Littelfuse T3300 User Manual

Protection Relays & Controls
Generator & Single-Function Protection–Voltage
T3300 SERIES
3-Phase Voltage Relay
Simplified Circuit Diagram
PHASE
1
PHASE
2
PHASE
3
17 18 19
21 22 23
25 26 27
T3300
(Voltage Relay)
(Inputs are isolated)
UNDERVOLTAGE
ALARM
OVERVOLTAGE
ALARM
16 15
14
12 11 10
Description
The T3300 consists of two circuits, one circuit for overvoltage and one for undervoltage monitoring. Each circuit has individual settings for voltage levels and time delays.
Features & Benefits
FEATURES BENEFITS
Features & Benefits
Accepts high supply voltage variation
Visual indication of power, pick-up, and output trip
Direct line-line or line­neutral voltage supply (up to 690 Vac)
Combining 2 relays in same enclosure
Galvanic isolated inputs
DIN-rail or screw-mount & adjustment by potentiometers
Ensures correct operation in spite of voltage supply fluctuations (fulfills marine class requirement)
Provides quick and concise status information
Simplifies design and installation. No need for PTs.
Economic solution. 3-phase monitoring of both undervoltage and overvoltage in same unit, and occupying less space in the switch panel
Protects the unit against high AC voltage and currents from the installation including spikes
Easy installation
Ordering Information
TERMINALS
ORDERING NUMBER
T3300.0010 230 V T3300.0020 450 V 400 V T3300.0030 110 V 100 V
T3300.0040 480 V 415 V
Other vo ltages are available on request.
17-19 21-23 25-27
18-19 22-23 26-27
Specifications
Overvoltage Level 100-120% Delay 1-10 sec. Hysteresis 1-10% Undervoltage Level 80 -100% Delay 1-10 sec. Hysteresis 1-10 % Max. Voltage 660 V Voltage Range 70 -120 % Consumption Frequency Range 40-400 Hz Overvoltage Relay Normally de-energized Undervoltage Relay Normally energized Contact Rating AC: 250 V, 2 A, 250 VA
DC: 60 V, 2 A, 100 W
Overall Accuracy ±3% of highest value Repeatability ±1% Operating Temperature Dielectric Test 2500 V, 50 Hz EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Enclosure Material Polycarbonate. Flame retardant Weight 1.2 kg Dimensions H 70 mm (2.76”); W 150 mm (5.9”); D 115 mm (4.52”) Installation 35 mm DIN rail or 4 mm (
5 VA at U
N
–20°C to + 70°C
3
/16”) screws
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/t3300
Rev: 4-A-050213