Littelfuse T3200 User Manual

T3200 Insulation Monitoring Relay
SYS. 1 SYS. 2
13 15 11
T3200
3
2
1
10
+
-
20
INS. 2
18
COM.
19
INS. 1
SYS.
2
SYS.
1
7
9
8
6
5
3
L
L L
2
1
E2323
Double Insulation Monitoring Relay
• Price competitive due to the combined functions
• Visual indication of power, pick-up and relay tripping on both relays
• High precision digital countdown timer for delayed output
• 50 hours burn-in before final test
• Operating temperature range:
-20°C to +70°C
• Certified by major marine classification societies
• Flame retardant enclosure
• DIN rail or screw mounting
Application
The T3200 Insulation Monitoring Relay is intended for continuous insulation monitoring on three-phased insulated networks on board ships.
The T3200 continuously monitors two systems, galvanically separated from each other, e.g. the busbar and the lighting system, or two busbar systems.
The unit features two output relays for alarm purposes and two analog outputs for instrument reading. Instruments are available from SELCO as standard sized switchboard instruments.
Function
For each insulation system (I and II) the electronic measuring circuit will compare the measured insulation value to the preset value of the relay. An insulation drop to a value lower than the preset value will cause activation of the corresponding output relay resulting in alarm signals to be obtained between terminals 6 and 7 or 9 and 10 (system I or system II respectively).
Consequently, the output relays will be deactivated when the insulation values are satisfactory, while insulation values lower than the preset value will cause activation of the output relays. This means that power supply interruptions will not result in alarm signals as the output relays normally are deactivated.
The alarm signal can be delayed by means of a presetting function on the
front of the unit. In this way only continuous earth faults will cause alarm signals.
The instrument output has been adapted for connection of a megaohmmeter which indicates the actual insulation level, either by means of two instruments simultaneously indicating for both insulation systems (I and II), or by means of one instrument which can be connected to the two instrument outputs via a change-over switch. See connection diagram.
NOTE: The T3200 operates only on AC installations. Insulation faults in connection with thyristor controls and other semiconductor devices can cause errors in measurements.
Connection Diagram.
Installation
The measuring circuits for the two insulation systems I and II are connected to the network as shown on the connection diagram.
The supply voltage is connected to terminals 1-3 or 2-3 according to the supply source.
Dimensions.
7
0
115
5
0
85
7.5
1
0
100
Fixing holes
2 x ø 4.5 mm
Dimensions in mm
Type Approvals and Certificates
The T3200 has been designed and tested for use in harsh environments. The unit is based on standard components, providing long term durability. The T3200 carries the CE label and has been approved by the following marine classification societies:
Bureau Veritas
Polish Register of Shipping
Romanian Register of Shipping
Russian Maritime Register of Shipping
Specifications
T3200 Insulation Monitoring Relay
Insulation level 0 - 5MW Delay 1 - 10 sec. Max. voltage 660V Voltage range 80 - 110% Consumption Max. 2VA Frequency range 45 - 65Hz Measuring voltage 15V DC Internal resistance 200kW Instrument output 0 - 1mA Instrument resistance Max. 100W Output relays Normally de-energized Contact ratings AC: 400V, 2A, 250VA
DC: 110V, 2A, 100W
Overall accuracy ±5% of preset value Operating temperature -20°C to +70°C Dielectric test 2500V, 50Hz EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Enclosure material Polycarbonate. Flame retardant Weight 0.5kg Dimensions 70 x 100 x 115mm (H x W x D) Installation 35mm DIN rail or 4mm (3/16”) screws
The specifications are subject to change without notice.
Type Selection Table
Terminals Type 1-3 2-3 Function T3200.0010 230V T3200.0020 450V 400V T3200.0030 480V 415V T3200.0040 24V DC With 24V DC/DC converter T3200.0050 110V 100V T3200.0060 127V 120V
Other voltages are available on request.
Main office: SELCO A/S
Betonvej 10 DK-4000 Roskilde Denmark Phone: + 45 7026 1122 Fax: + 45 7026 2522 e-mail: selco.dk@selco.com www.selco.com
Accessories
Dimensions Weight E2323.0010 Megaohmmeter 96x96mm 0.5kg E2324.0010 Kiloohmmeter 96x96mm 0.5kg E2333.0010 Megaohmmeter 144x144mm 0.8kg
T3295-62E