjustment of the frequency is possible using the potentiometer DIFF. FREQ. on the front panel.
Connecting terminal 8 (FREQ. OUT) to 12 will disable the frequency control. This is used when running parallel with the grid, where the frequency is fixed by the grid.
Input from synchronizer
Between terminals 9 (FREQ. IN) and 12 the SELCO T4000 Auto Synchronizer or most other synchronizer makes can be connected. The synchronizer will then give the synchronizing output through the T4400. This signal is not affected by the output adjustments on the T4400.
External power measurement
Between terminals 10 (WATT IN) and 12 a negative voltage (0 to -1V DC from a watt converter) can be connected to substitute the internal load measuring circuit. In this case no input on terminals 5 and 6 is needed. Most standard measu­ring signals can be adapted with external resistors. 0-10V : series resistor 510kW 0-5mA : parallel resistor 200W
Communication between load sharers
For communication between the load sharers all terminals 12 (COM.) are interconnected, as well as all terminals 13 (+).
Output to the speed controller
Output to the electronic speed controller is taken from terminals 15 (REF.) and 16 (+) with terminal 15 as reference. If an inverse signal is needed, use terminals
W
15 (REF.) and 14 (-) rather than changing wires to 15 and 16. The output signal is an integrated signal. This means, the output signal will change as long as there is a load deviation. When load balance is obtained the output signal will stay at its current level.
Adjustments
LOAD DEV. can be used for fine adjust­ments of the load balance. LOAD DEV. should also be used to obtain balance with generators of different size and with different types of current transducers (CTs). For generators of same size and with same type of CT, the setting 0 should be used on all load sharers.
DIFF. FREQ. is used for adjustment of system frequency as described on page 2 in the section about frequency control. If the system frequency should be exactly 50 Hz or 60 Hz, the setting 0 should be used.
STABILITY is used for adjusting the regulation time. A high setting of STABILITY will give a slow but accurate regulation. A low setting will give a fast regulation. However, a too low setting may cause instability.
VARIABLE OUT is intended for adjusting the size of the output signal to the speed controller. The output increases with higher setting on the potentiometer. Too much output can result in instability. If this is the case, turn the potentiometer anti clockwise until stability is restored.
Interfacing
A detailed note on interfacing the T4000 and the T4400 to a wide number of different electronic speed controllers is available from SELCO. This note can also be downloaded from our web-site www.selco.com.
Trouble Shooting
If load balance is not obtainable
If load balance is not obtainable and the power goes to maximum or reverse power, one of the signals is inverted due to wrong polarity or interchanged wires. If this is the case, the following should be checked:
1. The polarity of the power measuring signals on terminal 11 (TEST OUT) must be positive with the generator on load. If the polarity is negative, change the voltage connections 1 and 3 or 2 and 3 or the current connections 5 and 6.